Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 7 1 214 4 2ND FLOOR D K ROAD AMEERPET HYDERABAD TELANGANA 500016 | MEDCHAL MALKAJGIRI | TELANGANA | 500016 | Admitted-Finance |
| 2 | Admitted-Finance 11TH FLOOR ECO CENTRE BUSINESS TOWER P NO 4 EM BLOCK SECTOR V KOLKATA 91 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700091 | Admitted-Finance |
| 3 | Admitted-Finance 1ST FLOOR BLOCK B VATIKA TOWERS GOLF COURSE ROAD SECTOR 54 GURUGRAM HARYANA 122002 | GURUGRAM | GURUGRAM | HARYANA | 122002 | Admitted-Finance |
| 4 | Admitted-Finance CRYSTAL TOWER 4TH FLOOR TELIBANDHA RAIPUR | RAIPUR | RAIPUR | CHHATTISGARH | Admitted-Finance |
| 5 | Admitted-Finance C O VOLTAS LIMITED SPARE PARTS DEPOT OLD HUTMENT COLONY NCL NIGAHI SINGRAULI M P 486884 | SINGRAULI | SINGRAULI | MADHYA PRADESH | 486884 | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹5.3 Cr
Closing Date
23 Feb 2024, 3:00 pmClosed
AGM (Mechanical Systems_GC Services)
Chennai Metro Rail Limited, METROS, Anna Salai, Nandanam, Chennai -600 035, Tamil Nadu, India
Design Verification, Validation, Supply,Installation, T/C,spares, special tools, O and M during 2 years DLP and 5 years CAMC of VAC, TVS, Electrical and SCADA works for 8 C4 UG stations including TVS SCADA at Thirumayilai station, ISMS at OCC, BOCC
2023_CMRL_775326_1
C4-VAC_TVS-12
Global Tenders
Construction Works
1160 days
CHENNAI
Please refer Tender documents.
9 documents required · 9 mandatory
₹40,000
GM/F CMRL
₹5.3 Cr
METROS, NANDANAM, CHENNAI
29 Jul 2024
10 Oct 2023
26 Feb 2024
10 Dec 2023
23 Feb 2024
2 Feb 2024
10 Oct 2023 - 16 Nov 2023
8 Nov 2023
Amount
PRICE CENTRE - A (GENERAL REQUIREMENT)
1-Project management cost (Monthly progress report, Interface Management works and Audits, Quality Assurance & Quality Control Audits & Report, Plans and Programs)(Ref Chapter-2 Part-2 Works Requirement)
2-Identify & Construction of Main Project Head office till DLP (Ref Chapter-15 of Part-2 Works Requirement )
3-Maintenance of Main Project Head office till DLP (Ref Chapter-15 of Part-2 Works Requirement )
4-Identify & Construction of Project Satellite site office till completion of project works (Ref Chapter-15 of Part-2 Works Requirement )
5-Maintenance of Project Satellite site office till completion of project works (Ref Chapter-15 of Part-2 Works Requirement )
6-Identification,construction and Maintenance of Store yard till completion of project works( minimum 2000 Sq.m) (Ref Chapter-7 of Part-2 Works Requirement )
7-Compliance with Occupational Safety, Health and Environmental Audits (Ref -Section VI A & E of Part -2 & Chapter-2 Part-2 Works Requirement)
8-Submission of Performance PBG till completion of DLP works (Price centre A to G) Ref - Part -1 & Chapter-2 Part-2 Works Requirement
9-Submission of all type of insurance/ CAR Policy/Professional Indemnity Insurance till completion of DLP (Price centre A to G) Ref - Part -3 & Chapter-2 Part-2 Works Requirement
10-Purchase of Primavera licenses Software till completion of Project (Ref Chapter-2,3 and 6 of Part-2 Works Requirement)
11-Web Primavera licenses (Ref: Chapter 2 of Part-2 Section VI "WORKS REQUIREMENTS")
12-laptop computer with latest generation or higher which is compatible to software used for BIM to Employer (Ref: Chapter 15 of Part-2 Section VI "WORKS REQUIREMENTS")
13-IDA Software for 1D Tunnel Ventilation Design(one year license) including training for Employer
14-Purchase of List of Standards for TVS/VAC System as per list (Ref Chapter-1 of Part-2 Works Requirement)
15-Development and implementation of Project Control And Monitoring software (Ref Chapter-22 of Part-2 Works Requirement)
16-Maintenance of Project Control And Monitoring software (Ref Chapter-22 of Part-2 Works Requirement)
17-Development and implementation of Web and mobile-based Comprehensive Maintenance Management System (CMMS) for TVS/VAC - Using Artificial Intelligence (It shall include but not limited to: Supply and Installation of all the required hardwares, softwares, Tablets for O&M Staffs, Internet Connectivity, Cloud subscription/License cost, etc.) (Ref Part-2 Section-VII, Sub Section – E)
18-International training/ conference/symposium/seminars for Employer staff(Ref Chapter-10 of part-2 works Requirement)
19-Deployment of Key Staffs (Ref Appendix-5 of Part-2 Works requirement)
a. Chief Project Manager / Contract Representative
b. Deputy Project Manager
c. Planning and Programme Manager
d. Design Manager – Mechanical
e. Design Manager – Electrical & SCADA
f .Interface Manager
g. Procurement Manager
h. Construction Manager – Mechanical
i. Construction and T&C Manager – Electrical
j. Deputy Construction Manager – Mechanical
k. Deputy Construction and T&C Manager – SCADA
l. BIM Manager
m. QA & QC Manager
n .OHSE Manager
o. Testing and Commissioning (T&C) Manager for VAC
p .Testing and Commissioning (T&C) Manager for TVS
q. Cost & Accounting Manager
r .Project Software Implementation Manager
20-Deployment of Non-Key Staffs (Ref Appendix-5 of Part-2 Works requirement )
a. 3D BIM Modeler – Mechanical
b. 3D BIM ModelerElectrical & Electronics
c .Testing and Commissioning Engineer – TVS system
d.Testing and Commissioning Engineer – VAC system
e. Testing and Commissioning Engineer - Electrical
f. Testing and Commissioning Engineer - SCADA
g. OHSE Senior Engineer
h. Safety Steward
i. Environment Engineer
j. Document Controller
k. QA & QC Engineer
l. Interface Engineer
m. Site Engineer –TVS/VAC Mechanical
n. Site Engineer TVS/VAC Electrical
o. Site Engineer - SCADA
p. Store Incharge
Description of Work / Item(s)
Amount
PRICE CENTRE - B (DESIGN VERIFICATION AND VALIDATION)
1-Design Verification and Validation of TVS Design Works which includes but not limited to Acoustic , SES ,CFD Simulation works etc (Ref -SubSection-A, Section VII of Part -2 & Appendices-5, SubSection-B Section VI of Part -2 )
2-Design Verification and Validation of VAC works (Ref -SubSection-A, Section VII of Part -2 )
3-Design Verification and Validation of TVS/VAC associated Electrical Works (Ref -SubSection-A, Section VII of Part -2)
4-Design Verification and Validation of ISMS Works (Ref -SubSection-A, Section VII of Part -2)
5-Submission of RAMS REPORT during Design Verification stage and Submission of Achievement RAMS REPORT before completion of DLP ( Ref -SubSection-A, Section VII of Part -2 & Chapter 12 Section VI of Part -2 and Appendices-5, SubSection-B Section VI of Part -2)
6-EMC Compliance Report (Ref -Chapter 12 Section VI of Part -2 & Appendices-5, SubSection-B Section VI of Part -2 )
Description of Work / Item(s)
Amount
PRICE CENTRE C - VAC WORKS
2- Manufacture, Supply, Delivery, Installation, Testing (Factory acceptance test,Partial acceptance test & System Acceptance Testing), Integrated Testing Commissioning & DLP of following equipment's / materials
3- Air Handling Units (DX- Coil type) compatible with VFD Motor Following various capacities of Air Handling Units (DX- Coil type) In Accordance with VAC Technical Specifications(Refer Part-2, Section VII, Sub section C, unit 4) and drawings.
3.01- Air flow capacity - 6937 LPS (6.94CMS), Cooling Load Capacity - 158.1 KW (44.95TR), Total Pressure drop -1840Pascal and compatible with VFD motor
3.02- Air flow capacity - 6227 LPS (6.23 CMS), Cooling Load Capacity - 161.3 KW (45.86 TR), Total Pressure drop -1120 Pascal and compatible with VFD motor
3.03- Air flow capacity - 6188 LPS (6.19 CMS), Cooling Load Capacity - 163.3 KW (46.43 TR), Total Pressure drop -1040 Pascal and compatible with VFD motor
3.04- Air flow capacity - 8082 LPS (8.1CMS), Cooling Load Capacity - 190 KW (54TR), Total Pressure drop -1660 Pascal and compatible with VFD motor
3.05- Air flow capacity - 7766 LPS (7.77 CMS), Cooling Load Capacity - 195.1 KW (55.47 TR), Total Pressure drop -1280 Pascal and compatible with VFD motor
3.06- Air flow capacity - 7535 LPS (7.54CMS), Cooling Load Capacity - 198.2 KW (56.5TR), Total Pressure drop -1110Pascal and compatible with VFD motor
3.07- Air flow capacity - 8365 LPS (8.37 CMS), Cooling Load Capacity - 202.8 KW (57.7 TR), Total Pressure drop -1170 Pascal and compatible with VFD motor
3.08- Air flow capacity - 8472 LPS (8.47 CMS), Cooling Load Capacity - 202.8 KW (57.7 TR), Total Pressure drop -1450 Pascal and compatible with VFD motor
3.09- Air flow capacity - 9303 LPS (9.3 CMS), Cooling Load Capacity - 222.0 KW (63.12 TR), Total Pressure drop -1530 Pascal and compatible with VFD motor
3.10- Air flow capacity - 9530 LPS (9.53 CMS), Cooling Load Capacity - 228.1 KW (64.86 TR), Total Pressure drop -1530 Pascal and compatible with VFD motor
3.11- Air flow capacity - 9071 LPS (9.07 CMS), Cooling Load Capacity - 225.1 KW (64.01 TR), Total Pressure drop -1180 Pascal and compatible with VFD motor
3.12- Air flow capacity - 9744 LPS (9.75 CMS), Cooling Load Capacity - 236.1 KW (67.13 TR), Total Pressure drop -1870 Pascal and compatible with VFD motor
3.13- Air flow capacity - 9825 LPS (9.83 CMS), Cooling Load Capacity - 229.9 KW (65.4 TR), Total Pressure drop -1260 Pascal and compatible with VFD motor
3.14- Air flow capacity - 10288 LPS (10.3 CMS), Cooling Load Capacity - 238 KW (67.62 TR), Total Pressure drop -1670 Pascal and compatible with VFD motor
3.15- Air flow capacity - 11921 LPS (11.92 CMS), Cooling Load Capacity - 291.30 KW (82.83 TR), Total Pressure drop -1240 Pascal and compatible with VFD motor
3.16- Air flow capacity - 14199 LPS (14.2CMS), Cooling Load Capacity - 326 KW (92.7TR), Total Pressure drop -1790 Pascal and compatible with VFD motor
3.17- Air flow capacity - 10830 LPS (10.83CMS), Cooling Load Capacity - 327.3 KW (93.06TR), Total Pressure drop -1260 Pascal and compatible with VFD motor
3.18- Air flow capacity - 14800 LPS (14.8CMS), Cooling Load Capacity - 340.9 KW (96.9TR), Total Pressure drop -1540 Pascal and compatible with VFD motor
3.19- Air flow capacity - 12707 LPS (12.71CMS), Cooling Load Capacity - 402 KW (114.2TR), Total Pressure drop -1210 Pascal and compatible with VFD motor
3.20- Air flow capacity - 11534 LPS (11.5 CMS), Cooling Load Capacity - 261.8 KW (74.44 TR), Total Pressure drop -1450 Pascal and compatible with VFD motor
3.21- Air flow capacity - 12593 LPS (12.6 CMS), Cooling Load Capacity - 296.6 KW (84.34 TR), Total Pressure drop -1540 Pascal and compatible with VFD motor
3.22- Air flow capacity - 9422 LPS (9.42 CMS), Cooling Load Capacity - 302.1 KW (85.9 TR), Total Pressure drop -1540 Pascal and compatible with VFD motor
4- VRF Outdoor Units Following various capacities of outdoor units (ODU). In Accordance with VAC Technical Specifications(Refer Part-2, Section VII, Sub section C, unit 2) and drawings.
4.11- 30 HP (24 TR)- Combination of any S No "4.01" to "4.10" of above ODU Capacity
4.12- 36 HP (28.8 TR)- Combination of any S No "4.01" to "4.10" of above ODU Capacity
4.13- 40 HP (32 TR)- Combination of any S No "4.01" to "4.10" of above ODU Capacity
4.14- 42 HP (33.6TR)- Combination of any S No "4.01" to "4.10" of above ODU Capacity
4.15- 52 HP (41.6TR)- Combination of any S No "4.01" to "4.10" of above ODU Capacity
4.16- 60 HP (48TR)- Combination of any S No "4.01" to "4.10" of above ODU Capacity
4.17- 62 HP (49.6TR)- Combination of any S No "4.01" to "4.10" of above ODU Capacity
4.18- 64 HP (51.2TR)- Combination of any S No "4.01" to "4.10" of above ODU Capacity
4.19- 66 HP (52.8TR)- Combination of any S No "4.01" to "4.10" of above ODU Capacity
4.20- 78 HP (62.4TR)- Combination of any S No "4.01" to "4.10" of above ODU Capacity
4.21- 80 HP (64TR)- Combination of any S No "4.01" to "4.10" of above ODU Capacity
4.22- 88 HP (70.4TR)- Combination of any S No "4.01" to "4.10" of above ODU Capacity
4.23- 90 HP (72TR)- Combination of any S No "4.01" to "4.10" of above ODU Capacity
4.24- 92 HP (73.6TR)- Combination of any S No "4.01" to "4.10" of above ODU Capacity
4.25- 94 HP (75.2TR)- Combination of any S No "4.01" to "4.10" of above ODU Capacity
4.26- 96 HP (76.8TR)- Combination of any S No "4.01" to "4.10" of above ODU Capacity
4.27- 104 HP (83.2TR)- Combination of any S No "4.01" to "4.10" of above ODU Capacity
4.28- 114 HP (91.2TR)- Combination of any S No "4.01" to "4.10" of above ODU Capacity
4.29- 116 HP (92.8TR)- Combination of any S No "4.01" to "4.10" of above ODU Capacity
4.30- 120 HP (96TR)- Combination of any S No "4.01" to "4.10" of above ODU Capacity
4.31- 128 HP (102.4TR)-Combination of any S No "4.01" to "4.10" of above ODU Capacity
4.32- 134 HP (107.2TR)- Combination of any S No "4.01" to "4.10" of above ODU Capacity
4.34- 158 HP (126.4TR)- Combination of any S No "4.01" to "4.10" of above ODU Capacity
5.01- HIGH STATIC DUCTABLE/ CONCEALED INDOOR UNITS
5.02- HI-WALL INDOOR UNITS
5.03- CASSETTE TYPE INDOOR UNIT
5.04- Expansion Valve Kit & Communication Kit
5.04.01 - Electronic Expansion Valve & Communication Kit for AHUs including Air temperature sensor, Refrigerant temperature sensor, Remote, Wiring, Hot dip galvanized steel support & other related accessories etc. - In Accordance with VAC Technical Specifications and drawings. (Quantity/Lot shall be based on Number of VRF circuits) (Refer Part-2, Section VII, Sub section C, unit 2)
5.05- Refrigerant Y-joints & distributer of sizes as required to suit Various capacity of Indoor units (IDU) & AHU In Accordance with VAC Technical Specifications and drawings.(Refer Part-2, Section VII, Sub section C, Unit 2) Note : Bidder should procure Y-Branch joints & distributer joints only from VRF OEM.
5.06- Central Remote Controller
5.06.01- Intelligent Programmable Central Remote Controller(Master Controller) for VRF with digital touch screen type of latest generation and GI powder coated enclosure In Accordance with VAC Technical Specifications and drawings. (Refer Part-2, Section VII, Sub section C, unit 2)
5.06.02- VRF Touch Screen HMI (22 Inch) with GI powder coated enclosure In Accordance with VAC Technical Specifications (Refer Part-2, Section VII, Sub section C, Unit 2)
5.07- SS 316 secondary drain pan with insulation for Indoor unit. In Accordance with VAC Technical Specifications and drawings.(Refer Part-2, Section VII, Sub section C, unit 2)
5.08- Design, supply, fabrication, and erection of a modular support structure to accommodate VRV/VRF outdoor units, including associated cable trays for electrical and copper piping, and any required accessories at terrace, roof, or road level locations. complete in all respect as per technical specification.(Quantity/Set shall be based on Number of Outdoor units Module) ( Refer Part-2, Section VII, Sub section C,unit 2.8.2)
5.09- Design,supply,fabrication & erection of Canopy roofing for VRV/ VRF Outdoor units with Heavy duty Plastic / Acrylic Sheet and necessary Supporting Steel (SS316) and other accessories as per Standard installation drawing and Technical Specification.( Refer Part-2, Section VII, Sub section C, Unit 2)
5.10- Design,supply,fabrication & erection of Stainless Steel (SS316) fencing around VRV/ VRF Outdoor units with door,lock & other accessories for safety as per Standard installation drawing.( Refer Part-2, Section VII, Sub section C, Unit 2)
5.11- Design,supply,fabrication & erection of Stainless Steel (SS316) cage Ladder / staircase for accessing VRV/ VRF Outdoor units ,Tunnel ventilation dampers & other accessories as per Standard installation drawing.(Refer Part-2, Section VII, Sub section C, Unit 2)
5.11.01- 5 Meter Height
5.11.02- 10 Meter Height
6- Copper Pipes and Accessories
6.01.01- 54.0 mm O.D -Hard drawn copper tubes
6.01.02- 44.5 mm O.D Hard drawn copper tubes
6.01.03- 41.3 mm O.D.-Hard drawn copper tubes
6.01.04- 38.1 mm O.D.-Hard drawn copper tubes
6.01.05- 34.9 mm O.D.-Hard drawn copper tubes
6.01.06- 31.8 mm O.D-Hard drawn copper tubes
6.01.07- 28.6 mm O.D-Hard drawn copper tubes
6.01.08- 25.4 mm O.D.-Hard drawn copper tubes
6.01.09- 22.2 mm O.D.-Hard drawn copper tubes
6.01.10- 19.1 mm O.D.-Hard drawn copper tubes
6.01.11- 15.9 mm O.D.-Hard drawn copper tubes
6.01.12- 12.7 mm O.D.-Soft copper tubes
6.01.13- 9.53 mm O.D.-Soft copper tubes
6.01.14- 6.4 mm O.D.-Soft copper tubes
6.02- Hot dip Galvanized 2mm thick Raceway/Trunking ,1.6 mm thick cover with necessary supports and other accessories In Accordance with VAC Technical Specifications(Refer Part-2, Section VII, Sub section C, unit 3) and drawings.
6.02.01- 200 mm wide / 100mm depth / 2 mm thick
6.02.02- 300 mm wide / 100mm depth / 2 mm thick
6.02.03- 450 mm wide/ 100mm depth / 2 mm thick
6.02.04- 600 mm wide / 100mm depth / 2 mm thick
6.02.05- 200 mm wide / 150mm depth / 2 mm thick
6.02.06- 300 mm wide / 150mm depth / 2 mm thick
6.02.07- 350 mm wide / 150mm depth / 2 mm thick
6.02.08- 450 mm wide / 150mm depth / 2 mm thick
6.02.09- 600 mm wide /150mm depth / 2 mm thick
6.02.10- 750 mm wide /150mm depth / 2 mm thick
7- Following various size of Copper Tubes Insulation made up of closed cell elastomeric Nitrile rubber with factory treated glass woven cloth In Accordance with VAC Technical Specifications (Refer Part-2, Section VII, Sub section C, unit 12) and drawings.
7.01- Gas Pipes
7.01.01- 32 mm thickness (54.0 mm O.D.)
7.01.02- 32 mm thickness (44.5 mm O.D.)
7.01.03- 32 mm thickness (41.3 mm O.D.)
7.01.04- 32 mm thickness (38.1 mm O.D.)
7.01.05- 32 mm thickness (34.9 mm O.D.)
7.01.06- 32 mm thickness (31.8 mm OD)
7.01.07- 32 mm thickness (28.6 mm O.D.)
7.01.08- 32 mm thickness (25.4 mm O.D.)
7.01.09- 32 mm thickness (22.2 mm O.D.)
7.01.10- 32 mm thickness (19.1 mm O.D.)
7.01.11- 25 mm thickness (15.9 mm O.D.)
7.01.12- 25 mm thickness (12.7 mm O.D.)
7.01.13- 25 mm thickness (9.5 mm O.D.)
7.02- Liquid Pipes
7.02.01- 13 mm thickness (25.4 mm O.D.)
7.02.02- 13 mm thickness (22.2 mm O.D.)
7.02.03- 13 mm thickness (19.1 mm O.D.)
7.02.04- 13 mm thickness (15.9 mm O.D.)
7.02.05- 13 mm thickness (12.7 mm O.D.)
7.02.06- 13 mm thickness (9.5 mm O.D.)
7.02.07- 13 mm thickness (6.4 mm O.D.)
8- Condensate Drain Piping & fitting With insulation and Aluminium cladding In Accordance with VAC Technical Specifications and(Refer Part-2, Section VII, Sub section C, unit 2 & 4 ) drawings.( Price shall include cost of Insulation)
8.01- UPVC Pipe and 19 mm closed cell elastomeric Nitrile rubber with factory treated glass woven cloth
8.01.01- 40 mm dia
8.01.02- 32 mm dia
8.01.03- 25 mm dia
8.02- 0.6 mm Aluminium cladding for Drain pipe in accordance with VAC technical specifications (Refer Part-2, Section VII, Sub section C, unit2&4 ) drawings
9.01- Fire Rated Application : GI Sheet Metal Ducting with necessary supports and other accessories In Accordance with VAC Technical Specifications (Refer Part-2, Section VII, Sub section C, unit 8) and drawings.
9.01.01- 0.63 mm thick (24 Gauge)
9.01.02- 0.83 mm thick (22 Gauge)
9.01.03- 1.00 mm thick (20 Gauge)
9.01.04- 1.20 mm thick (18 Gauge)
9.02- Fire Rated Application : MS angular frame GI Sheet Metal Ducting with necessary supports and other accessories In Accordance with VAC Technical Specifications (Refer Part-2, Section VII, Sub section C, unit 8) and drawings.
9.02.01- 0.63 mm thick (24 Gauge)
9.02.02- 0.83 mm thick (22 Gauge)
9.02.03- 1.00 mm thick (20 Gauge)
9.02.04- 1.20 mm thick (18 Gauge)
9.03- Fire-Resistant Paint for fire rated duct. In Accordance with VAC Technical Specifications (Refer Part-2, Section VII, Sub section C, unit 8) and drawings.
9.04- Normal ( Non Fire Rated ) Application. GI Sheet Metal Ducting with necessary supports and other accessories In Accordance with VAC Technical Specifications (Refer Part-2, Section VII, Sub section C, unit 8) and drawings.
9.04.01- 0.63 mm thick (24 Gauge)
9.04.02- 0.83 mm thick (22 Gauge)
9.04.03- 1.00 mm thick (20 Gauge)
9.04.04- 1.20 mm thick (18 Gauge)
10.01- Duct Insulation for Normal and Fire-Rated Application. In Accordance with VAC Technical Specifications (Refer Part-2, Section VII, Sub section C, unit 12) and drawings.
10.01.01- 50 mm thick rockwool insulation of 105 kg/m3 density ,Suitable adhesive , and other accessories as per drawing and technical specification.
10.01.02- 50 mm thick rockwool insulation of 120 kg/m3 density ,Suitable adhesive , and other accessories as per drawing and technical specification.
10.01.03- 19 mm thick XLPE insulation of 25-30 kg/m3 density ,Suitable adhesive , and other accessories as per drawing and technical specification.
10.02- 0.6mm thick Aluminium cladding for ducting painted with black color and other accessories in accordance with VAC technical specifications (Refer Part-2, Section VII, Sub section C, unit 12 ) drawings
10.03- 0.6mm thick Stainless steel (SS 316) chicken wire mesh for ducting and VRF with other fixing accessories in accordance with VAC technical specifications (Refer Part-2, Section VII, Sub section C, unit 12 ) drawings
11- Fire Rated Insulated Flexible Ducting and Damper In Accordance with VAC Technical Specifications (Refer Part-2, Section VII, Sub section C, unit 8 ) and drawings.
11.01- Insulated flexible ducting dia 200 mm
11.02- Insulated flexible ducting dia 300 mm
11.03- Butterfly damper dia 200 mm
11.04- Butterfly damper dia 300 mm
12- Factory fabricated flexible duct connector (Canvas) In Accordance with VAC Technical Specifications (Refer Part-2, Section VII, Sub section C, unit 11) and drawings.
12.01- Fire Rated Flexible duct connector(Canvas) for Normal and fire Application
13- Grilles/Diffusers In Accordance with VAC Technical Specifications (Refer Part-2, Section VII, Sub section C, Unit 9) and drawings.
13.01- Square Supply air & Return air diffuser with VCDs (In various sizes like or to suite site)
13.02- Supply air grilles with VCDs (In various sizes like or to suite site)
13.03- Supply/Return/Exhaust Eggcrate Grille with High Temperature VCDs (In various sizes like or to suite site)
13.04- Fresh air grilles with VCDs (In various sizes like or to suite site)
13.05- Exhaust air grilles (In various sizes like or to suite site)
13.06- Staircase Pressurization grilles with VCDs (In various sizes like or to suite site)
13.07- MS Grille for supply and return with High Temperature VCDs (In various sizes like or to suite site)
13.08- Fresh air and exhaust Louvers (VAC & TVS) (In various sizes like or to suite site)
13.09- Acoustic Louvers (In various sizes like or to suite site)
14- Dampers In Accordance with VAC Technical Specifications (Refer Part-2, Section VII, Sub section C, Unit 9) and drawings.
14.01- Volume Control dampers (In various sizes like or to suite site)
14.02- High Temperature Volume Control dampers (In various sizes like or to suite site)
14.03- Fusible link fire damper (In various sizes like or to suite site)
14.04- Motorized Smoke dampers (In various sizes like or to suite site) With actuator and limit switch
14.05- Motorized Fire & Smoke dampers (In various sizes like or to suite site) With actuator and limit switch
14.06- Non Return damper (In various sizes like or to suite site)
14.07- Pressure Relief Damper (In various sizes like or to suite site)
14.08- Access Door for Damper (In various sizes like or to suite site)
15- Cones (Round to Rectangular transition piece) In Accordance with VAC Technical Specifications (Refer Part-2, Section VII, Sub section C, Unit 8) and drawings.
16- Vane Axial flow Fans/Mixed flow fans with necessary fixing arrangement and other accessories In Accordance with VAC Technical Specifications (Refer Part-2, Section VII, Sub section C, Unit 5) and drawings.
16.01- Fresh Air Fan (FAF) with VFD compatible of 2.25cms, 220 Pa External Static Pressure approximately
16.02- Fresh Air Fan (FAF) with VFD compatible of 0.97cms, 110 Pa External Static Pressure approximately
16.03- Fresh Air Fan (FAF) with VFD compatible of 1.09cms, 400 Pa External Static Pressure approximately
16.04- Fresh Air Fan (FAF) with VFD compatible of 2.53cms, 720 Pa External Static Pressure approximately
16.05- Fresh Air Fan (FAF) with VFD compatible of 3.2cms, 470 Pa External Static Pressure approximately
16.06- Fresh Air Fan (FAF) with VFD compatible of 2.22cms, 170 Pa External Static Pressure approximately
16.07- Fresh Air Fan (FAF) with VFD compatible of 3.66cms, 710 Pa External Static Pressure approximately
16.08- Fresh Air Fan (FAF) with VFD compatible of 3.6cms, 570 Pa External Static Pressure approximately
16.09- Fresh Air Fan (FAF) with VFD compatible of 3.3cms, 330 Pa External Static Pressure approximately
16.10- Fresh Air Fan (FAF) with VFD compatible of 2.05 cms, 670 Pa External Static Pressure approximately
16.11- Fresh Air Fan (FAF) with VFD compatible of 1.8cms, 240 Pa External Static Pressure approximately
16.12- Fresh Air Fan (FAF) with VFD compatible of 2.7cms, 740 Pa External Static Pressure approximately
16.13- Fresh Air Fan (FAF) with VFD compatible of 2.24cms, 700 Pa External Static Pressure approximately
16.14- Fresh Air Fan (FAF) with VFD compatible of 5.27cms, 450 Pa External Static Pressure approximately
16.15- Fresh Air Fan (FAF) with VFD compatible of 3.77cms, 430 Pa External Static Pressure approximately
16.16- Fresh Air Fan (FAF) with VFD compatible of 3.29cms, 680 Pa External Static Pressure approximately
16.17- Fresh Air Fan (FAF) with VFD compatible of 1.94cms, 510 Pa External Static Pressure approximately
16.18- Fresh Air Fan (FAF) with VFD compatible of 1.92cms, 140 Pa External Static Pressure approximately
16.19- Fresh Air Fan (FAF) with VFD compatible of 5.02cms, 580 Pa External Static Pressure approximately
16.20- Fresh Air Fan (FAF) with VFD compatible of 1.92cms, 380 Pa External Static Pressure approximately
16.21- Staircase Pressurization Fan (SPF) 10.4 cms, 370 Pa External Static Pressure approximately
16.22- Staircase Pressurization Fan (SPF) 10.6 cms, 220 Pa External Static Pressure approximately
16.23- Staircase Pressurization Fan (SPF) 10.85 cms, 270 Pa External Static Pressure approximately
16.24- Staircase Pressurization Fan (SPF) 8.2 cms, 560 Pa External Static Pressure approximately
16.25- Staircase Pressurization Fan (SPF) 16.55cms, 390 Pa External Static Pressure approximately
16.26- Staircase Pressurization Fan (SPF) 15.5cms, 870 Pa External Static Pressure approximately
16.27- Staircase Pressurization Fan (SPF) 8.5 cms, 230 Pa External Static Pressure approximately
16.28- Staircase Pressurisation Fan (SPF) 8.35cms, 490 Pa External Static Pressure approximately
16.29- Staircase Pressurization Fan (SPF) 15.5 cms, 870 Pa External Static Pressure approximately
16.30- Staircase Pressurization Fan (SPF) 10.6 cms, 450 Pa External Static Pressure approximately
16.31- Staircase Pressurization Fan (SPF) 17.65 cms, 780 Pa External Static Pressure approximately
16.32- Staircase Pressurization Fan (SPF) 13.6 cms, 530 Pa External Static Pressure approximately
16.33- Staircase Pressurisation Fan (SPF) 16.65cms, 540 Pa External Static Pressure approximately
16.34- Staircase Pressurization Fan (SPF) 18.15 cms, 950 Pa External Static Pressure approximately
16.35- Staircase Pressurization Fan (SPF) 10.85 cms, 540 Pa External Static Pressure approximately
17- Cabinet (Box type) centrifugal fans with necessary fixing arrangement and other accessories In Accordance with VAC Technical Specifications (Refer Part-2, Section VII, Sub section C, Unit 5) and drawings. Belt driven fans are not acceptable.
17.01- Toilet Supply Fan (TSF), 2.15 cms 340 Pa External Static Pressure approximately
17.02- Toilet exhaust Fan (TEF), 2.5 cms, 400 Pa External Static Pressure approximately
17.03- Toilet Supply Fan (TSF), 2.34 cms 810 Pa External Static Pressure approximately
17.04- Toilet exhaust Fan (TEF), 2.6 cms, 580 Pa External Static Pressure approximately
17.05- Toilet Supply Fan (TSF), 3.04 cms 340 Pa External Static Pressure approximately
17.06- Toilet exhaust Fan (TEF), 3.37 cms, 660 Pa External Static Pressure approximately
17.07- Toilet Supply Fan (TSF), 3.64 cms 400 Pa External Static Pressure approximately
17.08- Toilet exhaust Fan (TEF), 4.05 cms, 750 Pa External Static Pressure approximately
17.09- Toilet Supply Fan (TSF), 2.71 cms 300 Pa External Static Pressure approximately
17.10- Toilet exhaust Fan (TEF), 3.01 cms, 400 Pa External Static Pressure approximately
17.11- Toilet Supply Fan (TSF), 2.04 cms 680 Pa External Static Pressure approximately
17.12- Toilet exhaust Fan (TEF), 2.27 cms, 710 Pa External Static Pressure approximately
17.13- Toilet Supply Fan (TSF), 2.79 cms 1020 Pa External Static Pressure approximately
17.14- Toilet exhaust Fan (TEF), 3.094 cms, 570 Pa External Static Pressure approximately
17.15- Toilet Supply Fan (TSF), 3.00 cms 530 Pa External Static Pressure approximately
17.16- Toilet exhaust Fan (TEF), 3.34 cms, 810 Pa External Static Pressure approximately
18- Propeller Fans with necessary fixing arrangement and other accessories In Accordance with VAC Technical Specifications (Refer Part-2, Section VII, Sub section C, Unit 5) and drawings.
18.01- 355 mm diameter
18.02- 400 mm diameter
18.03- 500 mm diameter
19- Air Curtains with necessary fixing arrangement and other accessories In Accordance with VAC Technical Specifications (Refer Part-2, Section VII, Sub section C, Unit 6) and drawings.
19.01- 2000 mm length
19.02- 1500 mm length
19.03- 1000 mm length
20- Tile fan (False Ceiling fan) with necessary fixing arrangement and other accessories In Accordance with VAC Technical Specifications (Refer Part-2, Section VII, Sub section C, Unit 5 ).
20.01- 603 mm X 603 mm
21- High Volume Low Speed Fan (HVLS) with necessary fixing arrangement and other accessories In Accordance with VAC Technical Specifications (Refer Part-2, Section VII, Sub section C, Unit 7) and drawings.
22.01- Attenuator in AHU - (2800mm W x 1500mm H x 2400mm L)
22.02- Attenuator in AHU - (2600mm W x 1550mm H x 1500mm L)
22.03- Attenuator in AHU - (2600mm W x 1700mm H x 1500mm L)
22.04- Attenuator in AHU - (2500mm W x 2000mm H x 1500mm L)
22.05- Attenuator in AHU - (2500mm W x 1000mm H x 1500mm L)
22.06- Attenuator in AHU - (2500mm W x 1800mm H x 600mm L)
22.07- Attenuator in AHU - (2500mm W x 2000mm H x 1200mm L)
22.08- Attenuator in AHU - (2500mm W x 1650mm H x 1500mm L)
22.09- Attenuator in AHU - (2500mm W x 1500mm H x 600mm L)
22.10- Attenuator in AHU - (1700mm W x 1150mm H x 900mm L)
22.11- Attenuator in AHU - (1650mm W x 1500mm H x 1500mm L)
22.12- Attenuator in AHU - (2250mm W x 800mm H x 600mm L)
22.13- Attenuator in AHU - (2050mm W x 1650mm H x 900mm L)
22.14- Attenuator in AHU - (2000mm W x 2250mm H x 1200mm L)
22.15- Attenuator in AHU - (2000mm W x 1500mm H x 600mm L)
22.16- Attenuator in AHU - (2000mm W x 1450mm H x 1500mm L)
22.17- Attenuator in AHU - (1750mm W x 1400mm H x 1000mm L)
22.18- Attenuator in AHU - (1500mm W x 1050mm H x 1200mm L)
22.19- Attenuator in AHU - (1700mm W x 1150mm H x 600mm L)
22.20- Attenuator in AHU - (1600mm W x 1400mm H x 900mm L)
22.21- Attenuator in AHU - (1600mm W x 1100mm H x 1500mm L)
22.22- Attenuator in AHU - (1500mm W x 2500mm H x 1200mm L)
22.23- Attenuator in AHU - (1500mm W x 1000mm H x 600mm L)
22.24- Attenuator in AHU - (1500mm W x 900mm H x 600mm L)
22.25- Attenuator in AHU - (1500mm W x 1050mm H x 1200mm L)
22.26- Attenuator in AHU - (1500mm W x 950mm H x 1500mm L)
22.27- Attenuator in AHU - (1400mm W x 1200mm H x 1800mm L)
22.28- Attenuator in AHU - (1400mm W x 1200mm H x 1200mm L)
22.29- Attenuator in AHU - (1400mm W x 1100mm H x 1000mm L)
22.30- Attenuator in AHU - (1400mm W x 1000mm H x 1500mm L)
22.31- Attenuator in AHU - (1100mm W x 600mm H x 900mm L)
22.32- Attenuator in AHU - (900mm W x 500mm H x 600mm L)
22.33- Attenuator in AHU - (1350mm W x 1000mm H x 600mm L)
22.34- Attenuator in AHU - (1250mm W x 950mm H x 1200mm L)
22.35- Attenuator in AHU - (1200mm W x 1000mm H x 600mm L)
22.36- Attenuator in AHU - (1200mm W x 900mm H x 1000mm L)
22.37- Attenuator in AHU - (1150mm W x 900mm H x 1800mm L)
22.38- Attenuator in AHU - (1150mm W x 900mm H x 1500mm L)
22.39- Attenuator in AHU - (1000mm W x 850mm H x 1800mm L)
22.4- Attenuator in SPF - (2500mm W x 1500mm H x 1500mm L)
22.41- Attenuator in SPF - (2500mm W x 1500mm H x 1200mm L)
22.42- Attenuator in SPF - (2500mm W x 1500mm H x 900mm L)
22.43- Attenuator in SPF - (2500mm W x 1500mm H x 600mm L)
22.44- Attenuator in SPF - (1600mm W x 1200mm H x 600mm L)
22.45- Attenuator in SPF - (2200mm W x 1900mm H x 600mm L)
22.46- Attenuator in SPF - (2000mm W x 1250mm H x 900mm L)
22.47- Attenuator in SPF - (2000mm W x 1250mm H x 600mm L)
22.48- Attenuator for AHU
23- 50mm thick Rock wool insulation, Density 105 Kg/m3 acoustic lining , finished with 0.80 mm perforated aluminium sheet with necessary fixing arrangement and other accessories In Accordance with VAC Technical Specifications (Refer Part-2, Section VII, Sub section C, Unit 10) and drawings.
24- Fire Stopper with necessary fixing arrangement and other accessories In Accordance with VAC Technical Specifications (Refer Part-2, Section VII, Sub section C, Unit 14) and drawings.
25- Design, fabrication, supply, and erection of a hot-dip galvanized steel structure, compliant with ASTM standards and having a minimum 80-micron coating thickness, along with other accessories for supporting Fans, Attenuators and Air curtain to provide a complete solution in all aspects.
26- Design,Providing and laying RCC foundation for supporting Fans ,AHU ,VRF/Chiller for complete in all aspect.
27- Measurement Instruments with necessary probes and casing In Accordance with VAC Technical Specifications (Refer Part-2, Section VII, Sub section C, Unit 15.10).
27.1-Thermal Imager
27.2-Multipurpose Air Capture Hood
27.3-Multifunctional Measurement device for IAQ Measurement
27.4-Portable Digital 4-Way Manifold gauge for VRF System.
27.5-Refrigerant gas leak detection device
Description of Work / Item(s)
Amount
PRICE CENTRE - D (TVS WORKS)
2- Manufacture, Supply, Delivery, Installation, Testing (Factory acceptance test, Partial acceptance test & System Acceptance Testing), Integrated Testing Commissioning & DLP of following equipment's / materials
3- TUNNEL VENTILATION FAN UNITS In Accordance with TVS Technical Specifications (Refer Part-2, Section VII, Sub section B, Content 2 - FAN AND MOTOR UNITS) and Drawings
3.01- Truly Reversible Multi Duty point axial flow fans, 415V / 3 PHASE / 50Hz, 2.3m-2.6m Impeller diameter Range, 100/100 cum/s, ESP 1230/1260 Pa (Duty points 1/2 Respectively) with their VFD compatible motor
3.02- Truly Reversible Multi Duty point axial flow fans, 415V / 3 PHASE / 50Hz, 2.3m-2.6m Impeller diameter Range, 100/100/60 cum/s, ESP 1060/1000/1400 Pa (Duty points 1/2/3 Respectively) with their VFD compatible motor
3.03- Truly Reversible Multi Duty point axial flow fans, 415V / 3 PHASE / 50Hz, 1.4m-1.8m Impeller diameter Range, 40/20 cum/s, ESP 890/560 Pa (Duty points 1/2 Respectively) with their VFD compatible motor
3.04- Truly Reversible Multi Duty point axial flow fans, 415V / 3 PHASE / 50Hz, 1.8m-2.2m Impeller diameter Range, 60/60/60 cum/s, ESP 1510/660/1070 Pa (Duty points 1/2/3 Respectively) with their VFD compatible motor
3.05- Uni-directional Multi Duty point axial flow fans, 415V / 3 PHASE / 50Hz, 1.2m-1.6m Impeller diameter Range, 20/20/23.6/10 cum/s, ESP 640/470/1380/1130 Pa (Duty points 1/2/3/4 Respectively) with their VFD compatible motor
3.06- Uni-directional Multi Duty point axial flow fans, 415V / 3 PHASE / 50Hz, 1.2m-1.6m Impeller diameter Range, 20/20/16.4 cum/s, ESP 650/470/1050 Pa (Duty points 1/2/3 Respectively) with their VFD compatible motor
3.07- Truly Reversible Multi Duty point axial flow fans, 415V / 3 PHASE / 50Hz, 1.8m-2.2m Impeller diameter Range, 60/60/60/60/60 cum/s, ESP 1430/590/1670/950/830 Pa (Duty points 1/2/3/4/5 Respectively) with their VFD compatible motor
3.08- Uni-directional Multi Duty point axial flow fans, 415V / 3 PHASE / 50Hz, 1.4m-1.8m Impeller diameter Range, 40/20/20/30/30 cum/s, ESP 1340/430/970/850/990 Pa (Duty points 1/2/3/4/5 Respectively) with their VFD compatible motor
3.09- Truly Reversible Multi Duty point axial flow fans, VERTICALLY MOUNTED, 415V / 3 PHASE / 50Hz, 1.8m-2.2m Impeller diameter Range, 60/60/60/60 cum/s, 1420/620/1770/1230 Pa (Duty points 1/2/3/4 Respectively) with their VFD compatible motor
3.1- Uni-directional Multi Duty point axial flow fans, 415V / 3 PHASE / 50Hz, 1.4m-1.8m Impeller diameter Range, 40/20 cum/s, 1230/540 Pa (Duty points 1/2 Respectively) with their VFD compatible motor
3.11- Truly Reversible Multi Duty point axial flow fans, 415V / 3 PHASE / 50Hz, 2.3m-2.6m Impeller diameter Range, 60/60/100/100 cum/s, ESP 1670/1120/1120/1060 Pa (Duty points 1/2/3/4 Respectively) with their VFD compatible motor
3.12- Truly Reversible Multi Duty point axial flow fans, 415V / 3 PHASE / 50Hz, 2.3m-2.6m Impeller diameter Range, 100/100/60/100 cum/s, ESP 1090/990/1450/1310 Pa (Duty points 1/2/3/4 Respectively) with their VFD compatible motor
3.13- Uni-directional Multi Duty point axial flow fans, 415V / 3 PHASE / 50Hz, 1.4m-1.8m Impeller diameter Range, 40/20 cum/s, ESP 1110/340 Pa (Duty points 1/2 Respectively) with their VFD compatible motor
3.14- Truly Reversible Multi Duty point axial flow fans, 415V / 3 PHASE / 50Hz, 1.8m-2.2m Impeller diameter Range, 60/60/60/60/60 cum/s, ESP 1510/590/1660/900/810 Pa (Duty points 1/2/3/4/5 Respectively) with their VFD compatible motor
3.15- Uni-directional Multi Duty point axial flow fans, 415V / 3 PHASE / 50Hz, 1.4m-1.8m Impeller diameter Range, 40/20/20/30/30 cum/s, ESP 1140/380/1200/1160/950 Pa (Duty points 1/2/3/4/5 Respectively) with their VFD compatible motor
4- STATION SMOKE EXTRACTION FAN UNITS In Accordance with TVS Technical Specifications (Refer Part-2, Section VII, Sub section B, Content 2 - FAN AND MOTOR UNITS) and VAC drawings
4.01- Uni-directional Multi Duty point axial flow fans, 415V / 3 PHASE / 50Hz, 0.8m-1.2m Impeller diameter Range, 3.5/8.4 cum/s, ESP 450/1020 Pa (Duty points 1/2 Respectively) with their VFD compatible motor
4.02- Uni-directional Multi Duty point axial flow fans, 415V / 3 PHASE / 50Hz, 1.4m-1.8m Impeller diameter Range, 40/30/30 cum/s, ESP 1200/1160/1170 Pa (Duty points 1/2/3 Respectively) with their VFD compatible motor
4.03- Uni-directional Multi Duty point axial flow fans, 415V / 3 PHASE / 50Hz, 1.4m-1.8m Impeller diameter Range, 20/30/30 cum/s, ESP 1200/1260/950 Pa (Duty points 1/2/3/4/5 Respectively) with their VFD compatible motor
4.04- Uni-directional Multi Duty point axial flow fans, 415V / 3 PHASE / 50Hz, 0.7m-1.1m Impeller diameter Range, 7.36/9.75 cum/s, ESP 1270/1390 Pa (Duty points 1/2 Respectively) with their VFD compatible motor
4.05- Uni-directional Multi Duty point axial flow fans, 415V / 3 PHASE / 50Hz, 1.05m-1.45m Impeller diameter Range, 15 cum/s, ESP 550 Pa (Duty points 1 Respectively) with their VFD compatible motor
4.06- Uni-directional Multi Duty point axial flow fans, 415V / 3 PHASE / 50Hz, 1.2m-1.6m Impeller diameter Range, 30 cum/s, ESP 990 Pa (Duty points 1 Respectively) with their VFD compatible motor
5- TUNNEL VENTILATION MOTORISED DAMPER UNIT In Accordance with TVS Technical Specifications (Refer Part-2, Section VII, Sub section B, Content 3 - DAMPERS AND DAMPER ACTUATORS) and Drawings
5.01- Damper size: 3600mm X 5600mm
5.02- Damper size: 4000mm X 1500mm
5.03- Damper size: 3900mm X 1400mm
5.04- Damper size: 5000mm X 2000mm
5.05- Damper size: 3365mm X 1350mm
5.06- Damper size: 2500mm X 1600mm
5.07- Damper size: 2500mm X 2500mm
5.08- Damper size: 5500mm X 3650mm
5.09- Damper size: 3500mm X 3500mm
5.1- Damper size: 3300mm X 3050mm
5.11- Damper size: 2800mm X 2150mm
5.12- Damper size: 7500mm X 2670mm
5.13- Damper size: 7700mm X 2600mm
5.14- Damper size: 2200mm X 2100mm
5.15- Damper size: 3000mm X 2000mm
5.16- Damper size: 2350mm X 1700mm
5.17- Damper size: 5750mm X 3600mm
5.18- Damper size: 3900mm X 2600mm
5.19- Damper size: 2750mm X 2100mm
5.2- Damper size: 4450mm X 4300mm
5.21- Damper size: 3550mm X 2834mm
5.22- Damper size: 4900mm X 4100mm
5.23- Damper size: 2500mm X 2000mm
5.24- Damper size: 7850mm X 2600mm
5.25- Damper size: 3850mm X 2600mm
5.26- Damper size: 3500mm X 1850mm
5.27- Damper size: 4800mm X 4050mm
5.28- Damper size: 4500mm X 4500mm
5.29- Damper size: 5400mm X 3900mm
5.30- Damper size: 4000mm X 3650mm
5.31- Damper size: 3250mm X 1950mm
5.32- Damper size: 4750mm X 4200mm
5.33- Damper size: 5000mm X 4000mm
5.34- Damper size: 8500mm X 2600mm
5.35- Damper size: 4000mm X 2500mm
5.36- Damper size: 3600mm X 2500mm
6- TUNNEL VENTILATION SOUND ATTENUATORS In Accordance with TVS Technical Specifications (Refer Part-2, Section VII, Sub section B , Content 5 - SOUND ATTENUATORS) and Drawings
6.01- Sound attenuators for TVF: 3.5m(W) x 3.5m(H) x 2.15m(L)
6.02- Sound attenuators for TVF: 3.5m(W) x 3.5m(H) x 1.5m(L)
6.03- Sound attenuators for TVF: 3.5m(W) x 3.5m(H) x 1.0m(L)
6.04- Sound attenuators for OTEF, 2.5m(W) x 2.5m(H) x 1.705m(L)
6.05- Sound attenuators for OTEF, 2.35m(W) x 1.7m(H) x 1.705m(L)
6.06- Sound attenuators for OTEF, 3.25m(W) x 1.95m(H) x 1.705m(L)
6.07- Sound attenuators for OTEF, 4.5m(W) x 3.35m(H) x 1.705m(L)
6.08- Sound attenuators for SEF, 3.0m(W) x 3.0m(H) x 1.705m(L)
6.09- Sound attenuators for SEF, 3.5m(W) x 2.8m(H) x 1.705m(L)
6.1- Sound attenuators for SEF, 1.5m(W) x 1.15m(H) x 1.705m(L)
6.11- Sound attenuators for SEF, 2.0m(W) x 2.0m(H) x 1.5m(L)
6.12- Sound attenuators for SEF, 1.2m(W) x 1.0m(H) x 2.15m(L)
6.13- Sound attenuators for SEF, 1.0m(W) x 1.2m(H) x 1.8m(L)
7- SLIDING PLATE DAMPERS for Overtrack Exhaust. In Accordance with TVS Technical Specifications (Refer Part-2, Section VII, Sub section B, Content 6 - OTE SLIDING PLATE DAMPERS)
8- TUNNEL VENTILATION NOZZLES.- In Accordance with TVS Technical Specifications & Drawings, (Refer Part-2, Section VII, Sub section B, Content 8 - NOZZLES) Nozzles Design and supports to suite the Drawings.
9- FLEXIBLE CONNECTOR - In Accordance with TVS Technical Specifications (Refer Part-2, Section VII, Sub section B, Content 4 - FLEXIBLE CONNECTORS FOR TVF AND OTEF FANS) and Drawings
10- TUNNEL VENTILATION FAN TRANSITION PIECES - In Accordance with TVS Technical Specifications (Refer Part-2, Section VII, Sub Section B, Chapter 7 - TRASITION PIECES (CONES)) and TVS drawings
10.01- Transition Piece: 2300-2600mm round internal diameter to 3500mm x 3500mm (internal) rectangle; Length: 2m
10.02- Transition Piece: 1800-2200mm round internal diameter to 3500mm x 3500mm (internal) rectangle; Length: 2m
10.03- Transition Piece: 1200-1600mm round internal diameter to 2350mm x 1700mm (internal) rectangle; Length: 1.2m
10.04- Transition Piece: 1400-1800mm round internal diameter to 2500mm x 2500mm (internal) rectangle; Length: 1.2m
10.05- Transition Piece: 1400-1800mm round internal diameter to 3250mm x 1950mm (internal) rectangle; Length: 2m
10.06- Transition Piece: 1050-1450mm round internal diameter to 2000mm x 2000mm (internal) rectangle; Length: 0.91m
10.07- Transition Piece: 700-1100mm round internal diameter to 800mm x 800mm (internal) rectangle; Length: 0.4m
10.08- Transition Piece: 1200-1600mm round internal diameter to 2000mm x 2000mm (internal) rectangle; Length: 0.725m
10.09- Transition Piece: 800-1200mm round internal diameter to 1200mm x 800mm (internal) rectangle; Length: 0.4m
11-Fire rated leakproof Access door (Size - 600 mm x 600 mm) In Accordance with TVS Technical Specifications (Refer Part-2, Section VII, Sub section B, Content 6 - OTE SLIDING PLATE DAMPERS)
12- Design, fabrication, supply, and erection of a hot-dip galvanized steel structure, compliant with ASTM standards and having a minimum 80-micron coating thickness, along with other accessories for supporting fans, attenuators, and cones (Transition Piece) to provide a complete solution in all aspects.
Description of Work / Item(s)
Amount
1- PRICE CENTRE E - VAC & TVS ELECTRICAL WORKS
2 - General Manufacture, Supply, Delivery, Installation, Testing (Factory acceptance test,Partial acceptance test & System Acceptance Testing), Integrated Testing Commissioning & DLP of following equipment's / materials
3 - LV Switchboards / MCC's / Distribution Boards
3.1 - VAC PANEL - NON ESSENTIAL -Smart Panel with Mimic Diagram,TTA form 4b, type 6 panel, IP54 conforming to specification as specified in Part-2 section VII sub section D Unit-02 and drawings. (Fully Front Accessible panel)
3.1.2 - Busbar : rated 400 Amps, suitable to withstand symmetrical fault level of 25kA for 1 sec. at 415V as specified in Part-2 section VII sub section D Unit-02 Clause 2.6
3.1.3 - ISMS Connectivity: All the breakers should be provided with control and monitoring facilities,Smart Panel facility with Local touch screen, control panel in front side of the panel. Required PLCs ,relays, contactors ,IO cards, Ethernet switches,SMPS,Control Transformers, cabling works., etc. for functional requirement as specified in Part-2 Section VII Subsection D Unit No.2 Clause 2.28 and drawings. Smart Panel shall be interfacing with ISMS system through Modbus TCP/IP for Control & monitoring.
3.1.4 - OUTGOING FEEDERS
3.1.7 - 32A,TP MCCB, 415V, 25kA suitable space provision for 7.5kW VFD unit (FAF) . Having microprocessor trip unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.1.8 - 32A,TP MCCB, 415V, 25kA suitable space provision for 0.55kW VFD unit (FAF) . Having microprocessor trip unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.1.9 - 16A,TP MPCB, 415V, 25kA with 3kW DOL unit (TSF) . Having microprocessor trip unit with over load, short circuit. And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.1.10 - 16A,TP MPCB, 415V, 25kA with 4kW DOL unit (TEF) . Having microprocessor trip unit with over load, short circuit. And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.1.11 - 32A,4P MCCB, 415V, 25kA Having microprocessor trip unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.1.12 - SPARE:-
3.1.13 - 63A,TPN MCCB, 415V, 25kA. Having microprocessor trip unit with adjustable protection against over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.
3.1.14 - 32A,4P MCCB, 415V, 25kA. Having microprocessor trip unit with adjustable protection against over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.
3.1.15 - Panel Enclosure & other Accessories (Exhaust fan, louvers, etc.) as specified in Part-2 section VII sub section D Unit-02 Clause 2.4
3.2 - VAC PANEL -01- NON ESSENTIAL (Smart Panel) with Mimic Diagram,TTA form 4b, type 6 panel, IP54 conforming to specification as specified in Part-2 section VII sub section D Unit-02 and drawings. (Fully Front Accessible panel)
3.2.2 - Busbar : rated 1000 Amps, suitable to withstand symmetrical fault level of 50kA for 1 sec. at 415V as specified in Part-2 section VII sub section D Unit-02 Clause 2.6
3.2.3 - ISMS Connectivity: All the breakers should be provided with control and monitoring facilities,Smart Panel facility with Local touch screen, control panel in front side of the panel. Required PLCs ,relays, contactors ,IO cards, Ethernet switches,SMPS,Control Transformers, cabling works., etc. for functional requirement as specified in Part-2 Section VII Subsection D Unit No.2 Clause 2.28 and drawings. Smart Panel shall be interfacing with ISMS system through Modbus TCP/IP for Control & monitoring.
3.2.4 - OUTGOING FEEDERS
3.2.5 - 800A,4P ACB,415V,50kA. Having microprocessor trip unit with adjustable protection against over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.and lamp test push button
3.2.8 - 32A TP MCCB, 415V, 25kA suitable space provision for 5.5 kW VFD unit (FAF) Having microprocessor trip unit with adjustable protection against over load, short circuit, earth fault. And LED indication lamps for ON,OFF,TRIP Start/stop, Emergency stop push buttons.
3.2.9 - 32A,TP MCCB, 415V, 25kA suitable space provision for 3kW VFD unit (FAF) . Having microprocessor trip unit with adjustable protection against over load, short circuit, earth fault. And LED indication lamps for ON,OFF,TRIP Start/stop, Emergency stop push buttons.
3.2.10 - 16A,TP MPCB, 415V, 25kA with 3kW DOL Starter unit (TSF) . Having microprocessor trip unit with over load, short circuit. And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.2.11 - 16A,TP MPCB, 415V, 25kA with 5.5kW DOL Starter unit (TEF) . Having microprocessor trip unit with over load, short circuit. And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.2.12 - SPARE:-
3.2.13 - 63A,TPN MCCB,415V,25kA. Having microprocessor trip unit with adjustable protection against over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.and lamp test push button
3.2.14 - 32A,TP MCCB,415V,25kA. Having microprocessor trip unit with adjustable protection against over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.and lamp test push button
3.2.15 - Panel Enclosure & other Accessories (Exhaust fan, louvers, etc.) as specified in Part-2 section VII sub section D Unit-02 Clause 2.4
3.3 - VAC PANEL -01- NON ESSENTIAL (Smart Panel)with Mimic Diagram,TTA form 4b, type 6 panel, IP54 conforming to specification as specified in Part-2 section VII sub section D Unit-02 and drawings. (Fully Front Accessible panel)
3.3.2 - Busbar : rated 630 Amps, suitable to withstand symmetrical fault level of 25kA for 1 sec. at 415V as specified in Part-2 section VII sub section D Unit-02 Clause 2.6
3.3.3 - ISMS Connectivity: All the breakers should be provided with control and monitoring facilities,Smart Panel facility with Local touch screen, control panel in front side of the panel. Required PLCs ,relays, contactors ,IO cards, Ethernet switches,SMPS,Control Transformers, cabling works., etc. for functional requirement as specified in Part-2 Section VII Subsection D Unit No.2 Clause 2.28 and drawings. Smart Panel shall be interfacing with ISMS system through Modbus TCP/IP for Control & monitoring.
3.3.4 - OUTGOING FEEDERS
3.3.5 - 400A,4P MCCB,415V,25kA. Having microprocessor trip unit with adjustable protection against over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.and lamp test push button
3.3.8 - 32A, TP MCCB, 415V, 25kA suitable space provision for 3 kW VFD unit (FAF) Having microprocessor trip unit with adjustable protection against over load, short circuit, earth fault. And LED indication lamps for ON,OFF,TRIP Start/stop, Emergency stop push buttons.
3.3.9 - 32A,TP MCCB, 415V, 25kA suitable space provision for 1.5 kW VFD unit (FAF) . Having microprocessor trip unit with adjustable protection against over load, short circuit, earth fault. And LED indication lamps for ON,OFF,TRIP Start/stop, Emergency stop push buttons.
3.3.10 - SPARE:-
3.3.11 - 400A,4P MCCB,415V,25kA. Having microprocessor trip unit with adjustable protection against over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.and lamp test push button
3.3.12 - 63A,TPN MCCB,415V,25kA. Having microprocessor trip unit with adjustable protection against over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.and lamp test push button
3.3.13 - Panel Enclosure & other Accessories (Exhaust fan, louvers, etc.) as specified in Part-2 section VII sub section D Unit-02 Clause 2.4
3.4 - VAC PANEL -01- NON ESSENTIAL (Smart Panel)with Mimic Diagram,TTA form 4b, type 6 panel, IP54 conforming to specification as specified in Part-2 section VII sub section D Unit-02 and drawings. (Fully Front Accessible panel)
3.4.2 - Busbar : rated 630 Amps, suitable to withstand symmetrical fault level of 25kA for 1 sec. at 415V as specified in Part-2 section VII sub section D Unit-02 Clause 2.6
3.4.3 - ISMS Connectivity: All the breakers should be provided with control and monitoring facilities,Smart Panel facility with Local touch screen, control panel in front side of the panel. Required PLCs ,relays, contactors ,IO cards, Ethernet switches,SMPS,Control Transformers, cabling works., etc. for functional requirement as specified in Part-2 Section VII Subsection D Unit No.2 Clause 2.28 and drawings. Smart Panel shall be interfacing with ISMS system through Modbus TCP/IP for Control & monitoring.
3.4.4 - OUTGOING FEEDERS
3.4.5 - 400A,4P MCCB,415V,25kA. Having microprocessor trip unit with adjustable protection against over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.and lamp test push button
3.4.7 - 32A,TP MCCB, 415V, 25kA suitable space provision for 5.5 kW VFD unit (FAF) Having microprocessor trip unit with adjustable protection against over load, short circuit, earth fault. And LED indication lamps for ON,OFF,TRIP Start/stop, Emergency stop push buttons.
3.4.8 - 32A,TP MCCB, 415V, 25kA suitable space provision for 3kW VFD unit (FAF) . Having microprocessor trip unit with adjustable protection against over load, short circuit, earth fault. And LED indication lamps for ON,OFF,TRIP Start/stop, Emergency stop push buttons.
3.4.9 - 16A,TP MPCB, 415V, 25kA with 2.2kW DOL Starter unit (TSF) . Having microprocessor trip unit with over load, short circuit. And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.4.10 - 16A,TP MPCB, 415V, 25kA with 4kW DOL Starter unit (TEF) . Having microprocessor trip unit with over load, short circuit. And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.4.11 - SPARE:-
3.4.12 - 400A,4P MCCB,415V,25kA. Having microprocessor trip unit with adjustable protection against over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.and lamp test push button
3.4.13 - 63A,TPN MCCB,415V,25kA. Having microprocessor trip unit with adjustable protection against over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.and lamp test push button
3.4.14 - Panel Enclosure & other Accessories (Exhaust fan, louvers, etc.) as specified in Part-2 section VII sub section D Unit-02 Clause 2.4
3.3 - VAC PANEL -02
3.3.1 - VAC PANEL -02 - NON ESSENTIAL (Smart Panel)with Mimic Diagram,TTA form 4b, type 6 panel, IP54 conforming to specification as specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.3.3 - Busbar : rated 400 Amps, suitable to withstand symmetrical fault level of 25kA for 1 sec. at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.6
3.3.4 - ISMS Connectivity: All the breakers should be provided with control and monitoring facilities,Smart Panel facility with Local touch screen, control panel in front side of the panel. Required PLCs ,relays, contactors ,IO cards, Ethernet switches,SMPS,Control Transformers, cabling works., etc. for functional requirement as specified in Part-2 Section VII Subsection D Unit No.2 Clause 2.28 and drawings. Smart Panel shall be interfacing with ISMS system through Modbus TCP/IP for Control & monitoring.
3.3.5 - OUTGOING FEEDERS
3.3.6 - 200A,4P MCCB,415V,25kA. Having microprocessor trip unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.
3.3.8 - 32A,TP MCCB, 415V, 25kA suitable space provision for 1.10kW VFD unit (FAF),Having microprocessor trip unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP, Start/stop,lamp test & Emergency stop push buttons.
3.3.9 - 16A,TP MPCB, 415V, 25kA with 2.2kW DOL Starter unit (TSF) . Having microprocessor trip unit with over load, short circuit. And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.3.10 - 16A,TP MPCB, 415V, 25kA with 3.70kW DOL Starter unit (TEF) . Having microprocessor trip unit with over load, short circuit. And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.3.11 - SPARE:-
3.3.12 - 200A,4P MCCB,415V,25kA. Having microprocessor trip unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP,and lamp test push button.
3.3.15 - Panel Enclosure & other Accessories (Exhaust fan, louvers, etc.) as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.4
3.4 - VAC PANEL -02 - NON ESSENTIAL (Smart Panel)with Mimic Diagram,TTA form 4b, type 6 panel, IP54 conforming to specification as specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.4.2 - Busbar : rated 630 Amps, suitable to withstand symmetrical fault level of 25kA for 1 sec. at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.6
3.4.3 - ISMS Connectivity: All the breakers should be provided with control and monitoring facilities,Smart Panel facility with Local touch screen, control panel in front side of the panel. Required PLCs ,relays, contactors ,IO cards, Ethernet switches,SMPS,Control Transformers, cabling works., etc. for functional requirement as specified in Part-2 Section VII Subsection D Unit No.2 Clause 2.28 and drawings. Smart Panel shall be interfacing with ISMS system through Modbus TCP/IP for Control & monitoring.
3.4.4 - OUTGOING FEEDERS
3.4.5 - 630A,4P MCCB,415V,25kA. Having microprocessor trip unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.
3.4.7 - 16A,TP MCCB, 415V, 25kA suitable space provision for 2.2kW VFD unit (FAF),Having microprocessor trip unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP, Start/stop,lamp test & Emergency stop push buttons.
3.4.8 - SPARE:-
3.4.9 - 63A,TPN MCCB,415V,25kA. Having microprocessor trip unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.
3.4.10 - Panel Enclosure & other Accessories (Exhaust fan, louvers, etc.) as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.4
3.5 - VAC PANEL -02 - NON ESSENTIAL (Smart Panel)with Mimic Diagram,TTA form 4b, type 6 panel, IP54 conforming to specification as specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.5.2 - Busbar : rated 200 Amps, suitable to withstand symmetrical fault level of 25kA for 1 sec. at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.6
3.5.3 - ISMS Connectivity: All the breakers should be provided with control and monitoring facilities,Smart Panel facility with Local touch screen, control panel in front side of the panel. Required PLCs ,relays, contactors ,IO cards, Ethernet switches,SMPS,Control Transformers, cabling works., etc. for functional requirement as specified in Part-2 Section VII Subsection D Unit No.2 Clause 2.28 and drawings. Smart Panel shall be interfacing with ISMS system through Modbus TCP/IP for Control & monitoring.
3.5.4 - OUTGOING FEEDERS
3.5.6 - 32A,TP MCCB, 415V, 25kA suitable space provision for 7.5kW VFD unit (FAF),Having microprocessor trip unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP, Start/stop,lamp test & Emergency stop push buttons.
3.5.7 - SPARE:-
3.5.8 - 63A,TPN MCCB,415V,25kA. Having microprocessor trip unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.
3.5.9 - Panel Enclosure & other Accessories (Exhaust fan, louvers, etc.) as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.4
3.6 - VAC PANEL - NON ESSENTIAL (Smart Panel) with Mimic Diagram,TTA form 4b, type 6 panel, IP54 conforming to specification as specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.6.2 - Busbar : rated 1000 Amps, suitable to withstand symmetrical fault level of 50kA for 1 sec. at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.6
3.6.3 - ISMS Connectivity: All the breakers should be provided with control and monitoring facilities,Smart Panel facility with Local touch screen, control panel in front side of the panel. Required PLCs ,relays, contactors ,IO cards, Ethernet switches,SMPS,Control Transformers, cabling works., etc. for functional requirement as specified in Part-2 Section VII Subsection D Unit No.2 Clause 2.28 and drawings. Smart Panel shall be interfacing with ISMS system through Modbus TCP/IP for Control & monitoring.
3.6.4 - OUTGOING FEEDERS
3.6.8 - 800A,4P, ACB, 415V, 50kA, . Having microprocessor trip unit with adjustable protection against over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP .
3.6.9 - 32A,4P MCCB, 415V, 25kA, . Having microprocessor trip unit with adjustable protection against over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.
3.6.10 - 32A,TP MCCB, 415V, 25kA suitable space provision for 4kW VFD unit (FAF) . Having microprocessor trip unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.6.11 - 32A,TP MCCB, 415V, 25kA suitable space provision for 3kW VFD unit (FAF) . Having microprocessor trip unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.6.12 - 16A,TP MPCB, 415V, 25kA with 3kW DOL Starter unit (TSF/TEF) . Having microprocessor trip unit with over load, short circuit. And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.6.13 - SPARES:-
3.6.14 - 100A,TPN MCCB, 415V, 25kA, . Having microprocessor trip unit with adjustable protection against over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.
3.6.15 - 63A,TPN MCCB, 415V, 25kA, . Having microprocessor trip unit with adjustable protection against over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.
3.6.16 - Panel Enclosure & other Accessories (Exhaust fan, louvers, etc.) as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.4
3.7 - VAC PANEL - NON ESSENTIAL (Smart Panel) with Mimic Diagram,TTA form 4b, type 6 panel, IP54 conforming to specification as specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.7.2 - Busbar : rated 400 Amps, suitable to withstand symmetrical fault level of 25kA for 1 sec. at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.6
3.7.3 - ISMS Connectivity: All the breakers should be provided with control and monitoring facilities,Smart Panel facility with Local touch screen, control panel in front side of the panel. Required PLCs ,relays, contactors ,IO cards, Ethernet switches,SMPS,Control Transformers, cabling works., etc. for functional requirement as specified in Part-2 Section VII Subsection D Unit No.2 Clause 2.28 and drawings. Smart Panel shall be interfacing with ISMS system through Modbus TCP/IP for Control & monitoring.
3.7.4 - OUTGOING FEEDERS
3.7.8 - 32A,TP MCCB, 415V, 25kA suitable space provision for 5.5kW VFD unit (FAF) . Having Micro processor trip unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.7.9 - 32A,TP MCCB, 415V, 25kA suitable space provision for 2.2kW VFD unit (FAF) . Having Micro processor trip unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.7.10 - 32A,TP MCCB, 415V, 25kA suitable space provision for 4kW VFD unit (FAF) . Having Micro processor trip unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.7.11 - 16A,TP MPCB, 415V, 25kA with 5.50kW DOL Starter unit (TSF) . Having microprocessor trip unit with over load, short circuit. And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.7.12 - 16A,TP MPCB, 415V, 25kA with 3.0kW DOL Starter unit (TEF) . Having microprocessor unit with over load, short circuit. And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.7.13 - 32A,4P,415V,25kA, MCCB with Start/stop push buttons , Having Micro processor trip unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.
3.7.14 - SPARES:-
3.7.15 - 100A,TP MCCB, 415V, 25kA, . Having microprocessor trip unit with adjustable protection against over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.
3.7.16 - 63A,TP MCCB, 415V, 25kA, . Having microprocessor trip unit with adjustable protection against over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.
3.7.17 - Panel Enclosure & other Accessories (Exhaust fan, louvers, etc.) as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.4
3.8 - VAC PANEL -01 NON ESSENTIAL (Smart Panel) with Mimic Diagram,TTA form 4b, type 6 panel, IP54 conforming to specification as specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.8.2 - Busbar : rated 630 Amps, suitable to withstand symmetrical fault level of 36kA for 1 sec. at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.6
3.8.3 - ISMS Connectivity: All the breakers should be provided with control and monitoring facilities,Smart Panel facility with Local touch screen, control panel in front side of the panel. Required PLCs ,relays, contactors ,IO cards, Ethernet switches,SMPS,Control Transformers, cabling works., etc. for functional requirement as specified in Part-2 Section VII Subsection D Unit No.2 Clause 2.28 and drawings. Smart Panel shall be interfacing with ISMS system through Modbus TCP/IP for Control & monitoring.
3.8.4 - OUTGOING FEEDERS
3.8.7 - 32A,TP MCCB, 415V, 25kA suitable space provision for 1.50kW VFD unit (FAF) . Having micro processor trip unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.8.8 - 32A,TP MCCB, 415V, 25kA suitable space provision for 0.25kW VFD unit (FAF) . Having micro processor trip unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.8.9 - 63A,4P, MCCB, 415V, 25kA. Having micro processor unit with adjustable protection against over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.
3.8.10 - 400A,4P MCCB, 415V, 25kA, . Having micro processor trip unit with adjustable protection against over load, short circuit, earth fault. And LED indication lamps for ON,OFF,TRIP.
3.8.11 - SPARE
3.8.12 - 400A,4P MCCB, 415V, 25kA, . Having micro processor trip unit with adjustable protection against over load, short circuit, earth fault. And LED indication lamps for ON,OFF,TRIP.
3.8.13 - 63A,4P, MCCB, 415V, 25kA. Having micro processor unit with adjustable protection against over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.
3.8.14 - Panel Enclosure & other Accessories (Exhaust fan, louvers, etc.) as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.4
3.9 - VAC PANEL -02 NON ESSENTIAL (Smart Panel) with Mimic Diagram,TTA form 4b, type 6 panel, IP54 conforming to specification as specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.9.2 - Busbar : rated 630 Amps, suitable to withstand symmetrical fault level of 25kA for 1 sec. at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.6
3.9.3 - ISMS Connectivity: All the breakers should be provided with control and monitoring facilities,Smart Panel facility with Local touch screen, control panel in front side of the panel. Required PLCs ,relays, contactors ,IO cards, Ethernet switches,SMPS,Control Transformers, cabling works., etc. for functional requirement as specified in Part-2 Section VII Subsection D Unit No.2 Clause 2.28 and drawings. Smart Panel shall be interfacing with ISMS system through Modbus TCP/IP for Control & monitoring.
3.9.4 - OUTGOING FEEDERS
3.9.7 - 32A,TP MCCB, 415V, 25kA suitable space provision for 4kW VFD unit (FAF) . Having microprocessor trip unit unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.9.8 - 32A,TP MCCB, 415V, 25kA suitable space provision for 1.5kW VFD unit (FAF) . Having microprocessor trip unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.9.9 - 100A,TP MCCB,415V,25kA.suitable space provision for 37kW VFD (EXF), Having microprocessor trip unit with adjustable protection against over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP, Start/stop,Emergency stop push buttons.
3.9.10 - 16A,TP MPCB, 415V, 16kA.suitable 5.5KW (TSF), Star-Delta starter with over load, short circuit. And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.9.11 - 16A,TP MPCB, 415V, 16kA. With 3KW (TEF), DOL starter with over load, short circuit. And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.9.12 - 400A,4P MCCB, 415V, 25kA, . Having Mirocprocessor trip unit with adjustable protection against over load, short circuit and adjustable earth fault .And LED indication lamps for ON,OFF,TRIP.
3.9.13 - SPARE
3.9.14 - 400A,4P MCCB, 415V, 25kA, . Having Mirocprocessor trip unit with adjustable protection against over load, short circuit and adjustable earth fault .And LED indication lamps for ON,OFF,TRIP.
3.9.15 - 63A,TPN MCCB, 415V, 25kA. Having microprocessor trip unit with adjustable protection against over load, short circuit and adjustable earth fault , And LED indication lamps for ON,OFF,TRIP.
3.9.16 - Panel Enclosure & other Accessories (Exhaust fan, louvers, etc.) as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.4
3.1 - VAC PANEL - NON ESSENTIAL (Smart Panel) with Mimic Diagram,TTA form 4b, type 6 panel, IP54 conforming to specification as specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.10.2 - Busbar : rated 400 Amps, suitable to withstand symmetrical fault level of 25kA for 1 sec. at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.6
3.10.3 - ISMS Connectivity: All the breakers should be provided with control and monitoring facilities,Smart Panel facility with Local touch screen, control panel in front side of the panel. Required PLCs ,relays, contactors ,IO cards, Ethernet switches,SMPS,Control Transformers, cabling works., etc. for functional requirement as specified in Part-2 Section VII Subsection D Unit No.2 Clause 2.28 and drawings. Smart Panel shall be interfacing with ISMS system through Modbus TCP/IP for Control & monitoring.
3.10.4 - OUTGOING FEEDERS
3.10.8 - 32A,TP MCCB, 415V, 25kA suitable space provision for 7.5kW VFD unit (FAF) . Having Micro processor trip unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.10.9 - 32A,TP MCCB, 415V, 25kA suitable space provision for 1.50kW VFD unit (FAF) . Having Micro processor trip unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.10.10 - 16A,TP MPCB, 415V, 25kA with 1.50kW DOL Starter unit (TSF) . Having microprocessor trip unit with over load, short circuit. And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.10.11 - 16A,TP MPCB, 415V, 25kA with 2.20kW DOL Starter unit (TEF) . Having microprocessor trip unit with over load, short circuit. And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.10.12 - 32A,4P,415V,25kA, MCCB with Start/stop push buttons , Having Micro processor trip unit with over load, short circuit and adjustable earth fault . And LED indication lamps for ON,OFF,TRIP.
3.10.13 - SPARES:-
3.10.14 - 100A,TP MCCB, 415V, 25kA, Having Micro processor trip unit with adjustable protection against over load, short circuit and adjustable earth fault And LED indication lamps for ON,OFF,TRIP.
3.10.15 - 63A,TPN MCCB, 415V, 25kA, Having Micro processor trip unit with adjustable protection against over load, short circuit and adjustable earth fault And LED indication lamps for ON,OFF,TRIP.
3.10.16 - Panel Enclosure & other Accessories (Exhaust fan, louvers, etc.) as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.4
3.11 - VRV PANEL -01 NON-ESSENTIAL (Smart Panel) with Mimic Diagram, TTA form 4b, type 6 panel, IP54 conforming to specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.11.2 - Busbar: rated 630 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.7
3.11.3 - ISMS Connectivity: All the breakers should be provided with control and monitoring facilities,Smart Panel facility with Local touch screen, control panel in front side of the panel. Required PLCs ,relays, contactors ,IO cards, Ethernet switches,SMPS,Control Transformers, cabling works., etc. for functional requirement as specified in Part-2 Section VII Subsection D Unit No.2 Clause 2.28 and drawings. Smart Panel shall be interfacing with ISMS system through Modbus TCP/IP for Control & monitoring.
3.11.4 - OUTGOING FEEDERS
3.11.5 - 40A,4P MCCB, 415V, 25kA, Having Micro processor trip unit with LSIG Protection. And LED indication lamps for ON,OFF,TRIP. KWH Meter shall be considered and shall be based on circuit wise (Cooling)
3.11.6 - SPARE:-
3.11.7 - 40A,4P MCCB, 415V, 25kA, Having Micro processor trip unit with LSIG Protection. And LED indication lamps for ON,OFF,TRIP.
3.11.8 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Clause 2.4
3.12 - VRV PANEL -01 NON-ESSENTIAL (Smart Panel) with Mimic Diagram, TTA form 4b, type 6 panel, IP54 conforming to specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.12.2 - Busbar: rated 400 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.7
3.12.3 - ISMS Connectivity: All the breakers should be provided with control and monitoring facilities,Smart Panel facility with Local touch screen, control panel in front side of the panel. Required PLCs ,relays, contactors ,IO cards, Ethernet switches,SMPS,Control Transformers, cabling works., etc. for functional requirement as specified in Part-2 Section VII Subsection D Unit No.2 Clause 2.28 and drawings. Smart Panel shall be interfacing with ISMS system through Modbus TCP/IP for Control & monitoring.
3.12.4 - OUTGOING FEEDERS
3.12.5 - 40A,4P MCCB, 415V, 25kA, Having Micro processor trip unit with LSIG Protection. And LED indication lamps for ON,OFF,TRIP. KWH Meter shall be considered and shall be based on circuit wise (Cooling)
3.12.6 - SPARE:-
3.12.7 - 40A,4P MCCB, 415V, 25kA, Having Micro processor trip unit with LSIG Protection. And LED indication lamps for ON,OFF,TRIP.
3.12.8 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Unit -2 Clause 2.4
3.13 - VRV PANEL -01 NON-ESSENTIAL (Smart Panel) with Mimic Diagram, TTA form 4b, type 6 panel, IP54 conforming to specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.13.2 - Busbar: rated 800 Amps, suitable to withstand symmetrical fault level of 50kA for 1 second at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.7
3.13.3 - ISMS Connectivity: All the breakers should be provided with control and monitoring facilities,Smart Panel facility with Local touch screen, control panel in front side of the panel. Required PLCs ,relays, contactors ,IO cards, Ethernet switches,SMPS,Control Transformers, cabling works., etc. for functional requirement as specified in Part-2 Section VII Subsection D Unit No.2 Clause 2.28 and drawings. Smart Panel shall be interfacing with ISMS system through Modbus TCP/IP for Control & monitoring.
3.13.4 - OUTGOING FEEDERS
3.13.5 - 40A,4P MCCB, 415V, 25kA, Having Micro processor trip unit with LSIG Protection. And LED indication lamps for ON,OFF,TRIP. KWH Meter shall be considered and shall be based on circuit wise (Cooling)
3.13.6 - 32A,4P MCCB, 415V, 25kA, Having Micro processor trip unit with adjustable protection against over load, short circuit and earth fault And LED indication lamps for ON,OFF,TRIP.
3.13.7 - SPARE:-
3.13.8 - 40A,4P MCCB, 415V, 25kA, Having Micro processor trip unit with LSIG Protection. And LED indication lamps for ON,OFF,TRIP.
3.13.9 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Unit -2 Clause 2.4
3.14 - VRV PANEL-02 NON-ESSENTIAL (Smart Panel) with Mimic Diagram, TTA form 4b, type 6 panel, IP54 conforming to specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.14.2 - Busbar: rated 200 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.6
3.14.3 - ISMS Connectivity: All the breakers should be provided with control and monitoring facilities,Smart Panel facility with Local touch screen, control panel in front side of the panel. Required PLCs ,relays, contactors ,IO cards, Ethernet switches,SMPS,Control Transformers, cabling works., etc. for functional requirement as specified in Part-2 Section VII Subsection D Unit No.2 Clause 2.28 and drawings. Smart Panel shall be interfacing with ISMS system through Modbus TCP/IP for Control & monitoring.
3.14.4 - OUTGOING FEEDERS
3.14.5 - 40A,4P MCCB, 415V, 25kA, Having Micro processor trip unit with LSIG Protection. And LED indication lamps for ON,OFF,TRIP. KWH Meter shall be considered and shall be based on circuit wise (Cooling)
3.14.6 - 32A,4P MCCB, 415V, 25kA, Having Micro processor trip unit with adjustable protection against over load, short circuit and earth fault And LED indication lamps for ON,OFF,TRIP, Start/stop push buttons.
3.14.7 - SPARE:-
3.14.8 - 40A,4P MCCB, 415V, 25kA, Having Micro processor trip unit with LSIG Protection. And LED indication lamps for ON,OFF,TRIP.
3.14.9 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Clause 2.4
3.15 - VRV PANEL-02 NON-ESSENTIAL (Smart Panel) with Mimic Diagram, TTA form 4b, type 6 panel, IP54 conforming to specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.15.2 - Busbar: rated 630 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.6
3.15.3 - ISMS Connectivity: All the breakers should be provided with control and monitoring facilities,Smart Panel facility with Local touch screen, control panel in front side of the panel. Required PLCs ,relays, contactors ,IO cards, Ethernet switches,SMPS,Control Transformers, cabling works., etc. for functional requirement as specified in Part-2 Section VII Subsection D Unit No.2 Clause 2.28 and drawings. Smart Panel shall be interfacing with ISMS system through Modbus TCP/IP for Control & monitoring.
3.15.4 - OUTGOING FEEDERS
3.15.5 - 40A,4P MCCB, 415V, 25kA, Having Micro processor trip unit with LSIG Protection. And LED indication lamps for ON,OFF,TRIP. KWH Meter shall be considered and shall be based on circuit wise (Cooling)
3.15.6 - 32A,4P,415V,25kA, MCCB with Start/stop push buttons , Having microprocessor trip unit with over load, short circuit and earth fault . And LED indication lamps for ON,OFF,TRIP.
3.15.7 - SPARE:-
3.15.8 - 40A,4P MCCB, 415V, 25kA, Having Micro processor trip unit with LSIG Protection. And LED indication lamps for ON,OFF,TRIP.
3.15.9 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Clause 2.4
3.16 - VRV PANEL -01 NON-ESSENTIAL (Smart Panel) with Mimic Diagram, TTA form 4b, type 6 panel, IP54 conforming to specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.16.2 - Busbar: rated 800 Amps, suitable to withstand symmetrical fault level of 50kA for 1 second at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.7
3.16.3 - ISMS Connectivity: All the breakers should be provided with control and monitoring facilities,Smart Panel facility with Local touch screen, control panel in front side of the panel. Required PLCs ,relays, contactors ,IO cards, Ethernet switches,SMPS,Control Transformers, cabling works., etc. for functional requirement as specified in Part-2 Section VII Subsection D Unit No.2 Clause 2.28 and drawings. Smart Panel shall be interfacing with ISMS system through Modbus TCP/IP for Control & monitoring.
3.16.4 - OUTGOING FEEDERS
3.16.5 - 40A,4P MCCB, 415V, 25kA, Having Micro processor trip unit with LSIG Protection. And LED indication lamps for ON,OFF,TRIP. KWH Meter shall be considered and shall be based on circuit wise (Cooling)
3.16.6 - SPARE:-
3.16.7 - 40A,4P MCCB, 415V, 25kA, Having Micro processor trip unit with LSIG Protection. And LED indication lamps for ON,OFF,TRIP.
3.16.8 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Unit -2 Clause 2.4
3.17 - VRV PANEL NON-ESSENTIAL (Smart Panel) with Mimic Diagram, TTA form 4b, type 6 panel, IP54 conforming to specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.17.2 - Busbar: rated 1000 Amps, suitable to withstand symmetrical fault level of 50kA for 1 second at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.7
3.17.3 - ISMS Connectivity: All the breakers should be provided with control and monitoring facilities,Smart Panel facility with Local touch screen, control panel in front side of the panel. Required PLCs ,relays, contactors ,IO cards, Ethernet switches,SMPS,Control Transformers, cabling works., etc. for functional requirement as specified in Part-2 Section VII Subsection D Unit No.2 Clause 2.28 and drawings. Smart Panel shall be interfacing with ISMS system through Modbus TCP/IP for Control & monitoring.
3.17.4 - OUTGOING FEEDERS
3.17.5 - 40A,4P MCCB, 415V, 25kA, Having Micro processor trip unit with LSIG Protection. And LED indication lamps for ON,OFF,TRIP. KWH Meter shall be considered and shall be based on circuit wise (Cooling)
3.17.6 - SPARE:-
3.17.7 - 40A,4P MCCB, 415V, 25kA, Having Micro processor trip unit with LSIG Protection. And LED indication lamps for ON,OFF,TRIP.
3.17.8 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Clause 2.4
3.18 - VRV PANEL -01 NON-ESSENTIAL (Smart Panel) with Mimic Diagram, TTA form 4b, type 6 panel, IP54 conforming to specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.18.2 - Busbar: rated 400 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.7
3.18.3 - ISMS Connectivity: All the breakers should be provided with control and monitoring facilities,Smart Panel facility with Local touch screen, control panel in front side of the panel. Required PLCs ,relays, contactors ,IO cards, Ethernet switches,SMPS,Control Transformers, cabling works., etc. for functional requirement as specified in Part-2 Section VII Subsection D Unit No.2 Clause 2.28 and drawings. Smart Panel shall be interfacing with ISMS system through Modbus TCP/IP for Control & monitoring.
3.18.4 - OUTGOING FEEDERS
3.18.5 - 40A,4P MCCB, 415V, 25kA, Having Micro processor trip unit with LSIG Protection. And LED indication lamps for ON,OFF,TRIP. KWH Meter shall be considered and shall be based on circuit wise (Cooling)
3.18.6 - SPARE:-
3.18.7 - 40A,4P MCCB, 415V, 25kA, Having Micro processor trip unit with LSIG Protection. And LED indication lamps for ON,OFF,TRIP.
3.18.8 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Clause 2.4
3.19 - VRV PANEL-02 NON-ESSENTIAL (Smart Panel) with Mimic Diagram, TTA form 4b, type 6 panel, IP54 conforming to specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.19.2 - Busbar: rated 400 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.6
3.19.3 - ISMS Connectivity: All the breakers should be provided with control and monitoring facilities,Smart Panel facility with Local touch screen, control panel in front side of the panel. Required PLCs ,relays, contactors ,IO cards, Ethernet switches,SMPS,Control Transformers, cabling works., etc. for functional requirement as specified in Part-2 Section VII Subsection D Unit No.2 Clause 2.28 and drawings. Smart Panel shall be interfacing with ISMS system through Modbus TCP/IP for Control & monitoring.
3.19.4 - OUTGOING FEEDERS
3.19.5 - 40A,4P MCCB, 415V, 25kA, Having Micro processor trip unit with LSIG Protection. And LED indication lamps for ON,OFF,TRIP. KWH Meter shall be considered and shall be based on circuit wise (Cooling)
3.19.6 - SPARE:-
3.19.7 - 40A,4P MCCB, 415V, 25kA, Having Micro processor trip unit with LSIG Protection. And LED indication lamps for ON,OFF,TRIP.
3.19.8 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Clause 2.4
3.2 - VRV PANEL NON-ESSENTIAL (Smart Panel) with Mimic Diagram, TTA form 4b, type 6 panel, IP54 conforming to specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.20.2 - Busbar: rated 630 Amps, suitable to withstand symmetrical fault level of 36kA for 1 second at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.7
3.20.3 - ISMS Connectivity: All the breakers should be provided with control and monitoring facilities,Smart Panel facility with Local touch screen, control panel in front side of the panel. Required PLCs ,relays, contactors ,IO cards, Ethernet switches,SMPS,Control Transformers, cabling works., etc. for functional requirement as specified in Part-2 Section VII Subsection D Unit No.2 Clause 2.28 and drawings. Smart Panel shall be interfacing with ISMS system through Modbus TCP/IP for Control & monitoring.
3.20.4 - OUTGOING FEEDERS
3.20.5 - 40A,4P MCCB, 415V, 25kA, Having Micro processor trip unit with LSIG Protection. And LED indication lamps for ON,OFF,TRIP. KWH Meter shall be considered and shall be based on circuit wise (Cooling)
3.20.6 - SPARE:-
3.20.7 - 40A,4P MCCB, 415V, 25kA, Having Micro processor trip unit with LSIG Protection. And LED indication lamps for ON,OFF,TRIP.
3.20.8 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Clause 2.4
3.21 - OTEF PANEL-01 with Mimic panel, Form 2b panel, IP 54 conforming to LV panels specification specified in Part-2 Section VII Sub Section-D Unit 2 and drawings.
3.21.2 - Busbar - Rated 400 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415 volts as specified in Part-2 Section VII Subsection D Unit 02 Clause 2.6 and drawings
3.21.3 - OUT GOING FEEDERS
3.21.4 - 200A,TP MCCB,415V,25kA. Having Thermal magnetic trip unit with over load, short circuit. And LED indication lamps for ON,OFF,TRIP,and lamp test push button.
3.21.5 - 63A,TP MCCB, 415V, 25kA suitable space provision for 30kW VFD unit (LEXF) . Having Thermal magnetic trip unit with over load, short circuit. And LED indication lamps for ON,OFF,TRIP, Start/stop push buttons.
3.21.7 - SPARE:-
3.21.8 - 200A,TP MCCB,415V,25kA. Having Thermal magnetic trip unit with over load, short circuit. And LED indication lamps for ON,OFF,TRIP,and lamp test push button.
3.21.9 - 63A,TP MCCB,415V,25kA. Having Thermal magnetic trip unit with over load, short circuit. And LED indication lamps for ON,OFF,TRIP,and lamp test push button.
3.21.11 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Unit 2 Clause 2.4 and drawings
3.22 - TVS PANEL-01 ESSENTIAL with Mimic Diagram, TTA form 4b, type 6 panel, IP54 conforming to LV panels specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.22.2 - Busbar: rated 800 Amps, suitable to withstand symmetrical fault level of 50kA for 1 sec. at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.6
3.22.3 - OUT GOING FEEDERS
3.22.4 - 630A,TP MCCB,415V,25kA. Having microprocessor based trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.22.5 - 32A 4P, MCCB, 415V,25kA,Having Thermal magnetic trip unit with adjustable protection against over load, short circuit.And LED indication lamps for ON,OFF,TRIP
3.22.6 - 32A TP, MCCB, 415V,25kA with suitable space provision for 7.5kW SoftStarter (SPF). Having Thermal trip unit with adjustable protection against over load, short circuit.And LED indication lamps for ON,OFF,TRIP and Start/stop push buttons.
3.22.7 - 32A TP, MCCB, 415V,25kA with suitable space provision for 5.5kW SoftStarter (SPF). Having Thermal trip unit with adjustable protection against over load, short circuit.And LED indication lamps for ON,OFF,TRIP and Start/stop push buttons.
3.22.8 - SPARE:-
3.22.9 - 630A,TP MCCB,415V,25kA. Having microprocessor based trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.22.10 - 32A 4P, MCCB, 415V,25kA,Having Thermal magnetic trip unit with adjustable protection against over load, short circuit.And LED indication lamps for ON,OFF,TRIP
3.22.11 - Panel Enclosure & other accessories as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.4
3.23 - TVS PANEL-02 ESSENTIAL with Mimic Diagram, TTA form 4b, type 6 panel, IP54 conforming to LV panels specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.23.2 - Busbar: rated 630 Amps, suitable to withstand symmetrical fault level of 25kA for 1 sec. at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.6
3.23.3 - OUT GOING FEEDERS
3.23.4 - 630A,TP MCCB,415V,25kA. Having microprocessor based trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.23.5 - 32A 4P,MCCB, 415V,25kA,Having Thermal magnetic trip unit with adjustable protection against over load, short circuit.And LED indication lamps for ON,OFF,TRIP
3.23.6 - 32A TP, MCCB, 415V,25kA with suitable space provision for 11kW SoftStarter (SPF). Having Thermal trip unit with adjustable protection against over load, short circuit.And LED indication lamps for ON,OFF,TRIP and Start/stop push buttons.
3.23.7 - 200A,TP MCCB,415V,25kA. Having microprocessor based trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.23.8 - SPARE:-
3.23.9 - 630A,TP MCCB,415V,25kA. Having microprocessor based trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.23.10 - 200A,TP MCCB,415V,25kA. Having microprocessor based trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.23.11 - Panel Enclosure & other accessories as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.4
3.24 - TVS PANEL -01 ESSENTIAL with Mimic Diagram, TTA form 4b, type 6 panel, IP54 conforming to LV panels specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.24.2 - Busbar: rated 800 Amps, suitable to withstand symmetrical fault level of 50kA for 1 sec. at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.6
3.24.3 - OUT GOING FEEDERS
3.24.4 - 400A,TP MCCB,415V,25kA. Having microprocessor trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP
3.24.5 - 200A,TP MCCB,415V,25kA Having Thermal magnetic trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP
3.24.6 - 32A,4P MCCB,415V,25kA. Having Thermal magnetic trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.24.7 - 32A,TP MCCB, 415V,25kA, suitable space provision for 4kW (SPF) SoftStarter . Having Thermal magnetic based trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP, Start/stop push buttons.
3.24.8 - SPARE:-
3.24.9 - 400A,TP MCCB,415V,25kA.Having microprocessor trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.24.10 - 200A,TP MCCB,415V,25kA. Having Thermal magnetic trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.24.11 - Panel Enclosure & other Accessories (Exhaust fan, louvers, etc.) as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.4
3.25 - TVS PANEL -02 ESSENTIAL with Mimic Diagram, TTA form 4b, type 6 panel, IP54 conforming to LV panels specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.25.2 - Busbar: rated 630 Amps, suitable to withstand symmetrical fault level of 25kA for 1 sec. at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.6
3.25.3 - OUT GOING FEEDERS
3.25.4 - 400A,TP MCCB,415V,25kA.Having microprocessor trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.25.5 - 100A,TP MCCB,415V,25kA. Having Thermal magnetic based trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.25.6 - 32A,4P MCCB,415V,25kA. Having Thermal magnetic trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.25.7 - 32A,TP MCCB, 415V,25kA, Suitable Space Provision for 7.5kW (SPF) SoftStarter. Having Thermal magnetic based trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP, Start/stop push buttons.
3.25.8 - 63A,TP MCCB, 415V,25kA, Suitable Space Provision for 22kW (SPF) SoftStarter. Having Thermal magnetic based trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP, Start/stop push buttons.
3.25.9 - 63A,TP MCCB, 415V,25kA, Suitable Space Provision for 18.5kW (SPF) SoftStarter. Having Thermal magnetic based trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP, Start/stop push buttons.
3.25.10 - SPARE:-
3.25.11 - 400A,TP MCCB,415V,25kA.Having microprocessor trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.25.12 - 100A,TP MCCB,415V,25kA. Having Thermal magnetic based trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.25.13 - 63A,TP MCCB,415V,25kA. Having Thermal magnetic based trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.25.14 - Panel Enclosure & other accessories as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.4
3.26 - TVS PANEL ESSENTIAL with Mimic Diagram, TTA form 4b, type 6 panel, IP54 conforming to LV panels specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.26.2 - Busbar: rated 1000 Amps, suitable to withstand symmetrical fault level of 50kA for 1 sec. at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.6
3.26.3 - OUT GOING FEEDERS
3.26.4 - 400A,TP MCCB,415V,25kA. Having microprocessor based trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.26.5 - 200A,TP MCCB,415V,25kA. Having Thermal magnetic trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.26.6 - 32A,4P MCCB,415V,25kA. Having Thermal magnetic trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.26.7 - 63A,TP MCCB, 415V,25kA, suitable Space Provision for 30kW SoftStarter (SPF). Having Thermal magnetic trip unit with adjustable protection against over load, short circuit.And LED indication lamps for ON,OFF,TRIP, Start/stop push buttons.
3.26.8 - 32A,TP MCCB, 415V 25kA, suitable Space Provision for 11kW SoftStarter (SPF). Having Thermal magnetic trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP, Start/stop push buttons.
3.26.9 - SPARES:-
3.26.10 - 400A,TP MCCB,415V,25kA. Having microprocessor based trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.26.11 - 200A,TP MCCB,415V,25kA. Having Thermal magnetic trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.26.12 - Panel Enclosure & other accessories as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.4
3.27 - TVS PANEL ESSENTIAL with Mimic Diagram, TTA form 4b, type 6 panel, IP54 conforming to LV panels specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.27.2 - Busbar: rated 1250A Amps, suitable to withstand symmetrical fault level of 50kA for 1 sec. at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.6
3.27.3 - OUT GOING FEEDERS
3.27.4 - 400A,TP MCCB,415V,25kA. Having microprocessor based trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.27.5 - 200A,TP MCCB,415V,25kA. Having Thermal magnetic trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.27.6 - 63A,4P MCCB,415V,25kA. Having Thermal magnetic trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.27.7 - 32A,4P MCCB,415V,25kA. Having Thermal magnetic trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.27.8 - 63A,TP MCCB, 415V,25kA, suitable Space Provision for 37kW SoftStarter (SPF). Having Thermal magnetic trip unit with adjustable protection against over load, short circuit.And LED indication lamps for ON,OFF,TRIP, Start/stop push buttons.
3.27.9 - 32A,TP MCCB, 415V,25kA, suitable Space Provision for 15kW SoftStarter (SPF). Having Thermal magnetic trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP, Start/stop push buttons.
3.27.10 - SPARES:-
3.27.11 - 400A,TP MCCB,415V,25kA. Having microprocessor trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP
3.27.12 - 200A,TP MCCB,415V,25kA.Having Thermal magnetic trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP
3.27.13 - Panel Enclosure & other accessories as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.4
3.28 - TVS PANEL-01 ESSENTIAL with Mimic Diagram, TTA form 4b, type 6 panel, IP54 conforming to LV panels specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.28.2 - Busbar: rated 1250 Amps, suitable to withstand symmetrical fault level of 50kA for 1 sec. at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.6
3.28.3 - OUT GOING FEEDERS
3.28.4 - 630A TP,MCCB, 415V,25kA, Having microprocessor based trip unit with adjustable protection against over load, short circuit.And LED indication lamps for ON,OFF,TRIP
3.28.5 - 200A TP,MCCB, 415V,25kA, Having Thermal magnetic trip unit with adjustable protection against over load, short circuit.And LED indication lamps for ON,OFF,TRIP
3.28.6 - 63A 4P, MCCB, 415V,25kA,Having Thermal magnetic trip unit with adjustable protection against over load, short circuit.And LED indication lamps for ON,OFF,TRIP
3.28.7 - 32A 4P MCCB, 415V,25kA,Having Thermal magnetic trip unit with adjustable protection against over load, short circuit.And LED indication lamps for ON,OFF,TRIP
3.28.8 - 63A,TP MCCB, 415V,25kA, suitable Space Provision for 22kW VFD (SEF). Having Thermal magnetic based trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP. Start/stop , Emergency stop push buttons.
3.28.9 - 63A,TP MCCB, 415V,25kA, suitable Space Provision for 30kW SoftStarter (SPF). Having Thermal magnetic based trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.Start/stop push buttons.
3.28.10 - SPARE:-
3.28.11 - 630A TP,MCCB, 415V,25kA, Having microprocessor based trip unit with adjustable protection against over load, short circuit.And LED indication lamps for ON,OFF,TRIP
3.28.12 - 200A TP,MCCB, 415V,25kA, Having Thermal magnetic trip unit with adjustable protection against over load, short circuit.And LED indication lamps for ON,OFF,TRIP
3.28.13 - Panel Enclosure & other accessories as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.4
3.29 - TVS PANEL-02 ESSENTIAL with Mimic Diagram, TTA form 4b, type 6 panel, IP54 conforming to LV panels specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.29.2 - Busbar: rated 800 Amps, suitable to withstand symmetrical fault level of 50kA for 1 sec. at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.6
3.29.3 - OUT GOING FEEDERS
3.29.4 - 630A TP,MCCB, 415V,25kA,Having micro processor trip unit with adjustable protection against over load, short circuit.And LED indication lamps for ON,OFF,TRIP
3.29.5 - 32A 4P,MCCB, 415V,25kA,Having Thermal magnetic trip unit with adjustable protection against over load, short circuit.And LED indication lamps for ON,OFF,TRIP
3.29.6 - 200A TP,MCCB, 415V,25kA,Having Thermal magnetic trip unit with adjustable protection against over load, short circuit.And LED indication lamps for ON,OFF,TRIP
3.29.7 - 32A,TP MCCB, 415V,25kA, suitable Space Provision for 4kW SoftStarter (SPF). Having Thermal magnetic based trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.Start/stop push buttons.
3.29.8 - 63A 4P,MCCB, 415V,25kA,Having Thermal magnetic trip unit with adjustable protection against over load, short circuit.And LED indication lamps for ON,OFF,TRIP
3.29.9 - SPARE:-
3.29.10 - 630A TP,MCCB, 415V,25kA,Having micro processor trip unit with adjustable protection against over load, short circuit.And LED indication lamps for ON,OFF,TRIP
3.29.11 - 200A TP,MCCB, 415V,25kA,Having Thermal magnetic trip unit with adjustable protection against over load, short circuit.And LED indication lamps for ON,OFF,TRIP
3.29.12 - Panel Enclosure & other accessories as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.4
3.3 - TVS PANEL ESSENTIAL with Mimic Diagram, TTA form 4b, type 6 panel, IP54 conforming to LV panels specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings. (Fully Front Accessible panel)
3.30.2 - Busbar: rated 1000A Amps, suitable to withstand symmetrical fault level of 50kA for 1 sec. at 415V as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.6
3.30.3 - OUT GOING FEEDERS
3.30.4 - 400A,TP MCCB,415V,25kA. Having microprocessor based trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.30.5 - 200A,TP MCCB,415V,25kA. Having Thermal magnetic trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.30.6 - 32A,4P MCCB,415V,25kA. Having Thermal magnetic trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.30.7 - 63A,4P MCCB,415V,25kA. Having Thermal magnetic trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.30.8 - 63A,TP MCCB, 415V,25kA, suitable Space Provision for 30kW SoftStarter (SPF). Having Thermal magnetic trip unit with adjustable protection against over load, short circuit.And LED indication lamps for ON,OFF,TRIP, Start/stop push buttons.
3.30.9 - 32A,TP MCCB, 415V,25kA, suitable for SoftStarter for 15kW (SPF). Having Thermal magnetic trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP, Start/stop, Emergency stop push buttons.
3.30.10 - SPARES:-
3.30.11 - 400A,TP MCCB,415V,25kA. Having microprocessor based trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.30.12 - 200A,TP MCCB,415V,25kA. Having Thermal magnetic trip unit with adjustable protection against over load, short circuit. And LED indication lamps for ON,OFF,TRIP.
3.30.13 - Panel Enclosure & other accessories as specified in Part-2 Section VII Subsection D Unit-02 Clause 2.4
3.31 - VAC PDB conforming to LV panels specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings.
3.31.2 - Busbar: Rated 32A Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415 volts as specified in Part-2 Section VII Subsection D Unit 02 Clause 2.6 and drawings.
3.31.4 - SPARE:-
3.31.6 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D unit 2 Clause 2.4 and drawings
3.32 - VAC PDB conforming to LV panels specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings.
3.32.2 - Busbar: Rated 63A Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415 volts as specified in Part-2 Section VII Subsection D Unit 02 Clause 2.6 and drawings.
3.32.5 - SPARE:-
3.32.8 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D unit 2 Clause 2.4 and drawings
3.33 - TVS DAMPER PANEL-01 with Mimic panel, Form 2b panel, IP 54 conforming to LV panels specification specified in Part-2 Section VII Sub Section-D Unit 2 and drawings.
3.33.2 - Busbar - Rated 32 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415 volts as specified in Part-2 Section VII Subsection D Unit 02 Clause 2.6 and drawings
3.33.4 - SPARE:-
3.33.6 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Unit 2 Clause 2.4 and drawings
3.34 - TVS DAMPER PANEL-02 with Mimic panel, Form 2b panel, IP 54 conforming to LV panels specification specified in Part-2 Section VII Sub Section-D Unit 2 and drawings.
3.34.2 - Busbar - Rated 32 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415 volts as specified in Part-2 Section VII Subsection D Unit 02 Clause 2.6 and drawings
3.34.4 - SPARE:-
3.34.6 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Unit 2 Clause 2.4 and drawings
3.35 - TVS DAMPER PANEL-01 with Mimic panel, Form 2b panel, IP 54 conforming to LV panels specification specified in Part-2 Section VII Sub Section-D Unit 2 and drawings.
3.35.2 - Busbar - Rated 32 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415 volts as specified in Part-2 Section VII Subsection D Unit 02 Clause 2.6 and drawings
3.35.4 - SPARE:-
3.35.6 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D unit 2 Clause 2.4 and drawings
3.36 - TVS DAMPER PANEL-02 with Mimic panel, Form 2b panel, IP 54 conforming to LV panels specification specified in Part-2 Section VII Sub Section-D Unit 2 and drawings.
3.36.2 - Busbar - Rated 32 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415 volts as specified in Part-2 Section VII Subsection D Unit 02 Clause 2.6 and drawings
3.36.4 - SPARE:-
3.36.6 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Unit 2 Clause 2.4 and drawings
3.37 - TVS DAMPER PANEL-01 with Mimic panel, Form 2b panel, IP 54 conforming to LV panels specification specified in Part-2 Section VII Sub Section-D Unit 2 and drawings.
3.37.2 - Busbar - Rated 32 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415 volts as specified in Part-2 Section VII Subsection D Unit 02 Clause 2.6 and drawings
3.37.4 - SPARES:-
3.37.6 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Unit 2 Clause 2.4 and drawings
3.38 - TVS DAMPER PANEL-02 with Mimic panel, Form 2b panel, IP 54 conforming to LV panels specification specified in Part-2 Section VII Sub Section-D Unit 2 and drawings.
3.38.2 - Busbar - rated 32 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415 volts as specified in Part-2 Section VII Subsection D Unit 02 Clause 2.6 and drawings
3.38.4 - SPARES:-
3.38.6 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Unit 2 Clause 2.4 and drawings
3.39 - TVS DAMPER PANEL-01 with Mimic panel, Form 2b panel, IP 54 conforming to LV panels specification specified in Part-2 Section VII Sub Section-D Unit 2 and drawings.
3.39.2 - Busbar - Rated 63 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415 volts as specified in Part-2 Section VII Subsection D Unit 02 Clause 2.6 and drawings
3.39.4 - SPARES:-
3.39.6 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D unit 2 Clause 2.4 and drawings
3.4 - TVS DAMPER PANEL-01 with Mimic panel, Form 2b panel, IP 54 conforming to LV panels specification specified in Part-2 Section VII Sub Section-D Unit 2 and drawings.
3.40.2 - Busbar - Rated 63 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415 volts as specified in Part-2 Section VII Subsection D Unit 02 Clause 2.6 and drawings
3.40.4 - SPARE:-
3.40.6 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Unit 2 Clause 2.4 and drawings
3.41 - TVS DAMPER PANEL-02 with Mimic panel, Form 2b panel, IP 54 conforming to LV panels specification specified in Part-2 Section VII Sub Section-D Unit 2 and drawings.
3.41.2 - Busbar - Rated 32 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415 volts as specified in Part-2 Section VII Subsection D Unit 02 Clause 2.6 and drawings
3.41.4 - SPARE:-
3.41.6 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Unit 2 Clause 2.4 and drawings
3.42 - TVS DAMPER PANEL-01 with Mimic panel, Form 2b panel, IP 54 conforming to LV panels specification specified in Part-2 Section VII Sub Section-D Unit 2 and drawings.
3.42.2 - Busbar - Rated 63 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415 volts as specified in Part-2 Section VII Subsection D Unit 02 Clause 2.6 and drawings
3.42.4 - SPARES:-
3.42.6 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Unit 2 Clause 2.4 and drawings
3.43 - VAC DAMPER PANEL-01 with Mimic panel, Form 2b panel, IP54 conforming to LV panels specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings.
3.43.2 - Busbar: rated 32 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415 volts as specified in Part-2 Section VII Subsection D Unit 02 Clause 2.6 and drawings.
3.43.4 - SPARE:-
3.43.6 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Unit 2 Clause 2.4 and drawings
3.44 - VAC DAMPER PANEL-01 with Mimic panel, Form 2b panel, IP54 conforming to LV panels specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings.
3.44.2 - Busbar: rated 32Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415 volts as specified in Part-2 Section VII Subsection D Unit 02 Clause 2.6 and drawings.
3.44.4 - SPARE:-
3.44.6 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Unit 2 Clause 2.4 and drawings
3.45 - VAC DAMPER PANEL-02 with Mimic panel, Form 2b panel, IP54 conforming to LV panels specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings.
3.45.2 - Busbar: rated 32Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415 volts as specified in Part-2 Section VII Subsection D Unit 02 Clause 2.7 and drawings.
3.45.4 - SPARE:-
3.45.6 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Unit 2 Clause 2.4 and drawings
3.46 - VAC DAMPER PANEL with Mimic panel, Form 2b panel, IP54 conforming to LV panels specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings.
3.46.2 - Busbar: Rated 32 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415 volts as specified in Part-2 Section VII Subsection D Unit 02 Clause 2.7 and drawings.
3.46.4 - SPARES:-
3.46.6 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Unit 2 Clause 2.4 and drawings
3.47 - VAC DAMPER PANEL with Mimic panel, Form 2b panel, IP54 conforming to LV panels specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings.
3.47.2 - Busbar: Rated 32 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415 volts as specified in Part-2 Section VII Subsection D Unit 02 Clause 2.7 and drawings.
3.47.4 - SPARES:-
3.47.6 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Unit 2 Clause 2.4 and drawings
3.48 - VAC DAMPER PANEL-01 with Mimic panel, Form 2b panel, IP54 conforming to LV panels specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings.
3.48.2 - Busbar: rated 32 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415 volts as specified in Part-2 Section VII Subsection D Unit 02 Clause 2.6 and drawings.
3.48.4 - SPARE:-
3.48.6 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Unit 2 Clause 2.4 and drawings
3.49 - VAC DAMPER PANEL-02 with Mimic panel, Form 2b panel, IP54 conforming to LV panels specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings.
3.49.2 - Busbar: rated 32 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415 volts as specified in Part-2 Section VII Subsection D Unit 02 Clause 2.7 and drawings.
3.49.4 - SPARE:-
3.49.6 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Unit 2 Clause 2.4 and drawings
3.5 - VAC DAMPER PANEL with Mimic panel, Form 2b panel, IP54 conforming to LV panels specification specified in Part-2 Section VII SubSection-D Unit-02 and drawings.
3.50.2 - Busbar: Rated 32 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415 volts as specified in Part-2 Section VII Subsection D Unit 02 Clause 2.7 and drawings.
3.50.4 - SPARES:-
3.50.6 - Panel Enclosure & other Accessories as specified in Part-2 Section VII Subsection D Unit 2 Clause 2.4 and drawings
3.51 - SCADA DB (6 Way - 7 Segment DB) conforming to LV panels specification specified in Part-2 Section VII SubSection-D Unit 02 and drawings
3.51.2 - Busbar - Rated 32 Amps, suitable to withstand symmetrical fault level of 25kA for 1 second at 415 volts as specified in Part-2 Section VII Subsection D Unit 02 Clause 2.6 and drawings
3.51.3 - Sub Incomer :25A DP, RCBO (100 mA Sensitivity)
3.51.4 - Outgoing feeders: 16A,10kA,SP,MCB (Spread equally in each phase)
3.51.5 - Distribution board Enclosure and other accessories
4 - Variable Frequncy drive as specified Part-2 Section VII Subsection D Unit 5.
4.1 - 355 kW VFD drive Panel with Dynamic Breaking resistor (TVS Fan)
4.2 - 315 kW VFD drive Panel with Dynamic Breaking resistor (TVS Fan)
4.3 - 250 kW VFD drive Panel with Dynamic Breaking resistor (TVS Fan)
4.4 - 200 kW VFD drive Panel with Dynamic Breaking resistor (TVS Fan)
4.5 - 110 kW VFD drive Panel with Dynamic Breaking resistor (TVS Fan)
4.6 - 110 kW VFD drive Panel (OTEF Fan)
4.7 - 90 kW VFD drive Panel (OTEF Fan)
4.8 - 75 kW VFD drive Panel (OTEF Fan)
4.9 - 55 kW VFD drive Panel (OTEF Fan)
4.10 - 37 kW VFD drive Panel (OTEF Fan)
4.11 - 90 kW VFD drive (SEF Fan)
4.12 - 75 kW VFD drive Panel (SEF Fan)
4.13 - 22 kW VFD drive (SEF Fan) suitable for mounting within TVS & VAC PANEL ESSENTIAL
4.14 - 37 kW VFD drive (EXF Fan) suitable for mounting within VAC panel
4.15 - 30 kW VFD drive (LEXF Fan) suitable for mounting within OTEF PANEL
4.16 - 55kW VFD drive (AHU) suitable for mounting within VAC panel
4.17 - 45kW VFD drive (AHU) suitable for mounting within VAC panel
4.18 - 37kW VFD drive (AHU) suitable for mounting within VAC panel
4.19 - 30kW VFD drive (AHU) suitable for mounting within VAC panel
4.20 - 22kW VFD drive (AHU) suitable for mounting within VAC panel
4.21 - 20kW VFD drive (AHU) suitable for mounting within VAC panel
4.22 - 18.5kW VFD drive (AHU) suitable for mounting within VAC panel
4.23 - 15kW VFD drive (AHU) suitable for mounting within VAC panel
4.24 - 11 kW VFD drive (AHU) suitable for mounting within VAC panel
4.25 - 7.5kW VFD drive (AHU) suitable for mounting within VAC panel
4.26 - 5.5kW VFD drive (AHU) suitable for mounting within VAC panel
4.27 - 4kW VFD drive (AHU) suitable for mounting within VAC panel
4.28 - 3.7kW VFD drive (AHU) suitable for mounting within VAC panel
4.29 - 7.5kW VFD drive (FAF) suitable for mounting within VAC panel
4.30 - 5.5kW VFD drive (FAF) suitable for mounting within VAC panel
4.31 - 4kW VFD drive (FAF) suitable for mounting within VAC panel
4.32 - 3kW VFD drive (FAF) suitable for mounting within VAC panel
4.33 - 2.2kW VFD drive (FAF) suitable for mounting within VAC panel
4.34 - 1.5kW VFD drive (FAF) suitable for mounting within VAC panel
4.35 - 1.1kW VFD drive (FAF) suitable for mounting within VAC panel
4.36 - 0.55kW VFD drive (FAF) suitable for mounting within VAC panel
4.37 - 0.25kW VFD drive (FAF) suitable for mounting within VAC panel
5 - SoftStarter as specified Part-2 Section VII Subsection D Unit 6
5.1 - 75kW SoftStarter (SEF) suitable for mounting within TVS & VAC PANEL ESSENTIAL
5.2 - 55kW SoftStarter (SEF) suitable for mounting within TVS & VAC PANEL ESSENTIAL
5.3 - 37kW SoftStarter (SPF) suitable for mounting within TVS & VAC PANEL ESSENTIAL
5.4 - 30kW SoftStarter (SPF) suitable for mounting within TVS & VAC PANEL ESSENTIAL
5.5 - 22kW SoftStarter (SPF) suitable for mounting within TVS & VAC PANEL ESSENTIAL
5.6 - 18.5 kW SoftStarter (SPF) suitable for mounting within TVS & VAC PANEL ESSENTIAL
5.7 - 15kW SoftStarter (SPF/SEF) suitable for mounting within TVS & VAC PANEL ESSENTIAL
5.8 - 11kW SoftStarter (SPF) suitable for mounting within TVS & VAC PANEL ESSENTIAL
5.9 - 7.5 kW SoftStarter (SPF) suitable for mounting within TVS & VAC PANEL ESSENTIAL
5.10 - 5.5 kW SoftStarter (SPF) suitable for mounting within TVS & VAC PANEL ESSENTIAL
5.11 - 4kW SoftStarter (SPF) suitable for mounting within TVS & VAC PANEL ESSENTIAL
5.12 - 55kW BYPASS SOFT STARTER (AHU) suitable for mounting within VAC panel
5.13 - 45kW BYPASS SOFT STARTER (AHU) suitable for mounting within VAC panel
5.14 - 37kW BYPASS SOFT STARTER (AHU) suitable for mounting within VAC panel
5.15 - 30kW BYPASS SOFT STARTER (AHU) suitable for mounting within VAC panel
5.16 - 22kW BYPASS SOFT STARTER (AHU) suitable for mounting within VAC panel
5.17 - 18.5kW BYPASS SOFT STARTER (AHU) suitable for mounting within VAC panel
5.18 - 15kW BYPASS SOFT STARTER (AHU) suitable for mounting within VAC panel
6 - Other accessories Supply and fixing of the following safety equipments in Aux. Sub.Station/Mechnical room/TVS panel room as per detailed descriptions given below and as per relevant IE rules & code of standard practice
6.1 - 1000 mm wide 2mm thick Insulating mat in front of all panels in ASS Rooms, Mechanical room, TVS Panel/DB Rooms and other rooms as required. as specified Part-2 Section VII Subsection D Unit 2 Clause 2.26
6.2 - Laminated standard shock treatment charts in Tamil, English & Hindi in ASS, Mechanical Room, TVSPanel/DB Room and Pump room
6.3 - Danger plate as per approved Style & sample written in Tamil, English & Hindi for MV installations as required as per IE rules, IEC and IS 2551 (latest) in Mechanical room, TVS Panel/DB Rooms
6.4 - Glass framed SLD board (A1 size) in all equipment rooms
6.5 - Glass framed Drawing board (A2 size) in all equipment rooms
6.6 - Glass framed Drawing/Layout board (A3 size) in all equipment rooms
7 - LV POWER CABLES
7.1 - CABLES (Non Fire Survival type Cable) and Termination includes gland with shrouds, lugs, necessary earthing arrangements conforming to cables specification specified in Part-2 Section VII SubSection-D Unit-03 and drawings.
7.1.1 - 4c X 300 Sq.mm Cu Conductor
7.1.2 - 4c X 240 Sq.mm Cu Conductor
7.1.3 - 4c X 185 Sq.mm Cu Conductor
7.1.4 - 4c X 150 Sq.mm Cu Conductor
7.1.5 - 4c X 120 Sq.mm Cu Conductor
7.1.6 - 4c X 95 Sq.mm Cu Conductor
7.1.7 - 4c X 70 Sq.mm Cu Conductor
7.1.8 - 4c X 50 Sq.mm Cu Conductor
7.1.9 - 4c X 35 Sq.mm Cu Conductor
7.1.10 - 4c X 25Sq.mm Cu Conductor
7.1.11 - 4c X 16 Sq.mm Cu Conductor
7.1.12 - 4c X 10 Sq.mm Cu Conductor
7.1.13 - 4c X 6 Sq.mm Cu Conductor
7.1.14 - 4c X 4 Sq.mm Cu Conductor
7.1.15 - 4c X 2.5 Sq.mm Cu Conductor
7.1.16 - 4c X 1.5 Sq.mm Cu Conductor
7.1.17 - 3c X 300 Sq.mm Cu Conductor
7.1.18 - 3c X 240 Sq.mm Cu Conductor
7.1.19 - 3c X 185 Sq.mm Cu Conductor
7.1.20 - 3c X 150 Sq.mm Cu Conductor
7.1.21 - 3c X 120 Sq.mm Cu Conductor
7.1.22 - 3c X 95 Sq.mm Cu Conductor
7.1.23 - 3c X 70 Sq.mm Cu Conductor
7.1.24 - 3c X 50 Sq.mm Cu Conductor
7.1.25 - 3c X 35 Sq.mm Cu Conductor
7.1.26 - 3c X 25 Sq.mm Cu Conductor
7.1.27 - 3c X 16 Sq.mm Cu Conductor
7.1.28 - 3c X 10 Sq.mm Cu Conductor
7.1.29 - 3c X 6 Sq.mm Cu Conductor
7.1.30 - 3c X 4 Sq.mm Cu Conductor
7.1.31 - 3c X 2.5 Sq.mm Cu Conductor
7.1.32 - 2c X 4 Sq.mm Cu Conductor
7.1.33 - 2c X 2.5 Sq.mm Cu Conductor
7.1.34 - 2c X 1.5 Sq.mm Cu Conductor
7.2 - CABLES (Fire Survival type Cable) and Termination includes gland with shrouds, lugs, necessary earthing arrangements conforming to cables specification specified in Part-2 Section VII SubSection-D Unit no.03 and drawings.
7.2.1 - 4c X 300 Sq.mm Cu Conductor
7.2.2 - 4c X 240 Sq.mm Cu Conductor
7.2.3 - 4c X 185 Sq.mm Cu Conductor
7.2.4 - 4c X 150 Sq.mm Cu Conductor
7.2.5 - 4c X 120 Sq.mm Cu Conductor
7.2.6 - 4c X 95 Sq.mm Cu Conductor
7.2.7 - 4c X 70 Sq.mm Cu Conductor
7.2.8 - 4c X 50 Sq.mm Cu Conductor
7.2.9 - 4c X 35 Sq.mm Cu Conductor
7.2.10 - 4c X 25Sq.mm Cu Conductor
7.2.11 - 4c X 16 Sq.mm Cu Conductor
7.2.12 - 4c X 10 Sq.mm Cu Conductor
7.2.13 - 4c X 6 Sq.mm Cu Conductor
7.2.14 - 4c X 4 Sq.mm Cu Conductor
7.2.15 - 4c X 2.5 Sq.mm Cu Conductor
7.2.16 - 4c X 1.5 Sq.mm Cu Conductor
7.2.17 - 3c X 300 Sq.mm Cu Conductor
7.2.18 - 3c X 240 Sq.mm Cu Conductor
7.2.19 - 3c X 185 Sq.mm Cu Conductor
7.2.20 - 3c X 150 Sq.mm Cu Conductor
7.2.21 - 3c X 120 Sq.mm Cu Conductor
7.2.22 - 3c X 95 Sq.mm Cu Conductor
7.2.23 - 3c X 70 Sq.mm Cu Conductor
7.2.24 - 3c X 50 Sq.mm Cu Conductor
7.2.25 - 3c X 35 Sq.mm Cu Conductor
7.2.26 - 3c X 25 Sq.mm Cu Conductor
7.2.27 - 3c X 16 Sq.mm Cu Conductor
7.2.28 - 3c X 10 Sq.mm Cu Conductor
7.2.29 - 3c X 6 Sq.mm Cu Conductor
7.2.30 - 3c X 4 Sq.mm Cu Conductor
7.2.31 - 3c X 2.5 Sq.mm Cu Conductor
7.2.32 - 2c X 4 Sq.mm Cu Conductor
7.2.33 - 2c X 2.5 Sq.mm Cu Conductor
7.2.34 - 2c X 1.5 Sq.mm Cu Conductor
7.2.35 - 2c X 1 Sq.mm Cu Conductor
7.3 - CONTROL CABLES (FS cable) and Termination includes gland with shrouds, lugs, necessary earthing arrangements conforming to cables specification specified in Part-2 Section VII SubSection-E (ISMS) Unit no.08 and drawings.
7.3.1 - 8c X 1.5 sq. mm Cu Conductor (FS)
7.3.2 - 10c X 1.5 sq. mm Cu Conductor (FS)
7.3.3 - 3c X 1.5 Sq.mm Cu Conductor (FS)
7.3.4 - 2c X 1.5 Sq.mm Cu Conductor (FS)
7.3.5 - 2c X 1.5 Sq.mm Cu Conductor (Non.FS)
8 - CABLE TRAY
8.1 - Perforated type cable tray and accessories with suitable Modular brackets/supports conforming to specification specified in Part-2 section VII Sub section-D Unit no.04 and drawings
8.1.1 - 600 mm wide x 75 mm deep x 2 mm thick
8.1.2 - 450 mm wide x 75 mm deep x 2 mm thick
8.1.3 - 300 mm wide x 50 mm deep x 2 mm thick
8.1.4 - 200 mm wide x 50 mm deep x 2 mm thick
8.1.5 - 150mm wide x 50mm deep x 2 mm thick
8.1.6 - 100mm wide x 50mm deep x 2 mm thick
8.1.7 - 50mm wide x 50mm deep x 2 mm thick
8.2 - Ladder type cable tray and accessories with suitable Modular brackets/supports conforming to specification specified in Part-2 section VII Sub section-D Unit 04 and drawings
8.2.1 - 600 mm wide x 75 mm deep x 2 mm thick
8.2.2 - 450 mm wide x 75 mm deep x 2 mm thick
8.2.3 - 300 mm wide x 50 mm deep x 2 mm thick
8.3 - Cable tray covers and accessories with suitable Modular brackets/supports conforming to specification specified in Part-2 section VII Sub section-D Unit 04 and drawings
8.3.1 - 600 mm wide x 75 mm deep x 1.6 mm thick
8.3.2 - 450 mm widex 75 mm deep x 1.6 mm thick
8.3.3 - 300 mm wide x 50 mm deep x 1.6 mm thick
8.3.4 - 200 mm wide x 50 mm deep x 1.6 mm thick
8.3.5 - 150mm wide x 50mm deep x 1.6 mm thick
8.3.6 - 100mm wide x 50mm deep x 1.6 mm thick
8.3.7 - 50mm wide x 50mm deep x 1.6 mm thick
9 - Supply & Installation for closing of wall and floor penetrations which has multiple non combustible penetrants with Mortar based UL listed firestop system to provide 2 Hr Fire rating.
10 - Supply and installation for closing of wall and floor penetrations which has cable tray penetrants with intumescent sealant based UL listed firestop system to provide 2 Hr Fire rating and water resistant properties.
11 - EARTHING PROTECTION conforming to earthing specification specified in Part-2 Section VII SubSection-D Unit 07 and drawings
11.1 - GI Strips/wire for interconnecting the earthing stations ,panels,DBs, Equipments as per specifications & drawing as required.
11.1.1 - 50 mm x 10 mm GI strip
11.1.2 - 50 mm x 6 mm GI strip
11.1.3 - 40 mm x 6 mm GI strip
11.1.4 - 25 mm x 6 mm GI strip
11.1.5 - 25 mm x 3 mm GI strip
11.1.6 - 10 SWG / 4 mm diameter, copper Wire
11.1.7 - 8 SWG / 4 mm diameter, copper Wire
11.2 - PVC insulated, FRLSH, Copper Cables for Earthing in green colour, for interconnecting the earth station with METs / CETs of the following sizes with accessories as per specifications & drawing as required.
11.2.1 - 1Cx35 Sq. mm, Cu Cable
11.2.2 - 1Cx25 Sq. mm, Cu Cable
11.2.3 - 1Cx16 Sq. mm, Cu Cable
11.2.4 - 1Cx10 Sq. mm, Cu Cable
11.2.5 - 1Cx6 Sq. mm, Cu Cable
11.2.6 - 1 X 2.5 sq. mm, Cu
11.2.7 - 1 x 4 sq. mm, Cu
12 - Wiring & Accessories
12.1 - 3 Phase, 100A TP Disconnector switch, in a Poly Carbonate IP-65 enclosure, (as specified in Part-2 section VII Sub section-D unit 4 Clause 4.2.5 and drawings)
12.2 - 3 Phase, 100A TPN Disconnector switch, with 100A FP RCBO of 300mA sensitivity, in a Poly Carbonate IP-65 enclosure, (as specified in Part-2 section VII Sub section-D unit 4 Clause 4.2.5 and drawings)
12.3 - 3 Phase, 63A TP Disconnector switch, in a Poly Carbonate IP-65 enclosure, (as specified in Part-2 section VII Sub section-D unit 4 Clause 4.2.5 and drawings)
12.4 - 3 Phase, 63A TPN Disconnector switch, in a Poly Carbonate IP-65 enclosure, (as specified in Part-2 section VII Sub section-D unit 4 Clause 4.2.5 and drawings)
12.5 - 3 Phase, 32A TP Disconnector switch, in a Poly Carbonate IP-65 enclosure, (as specified in Part-2 section VII Sub section-D unit 4 Clause 4.2.5 and drawings)
12.6 - 3 Phase, 40A TPN Disconnector switch, in a Poly Carbonate IP-65 enclosure, (as specified in Part-2 section VII Sub section-D unit 4 Clause 4.2.5 and drawings)
12.6 - 3 Phase, 32A TPN Disconnector switch, in a Poly Carbonate IP-65 enclosure, (as specified in Part-2 section VII Sub section-D unit 4 Clause 4.2.5 and drawings)
12.7 - 3 Phase, 20A TP Disconnector switch, in a Poly Carbonate IP-65 enclosure, (as specified in Part-2 section VII Sub section-D unit 4 Clause 4.2.5 and drawings)
12.8 - 3 Phase, 20A TPN Disconnector switch, in a Poly Carbonate IP-65 enclosure, (as specified in Part-2 section VII Sub section-D unit 4 Clause 4.2.5 and drawings)
12.9 - 3 Phase, 16A TP Disconnector switch,in a Poly Carbonate IP-65 enclosure, (as specified in Part-2 section VII Sub section-D Clause 4.2.5 and drawings)
12.10 - 1 Phase, 16A DP Disconnector switch, in a Poly Carbonate IP-65 enclosure, (as specified in Part-2 section VII Sub section-D unit 4 Clause 4.2.5 and drawings)
12.11 - 3 Phase, 10A TPN Disconnector switch,in a Poly Carbonate IP-65 enclosure, (as specified in Part-2 section VII Sub section-D unit 4 Clause 4.2.5 and drawings)
12.12 - 3 Phase, 10A TP Disconnector switch,in a Poly Carbonate IP-65 enclosure, (as specified in Part-2 section VII Sub section-D unit 4 Clause 4.2.5 and drawings)
12.13 - 1 Phase, 6A DP Disconnector switch, in a Poly Carbonate IP-65 enclosure, (as specified in Part-2 section VII Sub section-D unit 4 Clause 4.2.5 and drawings)
12.14 - 1 Phase, 3 pin, 16A 240V Modular unswitched socket on a suitable size mounting boxes (as specified in Part-2 section VII Sub section-D unit 4 Clause 4.2.4 and drawings)
12.15 - 1 Phase, 5 pin, 6/16A, 240V Modular socket with switch on a suitable size mounting boxes (as specified in Part-2 section VII Sub section-D unit 4 Clause 4.2.4 and drawings)
12.16 - Mushroom head with Key lockable, 3 Phase, Emergency push Button box, (as specified in Part-2 section VII Sub section-D unit 4 Clause 4.2.6 and drawings)
12.17 - Polycarbonate cable junction boxes, IP-66 (IK-10) (as specified in Part-2 section VII Sub section-D unit 4 Clause 4.2.7 and drawings)
13 - Wiring for the following 16A socket outlet point with 3 x 4 sq. mm, 1100V grade as per BS-7211 FRLSH copper conductor wires in heavy gauge GI conduit surface run with GI saddles. as per specifications as specified in Part-2 section VII sub section D unit 3 clause 3.4.1 and drawings as required
13.1 - One no. 6/16A socket outlet point controlled by one 16A switch.
13.2 - Secondary or looping 2 Nos. 6A or 1 No. 16A socket outlet points wiring above using 3 x 4 sq. mm copper (P+N+PE) wires (Non fire survivel) in 25mm dia GI conduit for socket outlets including providing terminal block, ceiling rose & other accessories etc as required (excluding the cost of switches, sockets & switch boxes) as per specificationsas specified in Part-2 section VII sub section D Unit 3 clause 3.4.1 and drawings as required
14 - Wiring for the following 16A socket outlet point with 3 x 4 sq. mm, 1100 Volt grade as per BS-7211 (for wires) & BS 6387 (for cables) copper conductor wires in heavy gauge GI conduit surface run with GI saddles. as per specifications as specified in Part-2 section VII sub section D unit 3 clause 3.4.1 and drawings as required
14.1 - One no. 6/16A socket outlet point controlled by one 16A switch.( UPS socket outlets)
14.2 - Secondary or looping 2 Nos. 6A or 1 No. 16A socket outlet points wiring above using 3 x 4 sq. mm copper (P+N+PE) wires (Fire survival) in 25mm dia GI conduit for socket outlets including providing terminal block, ceiling rose & other accessories etc as required (excluding the cost of switches, sockets & switch boxes)as per specifications as specified in Part-2 section VII sub section D unit 3 clause 3.4.1 and drawings as required
Description of Work / Item(s)
Amount
1- PRICE CENTRE - F (ISMS WORKS)
2- General: ISMS System shall provide with Manufacturing, Supply, Installation, Testing(FAT, SAT,PAT, etc), Integrated Testing and Commissioning along with operational acceptance along with DLP for two years.
3- SCADA Central Processing Equipment (Server ) (Refer Section VII, Sub Section E, Clause 5.2)
4- Optical Mouse and Keyboard (Refer Section VII, Sub Section E, Clause 5.7 & 5.8)
5- Antivirus Software (Refer Section VII, Sub Section E, Clause 5.9)
6- Standard MS Office Package (Refer Section VII, Sub Section E, Clause 5.6)
7- SCADA Colour Monitor(32 Inch monitor) (Refer Section VII, Sub section E, Clause 5.3)
8- SCADA Printers (Refer Section VII, Sub section E, Clause 5.10)
9- NETWORK SWITCHES: (Refer Section VII, Sub section E, Clause 5.11)
9.1- At Stations- OFC Ethernet Switches-L3 , 12 port (04 OFC port + 8 Ethernet Ports) {Managed} (Refer Section VII, Sub section E, Clause 5.11.1)
9.2- At Stations - OFC Ethernet Switches-L2 - 8 port (02 OFC port + 06 Ethernet Ports) {Unmanaged} (Refer Section VII, Sub section E, Clause 5.11.2)
9.3- At Stations - OFC Ethernet Switches-L2 - 12 port (02 OFC port + 10 Ethernet Ports) {Unmanaged} (Refer Section VII, Sub section E, Clause 5.11.2)
9.4- OFC Ethernet Switches-L3 , 14 port (02 OFC port + 12 Ethernet Ports) {Managed} (Refer Section VII, Sub section E, Clause 5.11.1)
9.5- Network Switch Rack (Refer Section VII, Sub section E, Clause 5.12)
9.6- Network Server Rack for OCC & BOCC (Refer Section VII, Sub section E, Clause 5.13.1)
9.7- Network Server Rack for Station Server and OCC & BOCC Workstations (Refer Section VII, Sub section E, Clause 5.13.2)
10- SCADA VAC HMI Touch Screen (12 Inch) (Refer Section VII, Sub section E, Clause 6.5)
11- ISMS PLC, Remote I/O and It's Sub-components and Mounting Panel (For I/O distribution refer I/O Schedule) (Refer Section VII, Sub section E, Clause 4.1 to 4.8 , 4.11 & 5.16)
11.1- Main PLC (Primary PLC)
11.1.1- Minimum SIL-2 CPU(Primary)
11.1.2- RIO Communication Module
11.1.3- SIL-2 DI(8 Ch)
11.1.4- SIL-2 DI(16 Ch)
11.1.5- SIL-2 DI(32 Ch)
11.1.6- SIL-2 DI(64 Ch)
11.1.7- SIL-2 DO(8 Ch)
11.1.8- SIL-2 DO(16 Ch)
11.1.9- SIL-2 DO(32 Ch)
11.1.10- SIL-2 AI(8 Ch)
11.1.11- SIL-2 AI(16 Ch)
11.1.12- SIL-2 AO(4 Ch)
11.1.13- SIL-2 AO(8 Ch)
11.1.14- Non Safe DI(8 Ch)
11.1.15- Non Safe DI(16 Ch)
11.1.16- Non Safe DI(32 Ch)
11.1.17- Non Safe DI(64 Ch)
11.1.18- Non Safe DO(8 Ch)
11.1.19- Non Safe DO(16 Ch)
11.1.20- Non Safe DO(32 Ch)
11.1.21- Non Safe AI(8 Ch)
11.1.22- Non Safe AI(16 Ch)
11.1.23- Non Safe AO(4 Ch)
11.1.24- Non Safe AO(8 Ch)
11.1.25- Serial Communication Module
11.1.26- PLC Enclosure
11.1.27- Misceleneous components (PLC configuration required components like Backplane, Redundant Power supply in Rack module, Connectors, MCB's, Surge Protection Device, Dual Bulk Power supply, diode oring module, terminal blocks(8/16/20/24/32/64/128), relays, LIU accessories, Pushbutton, Indication lamps, Internal wires, Alarm buzzer, Louvers,LED Light, Fans, etc.,)
11.2- Secondary PLC
11.2.1- Minimum SIL-2 CPU(Secondary)
11.2.2- RIO Communication Module
11.2.3- SIL-2 DI(8 Ch)
11.2.4- SIL-2 DI(16 Ch)
11.2.5- SIL-2 DI(32 Ch)
11.2.6- SIL-2 DI(64 Ch)
11.2.7- SIL-2 DO(8 Ch)
11.2.8- SIL-2 DO(16 Ch)
11.2.9- SIL-2 DO(32 Ch)
11.2.10- SIL-2 AI(16 Ch)
11.2.11- Non Safe DI(8 Ch)
11.2.12- Non Safe DI(16 Ch)
11.2.13- Non Safe DI(32 Ch)
11.2.14- Non Safe DI(64 Ch)
11.2.15- Non Safe DO(8 Ch)
11.2.16- Non Safe DO(16 Ch)
11.2.17- Non Safe DO(32 Ch)
11.2.18- Non Safe AI(8 Ch)
11.2.19- Non Safe AI(16 Ch)
11.2.20- Non Safe AO(4 Ch)
11.2.21- Non Safe AO(8 Ch)
11.2.22- Serial Communication Module
11.2.23- PLC Enclosure
11.2.24- Misceleneous components (PLC configuration required components like Backplane, Redundant Power supply in Rack module, Connectors, MCB's, Surge Protection Device, Dual Bulk Power supply, diode oring module, terminal blocks(8/16/20/24/32/64/128), relays, LIU accessories, Pushbutton, Indication lamps, Internal wires, Alarm buzzer, Louvers,LED Light, Fans, etc.,)
11.3- Remote I/O-1
11.3.1- RIO Communication Module
11.3.2- SIL-2 DI(32 Ch)
11.3.3- SIL-2 DI(64 Ch)
11.3.4- SIL-2 DO(8 Ch)
11.3.5- SIL-2 DO(32 Ch)
11.3.6- SIL-2 AI(16 Ch)
11.3.7- Non Safe DI(8 Ch)
11.3.8- Non Safe DI(64 Ch)
11.3.9- Non Safe DO(8 Ch)
11.3.10- Non Safe DO(16 Ch)
11.3.11- Non Safe DO(32 Ch)
11.3.12- Non Safe AI(16 Ch)
11.3.13- Non Safe AO(4 Ch)
11.3.14- Non Safe AO(8 Ch)
11.3.15- Serial Communication Module
11.3.16- PLC Enclosure
11.3.17- Misceleneous components (PLC configuration required components like Backplane, Redundant Power supply in Rack module, Connectors, MCB's, Surge Protection Device, Dual Bulk Power supply, diode oring module, terminal blocks(8/16/20/24/32/64/128), relays, LIU accessories, Pushbutton, Indication lamps, Internal wires, Alarm buzzer, Louvers,LED Light, Fans, etc.,)
11.4- Remote I/O-2
11.4.1- RIO Communication Module
11.4.2- SIL-2 DI(8 Ch)
11.4.3- SIL-2 DI(16 Ch)
11.4.4- SIL-2 DI(64 Ch)
11.4.5- SIL-2 DO(8 Ch)
11.4.6- SIL-2 DO(16 Ch)
11.4.7- SIL-2 DO(32 Ch)
11.4.8- SIL-2 AI(16 Ch)
11.4.9- Non Safe DI(8 Ch)
11.4.10- Non Safe DI(64 Ch)
11.4.11- Non Safe DO(8 Ch)
11.4.12- Non Safe DO(16 Ch)
11.4.13- Non Safe DO(32 Ch)
11.4.14- Non Safe AI(8 Ch)
11.4.15- Non Safe AI(16 Ch)
11.4.16- Non Safe AO(4 Ch)
11.4.17- Non Safe AO(8 Ch)
11.4.18- Serial Communication Module
11.4.19- PLC Enclosure
11.4.20- Misceleneous components (PLC configuration required components like Backplane, Redundant Power supply in Rack module, Connectors, MCB's, Surge Protection Device, Dual Bulk Power supply, diode oring module, terminal blocks(8/16/20/24/32/64/128), relays, LIU accessories, Pushbutton, Indication lamps, Internal wires, Alarm buzzer, Louvers,LED Light, Fans, etc.,)
11.5- Non SIL CPU
11.5.1- Non SIL CPU
11.5.2- RIO Communication Module
11.5.3- Non Safe DI(8 Ch)
11.5.4- Non Safe DI(16 Ch)
11.5.5- Non Safe DI(32 Ch)
11.5.6- Non Safe DI(64 Ch)
11.5.7- Non Safe DO(8 Ch)
11.5.8- Non Safe DO(16 Ch)
11.5.9- Non Safe DO(32 Ch)
11.5.10- Non Safe AI(8 Ch)
11.5.11- Non Safe AI(16 Ch)
11.5.12- Non Safe AO(4 Ch)
11.5.13- Non Safe AO(8 Ch)
11.5.14- Serial Communication Module
11.5.15- PLC Enclosure
11.5.16- Misceleneous components (PLC configuration required components like Backplane, Redundant Power supply in Rack module, Connectors, MCB's, Surge Protection Device, Dual Bulk Power supply, diode oring module, terminal blocks(8/16/20/24/32/64/128), relays, LIU accessories, Pushbutton, Indication lamps, Internal wires, Alarm buzzer, Louvers,LED Light, Fans, etc.,)
12*- Station Software
12.1- SIL-2 PLC SOFTWARE SIL-2 Programming Software license Supply and Development in stations (Refer Section VII, Sub section E, Clause 4.9 & 4.10)
12.2- Non SIL PLC SOFTWARE Non SIL Programming Software license Supply and Development in stations (Refer Section VII, Sub section E, Clause 4.11)
12.3- SCADA Software: ISMS SCADA software license Supply and Development based on the Employer requirements in Stations. (Refer Section VII, Sub section E, Clause 6.1 to 6.4)
13- CCTV Cameras with supporting accessories (CCTV Supporting software -Cost is Inclusive in SCADA Software) (Refer Section VII, Sub section E, Clause 5.14)
14- OCC/BOCC Workstation (Refer Section VII, Sub section E, Clause 5.4)
15- OCC/BOCC Server (Refer Section VII, Sub section E, Clause 5.1)
16- OCC/BOCC Monitor (32 Inch) (Refer Section VII, Sub section E, Clause 5.3)
17- OCC/BOCC IBP HMI Touch Screen (15 Inch) (Refer Section VII, Sub section E, Clause 6.5)
18- OCC - Redundant hot stand by SIL-2 PLC, I/O modules and It's Sub-components and Mounting Panel (For I/O distribution refer I/O Schedule) (Refer Section VII, Sub section E, Clause 4.1 to 4.8 & 5.16)
18.1- SIL-2 CPU
18.2- SIL-2 DI(32 Ch)
18.3- Non Safe DO(32 Ch)
18.4- PLC Enclosure - (Corridor-4 - 9 UG stations)
18.5- Misceleneous components (PLC configuration required components like Backplane, Redundant Power supply in Rack module, Connectors, MCB's, Surge Protection Device, Dual Bulk Power supply, diode oring module, terminal blocks(8/16/20/24/32/64/128), relays, LIU accessories, Pushbutton, Indication lamps, Internal wires, Alarm buzzer, Louvers,LED Light, Fans, Mode Mimics, etc.,)
19- BOCC - Redundant hot stand by SIL-2 PLC, I/O modules and It's Sub-components and Mounting Panel (For I/O distribution refer I/O Schedule) (Refer Section VII, Sub section E, Clause 4.1 to 4.8 & 5.16)
19.1- SIL-2 CPU
19.2- SIL-2 DI(32 Ch)
19.3- Non Safe DO(32 Ch)
19.4- PLC Enclosure - (Corridor-4 - 9 UG stations)
19.5- Misceleneous components (PLC configuration required components like Backplane, Redundant Power supply in Rack module, Connectors, MCB's, Surge Protection Device, Dual Bulk Power supply, diode oring module, terminal blocks(8/16/20/24/32/64/128), relays, LIU accessories, Pushbutton, Indication lamps, Internal wires, Alarm buzzer, Louvers,LED Light, Fans, Mode Mimics, etc.,)
20*- OCC & BOCC Software
20.1- PLC SOFTWARE SIL-2 Programming Software license Supply and Development in OCC (Refer Section VII, Sub section E, Clause 4.9 & 4.10) - (Corridor-4 - 9 UG stations)
20.2- PLC SOFTWARE SIL-2 Programming Software license Supply and Development in BOCC(Refer Section VII, Sub section E, Clause 4.9 & 4.10) - (Corridor-4 - 9 UG stations)
20.3- SCADA Software: ISMS SCADA software license Supply and Development based on the Employer requirements in OCC. (Refer Section VII, Sub section E, Clause 6.1 to 6.4) - (Corridor-4 - 9 UG stations)
20.4- SCADA Software: ISMS SCADA software license Supply and Development based on the Employer requirements in BOCC. (Refer Section VII, Sub section E, Clause 6.1 to 6.4) - (Corridor-4 - 9 UG stations)
21*- Cyber Security (Refer Section VII, Sub section E, Clause 6.4.4)
22- Programming Maintenance Terminal(PMT) (Refer Section VII, Sub section E, Clause 5.5)
23- Sensors & Instruments (Refer Section VII, Sub section E, Clause 7 to 7.20)
23.1- CO2 Sensor
23.2- Differential Pressure Switch (Air)
23.3- Differential Pressure Switch (Water)
23.4- Differential Pressure Transmitter (Water)
23.5- Tunnel Air Velocity Sensor/ Atmosphere Air Velocity Sensor
23.6- Air Velocity Sensor (for Nozzle and Tunnel opening)
23.7- Trackway Air temperature Transmitter
23.8- Train Detection Sensor
23.9- PM -10 & 2.5 sensor
23.10- Duct Smoke Detector
23.11- Water Level Switch
23.12- Water Level Transmitter
23.13- Duct type Temperature and Humidity Sensors
23.14- Public Area and Room Temperature and Humidity Sensors
23.15- Ambient Temperature and Humidity Sensors
23.16- Hydrogen Sensor
23.17- Pressure Transmitter (Air)
23.18- Multi Channel Displays
24- Cable Containment(Perforated Cable trays) System along with accessories(bends, supports, etc) (Refer Section VII, Sub section E, Clause 9)
24.1- 600 mm wide x 75 mm deep
24.2- 450 mm wide x 75 mm deep
24.3- 300 mm wide x 50 mm deep
24.4- 200 mm wide x 50 mm deep
24.5- 150 mm wide x 50 mm deep
24.6- 100 mm wide x 50 mm deep
24.7- 50 mm wide x 50 mm deep
24.8- 25 mm GI Conduit
25- Cables( Refer Section VII, Sub section E, Clause 8.1 to 8.6)
25.1- Control Cable - Fire Survival Cables
25.1.1- 1 Pair Cable * 1.0 SQ.mm
25.1.2- 2 Pair Cable * 1.0 SQ.mm
25.1.3- 3 Pair Cable * 1.0 SQ.mm
25.1.4- 4 Pair Cable * 1.0 SQ.mm
25.1.5- 6 Pair Cable * 1.0 SQ.mm
25.1.6- 2 Core Cable * 1.0 SQ.mm
25.1.7- 4 Core Cable * 1.0 SQ.mm
25.1.8- 6 Core Cable * 1.0 SQ.mm
25.1.9- 8 Core Cable * 1.0 SQ.mm
25.1.10- 10 Core Cable * 1.0 SQ.mm
25.1.11- 12 Core Cable * 1.0 SQ.mm
25.2- Control Cable- Non Fire Survival Cables
25.2.1- 1 Pair Cable * 1.0 SQ.mm
25.2.2- 2 Pair Cable * 1.0 SQ.mm
25.2.3- 3 Pair Cable * 1.0 SQ.mm
25.2.4- 4 Pair Cable * 1.0 SQ.mm
25.2.5- 6 Pair Cable * 1.0 SQ.mm
25.2.6- 2 Core Cable * 1.0 SQ.mm
25.2.7- 4 Core Cable * 1.0 SQ.mm
25.2.8- 6 Core Cable * 1.0 SQ.mm
25.2.9- 8Core Cable * 1.0 SQ.mm
25.2.10- 10 Core Cable * 1.0 SQ.mm
25.2.11- 12 Core Cable * 1.0 SQ.mm
25.3- Fiber optical armoured single mode cable( Refer Section VII, Sub Section E, Clause 10.2)
25.4- CAT 6 cable (Refer Section VII, Sub Section E, Clause 10.1)
26- Submission of V Cycle Documents (TVS-12 contractor shall develop the V life cycle documents for all 9 UG stations (Corridor 4) and for the overall V life cycle document development from the OCC and BOCC level) as part of SIL-2 Assessment and support ISA for the SIL-2 Certification (Refer Section VII, Sub Section E, Clause 11)
27- Office Chair for stations and OCC & BOCC scada operator ( Refer Section VII, Sub section E, Clause 5.15)
Description of Work / Item(s)
Amount
PRICE CENTRE - G (Operation & Maintenance and Assistance during DLP)
Assist During DLP (Ref Chapter-19, Section VI of Part -2)
1-Class room Training for Employer's staffs for TVS/VAC Systems
2-On-Site Training for Employer's staffs for TVS/VAC Systems
3-Identify & Construction of DLP office cum storage (Minimum 300Sqm) (Ref Chapter-19, Section VI of Part -2 )
4-Maintenance of DLP office (Minimum 300Sqm) (Ref Chapter-19, Section VI of Part -2 )
Operation & Maintenance (Ref Chapter-21, Section VI of Part -2 )
5-O&M Manager
6-Junior Engineer /Electrical/Mechanical/AC
7-TVS/VAC Operator for Underground Stations
8-TVS/VAC Operator at OCC & BOCC
9-Maintenance of Web and Mobile App based Comprehensive Maintenance Management System (CMMS) for TVS/VAC during DLP period (Ref Chapter-21, Section VI Part -2 )
Description of Work / Item(s)
Amount
PRICE CENTRE - H (CAMC TVS/VAC/SCADA &VAC & TVS ELECTRICAL)
1-CAMC of Tunnel Ventilation System equipment’s installed in one side Stations and associated tunnels including Electrical and ISMS (Ref Chapter 20 Section VI of Part -2 )
2-CAMC of Tunnel Ventilation System equipment’s installed in both side stations and associated tunnels including Electrical and ISMS (Ref Chapter 20 Section VI of Part -2 )
3-CAMC of Ventilation and Air Conditioning system for VRF system equipment’s installed stations including Electrical and ISMS (Ref Chapter 20 Section VI of Part -2 )
4-CAMC of Thirumayilai Station ISMS systems (Ref Chapter 20 Section VI of Part -2 )
Operation & Maintenance (Ref Chapter 21 Section VI of Part -2 )
5-O&M Manager
6-Junior Engineer /Electrical/Mechanical/AC
7-Technicians /Electrical/Fitter/AC
8-TVS/VAC Operator at OCC & BOCC
9-Maintenance of Web and Mobile App based Comprehensive Maintenance Management System (CMMS) for TVS/VAC during CAMC period (Ref Chapter-21, Section VI Part -2 )
10-Maintenance of CAMC office (Continuation of DLP office of Minimum 300 Sqm) (Ref Chapter 20 Section VI of Part -2 )
11-Submission of Performance PBG for CAMC (Price Centre H)
12-Submission of all type of insurance/ CAR Policy/ Professional Indemnity Insurance (Ref) for CAMC (Price Centre H)
Description of Work / Item(s)
Amount
PRICE CENTRE - I (Custom duty TVS/VAC/SCADA &VAC & TVS ELECTRICAL)
Basic Custom Duty
Social Welfare Surcharges
ABS FUJITSU GENERAL PVT LTD
Larsen & Toubro
Blue Star Limited
UNIVERSAL MEP PROJECTS & ENGINEERING SERVICES LIMITED
EFKON India Private Limited
Blue Star Limited
Larsen & Toubro
UNIVERSAL MEP PROJECTS & ENGINEERING SERVICES LIMITED
ABS FUJITSU GENERAL PVT LTD
Blue Star Limited
Larsen & Toubro
UNIVERSAL MEP PROJECTS & ENGINEERING SERVICES LIMITED
EFKON India Private Limited
Blue Star Limited
Larsen & Toubro
UNIVERSAL MEP PROJECTS & ENGINEERING SERVICES LIMITED
EFKON India Private Limited
Blue Star Limited
Larsen & Toubro
UNIVERSAL MEP PROJECTS & ENGINEERING SERVICES LIMITED
EFKON India Private Limited
Blue Star Limited
Larsen & Toubro
UNIVERSAL MEP PROJECTS & ENGINEERING SERVICES LIMITED
Larsen & Toubro
UNIVERSAL MEP PROJECTS & ENGINEERING SERVICES LIMITED
EFKON India Private Limited
Blue Star Limited
EFKON India Private Limited
Larsen & Toubro
UNIVERSAL MEP PROJECTS & ENGINEERING SERVICES LIMITED
Blue Star Limited
ABS FUJITSU GENERAL PVT LTD
UNIVERSAL MEP PROJECTS & ENGINEERING SERVICES LIMITED
Blue Star Limited
Larsen & Toubro
US Dollar
European Euro
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
US Dollar
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid