Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.4 LAccepted-AOC 1 19 12 KATHAR MEERAN NAGAR THERMAL NAGAR TUTICORIN 628 006 | TUTICORIN | TAMIL NADU | 628006 | L1 | Accepted-AOC Work was Awarded | |
| 2 | L2₹5.3 L+₹60,760 (13.1%)Rejected-AOC 40 E SUNDARAVELPURAM 7TH STREET TUTICORIN 628 002 | TUTICORIN | TAMIL NADU | 628002 | L2 | Rejected-AOC Work was not Awarded |
Tender Value
Refer Docs
EMD Value
₹4,700
Closing Date
19 Feb 2025, 2:00 pmClosed
CE/TTPS
Chief Engineer / TTPS, Tuticorin
Fault attending in boiler auxiliary motors and modules valve motors soot blower motor and preventive maintenance of Ash silo transformer A and B of unit IV and V for the period from 01 04 2025 to 31 03 2026.
2025_EB_522638_1
CE/SE/ES/TTPS/No.17/2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
365 days
TTPS
As per BQR conditions in NIT
7 documents required · 7 mandatory
₹0
₹4,700
Yes
2 May 2025
4 Feb 2025
20 Feb 2025
4 Feb 2025
19 Feb 2025
4 Feb 2025
Maintenance of L.T. Boiler auxiliary motor De-termination of power cable, removal of L.T. Boiler auxiliary motor from the bed, measurement of IR values and winding resistance values of the motor, field coil and tacho-coil in the RC feeder motor and fault rectification by dismantling the motor and replacing the failed and worn out parts, reassembling and re fixing the motor on the bed, checking complete alignment, reconnecting the power cable and conducting trial run satisfactorily.(Including Cost of consumables, and hire charges for T&P).
Maintenance of L.T. Boiler valve motor / Soot blower motor Determination of power cable, removal of valve motor from the actuator, measurement of IR values and winding resistance values in the motor, and fault rectification by dismantling the motor and replacing the failed and worn out parts, reassembling and re fixing the motor on the actuator, reconnecting the power cable and conducting trial run satisfactorily. (Including Cost of consumables, and hire charges for T&P) Valve Motor - 12 Nos. Soot blower motor-24 Nos. Total - 36 Nos.
Rectification of LT Module Inspection of module during fault and rectification of the fault by tracing the control circuit, checking of tightness, replacing failed parts, complete checking the healthiness of module and out going cable in the BMCC, BVMCC, and soot blower modules.
Maintenance of Ash Silo Transformer Removal of Terminal box cover, measurement of IR values, checking tightness, inspection of cables, breather, explosion vent, oil level and collecting of oil sample for BDV test and complete cleaning of Ash silo Transformer A & B. (Including Cost of consumables, and hire charges for T&P).
S. MURUGAN CONTRACTOR (BID ID -1253724)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .