Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | Safe India Hi-Tech Systems L1₹7.5 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹7.8 L+₹25,819 (3.44%)Rejected-Finance GLYPTIC RAIPUR P O BHITA BURDWAN 713102 | BURDWAN | PURBA BARDHAMAN | WEST BENGAL | 713102 | L2 | Rejected-Finance L2 | |
| 3 | L3₹7.8 L+₹28,880 (3.85%)Rejected-Finance | L3 | Rejected-Finance L3 | |
| 4 | L4₹8.0 L+₹49,900 (6.65%)Rejected-Finance NO 501 SACAYA TECHNOLOGIES PVT LTD 7TH CROSS 7TH MAIN JP NAGAR BENGALURU KARNATAKA 560078 | BENGALURU URBAN | KARNATAKA | 560078 | L4 | Rejected-Finance L4 | |
| 5 | L5₹8.4 L+₹94,800 (12.6%)Rejected-Finance 1001 SHIVALIK ABAISE 100 FEET ROAD OPP ANANDNAGAR APARTMENT PRAHALADNAGAR AHMEDABAD AHMEDABAD GUJARAT 380015 | AHMADABAD | GUJARAT | 380015 | L5 | Rejected-Finance L5 |
Tender Value
Refer Docs
Closing Date
15 Feb 2021, 6:00 pmClosed
AGM (E-E)
HAL AIRPORT, BANGALORE
Provision of Addressable Fire Alarm System at AAI Technical Block, HAL Airport , Bangalore.
2021_AAI_69147_1
AAI/BG/E-E/FIRE-ALARM/2020-21
Open Tender
Electrical Works
Works
90 days
HAL AIRPORT, BANGALORE
Please refer Tender documents.
4 documents required · 4 mandatory
₹1,120
Exempted
15 Mar 2021
4 Feb 2021
17 Feb 2021
4 Feb 2021
15 Feb 2021
4 Feb 2021
4 Feb 2021 - 8 Feb 2021
Amount
Supply, Installation, Testing & Commissioning of UL / EN listed (latest version) Modular Microprocessor based expandable intellegent Addressable Type Fire Alarm Control Panel of following loops, with minimum 320 character graphics / LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM) ,The panel should be equiped with loop capacity to take minimum 240 intellegent addressable detectors/ devices (In any combination ) in one loop, 230 volts, 50 Hz AC power supply, automatic battery charger, 24 volts sealed maintenance free lead acid batteries sufficient for 2 hours normal working and then be capable of operating the system for 30 minutes during an emergency / fault conditions along with battery stand as required.
Supply, Installation, Testing & commissioning of UL / EN listed (latest version) intelligent addressable multi criteria detector {Smoke + heat } with inbuilt fault isolator / isolator base and with unique optical sensing chamber, visible LED, fully coated circuit board, superior RF / Transient protection suitable for 2 wires loop connection, complete with plug into common separate base & housing constructed of LEXAN (or polycarbonate) complete with connections etc. as required and to be installed below / above false ceiling roof and concealed space and as per enclosed specifications ,complete as required. (Cost of plug in common base shall deemed to be included in cost of detectors)
Supply, installation, testing and commissioning of UL / EN listed (latest version) Intelligent addressable Control Module/ Relay Module (output module) with inbuilt fault isolator /hooter complete with termination etc. complete as required and as per enclosed specifications.
Supply, Installation, Testing & commissioning of UL / EN listed (latest version) intelligent addressable Manual call station (Resetable pull / push type) suitable for semi flush mounting, IP 54 for indoor use & IP 65 for outdoor use with inbuilt fault isolator / isolator module with double gang outlet box, equipment for key operated test-reset lock, electronic or rotary switches for address setting.Manual pull station shall be connected with two wire to SLC loop of Fire Control Panel. Cover shall be made out of LEXAN (or polycarbonate equivalent) with clear operating instruction and the word Fire appearing on the front complete with connections etc. as required and as per enclosed specifications.
Supply, installation, testing and commissioning of UL / EN listed (latest version) loop powered addressable Hooter-cum- strobe with inbuilt fault isolator / isolator module with adjustable sound level in the range of min. 90 db to Max. 120 db at 1M distance complete with termination etc. as required and as per enclosed specification.
Providing, installation, testing & commissioning of UL / EN listed (Latest Version) Monitor Module / input module with inbuilt fault isolator / isolator module (for monitoring different electrical / mechanical device etc) as per specifications.
Supply, Installation, Testing & Commissioning of UL / EN listed (latest version) Repeater Panel shall provide pin point location of the fault or fire event and should Provide complete control of system at remote location. The panel shall have a 320 character graphics / LCD display with touch screen or other keypad.
Supply, installation, testing and commissioning of UL / EN listed (Latest Version) Response Indicators for getting fire indications of detectors i/c mounting boxes installed above false ceiling area interconnecting to loop cable etc. as per specification complete as required.
Supplying, installation, testing & commissioning of Auto Dialer
Supplying & laying of 2 x 1.5 sqmm FRLS armoured cable, 600 / 1000V rated with annealed copper conductor as per applicable IS standared complete as required.
GLYPTIC
SALIMAX SYSTEMS AND CONTROLS ENGG
Sacaya Technologies Pvt Ltd
CENTRE TAP ENGINEERING
Ponmani International (India) Pvt Ltd
SUPER INDIA BUILDPRO PRIVATE LIMITED
DOGRA AND DOGRA ENTERPRISES
Nexus Fire And Security Systems
RPN Systems And Solutions
PRIASHA ENTERPRISES
OASIS ENGINEERS
stage.html
html • 0.07 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .