Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.2 LAccepted-AOC 300 PREM BASTI 10 SANGRUR SANGRUR PUNJAB 148001 | SANGRUR | PUNJAB | 148001 | L1 | Accepted-AOC Being lowest bidder | |
| 2 | L2₹23.9 L+₹2.7 L (12.9%)Rejected-AOC ASTBAL MOHALLA BANASAR BAGH ROAD PATIALA GATE SANGRUR 148001 | SANGRUR | SANGRUR | PUNJAB | 148001 | L2 | Rejected-AOC Being other than lowest bidder | |
| 3 | L3₹27.0 L+₹5.8 L (27.4%)Rejected-AOC 44 NEAR DURGA MANDIR TRIPURI TOABA TRIPURI TOWN PATIALA 147004 PB | PATIALA | PUNJAB | 147004 | L3 | Rejected-AOC Being other than lowest bidder |
| Sl No | Description | Qty | Unit | AGGARWAL & CO L1 | NARINDER KUMAR SONS L2 | Mohinder Pal and Sons L3 |
|---|---|---|---|---|---|---|
| 1.00'Notes: (i) Please refer Schedule 'A' Notes of tender documents. | ||||||
| 2.00 | Taking down carefully copper/ aluminium point wiring (light fan socket or power) complete along with fittings such as switches, ceiling roses,pendants, regulators,Tube fittings and other Kits & fittings/conduit from surface /wall . Removing the material from work site and making good the disturbed portion/ surface of wall/ floor/ ceiling etc by using cement mortar and colour/ white wash to match with the existing surface / location complete all as specified and directed.
Note :- Serviceable fitting / fixtures will be reused in the work as directed. | 213 | Point | 10 ₹2,130 | 1 ₹213 Lowest | 5 ₹1,065 |
| 3.00 | Taking down un-serviceable main switch, DB’s insulators, DB for MCB etc of any type and any capacity and further disposal including making good the disturbed surface and matching the colour of wall with the existing colour wash / paint / distemper wherever required (as per the existing ) omplete all as specified and directed. | 60 | Each | 10 ₹600 | 1 ₹60 Lowest | 20 ₹1,200 |
| 4.00M&L for point wiring with FRLS PVC insulated unsheathed multi-stranded copper conductor 1.5 Sq.mm (nominal area ) single core cable 1100 Volt grade drawn in and including rigid non metallic concealed PVC Conduit of suitable size (not less than 20 mm) in wall , on surface of ceiling with all fittings, such as tee, bend, elbow, socket etc including pressed steel sunken boxes (Terminal boxes) with earth dolly,duly galvanised, with white shade frame & cover plate of suitable module for modular switch / or sockets including FRLS PVC insulated unsheathed stranded copper conductor 1.5 Sq.mm (nominal area ) single core cable as earth continuity conductor to common earth and connected to earth dolly, and making the disturbed surface good again using cement mortar & colour/whitewash matching existing painted surface omplete all as specified and directed, for the following :- | ||||||
| 4.01 | One light/fan point controlled by one 1-way switch omplete all as specified and directed. | 85 | Point | 320 ₹27,200 | 300 ₹25,500 Lowest | 300 ₹25,500 Lowest |
| 4.02 | One light point controlled by two 2-way switch omplete all as specified and directed. | 8 | Point | 290 ₹2,320 Lowest | 300 ₹2,400 | 325 ₹2,600 |
| 4.03 | One 3/5 pin socket outlet, 5 Amp on independent board omplete all as specified and directed. | 30 | Point | 290 ₹8,700 Lowest | 300 ₹9,000 | 300 ₹9,000 |
| 4.04 | One 3/5 pin socket outlet, 5 Amp on same board omplete all as specified and directed. | 20 | Point | 100 ₹2,000 | 30 ₹600 Lowest | 120 ₹2,400 |
| 4.05 | One bell /buzzer point controlled by one push button on independent board omplete all as specified and directed. | 10 | Point | 290 ₹2,900 Lowest | 300 ₹3,000 | 300 ₹3,000 |
| 5.00 | M&L for point wiring with FRLS PVC insulated unsheathed multi-stranded copper conductor 4.0 Sq.mm (nominal area ) single core cable 1100 Volt grade drawn in and including rigid non metallic concealed PVC Conduit in wall , on surface of ceiling with all fittings, such as tee, bend, elbow, socket etc including pressed steel sunken boxes (Terminal boxes) with earth dolly,duly galvanised, with white shade frame & cover plate of suitable module for modular switch / or sockets including FRLS PVC insulated unsheathed stranded copper conductor 4.0 Sq.mm (nominal area ) single core cable as earth continuity conductor to common earth and connected to earth dolly, and making the disturbed surface good again using cement mortar & colour/whitewash matching existing painted surface omplete all as specified and directed. (For AC and Geyser) | 20 | Point | 450 ₹9,000 Lowest | 700 ₹14,000 | 480 ₹9,600 |
Tender Value
Refer Docs
EMD Value
₹72,000
Closing Date
4 Aug 2025, 6:00 pmClosed
Garrison Engineer (South) Patiala
MILITARY ENGINEER SERVICES GARRISON ENGINEER SOUTH SANGRUR ROAD PATIALA CANTT
As per tender documents
2025_MES_719006_1
GE(S)/PAT/T-19/2025-26
Open Tender
Civil Works
Item Rate
240 days
Sangrur
Refer tender documents
8 documents required · 8 mandatory
₹500
Yes
GE (South) Patiala
₹72,000
Yes
20 Sept 2025
7 Jul 2025
6 Aug 2025
7 Jul 2025
4 Aug 2025
21 Jul 2025
7 Jul 2025 - 14 Jul 2025
Amount
'Notes: (i) Please refer Schedule 'A' Notes of tender documents.
Taking down carefully copper/ aluminium point wiring (light fan socket or power) complete along with fittings such as switches, ceiling roses,pendants, regulators,Tube fittings and other Kits & fittings/conduit from surface /wall . Removing the material from work site and making good the disturbed portion/ surface of wall/ floor/ ceiling etc by using cement mortar and colour/ white wash to match with the existing surface / location complete all as specified and directed. Note :- Serviceable fitting / fixtures will be reused in the work as directed.
Taking down un-serviceable main switch, DB’s insulators, DB for MCB etc of any type and any capacity and further disposal including making good the disturbed surface and matching the colour of wall with the existing colour wash / paint / distemper wherever required (as per the existing ) omplete all as specified and directed.
M&L for point wiring with FRLS PVC insulated unsheathed multi-stranded copper conductor 1.5 Sq.mm (nominal area ) single core cable 1100 Volt grade drawn in and including rigid non metallic concealed PVC Conduit of suitable size (not less than 20 mm) in wall , on surface of ceiling with all fittings, such as tee, bend, elbow, socket etc including pressed steel sunken boxes (Terminal boxes) with earth dolly,duly galvanised, with white shade frame & cover plate of suitable module for modular switch / or sockets including FRLS PVC insulated unsheathed stranded copper conductor 1.5 Sq.mm (nominal area ) single core cable as earth continuity conductor to common earth and connected to earth dolly, and making the disturbed surface good again using cement mortar & colour/whitewash matching existing painted surface omplete all as specified and directed, for the following :-
One light/fan point controlled by one 1-way switch omplete all as specified and directed.
One light point controlled by two 2-way switch omplete all as specified and directed.
One 3/5 pin socket outlet, 5 Amp on independent board omplete all as specified and directed.
One 3/5 pin socket outlet, 5 Amp on same board omplete all as specified and directed.
One bell /buzzer point controlled by one push button on independent board omplete all as specified and directed.
M&L for point wiring with FRLS PVC insulated unsheathed multi-stranded copper conductor 4.0 Sq.mm (nominal area ) single core cable 1100 Volt grade drawn in and including rigid non metallic concealed PVC Conduit in wall , on surface of ceiling with all fittings, such as tee, bend, elbow, socket etc including pressed steel sunken boxes (Terminal boxes) with earth dolly,duly galvanised, with white shade frame & cover plate of suitable module for modular switch / or sockets including FRLS PVC insulated unsheathed stranded copper conductor 4.0 Sq.mm (nominal area ) single core cable as earth continuity conductor to common earth and connected to earth dolly, and making the disturbed surface good again using cement mortar & colour/whitewash matching existing painted surface omplete all as specified and directed. (For AC and Geyser)
M&L for point wiring with FRLS PVC insulated unsheathed multi-stranded copper conductor 2.5 Sq.mm (nominal area ) single core cable 1100 Volt grade drawn in and including rigid non metallic concealed PVC Conduit in wall , surface of ceiling with all fittings, such as tee, bend, elbow, socket etc including pressed steel sunken boxes (Terminal boxes) with earth dolly,duly galvanised, with white shade frame & cover plate of suitable module for modular switch / or sockets including FRLS PVC insulated unsheathed stranded copper conductor 2.5 Sq.mm (nominal area ) single core cable as earth continuity conducter to common earth and connected to earth dolly,and making the disturbed surface good again using cement mortar & colour/whitewash matching existing painted surface omplete all as specified and directed. (For power points)
Dismantling/Taking down existing unsv sub main wiring from batten / conduit of any size all as directed. Removing the material from work site and making good the disturbed portion/ surface of wall/ floor/ ceiling etc by using cement mortar and colour/ white wash to match with the existing surface / location omplete all as specified and directed.
M &L for sub main surface wiring with PVC insulated unsheathed copper conductor cable of size 10 Sqmm single core including concealed rigid nonmetallic PVC conduit of suitable size (Not less than 25 mm dia) in wall and surface of ceiling including 10 Sqmm PVC insulated unsheathed copper conductor cable for continuous earthing form main earth dolly including making good the disturbed potion of wall omplete all as specified and directed. Note :- Two run of 10 Sqmm copper cable one run of 10 Sqmm copper cable and PVC conduit will be measured as a single length
M &L for sub main surface wiring with PVC insulated unsheathed copper conductor cable of size 6 Sqmm single core including concealed rigid nonmetallic PVC conduit of suitable size (Not less than 25 mm dia) in wall and surface of ceiling including 6 Sqmm PVC insulated unsheathed copper conductor cable for continuous earthing form main earth dolly including making good the disturbed potion of wall omplete all as specified and directed. Note :- Two run of 6 Sqmm copper cable one run of 6 Sqmm copper cable and PVC conduit will be measured as a single length
S&F Switch Modular type, 6 Amp, 240 Volts , one way complete fixed as in repair all as specified and directed.
S&F Switch Modular type, 6 Amp, 240 Volts , Two way complete fixed as in repair all as specified and directed.
S&F Switch Modular type, 16 Amp,240 Volts , one way complete fixed as in repair all as specified and directed.
S&F Socket outlet, Modular type, 6 Amp complete fixed as in repair all as specified and directed.
S&F Socket outlet, Modular type, 6&16 Amp complete fixed as in repair all as specified and directed.
S&F Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 A complete all as specified and directed.
S&F Bell Push, Modular type, 6 Amp complete fixed as in repair all as specified and directed.
S&F Fan regulator, modular type electronic step type complete fixed as in repair all as specified and directed.
S&F ceiling rose surface bakelite two to three terminal 65x50 mm complete all as specified and directed.
Supply and fixing in replacement LED luminaire 600 mm x 600 mm, 40 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified & directed.
S&F in replacement Tube light fittings LED type 1x20 Watt 4 ft long incl LED tube rod and incl 3 core flexible wire 0.75 Sqmm copper cable complete all as specified & directed.
S&F in replacement Tube light fittings LED type 1X10 Watt, 2 ft long incl LED tube rod and incl 3 core flexible wire 0.75 Sqmm copper cable complete all as specified & directed.
S&F in replacement LED bulk head,10 W complete all as specified & directed.
S&F Lamp holder, PVC/Polycarbonate type with back plate suitable for batten fittings complete all as specified & directed.
S&F in bell ding dong operating on AC 230 volt single phase complete all as specified & directed.
S&F MCB DB SPN 2 Way with acrylic double door complete all as specified and directed.
S&F MCB DB SPN 4 Way with acrylic double door complete all as specified and directed.
S&F MCB DB SPN 8 Way with acrylic double door complete all as specified and directed.
S&F including flushing in wall MCB distribution board vertical TPN 4 way 415 Volts AC double door type sheet steel phosphotised powder painted with bus bar neutral earth bar including provision of MCB TPN, FP 100 Amp conforming to IP 43 as incomer all as complete specified and directed.
S&F MCB 4 TPN 63 Amp 415 volt with breaking capacity of 16 KA complete all as specified and directed.
S&F MCB 4 TPN 100 Amp 415 volt with breaking capacity of 16 KA complete all as specified and directed.
S&F MCB SPN 240V 40 Amps C series 10 KA complete all as specified and directed.
S&F MCB SP 240V 6 to 32 Amps C series 10 KA complete all as specified and directed.
Taking Down the KWH meter along with wooden board/DB after removing all electrical connection complete all as specified & directed.
Refixing & connecting the same after complete repair or new serviceable KWH energy meter after wiring complete all as specified & directed.
S&F Sheet metal enclosure factory made of size 20cm x 25cm x 12.5 cm deep box made out of 2mm thick ms sheet with double door with locking arrangement , epoxy power coated holes drilled for cable entries suitable for accomodating electric energy meter including brick/cement works as per site requirement includiing flushing the box in walll and making good the disturbed portion of wall /surface complete all as specified & directed.
Taking down old U/S aluminium service cable of any size from trenches/pipe/floor/walls complete all as specified & directed.
S&F PVC insulated , armoured heavy duty electric cable with aluminium conductor , 1100 volts grade , cross sectional area 25 sq mm as in repairs complete all as specified & directed.
M&L for earthing complete with galvanised steel earth plate electrode 600x600x6mm thick buried directly in ground (earth pit not less than 2 mtr deep below ground level with top edge of the plate not less than 1.4 mtr below normal ground level , connected earth wire 4 sqmm by means of bolts nuts check nuts and washers of galvanised iron or steel all as shown in electrical plate No 5 connected to earthing test point all as specified or indicated including PCC pit in PCC(1:3:6) type C-1 cast iron frame 50mm thick pre cast RCC(1: 1 1/2:3) nominal mix cover slab reinforced with 8 mm dia mild steel deformed bar 15cc and suitable handle of 10 mm Dia round bar including necessary excavation earth work in soft/loose soil and disposal of spoil to a distance not exc 50m and funnel with watering pipe wire mesh copper lugs etc GI protection pipe of size 15 mm bore including testing complete all as specified & directed.
S&F PVC flat twin core cable of size 2.5 sq mm, weather proof as in repairs complete all as specified & directed.
S&F PVC flat twin core cable of size 1.5 sq mm, weather proof as in repairs complete all as specified & directed.
S&F Switch piano flush type single pole, one way 6 amp as in repairs complete all as specified & directed.
S&F Switch piano flush type single pole, one way 16 amp as in repairs complete all as specified & directed.
S&F Bell multi music type as in repiars complete all as specified & directed.
S&F Socket outlet 2 in 1, 3 pin , 6 and 16 amp flush type as in repairs complete all as specified & directed.
S&F Socket outlet, 3 pin , 6 amp flush type as in repairs complete all as specified & directed.
S&F Switch socket combination 2 in 1 , 3 pin , 6 and 16 amp flush universal type as in repairs complete all as specified & directed.
S&F PVC rectangular block for mounting, switches, sockets, fan regulators etc. with 3 mm thick plastic laminated sheet cover of size 100 mm x 100 mm and 50 mm deep as in repairs complete all as specified & directed.
S&F PVC rectangular block for mounting, switches, sockets, fan regulators etc. with 3 mm thick plastic laminated sheet cover of size 175 mm x 100 mm and 50 mm deep as in repairs complete all as specified & directed.
S&F Modular white cover plate with frame 1 module complete all as specified & directed.
S&F Modular white cover plate with frame 2 module complete all as specified & directed.
S&F Modular white cover plate with frame 3 module complete all as specified & directed.
S&F Modular white cover plate with frame 4 module complete all as specified & directed.
S&F Modular white cover plate with frame 8 module complete all as specified & directed.
S&F Modular metal flush box 1/2 module complete all as specified & directed.
S&F Modular metal flush box 3 module complete all as specified & directed.
S&F Modular metal flush box 4 module complete all as specified & directed.
S&F Modular metal flush box 8 module complete all as specified & directed.
S&F Modular white blank plate complete all as specified & directed.
Dismantling and taking out the RCC poles/struts in any location and of any size complete all as specified & directed.
Taking down insulators of any type, any size shape from any location complete all as specified & directed.
Dismantling stay assembly complete with accessories complete all as specified & directed.
S&F in repairs stay assembly complete with accessories as shown in electrical plate No1 with 20 mm dia stay rod, stay wire and loop insulator incl taking out old unsv stay assembly complete all as specified & directed. Note : Earth work and PCC shall be measured and paid separately.
S&F in repairs Anti climbing device, spikes type fabricated out of MS bars(round,square an flat) including nuts, bolts washers and welding in two halves made to shape to suit the cross section of the pole complete all as specified and directed.
M&L for painting to existing of PCC poles 11/9 Mtr long long with one coat of synthetic enamel paint in alternate strips of black and yelow colours 30 cm height each total 05 Nos commencing form the top of PCC coping incuding painting of coss arms, nut bolts, clamps, junction boxes complete etc as fixed on pole with tow coats of aluminium paint and marking pole No with paint as per approved pattern,complete all as specified & directed. Note: Numbring shall be hand written only, size of letter 100X10mm (Heightxwidth)
Excavation in trenches n.exc 1.5 mtr deep and n.exc 1.5 mtr wide getting out in hard and dense soil complete all as specified & directed.
All as per item No-above but depth exceeding 1.5 meter and not exceeding 3 mtre complete all as specified & directed.
Returning filling in including spreading leveling, watering and well ramming in layers complete all as specified & directed.
Removing excavated soil to a distance not exc. 50 mtr and depositing where complete all as specified & directed.
M&L for sand cushioning with dry and clean over and under the cable, 80 mm sand laid before laying and 150 mm laid before laying the cable complete all as specified & directed.
S&F in repairs GI tube light grade 80 mm dia complete all as specified & directed.
M&L for PCC type D2 1:4:8 (40 mm graded aggregate) in cement concrete in foundations, filling and mass concrete for base of poles complete all as specified & directed.
M&L for PCC type C2 1:3:6 (40 mm graded aggregate) in cement concrete in foundations, filling and mass concrete complete all as specified & directed.
Material and labour for providing PCC 1:2:4 type B1 using 20 mm graded stone aggregate as in platform, filling and mass concrete, coping to pole etc., including dismantling/ breaking the existing concrete all as specified including necessary form work if required and applying two coats of white wash to exposed surfaces coping/platform complete all as specified & directed.
Supply and errecting in replacement prestressed concrete pole 9 mtr long, 102x172mm at top and 102x279mm at bottom, class 10 including painting upto 1.5 mtr from coping in alternate layers of black and yellow color paint and numbering of pole complete all as specified and directed.
S&F in replacement Pin type porcelain, vitreous,white,brown or green insulator including one galvanised mild steel spindle , two galvanised iron washers and one galvanised iron nut ,100mm height ,65mm dia for 1100 volt grade complete incl taking down old unsv insulators complete all as specified & directed.
S&F in repairs Shackle type porcelain, vitreous,white,brown or green insulator including galvanised mild steel straps, wahers, insulator bolts, washers and nuts of 1100 Volts grade height 100 mm dia 115 mm section of straps 31x5 mm and 14 mm dia bolts incl taking down old unsv insulators complete all as specified and directed.
S&F in repairs Danger notice plate of 1.6 mm thick mild steel sheet vitreous enamelled white with letters figures and conventional skull and bones in signal red colour and fixed with MS clamps bolts and nuts of approved size for LT 20x15cm size complete all as specified and directed.
Stringing and fixing only in position of sagged ACSR conductor in OH lines of street light conductor (squirrel/weasel), GI Earth wire complete including removing and refixing of UG cable/service wires to the ACSR conductor complete all as specified & directed. Note : The unit rate includes the cutting of branches of trees cominmg across the overhead line as directed.
Supply and laying in repairs XLPE/PVC insulated armoured and sheathed LT 1100 volts grade with aluminium conductor of size 240 sqmm 3½ core complete including taking out old unsv cable complete all as specified & directed.
All as item above but of size 185 sqmm 3½ core complete all as specified and directed.
All as item above but of size 95 sqmm 3½ core complete all as specified and directed.
All as item above but of size 70 sqmm 3½ core complete all as specified and directed.
All as item above but of size 50 sqmm 3½ core complete all as specified and directed.
All as item above but of size 35 sqmm 3½ core complete all as specified and directed.
All as item above but of size16 sqmm 4 core complete all as specified and directed.
All as item above but of size 10 sqmm 2 core complete all as specified and directed.
Laying only old serviceable bricks complete all as specified & directed.
Supply and laying best quality bricks locally availanle sub class ‘B’ bricks (old size) for cable protection cover laid flat and dry in trenches over the cable perpendicular to the direction of cable complete all as specified & directed.
S&F in repairs GI tube light grade 50 mm dia complete all as specified & directed.
S&F in replacement LT over Head line spacers, 4 wire 1100 volt grade complete all as specified & directed.
Supply and fix in replacement of 630 Amps MCCB, 415 Volts, 50 HZ, Breaking capacity 50 KA, 4 Pole, with thermal and Magnetic adjustment complete all as specified & directed.
Supply and fix in replacement of 400 Amps MCCB, 415 Volts, 50 HZ, Breaking capacity 36 KA, 4 Pole, with thermal and Magnetic adjustment complete all as specified & directed.
Supply and fix in replacement of MCCB 250 Amps, 415 Volts, 50 HZ, Breaking capacity 25 KA, 4 Pole, with thermal and Magnetic adjustment complete all as specified & directed.
Supply and fix in replacement of MCCB FP 160 Amps, 415 Volts, 50 HZ, Breaking capacity 25 KA, 4 Pole, with thermal and Magnetic adjustment complete all as specified and as directed.
Supply and fix in replacement of MCCB FP 125 Amps, 415 Volts, 50 HZ, Breaking capacity 25 KA, 4 Pole, with thermal and Magnetic adjustment complete all as specified and as directed.
Supply and fix in replacement of MCCB FP 100 Amps, 415 Volts, 50 HZ, Breaking capacity 25 KA, 4 Pole, with thermal and Magnetic adjustment complete all as specified and as directed.
Supply and fix in replacement of MCCB FP 63 Amps, 415 Volts, 50 HZ, Breaking capacity 25 KA, 4 Pole, with thermal and Magnetic adjustment complete all as specified and as directed.
Supply and fix in replacement LED type indication lamp set R-Y-B working at 220/240 V0lts AC incl taking out the old one complete all as specified and as directed.
Supply and replace in repairs LED flood light of 120 watt Pressure die-cast aluminium fixture complete with all accessories and all for fixing arrangements for existing high mast light of 15 mtr long complete all as specified & directed.
Supply and fix in repairs LED 20 watt post top with die cast aluminium body and with white powder coated aluminium reflector and IP-65 protection complete with fixing arrangements and elect connections complete all as specified & directed.
Supply and fixing in repairs power factor improvement statics condensor capacitor bank of capacity 25 KVAR including interconnection with LT panel with appropriate size of electrical cable complete all as specified & directed.
All as item above herein before but of capacity 12.5 KVAR complete all as specified & directed.
All as item above herein before but of capacity 10 KVAR complete all as specified & directed.
All as item above herein before but of capacity 5 KVAR complete all as specified & directed.
Repair/Maint LT electrical network in the jurisdiction of AGE B/R Sangrur cantt area scattered within 1 KM radius intimated by Engr-in-charge, JE, having good knowledge of comprising of LT line and fault rectification the defects are as under complete all as specified & directed. Note: Store/material required will be issued by department
Cleaning of all type of grass vegetation, saplins, shrubs, brush wood undergrowth roots etc, LT Panels, tightening of connections in LT breakers/ switchgears, APFC panel installed in sub station No -1,2,3,4,5,6,7,8,9,10,11,12,13&14 at various locations complete all as specified & directed.
Finding and rectification of fault on LT line and repair the LT line complete all as specified & directed.
Replacement of LED street lights of any type from existing pole complete all as specified & directed.
Connecting/disconnecting of airconditioner in married offrs qtrs,OTM,Offrs mess from the existing lines complete all as specified & directed.
Note (A) : (a) Contractor will provide all T&P, communication device (Mobile Phone) to deployed persons required for repair of LT Electrical switch gear including safety equipments such as all types of T&Ps (Bambooladders, screw drivers, wire/cable cutters with blades, multi meters, cutting pliers, tourch lights etc) for routine maintenance and protection of the trademan as well as daily activity incl safety dress, hand gloves, rubber boots, safety belts and helmets etc, complaint register, job card and necessary transportation required for attending complaints/faults/brake downs duty wiil be provided by the contractor without any extra cost. (b) On intimation of any type of fault tripping of LT switch gear incomer as well as outgoing feeder the contractor is responsible to locate the fault by the dedicated team comprising tradesman helpers required numbers as per the gravity/nature of the work involved to restorethe power supply and communicate with SBA on duty and getting permit card for working on LT lines and deposit the permit card after rectification of fault, all the activities shall be carried out within reasonable time as given by the Engineer-in-charge. (c) Periodical maintenance of following feeders which includes trimming of tree branches which are touching with LT feeders and overhead line, maintenance of GOD, jumpers, maintenance of defective disc or pin type insulators, tightening of jumpers, fixed and moving parts of GODs, restretching of LT overhead line conductors falling due to storms.
Note (B) : Penalty Charges : If any of the activity mentioned above is not performed by the contractor than recovery as under will be affected :- (a) Not providing T&P, protective clothing or safety equipment and not used by the team - Rs 500 per Job. (b) Not providing mobile phones duly re-charged or suitable transportation as per specified above or not attending the call - Rs 500 per job per mobile. (c) Not taken repair action within 01 hour after receiving job workt - Rs 500 per job.
Supply laying jointing in repairs aluminium service cable 16 sqmm 2 core fixing on wall/ducts etc including necessary fixing arrangement such as cable lugs glands etc complete after removing/taking out extg unsv cable to the entire satisfaction and complete all as specified & directed.
Supply laying jointing in repairs aluminium service cable 10 sqmm 2 core fixing on wall/ducts etc including necessary fixing arrangement such as cable lugs glands etc complete after removing/taking out extg unsv cable to the entire satisfaction and complete all as specified & directed.
Periodical cutting of all tree branches along above/under the over head lines with clearance of 2.0 mtr in Cantt area. (Approx length of LT over head lines - 10.00 Kms) complete all as specified & directed. Note : (i) Periodical (Quarterly as per schedule fixed by the GE/Engr-in-Charge and approved by the Stn HQ. (ii) Payment shall be made at the end the of each qtr. (iii) Cutting/Trimming record register sign by contracrt to be maintained Quarterly basis.
Servicing incl calibration/setting of all parameters and repairs of Electric Boom Barrier complete incl cleaning and greasing and testing for satiafactory operation as per manufacturer standards complete all as specified and directed.
Servicing incl calibration/setting of all parameters and repairs of Servo voltage stabilizer 100 KVA including replacement of all defective parts, cleaning and greasing and testing for satiafactory operation as per manufacturer standards complete all as specified and directed.
Servicing of Electric siren complete incl cleaning and greasing and testing for satiafactory operation as per manufacturer standards complete all as specified and directed.
Servicing of High Mast Light complete incl cleaning and greasing and testing for satiafactory operation as per manufacturer standards complete all as specified and directed.
Supply and replacement of High Mast Light forward and reverse starter as per existing make and model and making all connections as per existing complete all as specified and directed.
Supply and replacement of LED aviation light 10 watt as per existing make and model and making all connections as per existing at height of 15 mtr long high mast pole complete all as specified and directed.
Supply , installation, commissionning and testing in replacement of outdoor LT feeder pillar kiosk type made out of CRCA sheet 3.15 mm thick vermin proof factory made CPRI approved, with copper bus bar of capacity 100 Amps for 3 phase and neutral with nessary angle iron 50 x 50 x 6 mm support frame including two coats powder painting over a coat of red oxide primer and grout in PCC complete all as specified and directed comprising of the following complete all as specified and directed :- (High Mast) INCOMING : MCCB 40 A, 415 V, 4 pole with over load short circuit protection, breaking capacity 25 KA-01 No Indicator lamps RYB LED type(Set of Three)-01 No OUTGOING : MCCB 32 A, 415 V, 4 pole with over load short circuit protection, breaking capacity 25 KA-01 No MCB DP 6-32 A -01 No Wiring of above accessory with suitable size of copper conductor cable Note :-(i) All MCCBs / instruments / MCBs / Bus Bar shall be housed in a separate housing with on- off latches in the housing. (ii) Space for provn of one extra MCCB should be provided in the panel.
REPAIR TO GEYSERS WORKS Note:- Attending of day to day complaints of geysers by draning out the water and taking down carefully from wall after unscrewing nut/bolts geyser 50/35/25 Ltr capacity and opening the same for taking out internal tank, syphon assembley etc including replacement of defective unserviceable parts, reassembling and refixing after repair complete all as specified & directed. Note: i) Spares shall me measured and paid sepratley under respective items of Sch. ii) Penal charges of Rs 250 per day per complaint shall be imposed on contractor for not attending the complaint within 24 hrs. iii) Complaint register, complaint slips and stationary required to be provided by the contractor and his rep should be present 9.00 to 11.00 am in the MES complaint cell daily for receiving the complaints from mes rep throughout the contract period.
Supply only heating unit (element) 240 volt AC ISI marked of 1500 watts Circular/triangular shape rating as required at site including rubber washers complete all as specified & directed.
Supply only heating unit (element) 240 volt AC ISI marked of 1500 watts special type suitable for Bajaj / CG Geyser ( as per sample ) shape rating as required at site including rubber washers complete all as specified & directed.
Supply and replace thermostat switch suitable for 25/35/50 ltr geyser AC 230 volt adjustable range from 0-90 degree Celsius, complete all as specified and directed.
Supply and replace special type thermostat switch suitable for 25/35/50 ltr geyser AC 230 volt adjustable range from 0-90 degree Celsius for Bajat/CG Gerysers ( as per sample ), complete all as specified and directed.
Supply and replacement internal steel tank of geyser 25 ltr capacity complete with syphon-assembly, 1.5 kw element , rubber gasket , thermostat switch , complete all as specified and directed . Note: The tank shall be tested at site and shall be able to with stand the requisite pressure. Necessary testing equipment shall be arranged by the contractor .
Supply and replacement internal steel tank of geyser 50 ltr capacity complete with syphon-assembly, 2.0 kw element , rubber gasket , thermostat switch , complete all as specified and directed. Note: The tank shall be tested at site and shall be able to with stand requisite pressure . Necessary testing equipment shall be arranged by the contractor .
Supply and replacement of syphon assembly made out of brass of 50 ltr capacity including necessary studs, screws and rubber gasket/washers complete all as specified and directed.
All as per Srl item No. 128 above but for 25 ltr capacity, complete all as specified and directed.
Supply and replacement outer body suitable for 50 ltr geyser made out of MS sheet factory made complete with fixing bracket matching with existing, complete all as specified and directed.
Supply and replacement outer body suitable for 25 ltr geyser made out of MS sheet factory made complete with fixing bracket matching with existing complete all as specified and directed.
Supply and replace glass wool of 25 ltrs capacity geyser, complete all as specified & directed.
All as per Serial item No. 132 here in before but in 50 ltrs capacity geyser, complete all as specified & directed.
Supply and replace indicator lamp round/square type suitable for geyser 25/50 ltr all as per sample AC 230 Volt, complete all as specified & directed.
Supply and replace PVC connection 15mm dia 60 cm long complete with brass flair nuts at both ends. ( ISI marked and suitable for hot water supply upto 100 degree celcius), complete all as specified & directed.
Supply and replace PVC connection 15mm dia 90 cm Longcomplete with brass flair nuts at both ends. ( ISI marked and suitable for hot water supply upto 100 degree celcius), complete all as specified & directed.
Supply and fixing anchor bolt 12mmX100mm long complete all as specified and directed Note:- Anchor bolt shall be grouted with hammer drill only
Supply and fixing in replacement of defective mild steel base plate cup any type with screws of suitable size as per requirement complete, all as specified and as directed.
Supply and fixing in replacement of 15mm stop valve CP fancy type,cast copper alloy, screwed down high pressure with crutch or butterfly handle screwed both ends for iron pipe with unions, complete all as specified & directed.
Supply and fixing in replacement of 1100 Volt grade cable flexible 3 Core PVC insulated PVC sheathed with stranded copper conductor of size 2.5 sqmm, complete all as specified & directed.
Supply and fixing in replacement of CP connection brass with flair nuts all as per sample, complete all as specified & directed.
Cleaning / scrapping of old paint/dust and painting of geysers of 25/35/50 litres capacity at site/ stores with two coat of super enameled painting by spray, complete all as specified and as directed.
Supply and fixing in replacement single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amps, complete all as specified & directed.
Supply and fixing in replacement of mild steel galvanised iron water tubing 15mm bore with screwed & socket joints, medium grade, in short lenghts, with and including all fittings such as sockets, bends, elbow, unions, tees, diminishing pieces etc, fixed to wall or ceiling or in floor complete all as specified and directed.
Supply and fixing plug top 15 Amp three pin for geysers, complete all as specified & directed.
S&F in repair Bib taps, cast copper alloy with crutch or butterfly handle, screwed down, screwed for iron pipe or for brass ferrule and fixed of size 15mm dia, complete all as specified & directed.
M&L in repair for point wiring with 2.50 sqmm in copper conductor cable ( multistrand) FRLS single core PVC insulated cable in and including PVC conduit ( ISI Marked) with all accessories ie PVC gutties etc terminated in sunken/pressed metal flush box and white modular cover plate with frame for mounting of switches /sockets/ fan regulators etc and continuous earth wire 1.5 Sqmm copper stranded conductor as continuous earth wire connected to common earth dolly complete all as specified & directed. Note : i) Eye/bottle thimbles shall be used for connection in switches/sockets & MCB's in DB's without any extra cost. ii) Electric rewiring should be done in proper colour coding i.e. Red for phase, Black for neutral and Green for Earth.
Supply and fixing Gang box containing 15 Amp switch socket combination, modular type, complete all as specified & directed.
Supply and fixing Gang box containing 05 Amp switch socket combination, modular type, complete fixed as in repair all as specified.
REPAIR TO SOLAR WATER HEATING SYSTEM Attending of day to day Solar Water Heating System complaints taking down, opening up, reassembling, refixing and testing of Solar Water Heating System including replacement of unserviceable parts wherever required at the discretion of the Engr-in- Charge shall be carried out by the contractor for efficient functioning of Solar Water heating System. The cost of material will be measured and paid seperately for replalacement of parts complete all as specified and directed. Note: (i) Schedule of repair to Solar Water heating System is catered for attending day to day complaints of different items within the prescribed time schedule as decided by the EIC on complaint slip, failure to attend the complaint within the prescribed time shall attract a penalty of Rs 250 per day per complaint. (ii) All repair to Solar water heating system shall be carried out from an authorized person of the manufacturer of the system and proof there of shall be produced to the GE before undertaking repairs. Contractor is advised to visit the site to ascertain the model and manufacturer of system before quoting his rates.
Supply and replacement solar flat plate collector having collection area not less than 2.0 sqm made out of aluminium frame and toughened glass suitable for solar panel system complete all as specified and directed.(As per sample )
Supply & fix in repairs Heating element, 3 KW, ISI marked, copper sheathed, nickel plated suitable for any type, make, size of solar water geysers, complete all as specified and directed.
Repairs and replacement to existing MS framed supports to SS water tank of solar heating system of capacity 200/300/500 LPD by welding , provinding necessary MS pieces to strenghthing the frame, complete all as specified and directed.
M&L for De scaling of solar water heater complete of 300 LPD capacity with 02 Nos solar panel using suitable chemical including unsv nut bolts washer etc complete all as specified & directed.
M&L for De scaling of solar water heater complete of 500 LPD capacity with 02 Nos solar panel using suitable chemical including unsv nut bolts washer etc complete all as specified & directed.
M&L for preparing new surface of steel of any description and applying two coats of synthetic enamel paint over a coat of red oxide complete all as directed and specified.
NARINDER KUMAR SONS (BID ID -3375268)
Mohinder Pal and Sons (BID ID -3370217)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .