EE II CKHED
central kolkata health electrical division P12 CIT Road 1st floor Kol 14
Repairing and renovation of Electrical Installation Works for Plastic OT at Ground Floor Baker Building under the NRS Medical College and Hospital Kolkata SITC of UPS
2026_WBPWD_987915_1
WBPWD/EE-II/ CKHED/eNIT-94/25-26
Open Tender
ELECTRICAL WORKS ORG
30 days
NRS MCH
As per NIT
4 documents required · 4 mandatory
₹10,399
central kolkata health electrical division
29 Jan 2026
13 Jan 2026
29 Jan 2026
13 Jan 2026
27 Jan 2026
18 Jan 2026
17 Jan 2026
SITC of 15 KVA UPS including Battery Bank of not less than 19200 VAH or higher (SMF Battery 12 Volt, not less than 45AH ) 3ph Input & 1ph Output, static by pass arrangement, compitable with D.G. Set, DSP controlled IGBT based rectifire with minimum 95% efficiency on 100% Load. For active input P.F. Correction system to obtain minimum 0.95 lag at 100% resistive Load, Wave form - Pure sine wave. It Should be capable of operating in 50’c above ambient temprature, Built in Solid State float cum boost charger with automatic boost / trickel charge mode with current Limiting features. The charger should be designed for at least 15% of the total battery current. The UPS Should have current limiting protection, built in over load / Short circuit protection with snubber circuits for current limit. Soft start arrangement, Over voltage / under voltage protection, mains ON, Inverter ON/ OFF/ FAULTY/ TRIP (Reason), Charger ON/ FAULTY or TRIP, Battery Low, Static by-pass ON, Over temperature. Inbuilt Isolation Transformer of 1:1 ratio connected in Delta- Star Mode . Battery set Complete with self-standing cubicle or cabinet. The UPS should have external automatic load transfer switch for parallel operation.
Regulated Sealed Lead Acid Battery, Construction type : AGM or VRSLAB in ABS Flame Retardant Rating (12V SMF Battery -1 Lot) (Battery Make Amararaja Quntra/Exide Power Safe.Back up time 30 Min at full load. Certificate : ISO 9001:2015, ISO 14001:2015, IOS 18001,OHSAS 18001. CE Certification: IEC/ EN 62040-1-1, IEC/EN50091- 1,IEC/EN 60950(Safety),IEC/ EN 5009 I-2,IEC/ EN 62040-2 (EMC Emmission), IEC/EN 62040-3 (Performance & Design), IEC/EN 61000-4(EMC Emmunity) & IEC/ EN 60146 (Design & Manufacture) (Make: APC-Schneider Electric / NUMERIC/ Power One/ VERTIV/ Switching AVO/ Better Power/ Delta) Warranty : One Year on UPS and One Year on SMF Battery on site against any manufacturing defects. Certificate
SITC of wall mounted compartmenatalised L. T. Cubicle panel board made out of 16 SWG CRCA sheet with dust & vermin proof gasketted front open door with mechanical locking arrangement and to be fixed on wall b y means of 4nos. heavy duty M.S. bullet fastner. The board to be painted by powser coated paint includ-ing incorporating the following electrical accessories and making all necy. connections as per direction of E.I.C. (Approx. siz :900mm. X400mm. X 250mm) : - (a) 415V. 100A. 4-pole on load change over switch of open execu tion type [Make: L & T or similar specification of Havels / L&T]. ........................01 No. (b) Supplying and fixing 415 V 100 A Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs and necessary connection [Make:L & T or similar specification of Legrand/ Schneider]..................01 No. (c) 100A. 4-pole M.S.stud connector..................................01 No.
Supplying and Drawing 1.1 KV single core stranded 'FRLS' PVC insulated & unsheathed single core stranded copper wire (RR Kable/Finolex) of the following sizes in the PVC (40/50mm size) conduit pipe and by the prelaid GI fish wire and making necy. connection as required, as directed by EIC.
4x80/0.4 (10 sqmm) + 2x84/0.3 (6 sqmm) as ECC.(VTPN to changeover+Changeover to UPS and UPS to Changeover)
Finising the end of above PVC insulated & unsheathed copper wire.
4x80/0.4 (10 sqmm) + 2x84/0.3 (6 sqmm) as ECC
Terms and Condition: The Agency mlist procure the materials from the Manufacturer/ OEM or from their authorised sales channel so that the standard warranty/ support of the Manufacturer/ OEM becomes applicable to the products to be delivered and installed by them. Documents that authenticate such procurement from the Manufacturer/ OEM or from their authorized sales channel and standard warranty/ support should be sent from the e-mail of the Manufacturer/ OEM/ authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
Rate should be quoted incl. of all taxes and cess. (GST @18%)
Defect Liability period : 1 year
Please Enable Macros to View BoQ information
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.45 MB
revised2911.pdf
Tender Documents • 0.50 MB
BOQ_2413184.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid