Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L 1₹2.9 LAccepted-Finance | ₹2.9 L | L 1 | Accepted-Finance Accepted |
| 2 | L 2₹3.5 LAccepted-Finance | ₹3.5 L | L 2 | Accepted-Finance Accepted |
| 3 | L 3₹3.6 LAccepted-Finance A 401 PLOT NO 2 SECTOR 3 CGHS SANSAD VIHAR DELHI 110075 | DELHI | DELHI | DELHI | 110075 | ₹3.6 L | L 3 | Accepted-Finance Accepted |
| 4 | L 4₹4.3 LAccepted-Finance A 6 STREET NO 2 JAGAT PURI DELHI 110051 | SHAHDARA | DELHI | 110051 | ₹4.3 L | L 4 | Accepted-Finance Accepted |
| 5 | L 5₹5.6 LAccepted-Finance 30 74 BLOCK NO EXTRA 30 TRILOK PURI DELHI EAST DELHI 110091 | EAST | DELHI | 110091 | ₹5.6 L | L 5 | Accepted-Finance Accepted |
Tender Value
₹6.0 L
EMD Value
₹11,925
Closing Date
27 May 2026, 3:00 pmClosed
Er. Kanhaiya Sah
O/O EE (E), HPED, PWD, Chhat Ghat, New Delhi
RMO of 100 bedded LBS Hospital, Khichripur, Delhi.( SH Servicing and Maintenance of Substation Equipments)
2026_PWD_291702_1
07/EE(E)/HPED/PWD/2026-27
Open Tender
Electrical Works
30 days
At LBS Hospital Khichripur Delhi
As per tender documents
7 documents required · 7 mandatory
₹0
₹11,925
Yes
27 May 2026
21 May 2026
27 May 2026
21 May 2026
27 May 2026
21 May 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount | Item Code |
|---|---|---|---|---|---|---|
| 0.0 | Disconnecting, checking, complete servicing & cleaning of existing (TMC Make) 1250 KVA dry type transformer i/c replacement of gasket. The job also i/c complete servicing and cleaning of HT tapping & Busbar, maggering and tightening of all power components, testing of transformer, tightening of HT and LT connection i/c replacement of broken window panes etc. complete as required at site. | 2 | P/Job | 17,098 | ₹34,196 | BI01010001010000000000000515BI0100001105 |
| 0.0 | Testing and calibration of IDMT relay set having 2 Nos O/L and one No. earth fault relay installed in the existing HT/LT panel by secondary injection method i/c cleaning the contacts, resetting with required accuracy, complete checking & setting of control wiring i/c refixing of the relay unit etc. complete as required at site. | 3 | P/Job | 17,098 | ₹51,294 | BI01010001010000000000000515BI0100001106 |
| 0.0 | Servicing, checking and cleaning of 11 KV, 800 Amp HT breaker by opening HT panel and CT chamber, removing dust with vacuum cleaner, checking cleaning and decarbonising the contacts and joints of switch gear and CTs with CTC / CRC solution tightening of contacts and bus bars/ CT and PT connections/ cable end terminations, replacement of burnt / heated thimbles / nuts / bolts, HT tapping and monoplast compound i/c testing etc. complete as reqd. at site. The job also i/c servicing of moving gear assembly of 630 Amps, 3 phase, 11 KV, 350 MVA capacity VCB/OCB by opening the required parts i/c checking, cleaning, testing and rectification of defects, oiling & greasing of moving gear assembly with CR-2 spray and cadmium solution i/c testing & commissioning in the HT VCB panel etc. complete as required at site. | 5 | P/Job | 14,249 | ₹71,245 | BI01010001010000000000000515BI0100001107 |
| 0.0 | Servicing of Draw out type 630A – 2000 A, 3 Phase, 415 volt 50 Hz ACB in the MV Panel i/c cleaning & lubricating of moving parts, checking & testing of wring system, replacement of minor spare parts such as spring/ nuts/ bolts & washer, setting right the mechanism and reassembling, testing, commissioning etc. complete as reqd. at site. | 10 | P/Job | 9,024 | ₹90,240 | BI01010001010000000000000515BI0100001108 |
| 0.0 | Cleaning and checking of 3 phase, 4 wire 50 Hz AC supply bus trunking system arrangement of rating 800/1600/2000 Amps. i/c tightening of all joints, PVC tapping, etc. wherever required by opening of all the bus-trucking cover i/c removal of carbon, P/F the missing nut/bolts/screw/spring washer and refixing the covers at their original position etc. complete as required at site. | 50 | P/Mtr. | 1,425 | ₹71,250 | BI01010001010000000000000515BI0100001109 |
| 0.0 | Servicing of 11 KV/ 110 Volt PT complete i/c removal of PT from HT panel board, draining out the oil, removing core assembly, cleaning of dirty particles, tightening connections, checking of wiring , re-assembling, testing, commissioning etc. complete as required at site. | 1 | P/Job | 7,789 | ₹7,789 | BI01010001010000000000000515BI0100001110 |
| 0.0 | Testing the healthiness of related H/V 11 kV I/C and O/G cable with Hipot test in residence test (Meggar test), ampere test etc. complete as required at site. Note: Test report to be submitted. | 4 | P/Job | 6,649 | ₹26,596 | BI01010001010000000000000515BI0100001111 |
| 0.0 | Replacement of following faulty/ damage accessories / parts with new one for 11 KV H.T. Panel i/c buyback of the same, testing, commissioning etc. complete as reqd. at site. | - | - | - | - | BI01010001010000000000000515BI0100001112 |
| 0.9 | Master Trip Relay 24 Volts DC | 1 | Each | 7,882 | ₹7,882 | BI01010001010000000000000515BI0100001113 |
| 0.9 | Tripping Coil 24 Volts DC | 2 | Each | 6,486 | ₹12,972 | BI01010001010000000000000515BI0100001114 |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 9.23 MB
BOQ_387145.xls
BOQ • 0.27 MB
Download all tender documents and submit your bid