CWE AF SRINAGAR
CWE AF SRINAGAR C/O 01 WING AF
SPECIAL REPAIR TO POWER TRANSORMER 33KV 11 2.5 MVA CAPACITY UNDER GE AF AWANTIPUR
2020_MES_371618_1
CWE(AF)SGR/AWA-12/2020-21
Open Tender
Civil Works
Item Rate
180 days
GE AF AWANTIPUR
AS PER NIT
9 documents required · 9 mandatory
₹500
GE AF AWANTPUR
₹17,300
Yes
5 Nov 2020
24 Aug 2020
23 Sept 2020
24 Aug 2020
21 Sept 2020
8 Sept 2020
60 days
Amount
Isolation of transformer 2.5 MVA 33KV/11KV from existing electric circuit at GE (AF) Awantipur. Draining out oil in dry/ moisture free container, transportation of transformer to carry out repair work in any authorised transformer manufacturer in local region. Dismantling/ opening of transformer in presence of rep of accepting officer, reassembly of transformer after repair , filling of transformer oil, testing transformer in presence of rep of accepting officer for mandatory test like losses at no load and losses at 50% load , transformer winding impedance etc. Back loading of transformer to MES station at GE (AF) Awantipur, unloading the transformer, making all necessary HV/LV connections and testing the transformer on load to the satisfaction of Engineer-in-Charge. Note: - Arrangement for lifting of transformer , loading in suitable veh , unloading at MES substation after repair, connection of HT/LT cables will be the responsibility of contractor and rates deemed to be included in the quoted rates. Any damage to transformer during transportation will be the responsibility of contractor to make good without any extra claim . (Material required for repair will be measured and paid separately in respective schedule item).
Rewinding of HT limbs 3 Nos 33 KV side ( one limb of 8 coils with 18.2 Kg per coil) with standard super enameled copper wire including necessary insulation materials, varnishing to 11 KV winding, repair by soldering if required and other minor repairs work before installation of HT winding complete all as specified and directed. Note: - Insulating material between HV and LV like pressure ring, oil circulation ducts etc as per manufacturers design shall be deemed to be included in the unit rate quoted by bidder. Testing of LV winding and any insulation required will be the part of job.
Material and labour for transformer oil having BDV not less than 50 KV in first tripping with electrode gap of 5 mm and should meet the specification as per IS 6792 and should have characteristics for water content as per IS 13567, complete all as specified and directed Note: - BDV test will be carried out in presence of rep of accepting officer.
Material and labour for dehydration of transformer oil till achievement of BDV up to 35 KV and depositing in MES store yard complete all as specified and directed.
Material and labour for inspection , repair , testing and commissioning of tap change panel with all accessories as required at site,complete all as specified and directed
Material and labour for replacement of 33 KV HV bush assembly complete with bush rod and bushing suitable for 33 /11 KV , 2.5 MVA power transformer complete all as specified and directed
All as per serial item No-6 here-in-before but 11 KV (LV bush) assembly complete all as specified and directed.
Material and labour for servicing of buchholz relay for 2.5 MVA transformer including adjustment of contact gap complete all as specified and directed.
Material and labour for servicing of control panel installed for 33 KVA VCB by rewiring of control circuit and provision of following relays in replacement complete all as specified and directed.
(a) Complete relay including oil temp relay, winding relay and buchholz relay of article No-4965 Sr No-HD-9825031 of make Easun Reyrolle/ Siemens or any other suitable approved manufacturer.
(b) Over current protection relay (MIT-103, PC-05914) of current rating In-1 Amp/ 5 Amp, frequency 50 Hz, voltage- 18 to 135 Volt DC having Sr No-BR1007129 of make Easun Reyrolle/ Siemens or any other suitable approved manufacturer.
Material and labour for pre-commissioning test for 33/11 KV , 2.5 MVA transformer , including adjustment of all protection relays of HT panel with respect to total load of feeder, time adjustment as per incoming VCB at 132/33KV Grid Station,complete all as specified and directed
M/S MARVEL ELECTRICALS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .