Electrical Installation and Allied Work of Chassis Dyno Test Rig with Climatic Chamber and Solar Simulation at ARAI AEC Chakan Pune.
2026_ARAI_929741_1
AEC-CHAKAN-65-PR-60005715
Open Tender
Electrical Works
Buy
90 days
ARAI AEC center, Plot No A 22/2, Maharashtra Indust
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
₹2.2 L
Yes
ARAI AEC center,Plot No A 22/2, Maharashtra Indust
9 Oct 2026
9 Oct 2026
2 Nov 2026
9 Oct 2026
30 Oct 2026
10 Oct 2026
10 Oct 2026 - 16 Oct 2026
16 Oct 2026
Price Bid :- for Electrical Installation & Allied Work of Chassis Dyno Test Rig with Climatic Chamber & Solar Simulation at ARAI AEC Chakan Pune.
Name & Address of Bidder:-
SR.NO. PARTICULARS QTY UNIT Rate Amount Remark
Supply, Installation, Testing & Commissioning of Modular Online Double Conversion UPS System, complete with hot-swappable power modules, scalable modular architecture, N+1 internal power-module redundancy, provision for parallel operation of up to 6 UPS units, automatic synchronization and load sharing, high-efficiency eConversion/equivalent mode with efficiency >99%, static bypass and maintenance bypass, suitable battery system comprising Lithium-ion/VRLA/Ni-Cd batteries as specified, battery management system for Li-ion batteries, battery charger, battery protection and isolation, colour touchscreen HMI, microprocessor-based monitoring and control, EPMS interface, Modbus TCP/IP minimum, remote monitoring facility, protection and alarm functions, communication interfaces, EPO facility, complete with all necessary power/control cables, terminals, interconnections, accessories, safety provisions and documentation. The UPS shall comply with IEC 62040-3:2021, IEC 62040-1 and other applicable standards. UL certification shall be provided where specified. Live/hot-swappable module replacement shall be mandatory, with OEM certification/test evidence. The scope shall include engineering, design, supply, installation, testing, commissioning, FAT, SAT, performance testing, redundancy testing, live-module replacement demonstration/evidence, EPMS/BMS integration and O&M documentation, complete in all respects. Scope shall consist of Local Isolator required at Incoming and Outgoing side of UPS with suitable cabling (cable sizes as per OEM recommandation) between UPS and Isolators including all accessories.
1 40 KVA UPS (Standalone) for Industrial Load application(IGBT Rectifier & IGBT Inverter, ) Three Phase Input & Three Phase Output with battery banks and battery racks (60 min.battery Backup on 0.8 pf & full load) 1 Set As per EV Chassis dyno design topology, 63 Amps switchgear rating is mentioned, accodingly 40 kVA UPS rating is considered which will deliver 63 Amps load.
Design, Supply Installation, testing and commissioning of following totally type tested as per IEC 61439 1-2 Indoor type LT Panels as per tender technical datasheet & Single line diagrams. Panels shall be fabricated out of min 14 swg for Panel Body and 16 Swg for Partitions, CRCA sheet steel, with necessary structural supports in form of structural steel sections. Panels shall be floor mounted.The panel shall be compartmental type with suitable size of bus bar and separate cable and busbar chambers. The cable chambers shall be free from any live open connections. Multifunction meters for all incoming feeders, Indication lamps for all incoming and outgoing feeders for phase identifications and for indication of Switch status.Refer technical tender section 10 for detailed specifications.
Min 14 SWG CRCA
SPECIAL CONDITIONS (MANDETORY)
A) PANEL IP : 4X (WITH IEC CERTIFICATION, HAVING ASTA CERTIFICATION) WITH NATURAL / ACTIVE COOLING
B) PANEL CANOPY : IP 55 RATED DESINGED BY OEM FRANCHISE UNDER SUPERVISION OF OEM. FRANCHISE SHOULD BE PRODUCE IP55 CANOPY IEC CERTIFICATION.
C) BUSBAR MATERIAL - ALUIMINIUM / COPPER (AS PER OEM DESIGN)
D) CURRENT DENSITY - AS PER OEM TYPE TEST DESIGN.
E) HBC DESIGN CONSIDERING KA RATING OF PANEL - SHALL BE AS PER ASTA CERTIFICATION.
SPECIAL NOTE : OEM on letter to state complience to above conditions (A to E) , mentioning 13 type tests as per IEC 61439 mentioning ASTA Certification No. with ACB Make and Family. Certificate to follow CE Guidelines validity of Type Test Report.
FAULT CURRENT :- 50 KA
All panels Switchgear will be provided with lockout tagout (LOTO)arrangement.
INDICATIONS POSITION
FOR ALL INCOMERS PHASE INDICATION WITH SWITCH POSITION (ON, OFF AND TRIP)
FOR ALL OUTGOINGS FOR SWITCH POSITION INDICATION (ON, OFF AND TRIP)
SINGLE PHASING PREVENTER ON INCOMING BUS FOR PHASE IN BALANCE AND SINGLE PHASE PREVENTIONS
SURGE PROTECTION DEVICES
MFM + kWH as per SLD FOR INCOMING & OUTGOING FEEDER BREAKERS (WITH RS485 PORT SUITABLE FOR EMS & REMOTE MONITORING) Suggested Make : Simens PAC 3200 or equivalent true PF, 31st harmonics measurement
ALL ABOVE NOTES ARE APPLICABLE TO ALL PANELS LISTED BELOW
1 EV CHASSIS DYNO DISTRIBUTION PANEL 1 No.
PANEL SHOULD BE suitable FOR INDOOR CONDITION .PANEL SHOULD BE AS PER LATEST IEC 61439, 1-2. DESIGN SHOULD BE SUITABLE FOR 50 KA INTERNAL ARC PROTECTION. for IP43 - OEM to submit certificate of Copper/Aluminium, of min incomer rating or more is acceptable internal arc of 50kA 0.5 Sec without external means such as glass door.
FROM TOP. PLEASE REFER TO CABLE SCHEDULE FOR CABLES TERMINATING IN AND OUT, ACCORDINGLY SPACE PROVISION IN PANEL AND GLAND PLATE SHOULD BE DESIGNED ACCORDINGLY.
2500 A FP EDO ACB FOR EV CHASSIS DYNO LOAD
EDO TYPE MICROPROCESSOR BASED WITH LSI PROTECTION.
RACKING HANDLE, RACKING INTERLOCK, SAFTY SHUTTER, DOOR SEALING FRAME,READY TO CLOSED SHUNT TRIP COIL (230V), UNDER VOLTAGE COIL (415V), TRIP SIGNAL SWITCH, AUX. CONTACTS ( AS REQUIRED).
METER ON THIS FEEDER - VAF METER
1600 A FP EDO ACB FOR CLIMATIC CHAMBER CABINET
EDO TYPE MICROPROCESSOR BASED WITH LSI PROTECTION.
RACKING HANDLE, RACKING INTERLOCK, SAFTY SHUTTER, DOOR SEALING FRAME,READY TO CLOSED SHUNT TRIP COIL (230V), UNDER VOLTAGE COIL (415V), TRIP SIGNAL SWITCH, AUX. CONTACTS ( AS REQUIRED).
METER ON THIS FEEDER - KWH METER WITH ETHERNET PORT
1250 A FP EDO ACB FOR CHASSIS DYNO CABINET
EDO TYPE MICROPROCESSOR BASED WITH LSI PROTECTION.
RACKING HANDLE, RACKING INTERLOCK, SAFTY SHUTTER, DOOR SEALING FRAME,READY TO CLOSED SHUNT TRIP COIL (230V), UNDER VOLTAGE COIL (415V), TRIP SIGNAL SWITCH, AUX. CONTACTS ( AS REQUIRED).
METER ON THIS FEEDER - KWH & HARMONICS METER WITH ETHERNET PORT
630 A FP MCCB FOR SOLAR SIMULATION CABINET
MCCB WITH LI PROTECTION WITH MICROPROCESSOR BASED RELEASE WITH ADJUSTABLE OVERLOAD PROTECTION
METER ON THIS FEEDER - KWH & HARMONICS METER WITH ETHERNET PORT
63 A FP MCCB FOR PDB PANEL
MCCB WITH LI PROTECTION WITH MICROPROCESSOR BASED RELEASE WITH ADJUSTABLE OVERLOAD PROTECTION
METER ON THIS FEEDER - KWH & HARMONICS METER WITH ETHERNET PORT
100 A FP MCCB FOR 30 KVA UPS LOAD
MCCB WITH LI PROTECTION WITH MICROPROCESSOR BASED RELEASE WITH ADJUSTABLE OVERLOAD PROTECTION
METER ON THIS FEEDER - KWH & HARMONICS METER WITH ETHERNET PORT
1600 A FP EDO ACB FOR SPARE
EDO TYPE MICROPROCESSOR BASED WITH LSI PROTECTION.
RACKING HANDLE, RACKING INTERLOCK, SAFTY SHUTTER, DOOR SEALING FRAME,READY TO CLOSED SHUNT TRIP COIL (230V), UNDER VOLTAGE COIL (415V), TRIP SIGNAL SWITCH, AUX. CONTACTS ( AS REQUIRED).
400 A FP MCCB FOR SPARE
MCCB WITH LI PROTECTION WITH MICROPROCESSOR BASED RELEASE WITH ADJUSTABLE OVERLOAD PROTECTION
EMPTY COMPARTMENT PROVISION FOR FUTURE ADDITIONS IF ANY
VENDOR TO CONSIDER VACANT COMPARTMENTS, WHICH SHALL BE 25% OF OUTGOING FEEDER NUMEBERS. MAIN BUSBAR OF A MAIN INCOMER RATINGS, CAPACITY SHALL BE PROVIDED TILL THESE VACANT COMPARTMENTS.
2 UTILITY LOADS DISTRIBUTION PANEL 1 No.
PANEL SHOULD BE suitable FOR INDOOR CONDITION .PANEL SHOULD BE AS PER LATEST IEC 61439, 1-2. DESIGN SHOULD BE SUITABLE FOR 50 KA INTERNAL ARC PROTECTION. for IP43 - OEM to submit certificate of Copper/Aluminium, of min incomer rating or more is acceptable internal arc of 36 kA 0.5 Sec without external means such as glass door.
FROM TOP & BOTTOM. PLEASE REFER TO CABLE SCHEDULE FOR CABLES TERMINATING IN AND OUT, ACCORDINGLY SPACE PROVISION IN PANEL AND GLAND PLATE SHOULD BE DESIGNED ACCORDINGLY.
630 A FP MCCB FOR UTILITY LOADS
MCCB WITH LI PROTECTION WITH MICROPROCESSOR BASED RELEASE WITH ADJUSTABLE OVERLOAD PROTECTION
METER ON THIS FEEDER - VAF METER
315 A TP MCCB FOR HVAC LOAD DISTRIBUTION PANEL
MCCB WITH LI PROTECTION WITH MICROPROCESSOR BASED RELEASE WITH ADJUSTABLE OVERLOAD PROTECTION
METER ON THIS FEEDER - KWH & HARMONICS METER WITH ETHERNET PORT
315 A TP MCCB FOR FIRE FIGHTING PUMP LOAD
MCCB WITH LI PROTECTION WITH MICROPROCESSOR BASED RELEASE WITH ADJUSTABLE OVERLOAD PROTECTION
METER ON THIS FEEDER - VAF METER
250 A TP MCCB FOR CHILLED WATER PUMP PANEL
MCCB WITH LI PROTECTION WITH MICROPROCESSOR BASED RELEASE WITH ADJUSTABLE OVERLOAD PROTECTION
METER ON THIS FEEDER - KWH & HARMONICS METER WITH ETHERNET PORT
160 A TP MCCB FOR SHED AREA LIGHTING AND RAW POWER DISTRIBUTION FEEDER
MCCB WITH LI PROTECTION WITH MICROPROCESSOR BASED RELEASE WITH ADJUSTABLE OVERLOAD PROTECTION
METER ON THIS FEEDER - KWH & HARMONICS METER WITH ETHERNET PORT
100 A TP MCCB FOR STP
MCCB WITH LI PROTECTION WITH MICROPROCESSOR BASED RELEASE WITH ADJUSTABLE OVERLOAD PROTECTION
METER ON THIS FEEDER - VAF METER
125 A TP MCCB FOR COMPRESSOR LOADS
MCCB WITH LI PROTECTION WITH MICROPROCESSOR BASED RELEASE WITH ADJUSTABLE OVERLOAD PROTECTION
METER ON THIS FEEDER - KWH & HARMONICS METER WITH ETHERNET PORT
315 A TP MCCB FOR BUILDING COMMON LOAD
MCCB WITH LI PROTECTION WITH MICROPROCESSOR BASED RELEASE WITH ADJUSTABLE OVERLOAD PROTECTION
METER ON THIS FEEDER - KWH & HARMONICS METER WITH ETHERNET PORT
125 A TP MCCB FOR DYNO HVAC LOAD DB
MCCB WITH LI PROTECTION WITH MICROPROCESSOR BASED RELEASE WITH ADJUSTABLE OVERLOAD PROTECTION
METER ON THIS FEEDER - VAF METER
SUB DISTRIBUTION OF ABOVE FEEDER
63 A TP MCB FOR LIFT 01
63 A TP MCB FOR LIFT 02
63 A TP MCB FOR DYNO AREA AC REQUIREMENT
40 A TP MCB FOR UGWT PUMP LOAD
32 A TP MCB FOR CANTEEN AREA DB
25 A TP MCB FOR SECURITY GATE
25 A TP MCB FOR HVLS FAN SUPPLY DB
25 A DP MCB FOR TEMPORARY CONNECTION TO COMPRESSOR
25 A DP MCB FOR DM WATER PUMP AT TERRACE
25 A DP MCB FOR SPARE
63 A TP MCB FOR SPARE
32 A TP MCB FOR SPARE
25 A TP MCB FOR SPARE
630 A TP MCCB FOR SPARE
MCCB WITH LI PROTECTION WITH MICROPROCESSOR BASED RELEASE WITH ADJUSTABLE OVERLOAD PROTECTION
METER ON THIS FEEDER - VAF METER
125 A TP MCCB FOR SPARE
MCCB WITH LI PROTECTION WITH MICROPROCESSOR BASED RELEASE WITH ADJUSTABLE OVERLOAD PROTECTION
METER ON THIS FEEDER - VAF METER
EMPTY COMPARTMENT PROVISION FOR FUTURE ADDITIONS IF ANY
VENDOR TO CONSIDER VACANT COMPARTMENTS, WHICH SHALL BE 25% OF OUTGOING FEEDER NUMEBERS. MAIN BUSBAR OF A MAIN INCOMER RATINGS, CAPACITY SHALL BE PROVIDED TILL THESE VACANT COMPARTMENTS.
C READYMADE DISTRIBUTION BOARD
Supply, installation,testing,tagging, (Circuit numbering) and commissioning of following double door readymade recessed type MCB, DB, fabricated out of CRCA sheet and painted with powdercoating process OR made out of scratch proof polycarbonate body, and concealed in wall or on surface with necessary frame complete as required. DB's should be, - IP 4X RATED - Double Door - Powder coated metal doors and enclosure - Phase copper bus bars, Neutral and earth bar with tapped holes, - Necessary cable boxes for incoming / outgoing conduits and cables. - 1/3 phase distribution Suitable for Flush and surface mounted - DB's shall be as per IEC 61439-3
1 EV CHASSIS PDB PANEL 1 No.
12 WAY SPN MCB DB
32 A FP RCBO, 100 mA SENSITIVITY (COMPACT - 04 MODULE)
16 A SP MCB FOR CONTROL DESK POWER SUPPLY
16 A SP MCB FOR EQUIPMENT SUPPLY DESK POWER
16 A SP MCB FOR LIGHTING CIRCUIT
16 A SP MCB FOR SPARE - 03 NOS
2 CONTROL ROOM UPS POWER DB 1 No.
12 WAY SPN MCB DB
32 A FP RCBO, 100 mA SENSITIVITY (COMPACT - 04 MODULE)
16 A SP MCB FOR CONTROL DESK POWER SUPPLY
16 A SP MCB FOR EQUIPMENT SUPPLY DESK POWER
16 A SP MCB FOR LIGHTING CIRCUIT
16 A SP MCB FOR SPARE - 03 NOS
3 DYNO AREA HVAC DISTRIBUTION DB 1 No.
8 WAY VTPN MCCB DB
125 A TP MCCB FOR DYNO HVAC LOAD DB
16 A TP MCB FOR OUTDOOR UNITS - 06 NOS
16 A TP MCB FOR SPARE - 08 NOS
3 Supply, fixing, testing, of good quality industrial interlocked switched sockets with MCB's of different ratings in readymade IP 68 metal enclosure. Box should be suitable to terminate cables / wires easily, complete as required.
3.1 25A, 1Ø, P+N+E, Socket outlet with 25A DPMCB in readymade metal enclosure. 1 No.
3.2 4 MODULE WEATHERPROOF BOX WITH 16 A FP RCBO (COMPACT 04 MODULE) 6 No.
D CABLES AND END TERMINATION
1 Supply, testing, tagging, laying and commissioning of following sizes of 1100 Volt grade, XLPE / PVC insulated multistrand Al. / Cu. Conductor armoured / unarmoured cables (As Per latest IS 1554 & IS 7098) in readymade RCC trench, in provided PVC pipe, RCC pipe hume pipe, on cable trays / ladders etc. as. required complete with clamps for fixing tagging etc. Miscellaneous items such as cable dressing accessories like nylon tie, Aluminium clamps, GI cleats, cable tags, CI cable route markers at every 30 mtr etc. are included in the scope. Removal of empty drums, cartons and making the site normal as instructed by Purchaser/ client is included in scope.
1.1 3.5 CORE 300 SQ. MM AL XLPE ARMOURED CABLE 60 R.MTRS.
1.2 3.5 CORE 150 SQ. MM AL XLPE ARMOURED CABLE 680 R.MTRS.
1.3 3.5 CORE 50 SQ. MM AL XLPE ARMOURED CABLE 50 R.MTRS.
1.4 4 CORE 16 SQ. MM CU XLPE ARMOURED CABLE 400 R.MTRS.
1.5 4 CORE 10 SQ. MM CU XLPE ARMOURED CABLE 40 R.MTRS.
1.6 4 CORE 2.5 SQ. MM CU XLPE ARMOURED CABLE 140 R.MTRS.
1.7 3 CORE 4.0 SQ. MM CU XLPE ARMOURED CABLE 50 R.MTRS.
2 Supply and providing LV cable end termination for below listed cable with Aluminum/copper/bimetallic lugs as required , flange type brass cable glands (Double compression type), PVC glands for flexible cables with tapping, crimping, etc.
2.2 3.5 CORE 150 SQ. MM AL XLPE ARMOURED CABLE 6 NOS.
2.3 3.5 CORE 50 SQ. MM AL XLPE ARMOURED CABLE 2 NOS.
2.4 4 CORE 16 SQ. MM CU XLPE ARMOURED CABLE 6 NOS.
2.5 4 CORE 10 SQ. MM CU XLPE ARMOURED CABLE 2 NOS.
2.6 4 CORE 2.5 SQ. MM CU XLPE ARMOURED CABLE 12 NOS.
2.7 3 CORE 4.0 SQ. MM CU XLPE ARMOURED CABLE 2 NOS.
Supply, Installation, testing and Commisioning of prefabricated hot deep galvanised , ladder/perforated type cable trays of minimum 2mm thick as per latest IS code & details given below. Prefabricated, bends and couplers with G.I. Nuts and bolts. Gas cutting of cable trays at site is not permitted. If any welding is to be done on cable trays, the welded part shall be touched up with anti-corrosive primer and silver paint. The running rate shall include bends and couplers. The Running meter lengths of cable Trays Shall include all types of standard Joints,"+" "U"; "T”; "L" Horizontal, vertical, Bends etc.Straight, Left hand, Right Hand reducers etc. Horizontal, vertical inside & vertical outside elbows complete with all necessary Hardwares like Nuts Bolts, Plain & Spring washers. Special Note : Rate shall be inclusive of cost for primary & secondary supporting arrangement as per standards, site conditions and Connection of 10 sqmm copper flexible wire or suitable gi strip to earth terminals at coupling of cable trays. Supporting Arrangement can be in any form i.e. Structural Steel / Threaded Rod / Special Supporting arrangement like Hilti, Gripple etc. Vendor will propose the type of supporting arrangement for approval. ARAI and Consultant will approve them prior execution.
consider 2 mm thickness all ladders trays.
1.1 600 X 50 GI LADDER TRAY R.MTRS.
1.2 300 X 50 GI LADDER TRAY 15 R.MTRS.
2 CABLE TRAYS - PERFORATED TYPE
Consider 2 mm thickness for all trays.
2.1 300 X 50 mm GI perforated cable tray 60 R.MTRS.
2.2 150 X 50 mm GI perforated cable tray 15 R.MTRS.
3 CABLE TRAYS COVER
Consider 1.6 mm thickness for all trays covers.
3.1 300 mm GI tray cover 10 R.MTRS.
4 Supply, transport, unloading, shifting & Fabrication of steel sections and erection of MS base frames, MS angle channels, flat, MS C-Channel, MS Z-Channel etc for supporting various items of equipment such as various panels/local machine switches / proper cable laying in trenches / addition support for proper cable termination/ MS Fabricated cable trays/ junction boxes/ light fittings, DB etc. The scope include welding, bolting, chipping , grouting etc. The all MS steel assembly should be fabricated in the contractors shop and then HOT- Dip galvanisation of total assembly shall be done. Rate shall include total process of Galvanization and all allied costs. The scope is inclusive of minor civil work as required, supply of GI hardware materials, Base Plates and its bolts, consumables, tools & tackles and necessary labour Special Note : This Fabrication is only for Panel, DB Placements. It should not be considered for Cable Tray support as cable tray supports are part of Cable Tray SITC Item 0.8 MT.
F EARTHING STATIONS
1 Supply, installation, testing and commissioning of Indelec / OBO / Jef / Actord make eco safe maintenance free electrode of 25 mm diameter low carbon steel with 250 micron molecular copper bonded earthing rod of 6 mtrs. length along with carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity. It also includes necessary accessories like nuts and bolts, test link, insulators etc. This item includes 100 mm dia drill in ground, average 8 meter depth in back filled earth and 4 meter depth in virgin earth (total average 12 meters depth drill). It also includes suitable casing for the drill upto the backfilled area, installation of earth electrode, supply, installation and connection of earth strip from electrode to test link inclusive of inside the borewell earthing strip upto 9 meter, testing and connection complete as per code of practice IS:3043 complete. (Electrode type) Earthing Instruction Board to be supplied with Earthing for in periodic maintenance date and showing ohm value of particular earth pit. Scope consist of Construction of Chamber around Earthing pit Heavy Duty Metal / FRP Cover on top.
1.1 EV CHASSIS DYNO 2 Nos.
1.2 EV CLIMATIC CHAMBER 2 Nos.
1.3 EV SOLAR SIMULATION SYSTEM 2 Nos.
1.4 40 KVA UPS 2 Nos.
2 Supply, tagging, laying or fixing, testing of GI / Cu earthing strip / wire in ground- excavation item is separate in BOQ. All joints will have SS nut bolts or with Brazing
2.1 50 x 6 mm GI FLAT R.MTRS.
2.1 25 x 6 mm CU FLAT R.MTRS.
2.1 8 SWG GI WIRE - CONNECTION OF THIS WIRE AT EVERY CERTAIN INTERVAL SHOULD BE WITH LUGS ONLY 80 R.MTRS.
3 Supply, Installaton, Testing & Commisioning of Busbar of 0.5 Mtr length made out of 50 x 6 mm GI strip with drill holes of M8 at 25mm interval mounted on insulators with Enclosure. 1 Nos.
G LIGHT FITTINGS
1 Supply & Installation of following type of light fixtures as per drawings and specifications with all other accessories such as supporting rods/ropes/chains / frames, anchor fasteners, necessary hardware etc.The All fittings Should have warranty of minimum 3 years & warranty cards of all the fittings duly filled with stamp are to be submitted along with Final bill. It will be contractors responsibility to store light fitting. support the for light fitting from perlin rafter etc with the help of clamp, chain or any other supporting accessories will be in contractors scope.
LUMINARY WILL BE PROVIDED WITH FOLLOWING PROTECTION • Output over voltage & under voltage Protection • Over temperature • Output over current and short circuit Auto Recovery • Input high voltage cut off Auto Recovery
1.1 Supply, Installation ,Testing & Commissioning of 35-40 W LED LINEAR LIGHT FITTINGS INDUSTRIAL GRADE- 1200 MM LENGHT LUMEN OUTPUT OF LED FITTING - lumens output-Min 120 lumens/watt COLOR TEMPERATURE 5500 - 6000 K IP RATING OF LIGHT FITTING - IP4X AND ABOVE IK RATING- IK 08 AND ABOVE SURGE PROTECTION 2 KV AND ABOVE POWER FACTOR > 0.95 TOTAL HARMONIC DISTORTION (THD) < 10% COLOUR RENDERING INDEX (CRI) > 80 Nos.
1 Supply , Installation, Testing and Commissioning of following items with suitable accessories and supports ,accessories, labor etc. for wiring for lights, ceiling fans, exhaust fans, 6A sockets. Rate shall include GI conduit and its accessories in concealed / open conduit /Casing & capping & above false ceiling using pull/junction boxes, light outlet boxes, G.I.Switch outlet boxes, switch plates, 6A/16A one or two way switches, including testing and commissioning complete. The rate for point wiring shall include wiring from first switch point and then looping between the points. The rate shall also include the cost of providing 1no. 1.0 Sqmm PVC insulated copper conductor wire to connect all lights, switches sockets etc.
1.1 Primary or One way light points, using 25 mm Dia GI conduit and multi strand FRLS copper conductor wire 1.5 sq. mm. size for phase neutral and earth. point controlled by modular switches (Average Point Length 7 meter). Ceiling flexible PVC / GI conduit shall be included at the drop of light fixture. 18 Nos.
1.2 Secondary or light point in group, using 25 mm Dia GI conduit and multi strand FRLS copper conductor wire 1.5 sq. mm. size for phase neutral and earth. point controlled by modular switches (Average Point Length 5 meter). Ceiling flexible PVC / GI conduit shall be included at the drop of light fixture. 10 Nos.
2 SOCKET OUTLETS (EXCLUDE WIRING)
2.1 Supply, Installation of testing and commissioning of modular Single phase 6/16 Amps multi pin flush type socket outlets controlled by 16 A modular switch .The assembly shall be flush mounted in the partition/ wall. (RP) 12 Nos.
2.2 Supply, Installation of testing and commissioning of on board 6A plug point controlled by 6A modular switch. 6 Nos.
2.3 Supply, Installation of testing and commissioning of modular Single phase 2 nos. Of 6/16 Amps multi pin flush type socket outlets controlled by 2 no.s of 6 A modular switch .The assembly shall be flush mounted in in the partition/ wall. (RP). Kindly consider 16A Switch with indicator for the same. 4 Nos.
1 Supply and drawing of circuit Mains for the point wiring for areas controlled by 6/16 Amps switches and power wiring using 1100V grade PVC insulated multi strand copper conductor wire drawn into GI conduit pipes in concealed / open conduit system with necessary fixing accessories like bends, collars, junction boxes, clamps, spacers, etc., complete. Wiring shall be as per specifications.
1.1 2 Runs of 1.5 sqmm + 1 Run of 1.5 sqmm multi strand FRLS copper conductor wire in Existing Raceways/Cabletrays/Conduits. ( Rate Shall exclude Raceways/Cabletrays/Conduits) (For Lighting, Emergency Lighting Ciruit Mains, Modular Sockets Wiring) 150 R.MTRS.
1.2 2 Runs of 2.5 sqmm + 1 Run of 2.5 sqmm multi strand FRLS copper conductor wire in Existing Raceways/Cabletrays/Conduits. ( Rate Shall exclude Raceways/Cabletrays/Conduits) (For Lighting, Emergency Lighting Ciruit Mains, Modular Sockets Wiring) 285 R.MTRS.
2 Supply, installation, testing and commissioning of 25 mm Dia GI conduit for laying wires and cables mentioned in above sections including cost of junction boxes, bends, elbows, sockets, tees etc. laying in slab, cutting chasis and making good or surface mounted including all fixing hardware. 200 R.MTRS.
TOTAL AMOUNT OF WORK
GST Amount @ 18%
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.05 MB
TechnicalTender.pdf
Tender Documents • 2.98 MB
PriceBid1.xls
Tender Documents • 0.07 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .