Tender Value
₹20.2 L
EMD Value
₹40,500
Closing Date
27 Jul 2026, 3:00 pm
Electrical works in connection with at NBQ- (i) Construction of Relay room at A cabin(ii) Construction of relay room, SM room, S&T Maintenance room, staircase & Fencing at West cabin (iii) Construction of ASM & battery room at A cabin.
RNY-EL-T-06-2026-27
RNY-EL-T-06-2026-27
Open
180 Days
Unknown (Unspecified Location)
₹0
₹40,500
3 Jul 2026
3 Jul 2026
13 Jul 2026
A-Construction of Relay room at A-cabin
Supply and surface wiring of light/FL point by PVC insulated & un-sheathed FRLSH 01 multi strand copper single core 1.5 sq.mm cable through PVC casing & caping including ceiling rose. Cable connection to be done through 6 A flush type controlling switch installed in suitable size PVC board & connected by Cu flexible wire from ceiling rose to fittings as per direction of EIC at site.
Supply and surface wiring of ceiling fan point by PVC insulated & un-sheathed FRLSH 02 multi strand copper single core 1.5 sq.mm cable through PVC casing & caping including ceiling rose. Cable connection to be done through 6 A flush type controlling switch including 5 point electronic regulator installed in suitable size PVC board with earth continuity by 1.0 sq.mm multistrand copper cable & connected by Cu flexible wire from ceiling rose to fan as per direction of EIC at site.
Supply and surface wiring of exhaust fan point by PVC insulated & un-sheathed 03 FRLSH multi strand copper single core 1.5 sq.mm cable through PVC casing caping including ceiling rose. Cable connection to be done through 6 A flush type controlling switch including suitable size PVC board with earth continuity by 1.0 sq.mm multistrand copper cable & connected by Cu flexible wire from ceiling rose to fan as per direction of EIC at site.
Supply of of 1200mm sweep, BEE star rated - 5 star rated capacitor type ISI marking ceiling fan with 450mm down rod, canopy and all accessories as per direction of EIC at site.
Fixing and commissioning of ceiling fan 1200 mm sweep with suitable size GI pipe, MS hook, clamp, nut & bolts arrangements as required as per direction of EIC at site (Ceiling fan will be supplied by Railway)
Supply, testing and fixing of 300 mm sweep exhaust fan complete by cutting wall, masonary work as required and fixing by suitable nuts and bolts arrangement as per direction of EIC at site.
Supply and surface wiring of 6A 5 pin plug point by PVC insulated & un-sheathed 07 FRLSH multi strand copper single core 2.5 sq.mm cable through PVC casing & caping, with earth continuity by single core 1.0 sq mm copper cable including suitable size PVC board. Cable connection to be done through 6 A flush type controlling switch , socket installed in PVC board hylum sheet on top and as per direction of EIC at site.
Supply and surface wiring of 16 A, 6-pin Plug point/geyser point by PVC insulated and 08 un-sheathed FRLS multi stranded copper cable, single core 4.0 sq.mm with earth continuity by 1.0 sq.mm multistand copper cable through PVC casing & caping including suitable size PVC board. Cable connection to be done through 16 A flush type controlling switch, 16A socket installed in board and as per direction of EIC at site.
Supply, installation, testing & commissioning of 2.0 ton 3 star rated split AC including 09 indoor, outdoor unit compressor rotary type suitable for operation on 230volt/1-ph/50 Hz and copper pipe line along with insulation, wal fixing arrangements and other accessories for connecting indoor unit to outdoor unit with copper piping as per direction of EIC at site.
Surface wiring of AC pointcomplete unit of single phase motor starter(16 A-25A) & 25 10 A socket with 4 module plate and surface box (5 hp)by single core FRLS PVC insulated and unsheathed 4 sq mm stranded copper cable through suitable size PVC casing caping to be drawn from DB and fixed on wall/ceiling by suitable with earth contunity by 1.0 sq mm stranded copper cable including 4 module surface mounted unbreakable gang box as per the direction of EIC at site.
Supply & wiring of earth continuity through the circuit of Main line/ Submain line by 1.0 sq mm PVC insulated & unsheathed, single core,multi stranded FRLS copper conductor cable through PVC Casing capinge as per direction of EIC at site.
Supply & wiring of Main line/ Submain line by PVC insulated & unsheathed, single core, multi stranded FRLS copper conductor cable 2.5 sq.mm through PVC casing caping with controlling switch as per direction of EIC at site.
Supply & wiring of Main line/ Submain line by PVC insulated & unsheathed, single core, multi stranded FRLS copper conductor cable 4.0 sq.mm through PVC casing caping with controlling switch as per direction of EIC at site.
Supply & wiring of Main line line by PVC insulated & unsheathed, single core, multi stranded FRLS copper conductor cable 6.0 sq.mm through consealed PVC heavy gayge pipe with controlling switch as per direction of EIC at site.
Supply & fixing of PVC casing caping 25x12mm size by surface of wall for drawing of main/submain line as required of EIC at site
Supply, installation, testing & commissioning of SPN distribution board 8 way double door metal SPN DB consisting 40A, MCB DP - 1 no, 20A, MCB DP - 2 nos, 6A, MCB SP - 2 nos with enclosure and necessary fixing arrangements as per direction of EIC at site.
Supply, testing & commissioning of 25A, 2 pole, 30mA, 10kA RCCB as per direction of EIC at site.
Supply, installation, testing & commissioning of 18/20W LED tube light fitting with polycarbonate housing with THD less than 20% and surge protection 1.5KV 6000K (4 ft) complete 18 with driver circuit etc and all accessories as per direction of EIC at site. Lumens out put should be not less than 100 Lumens/watt, LED should be as per LM-80/IS: 16105. LED driver's efficiency should be minimum 90%, Power factor of complete fitting should be greater than 0.90, Input operating voltage: 140V to 277V AC and driver should be as per IEC: 62384/IS:16104. The LED fittings should be warranted for 5 years.
Supply and erection of earthing by made of B class GI pipe of 3000 mm length, 50 19 mm diameter & 3.6 mm thickness.The GI Strip ( should be welded with the earth pipe. Thepipe is provided with a tapered casing at the lower end in order to facilitate the driving. A funnel with perforated plate to be provided at the top of the pipe for pouring water during dry season to have an effective earth value.The connecting conductor from earth electrode to the distribution panel board should not be thinner than 8 SWG GI wire to carry the fault current. The earth fill shall be of homogeneous layer of common earth soil. Where soil restivity is high, earth restivity enhancing material may be used, Bentonite or similar earth enhancing material may be used in rocky soil. Earth box to be precasted RCC and The values of earth resistance measured should be painted on the Earth pit cover/lid along with the date of measurement. As per Drg. No. DRG NO:PCEE/ELG/DRG/2024/1 dated 30.09.2024 & as perTechnical circular no. EL/PS/2024/1 (EARTHING SYSTEM).
Laying of above LT XLPE insulated armoured aluminium cables as per instruction of site engineer (Cable should be supplied by Railway)
Excavation of trench of size 60 Cm width x 90 Cm depth for laying of CI/GI pipe/cable with sand/brick/clamp protection as required and filling of earth / ramming as required as per direction of EIC at site.
Supply and laying of GI pipe 50 mm dia thickness not less than 3.6 mm for cable protection with necessary bends, sockets, etc partly through underground and partly through trench as per direction of EIC at site.
Horizontal machine borring under track crossing at a depth of 2.0 mtr below GL including required size HDPE pipe observing all necessary safety for human life and others movement as per direction of engineer at site.
Supply, installation, testing & commissioning of 25 watt street light fittings complete including all accessories as per direction of EIC at site (Similar to model no LSTS-25-CDL). Lumens 24 out put should be of 100 Lumens/watt, LED should be as per LM-80/IS: 16105. LED driver's efficiency should be minimum 90%, Power factor of complete fitting should be greater than 0.90, Input operating voltage: 140V to 277V AC and driver should be as per IEC: 62384/IS:16104. The LED fittings should be warranted for 5 years.
Supply,Carrying, loading/unloading, muffing and erection of Galvanised tubular pole 9.0 mtr long , Type-410 SP-33 having weight 164 kgs, 5.00/2.0/2.0 mtr having sectional outer dia 25 165.1/139.7/114.3 mm and sectional thickness 5.40/4.50/3.65 mm respectively as per IS:2713-1980 including suitable size base plate & cap .The work includes digging the pit to 1/5th of the pole height. Execution of CC foundation work of size 45cmx45cm in ratio 1:2:4 by cement,sand and chips of size 19 mm and down upto full depth & 1ft above the GL as per direction of EIC at site.
Supply and erection of galvanized stay set for 11 KV OH line complete with 20 mm 26 dia, 1.8 mtrs long stay rod, anchor plate of size 23 cm x 23 cm x 6 mm thick, 16 mm dia turn buckle, thimble, stay clamp, 7/10 mm SWG GI stay wire & Strain insulator etc. in CC foundation with 1:3:6 ratio including excavation and refilling.
Supply, installation and commissioning of ball and socket type HT 11 KV Polymeric 27 Composite disc insulator minimum creep age distance 450mm, section length 430mm, rated mechanical tensile load 70KN, Wet power freq 1 min, withstand voltage 48KV, Dry lighting impulse withstand voltage 100KV including all accessories for fixing on the bracket with strain clamps, nuts, bolts & washers etc. as per IEC 1109, ISO 9001 : 2000. (2 nos in a set).
Supply, installation and commissioning of 11 KV HT Polymeric Composite pin 28 insulator size 146mm, minimum failing load 5KN, Wet power freq 1 min, withstand voltage 35KV(RMS), Dry lighting impulse withstand voltage 75Kvp(+ve), including all accessories for fixing on the bracket with nuts, bolts & washers etc. as per IEC 1109, ISO 9001 : 2000. (2 nos in a set).
Supply, installation, commissioning and replacement of HT 11 KV GO switch 200 amps, triple pole and each pole consist of galvanized steel base, HT insulator for replacement of the existing G.O. for the feeders.
Supply, installation, commissioning and replacement of HT 11 KV DO fuse (channel type) complete with all accessories for replacement of the existing G.O. for the feeders.
Supply, fitting and fixing of GI Channel to be fixed on pole with suitable size GI clamp 31 made of 50X5 mm, MS flat with 50X16 mm bolts, nuts and washers etc. The channel to be painted by 2-coats of red oxide as primer and 2 coats of Aluminium paint as final coat as per direction of EIC at site of size - 75x40x40 x6 .0 mm, 2.2 mtr long.
Supply, fitting and fixing of GI Channel to be fixed on pole with suitable size MS clamp 32 made of 50X5 mm, GI flat with 50X16 mm bolts, nuts and washers etc. The channel to be painted by 2-coats of red oxide as primer and 2 coats of Aluminium paint as final coat as per direction of EIC at site of size - 75x40x40 x 6.0 mm, 1.2 mtr long
Supply, fitting and fixing of GI Channel to be fixed on pole with suitable size MS clamp 33 made of 50X5 mm, GI flat with 50X16 mm bolts, nuts and washers etc. The channel to be painted by 2-coats of red oxide as primer and 2 coats of Aluminium paint as final coat as per direction of EIC at site of size - 75x40x40 x 6.0 mm, 0.3 mtr long.
Supply, fitting and fixing of GI angle to be fixed on pole with suitable size GI clamp 34 made of 50X5 mm, MS flat with 50X16 mm bolts, nuts and washers etc. The channel to be painted by 2-coats of red oxide as primer and 2 coats of Aluminium paint as final coat as per direction of EIC at site of size - 50x50x6mm, 2200 mm long.
"Supply, fitting and fixing of GI angle to be fixed on pole with suitable size GI clamp 35 made of 50X5 mm, MS flat with 50X16 mm bolts, nuts and washers etc. The channel to be painted by 2-coats of red oxide as primer and 2 coats of Aluminium paint as final coat as per direction of EIC at site of size - 50x50x6mm, 3300 mm long. "
Design, fabrication, supply, installation, testing and commissioning of outdoor type (KIOSK type) hinged, feeder pillar box comprising of following items and made of MS angle, channel 36 by MS sheet of not less than 18 SWG duly welded and painted by 2 coats of primer, two coats of finishing paint (spray paint) Doco/Nerolac brand of approved colour both in interior and exterior as per direction of EIC at site - i) 100A,4P, 18KA, Ics = 100% Icu, conforms to IEC 60947-2 MCCB - 1 nos, ii) 63A, MCB TPN - 1 nos, iii) 40A, MCB DP - 1 nos & iv) 200A 4P copper bus bar - 1 set.
B-Construction of Relay room,SM room,S&T maintenance room,stare
Supply and surface wiring of light/FL point by PVC insulated & un-sheathed FRLSH 01 multi strand copper single core 1.5 sq.mm cable through PVC casing & caping including ceiling rose. Cable connection to be done through 6 A flush type controlling switch installed in suitable size PVC board & connected by Cu flexible wire from ceiling rose to fittings as per direction of EIC at site.
Supply and surface wiring of ceiling fan point by PVC insulated & un-sheathed FRLSH 02 multi strand copper single core 1.5 sq.mm cable through PVC casing & caping including ceiling rose. Cable connection to be done through 6 A flush type controlling switch including 5 point electronic regulator installed in suitable size PVC board with earth continuity by 1.0 sq.mm multistrand copper cable & connected by Cu flexible wire from ceiling rose to fan as per direction of EIC at site.
Supply and surface wiring of exhaust fan point by PVC insulated & un-sheathed 03 FRLSH multi strand copper single core 1.5 sq.mm cable through PVC casing caping including ceiling rose. Cable connection to be done through 6 A flush type controlling switch including suitable size PVC board with earth continuity by 1.0 sq.mm multistrand copper cable & connected by Cu flexible wire from ceiling rose to fan as per direction of EIC at site.
Supply of of 1200mm sweep, BEE star rated - 5 star rated capacitor type ISI marking ceiling fan with 450mm down rod, canopy and all accessories as per direction of EIC at site.
Fixing and commissioning of ceiling fan 1200 mm sweep with suitable size GI pipe, MS hook, clamp, nut & bolts arrangements as required as per direction of EIC at site (Ceiling fan will be supplied by Railway )
Supply, testing and fixing of 300 mm sweep exhaust fan complete by cutting wall, 06 masonary work as required and fixing by suitable nuts and bolts arrangement as per direction of EIC at site.
Supply and surface wiring of 6A 5 pin plug point by PVC insulated & un-sheathed 07 FRLSH multi strand copper single core 2.5 sq.mm cable through PVC casing & caping, with earth continuity by single core 1.0 sq mm copper cable including suitable size PVC board. Cable connection to be done through 6 A flush type controlling switch , socket installed in PVC board hylum sheet on top and as per direction of EIC at site.
Supply and surface wiring of 16 A, 6-pin Plug point/geyser point by PVC insulated and 08 un-sheathed FRLS multi stranded copper cable, single core 4.0 sq.mm with earth continuity by 1.0 sq.mm multistand copper cable through PVC casing & caping including suitable size PVC board. Cable connection to be done through 16 A flush type controlling switch, 16A socket installed in board and as per direction of EIC at site.
Supply, installation, testing & commissioning of 2.0 ton 3 star rated split AC including 09 indoor, outdoor unit compressor rotary type suitable for operation on 230volt/1-ph/50 Hz and copper pipe line along with insulation, wal fixing arrangements and other accessories for connecting indoor unit to outdoor unit with copper piping as per direction of EIC at site.
Surface wiring of AC point complete unit of single phase motor starter(16 A-25A) & 10 25 A socket with 4 module plate and surface box (5 hp) by single core FRLS PVC insulated and unsheathed 4 sq mm stranded copper cable through suitable size PVC casing caping to be drawn from DB and fixed on wall/ceiling by suitable with earth contunity by 1.0 sq mm stranded copper cable including 4 module surface mounted unbreakable gang box as per the direction of EIC at site.
Supply & wiring of earth continuity through the circuit of Main line/ Submain line by 1.0 sq mm PVC insulated & unsheathed, single core,multi stranded FRLS copper conductor cable through PVC Casing capinge as per direction of EIC at site.
Supply & wiring of Main line/ Submain line by PVC insulated & unsheathed, single core, multi stranded FRLS copper conductor cable 2.5 sq.mm through PVC casing caping with controlling switch as per direction of EIC at site.
Supply & wiring of Main line/ Submain line by PVC insulated & unsheathed, single core, multi stranded FRLS copper conductor cable 4.0 sq.mm through PVC casing caping with controlling switch as per direction of EIC at site.
Supply & wiring of Main line line by PVC insulated & unsheathed, single core, multi stranded FRLS copper conductor cable 6.0 sq.mm through consealed PVC heavy gayge pipe with controlling switch as per direction of EIC at site.
Supply & fixing of PVC casing caping 25x12mm size by surface of wall for drawing of main/submain line as required of EIC at site.
Supply, installation, testing & commissioning of SPN distribution board 8 way double door metal SPN DB consisting 40A, MCB DP - 1 no, 20A, MCB DP- 2 nos, 6A, MCB SP- 2 nos with enclosure and necessary fixing arrangements as per direction of EIC at site.
Supply, testing & commissioning of 25A, 2 pole, 30mA, 10kA RCCB as per direction of EIC at site.
Supply, installation, testing & commissioning of 18/20W LED tube light fitting with polycarbonate housing with THD less than 20% and surge protection 1.5KV 6000K (4 ft) complete 18 with driver circuit etc and all accessories as per direction of EIC at site. Lumens out put should be not less than 100 Lumens/watt, LED should be as per LM-80/IS: 16105. LED driver's efficiency should be minimum 90%, Power factor of complete fitting should be greater than 0.90, Input operating voltage: 140V to 277V AC and driver should be as per IEC: 62384/IS:16104. The LED fittings should be warranted for 5 years.
Supply and erection of earthing by made of B class GI pipe of 3000 mm length, 50 19 mm diameter & 3.6 mm thickness.The GI Strip ( should be welded with the earth pipe. Thepipe is provided with a tapered casing at the lower end in order to facilitate the driving. A funnel with perforated plate to be provided at the top of the pipe for pouring water during dry season to have an effective earth value.The connecting conductor from earth electrode to the distribution panel board should not be thinner than 8 SWG GI wire to carry the fault current. The earth fill shall be of homogeneous layer of common earth soil. Where soil restivity is high, earth restivity enhancing material may be used, Bentonite or similar earth enhancing material may be used in rocky soil. Earth box to be precasted RCC and The values of earth resistance measured should be painted on the Earth pit cover/lid along with the date of measurement. As per Drg. No. DRG NO:PCEE/ELG/DRG/2024/1 dated 30.09.2024 & as perTechnical circular no. EL/PS/2024/1 (EARTHING SYSTEM).
Supply, carrying, loading & unloading of 5 mtr long with suitable size designer single 20 bracket G I octagonal pole including base plate, junction box and foundation bolt 4x16Nos (Length 450mm) etc and erection with execution of CC foundation work of size 45cmx45cm in ratio 1:2:4 by cement,sand and chips of size19 mm and down upto full depth & 1ft above the GL as per direction of EIC at site including 6A SP MCB.
Supply, installation, testing & commissioning of 25 watt street light fittings complete including all accessories as per direction of EIC at site . Lumens out put should be of 100 21 Lumens/watt, LED should be as per LM-80/IS: 16105. LED driver's efficiency should be minimum 90%, Power factor of complete fitting should be greater than 0.90, Input operating voltage: 140V to 277V AC and driver should be as per IEC: 62384/IS:16104. The LED fittings should be warranted for 5 years.
Laying of above LT XLPE insulated armoured aluminium cables as per instruction of site engineer (Cable should be supplied by Railway).
Excavation of trench of size 60 Cm width x 90 Cm depth for laying of CI pipe/cable with sand/brick/clamp protection as required and filling of earth / ramming as required as per direction of EIC at site.
Supply and laying of GI pipe 50 mm dia thickness not less than 3.6 mm for cable protection with necessary bends, sockets, etc partly through underground and partly through trench as per direction of EIC at site.
Horizontal machine borring under track crossing at a depth of 2.0 mtr below GL including required size HDPE pipe observing all necessary safety for human life and others movement as per direction of engineer at site.
Design, fabrication, supply, installation, testing and commissioning of outdoor type (KIOSK type) hinged, feeder pillar box comprising of following items and made of MS angle, channel 26 by MS sheet of not less than 18 SWG duly welded and painted by 2 coats of primer, two coats of finishing paint (spray paint) Doco/Nerolac brand of approved colour both in interior and exterior as per direction of EIC at site - i) 100A,4P, 18KA, Ics = 100% Icu, conforms to IEC 60947-2 MCCB - 1 nos, ii) 63A, MCB TPN - 1 nos, iii) 40A, MCB DP - 1 nos & iv) 200A 4P copper bus bar - 1 set.
Supply, installation, testing & commissioning of 25 watt street light fittings complete including all accessories as per direction of EIC at site (Similar to model no LSTS-25-CD). Lumens out 27 put should be of 100 Lumens/watt, LED should be as per LM-80/IS: 16105. LED driver's efficiency should be minimum 90%, Power factor of complete fitting should be greater than 0.90, Input operating voltage: 140V to 277V AC and driver should be as per IEC: 62384/IS:16104. The LED fittings should be warranted for 5 years.
Supply,Carrying, loading/unloading, muffing and erection of Galvanised tubular pole 9.0 mtr long , Type-410 SP-33 having weight 164 kgs, 5.00/2.0/2.0 mtr having sectional outer dia 28 165.1/139.7/114.3 mm and sectional thickness 5.40/4.50/3.65 mm respectively as per IS:2713-1980 including suitable size base plate & cap .The work includes digging the pit to 1/5th of the pole height. Execution of CC foundation work of size 45cmx45cm in ratio 1:2:4 by cement,sand and chips of size 19 mm and down upto full depth & 1ft above the GL as per direction of EIC at site.
Supply and erection of galvanized stay set for 11 KV OH line complete with 20 mm 29 dia, 1.8 mtrs long stay rod, anchor plate of size 23 cm x 23 cm x 6 mm thick, 16 mm dia turn buckle, thimble, stay clamp, 7/10 mm SWG GI stay wire & Strain insulator etc. in CC foundation with 1:3:6 ratio including excavation and refilling.
Supply, installation and commissioning of ball and socket type HT 11 KV Polymeric 30 Composite disc insulator minimum creep age distance 450mm, section length 430mm, rated mechanical tensile load 70KN, Wet power freq 1 min, withstand voltage 48KV, Dry lighting impulse withstand voltage 100KV including all accessories for fixing on the bracket with strain clamps, nuts, bolts & washers etc. as per IEC 1109, ISO 9001 : 2000. (2 nos in a set).
Supply, installation and commissioning of 11 KV HT Polymeric Composite pin 31 insulator size 146mm, minimum failing load 5KN, Wet power freq 1 min, withstand voltage 35KV(RMS), Dry lighting impulse withstand voltage 75Kvp(+ve), including all accessories for fixing on the bracket with nuts, bolts & washers etc. as per IEC 1109, ISO 9001 : 2000. (2 nos in a set).
Supply, installation, commissioning and replacement of HT 11 KV GO switch 200 amps, triple pole and each pole consist of galvanized steel base, HT insulator for replacement of the existing G.O. for the feeders.
Supply, installation, commissioning and replacement of HT 11 KV DO fuse (channel type) complete with all accessories for replacement of the existing G.O. for the feeders.
Supply, fitting and fixing of GI Channel to be fixed on pole with suitable size GI clamp 34 made of 50X5 mm, MS flat with 50X16 mm bolts, nuts and washers etc. The channel to be painted by 2-coats of red oxide as primer and 2 coats of Aluminium paint as final coat as per direction of EIC at site of size - 75x40x40 x6 .0 mm, 2.2 mtr long.
Supply, fitting and fixing of GI Channel to be fixed on pole with suitable size MS clamp 35 made of 50X5 mm, GI flat with 50X16 mm bolts, nuts and washers etc. The channel to be painted by 2-coats of red oxide as primer and 2 coats of Aluminium paint as final coat as per direction of EIC at site of size - 75x40x40 x 6.0 mm, 1.2 mtr long
Supply, fitting and fixing of GI Channel to be fixed on pole with suitable size MS clamp 36 made of 50X5 mm, GI flat with 50X16 mm bolts, nuts and washers etc. The channel to be painted by 2-coats of red oxide as primer and 2 coats of Aluminium paint as final coat as per direction of EIC at site of size - 75x40x40 x 6.0 mm, 0.3 mtr long.
Supply, fitting and fixing of GI angle to be fixed on pole with suitable size GI clamp 37 made of 50X5 mm, MS flat with 50X16 mm bolts, nuts and washers etc. The channel to be painted by 2-coats of red oxide as primer and 2 coats of Aluminium paint as final coat as per direction of EIC at site of size - 50x50x6mm, 2200 mm long.
"Supply, fitting and fixing of GI angle to be fixed on pole with suitable size GI clamp 38 made of 50X5 mm, MS flat with 50X16 mm bolts, nuts and washers etc. The channel to be painted by 2-coats of red oxide as primer and 2 coats of Aluminium paint as final coat as per direction of EIC at site of size - 50x50x6mm, 3300 mm long. "
C-Constrcution of ASM room at A cabin
Supply and surface wiring of light/FL point by PVC insulated & un-sheathed FRLSH 01 multi strand copper single core 1.5 sq.mm cable through PVC casing & caping including ceiling rose. Cable connection to be done through 6 A flush type controlling switch installed in suitable size PVC board & connected by Cu flexible wire from ceiling rose to fittings as per direction of EIC at site.
Supply and surface wiring of ceiling fan point by PVC insulated & un-sheathed FRLSH 02 multi strand copper single core 1.5 sq.mm cable through PVC casing & caping including ceiling rose. Cable connection to be done through 6 A flush type controlling switch including 5 point electronic regulator installed in suitable size PVC board with earth continuity by 1.0 sq.mm multistrand copper cable & connected by Cu flexible wire from ceiling rose to fan as per direction of EIC at site.
Supply and surface wiring of exhaust fan point by PVC insulated & un-sheathed FRLSH multi strand copper single core 1.5 sq.mm cable through PVC casing caping including ceiling 03 rose. Cable connection to be done through 6 A flush type controlling switch including suitable size PVC board with earth continuity by 1.0 sq.mm multistrand copper cable & connected by Cu flexible wire from ceiling rose to fan as per direction of EIC at site.
Supply of of 1200mm sweep, BEE star rated - 5 star rated capacitor type ISI marking ceiling fan.
Fixing and commissioning of ceiling fan 1200 mm sweep with suitable size GI pipe, MS hook, clamp, nut & bolts arrangements as required as per direction of EIC at site (Ceiling fan will be supplied by Railway )
Supply, testing and fixing of 300 mm sweep exhaust fan complete by cutting wall, masonary work as required and fixing by suitable nuts and bolts arrangement as per direction of EIC at site.
Supply and surface wiring of 6A 5 pin plug point by PVC insulated & un-sheathed 07 FRLSH multi strand copper single core 2.5 sq.mm cable through PVC casing & caping, with earth continuity by single core 1.0 sq mm copper cable including suitable size PVC board. Cable connection to be done through 6 A flush type controlling switch , socket installed in PVC board hylum sheet on top and as per direction of EIC at site.
Supply and surface wiring of 16 A, 6-pin Plug point/geyser point by PVC insulated and 08 un-sheathed FRLS multi stranded copper cable, single core 4.0 sq.mm with earth continuity by 1.0 sq.mm multistand copper cable through PVC casing & caping including suitable size PVC board. Cable connection to be done through 16 A flush type controlling switch, 16A socket installed in board and as per direction of EIC at site.
Supply & wiring of earth continuity through the circuit of Main line/ Submain line by 1.0 sq mm PVC insulated & unsheathed, single core,multi stranded FRLS copper conductor cable through PVC Casing capinge as per direction of EIC at site.
Supply & wiring of Main line/ Submain line by PVC insulated & unsheathed, single core, multi stranded FRLS copper conductor cable 2.5 sq.mm through PVC casing caping with controlling switch as per direction of EIC at site.
Supply & wiring of Main line/ Submain line by PVC insulated & unsheathed, single core, multi stranded FRLS copper conductor cable 4.0 sq.mm through PVC casing caping with controlling switch as per direction of EIC at site.
Supply & wiring of Main line line by PVC insulated & unsheathed, single core, multi stranded FRLS copper conductor cable 6.0 sq.mm through consealed PVC heavy gayge pipe with controlling switch as per direction of EIC at site.
Supply & fixing of PVC casing caping 25x12mm size by surface of wall for drawing of main/submain line as required of EIC at site.
Supply, installation, testing & commissioning of SPN distribution board 8 way double door metal SPN DB consisting 40A, MCB DP - 1 no, 20A, MCB DP - 2 nos, 6A, MCB SP - 2 nos with enclosure and necessary fixing arrangements as per direction of EIC at site.
Supply, testing & commissioning of 25A, 2 pole, 30mA, 10kA RCCB as per direction of EIC at site.
Supply, installation, testing & commissioning of 18/20W LED tube light fitting with polycarbonate housing with THD less than 20% and surge protection 1.5KV 6000K (4 ft) complete 16 with driver circuit etc and all accessories as per direction of EIC at site. Lumens out put should be not less than 100 Lumens/watt, LED should be as per LM-80/IS: 16105. LED driver's efficiency should be minimum 90%, Power factor of complete fitting should be greater than 0.90, Input operating voltage: 140V to 277V AC and driver should be as per IEC: 62384/IS:16104. The LED fittings should be warranted for 5 years.
Supply and erection of earthing by made of B class GI pipe of 3000 mm length, 50 mm diameter & 3.6 mm thickness.The GI Strip ( should be welded with the earth pipe. Thepipe is 17 provided with a tapered casing at the lower end in order to facilitate the driving. A funnel with perforated plate to be provided at the top of the pipe for pouring water during dry season to have an effective earth value.The connecting conductor from earth electrode to the distribution panel board should not be thinner than 8 SWG GI wire to carry the fault current. The earth fill shall be of homogeneous layer of common earth soil. Where soil restivity is high, earth restivity enhancing material may be used, Bentonite or similar earth enhancing material may be used in rocky soil. Earth box to be precasted RCC and The values of earth resistance measured should be painted on the Earth pit cover/lid along with the date of measurement. As per Drg. No. DRG NO:PCEE/ELG/DRG/2024/1 dated 30.09.2024 & as perTechnical circular no. EL/PS/2024/1 (EARTHING SYSTEM).
Supply, installation, testing & commissioning of 2.0 ton 3 star rated split AC including 18 indoor, outdoor unit compressor rotary type suitable for operation on 230volt/1-ph/50 Hz and copper pipe line along with insulation, wal fixing arrangements and other accessories for connecting indoor unit to outdoor unit with copper piping as per direction of EIC at site.
Surface wiring of AC pointcomplete unit of single phase motor starter(16 A-25A) & 25 19 A socket with 4 module plate and surface box (5 hp)by single core FRLS PVC insulated and unsheathed 4 sq mm stranded copper cable through suitable size PVC casing caping to be drawn from DB and fixed on wall/ceiling by suitable with earth contunity by 1.0 sq mm stranded copper cable including 4 module surface mounted unbreakable gang box as per the direction of EIC at site.
Design, fabrication, supply, installation, testing and commissioning of outdoor type (KIOSK type) hinged, feeder pillar box comprising of following items and made of MS angle, channel 20 by MS sheet of not less than 18 SWG duly welded and painted by 2 coats of primer, two coats of finishing paint (spray paint) Doco/Nerolac brand of approved colour both in interior and exterior as per direction of EIC at site - i) 100A,4P, 18KA, Ics = 100% Icu, conforms to IEC 60947-2 MCCB - 1 nos, ii) 63A, MCB TPN - 1 nos, iii) 40A, MCB DP - 1 nos & iv) 200A 4P copper bus bar - 1 set.
D-Construction of battery room at A Cabin
Supply and surface wiring of light/FL point by PVC insulated & un-sheathed FRLSH 01 multi strand copper single core 1.5 sq.mm cable through PVC casing & caping including ceiling rose. Cable connection to be done through 6 A flush type controlling switch installed in suitable size PVC board & connected by Cu flexible wire from ceiling rose to fittings as per direction of EIC at site.
Supply and surface wiring of ceiling fan point by PVC insulated & un-sheathed FRLSH 02 multi strand copper single core 1.5 sq.mm cable through PVC casing & caping including ceiling rose. Cable connection to be done through 6 A flush type controlling switch including 5 point electronic regulator installed in suitable size PVC board with earth continuity by 1.0 sq.mm multistrand copper cable & connected by Cu flexible wire from ceiling rose to fan as per direction of EIC at site.
Supply and surface wiring of exhaust fan point by PVC insulated & un-sheathed 03 FRLSH multi strand copper single core 1.5 sq.mm cable through PVC casing caping including ceiling rose. Cable connection to be done through 6 A flush type controlling switch including suitable size PVC board with earth continuity by 1.0 sq.mm multistrand copper cable & connected by Cu flexible wire from ceiling rose to fan as per direction of EIC at site.
Supply of of 1200mm sweep, BEE star rated - 5 star rated capacitor type ISI marking ceiling fan with 450mm down rod, canopy and all accessories as per direction of EIC at site.
Fixing and commissioning of ceiling fan 1200 mm sweep with suitable size GI pipe, MS hook, clamp, nut & bolts arrangements as required as per direction of EIC at site (Ceiling fan will be supplied by Railway )
Supply, testing and fixing of 300 mm sweep exhaust fan complete by cutting wall, masonary work as required and fixing by suitable nuts and bolts arrangement as per direction of EIC at site.
Supply and surface wiring of 6A 5 pin plug point by PVC insulated & un-sheathed FRLSH multi strand copper single core 2.5 sq.mm cable through PVC casing & caping, with earth continuity by single core 1.0 sq mm copper cable including suitable size PVC board. Cable connection to be done through 6 A flush type controlling switch , socket installed in PVC board hylum sheet on top and as per direction of EIC at site.
Supply and surface wiring of 16 A, 6-pin Plug point/geyser point by PVC insulated and 08 un-sheathed FRLS multi stranded copper cable, single core 4.0 sq.mm with earth continuity by 1.0 sq.mm multistand copper cable through PVC casing & caping including suitable size PVC board. Cable connection to be done through 16 A flush type controlling switch, 16A socket installed in board and as per direction of EIC at site.
Supply, installation, testing & commissioning of 2.0 ton 3 star rated split AC including 09 indoor, outdoor unit compressor rotary type suitable for operation on 230volt/1-ph/50 Hz and copper pipe line along with insulation, wal fixing arrangements and other accessories for connecting indoor unit to outdoor unit with copper piping as per direction of EIC at site.
Surface wiring of AC point complete unit of single phase motor starter(16 A-25A) & 10 25 A socket with 4 module plate and surface box (5 hp)by single core FRLS PVC insulated and unsheathed 4 sq mm stranded copper cable through suitable size PVC casing caping to be drawn from DB and fixed on wall/ceiling by suitable with earth contunity by 1.0 sq mm stranded copper cable including 4 module surface mounted unbreakable gang box as per the direction of EIC at site..
Supply & wiring of earth continuity through the circuit of Main line/ Submain line by 1.0 sq mm PVC insulated & unsheathed, single core,multi stranded FRLS copper conductor cable through PVC Casing capinge as per direction of EIC at site.
Supply & wiring of Main line/ Submain line by PVC insulated & unsheathed, single core, multi stranded FRLS copper conductor cable 2.5 sq.mm through PVC casing caping with controlling switch as per direction of EIC at site.
Supply & wiring of Main line/ Submain line by PVC insulated & unsheathed, single core, multi stranded FRLS copper conductor cable 4.0 sq.mm through PVC casing caping with controlling switch as per direction of EIC at site.
Supply & wiring of Main line line by PVC insulated & unsheathed, single core, multi stranded FRLS copper conductor cable 6.0 sq.mm through consealed PVC heavy gayge pipe with controlling switch as per direction of EIC at site.
Supply & fixing of PVC casing caping 25x12mm size by surface of wall for drawing of main/submain line as required of EIC at site.
Supply, installation, testing & commissioning of SPN distribution board 8 way double door metal SPN DB consisting 40A, MCB DP - 1 no, 20A, MCB DP- 2 nos, 6A, MCB SP- 2 nos with enclosure and necessary fixing arrangements as per direction of EIC at site.
Supply, testing & commissioning of 25A, 2 pole, 30mA, 10kA RCCB as per direction of EIC at site.
Supply, installation, testing & commissioning of 18/20W LED tube light fitting with polycarbonate housing with THD less than 20% and surge protection 1.5KV 6000K (4 ft) complete 18 with driver circuit etc and all accessories as per direction of EIC at site. Lumens out put should be not less than 100 Lumens/watt, LED should be as per LM-80/IS: 16105. LED driver's efficiency should be minimum 90%, Power factor of complete fitting should be greater than 0.90, Input operating voltage: 140V to 277V AC and driver should be as per IEC: 62384/IS:16104. The LED fittings should be warranted for 5 years.
Supply and erection of earthing by made of B class GI pipe of 3000 mm length, 50 19 mm diameter & 3.6 mm thickness.The GI Strip ( should be welded with the earth pipe. Thepipe is provided with a tapered casing at the lower end in order to facilitate the driving. A funnel with perforated plate to be provided at the top of the pipe for pouring water during dry season to have an effective earth value.The connecting conductor from earth electrode to the distribution panel board should not be thinner than 8 SWG GI wire to carry the fault current. The earth fill shall be of homogeneous layer of common earth soil. Where soil restivity is high, earth restivity enhancing material may be used, Bentonite or similar earth enhancing material may be used in rocky soil. Earth box to be precasted RCC and The values of earth resistance measured should be painted on the Earth pit cover/lid along with the date of measurement. As per Drg. No. DRG NO:PCEE/ELG/DRG/2024/1 dated 30.09.2024 & as perTechnical circular no. EL/PS/2024/1 (EARTHING SYSTEM).
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
TD-062026-27.pdf
ATTACHMENT
ACS-8_2.pdf
ATTACHMENT
GCC_April-2022_2022.pdf
ATTACHMENT
GCCUpdateduptoACS-11_1.pdf
ATTACHMENT
JPO8.5.24-CablediggingworksNFR.pdf
ATTACHMENT
ACS-09.pdf
ATTACHMENT
ACS-10.pdf
ATTACHMENT
GCCACS11.pdf
ATTACHMENT
TechCircularwithDrgforEarthingandCableLayingUG.pdf Drawing for pipe earthing and cable lay
ATTACHMENT
AnnexureNEW.pdf
ATTACHMENT
TechCircularwithDrgforEarthingandCableLayingUG.pdf
ATTACHMENT
Download all tender documents and submit your bid