Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.5 LAccepted-AOC H NO B III 95 MOHALLA GHARTHOLI MISSION ROAD PATHANKOT 145001 PB | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L1 | Accepted-AOC Lowest bid. | |
| 2 | L2₹17.5 L+₹95,076 (5.75%)Rejected-Finance | L2 | Rejected-Finance Other than lowest bid. | |
| 3 | L3₹17.6 L+₹1.1 L (6.44%)Rejected-Finance | L3 | Rejected-Finance Other than lowest bid. | |
| 4 | L4₹17.6 L+₹1.1 L (6.64%)Rejected-Finance H NO 07 SHIVAJI NAGAR PATHANKOT 145001 | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L4 | Rejected-Finance Other than lowest bid. | |
| 5 | L5₹18.3 L+₹1.8 L (10.8%)Rejected-Finance 225 NAROT COLONY MODEL TOWN PATHANKOT PB 145001 | PATHANKOT | PUNJAB | 145001 | L5 | Rejected-Finance Other than lowest bid. |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
16 Feb 2023, 6:00 pmClosed
GE SOUTH MAMUN
GE SOUTH MAMUN PATHANKOT
REPAIR/REPLACEMENT OF CONVENTIONAL LIGHT INTO LED LIGHT AND CERTAIN MISC CONNECTED ITEMS LIKE SUNKEN BOX, SWITCH/SOCKET AND MODULAR FIXTURE/FITTING WORK IN OTM ACCN HORSE REGT AREA, ARMD REGT AREA, GOC AREA AND CONNECTED AREA UNDER AGE E/M OF GE (SOU
2023_MES_576373_1
GE(S)/M-57/2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE SOUTH MAMUN
AS PER NIT
8 documents required · 8 mandatory
₹500
GE SOUTH MAMUN
₹50,000
Yes
9 Mar 2023
21 Jan 2023
23 Feb 2023
21 Jan 2023
16 Feb 2023
4 Feb 2023
Amount
Taking down carefully aluminium / copper point wiring (light / fan / socket or power) complete with all fitting, accessories such as swithes,sockets, bells, holders,tube light, bulk head, pendant ceiling roses & regulators and making good disturbed surfaces of walls, floors to match with existing specifications and keeping aside serviceable items for reuse and deposited to MES store yard and removing UNSV items from site, complete all as specified and directed.
M& L in replacement of Point wiring for one light point / fan point or bell point controlled by one switch with 1.5 sqmm PVC insulated unsheathed, FRLS , Multistranded copper conductor cable as in and including non metalic rigid PVC concealed conduit ISI marked, not less than 20mm dia, 1.5mm thick for one light, fan, bell pioint controlled by one switch including sunken steel boxes of suitable size with 3mm thick plastic laminated backelite sheet including FRLS PVC insulated unsheathed multistranded copper conductor cable of size 1.5sqmm (green colour ) as continious earth wire and connecting to earth dolly, and making good to distrub surfaces of wall/floor to match to existing finishes etc complete all as specified and directed. Note: The unit rate quoted include the cost of cutting chases in surfaces for conduits and fixing of sunken boxes and making good the distrubed surfaces to match the existing surfaces.
All as per Srl item No. 2.00 here-in before but point wiring in existing PVC conduit pipe, complete all as specified and directed.
All as per Srl item No. 2.00 here-in before but with FRLS, multistranded copper conductor in PVC Casing and capping including necessary PVC accessories i.e. Tee, elbow, socket etc., complete all as specified and directed.
M&L for point wiring for one 2 way light point / fan point / bell point controlled by one switch with 1.5 Sqmm (red or yellow or blue colour) for phase, black for neutral PVC insulated unsheathed copper conductor single core multistranded FRLS cable and 1.5 Sqmm PVC insulated unsheathed copper conductor single core multistranded FRLS (green colour) cable as earth lead drawn in as earth continuity wire in green colour connected to common earth dolly and each terminal/joints fitted with thimble and including connected non metallic rigid PVC conduit not less than 20 mm dia 1.5mm thick including CI/MS terminal box of required size including 3mm thick plastic laminated top sheet cover fitted with brass screw and cup washer including cutting chases to walls and making good the disturbed surfaces to match with the existing specifications, complete all as specified and directed. Note : Including in ceiling portion surface conduit wiring shall be carried out.
All as per Srl item No. 2.00 here-in before but for one 3 pin 5 Amps socket outlet on independent board, complete all as specified and directed.
All as per Srl item No. 2.00 here-in before but for one 3 pin 5 Amps socket outlet on independent board in existing conduit, complete all as specified and directed.
All as per Srl item No. 2.00 here-in before but for one 3 pin 5 Amps socket outlet on independent board in PVC casing & caping including necessary PVC accessaries i.e Tee, elbow, socket etc., complete all as specified and directed.
All as per Srl item No. 2.00 here-in before but for one 3 pin 5 Amps socket outlet on same board with other switch, complete all as specified and directed.
All as per Srl item No. 2.00 here-in before but for one 3/5 pin 15Amps socket outlet on independent board using 2.5 sqmm FRLS PVC insulated unsheathed multistranded copper conductor drawn in and including connected non metallic rigid PVC conduit including not less than 20mm dia 1.5mm thick including sunken steel boxes of required size including 3mm thick plastic laminated bakelite sheet cover including 2.5.00 Sqmm multistandard PVC insulated unsheathed copper conductor single core multistranded FRLS (green colour) cable earth wire connecting to earth dolly complete all as specified and directed.
All as per Srl item No. 2.00 here-in before but for metal plug top AC & Geyser point using 4.0 Sqmm FRLS PVC insulated unsheathed copper conductor cable including non metallic rigid PVC concealed conduit not less than 20mm dia 1.5mm thick including sunken steel boxes of required size including 3mm thick plastic laminated bakelite sheet cover including 2.50 Sqmm PVC insulated unsheathed copper conductor single core multistranded FRLS (green colour) cable earth wire connecting to earth dolly complete all as specified and directed.
All as per Srl item No. 2.00 here-in before but for one 3/5 pin 15Amps socket outlet on independent board using 2.50 Sqmm FRLS PVC insulated unsheathed copper conductor cable in existing non metallic rigid PVC concealed conduit including sunken steel boxes of required size including 3mm thick plastic laminated bakelite sheet cover including 2.50 Sqmm PVC insulated unsheathed copper conductor single core multistranded FRLS (green colour) cable earth wire connecting to earth dolly complete all as specified and directed.
All as per Srl item No. 2.00 here-in before but for one 3/5 pin 15Amps socket outlet on independent board using 2.50 Sqmm FRLS PVC insulated unsheathed multistandard copper conductor cable drwan in and including PVC casing caping (ISI Marked) including necessary accessaries such as tee, elbow, sockets etc.,including not less than 20mm dia 1.5mm thickincluding sunken steel boxes of required size dully engrouted in wall by cutting, chasing and making good the disturbed surfaces with 3mm thick plastic laminated bakelite sheet cover including 2.50 Sqmm PVC insulated unsheathed copper conductor single core multistranded FRLS (green colour) cable earth wire connecting to earth dolly complete all as specified and directed. Note :- Rate are deemed to be including providing PVC accessories i.e Tee,elbow,socket etc.
S&F Switch piano flush button, single pole, one way, 5/6 Amps, 230 Volts AC with polycarbonate body, complete all as specified and directed.
S&F in repair Switch piano flush button, single pole, one way, 5/6 Amps, 230 Volts AC with polycarbonate body, complete all as specified and directed.
S&F Switch piano flush button, single pole, two way, 5/6 Amps, 230 Volts AC with polycarbonate body, complete all as specified and directed.
S&F bell push flush button, single pole, two way, 5/6 Amps, 230 Volts AC with polycarbonate body, complete all as specified and directed.
S&F for multi socket outlet for 2 & 3 pin, 6A flush type , complete all as specified and directed.
S&F for Socket outlet, 3 Pin, 6 and 16 Amps, multipurpose, 2 in 1, flush type, 230 Volts AC with polycarbonate body, complete all as specified and directed.
S&Fin repair Socket outlet, 3 Pin, 6 and 16 Amps, multipurpose, 2 in 1, flush type, 230 Volts AC with polycarbonate body, complete all as specified and directed.
S&F for Switch piano flush button, single pole, one way, 16 Amps, 230 Volts AC with polycarbonate body, complete all as specified and directed.
S&F in repair Switch piano flush button, single pole, one way, 16 Amps, 230 Volts AC with polycarbonate body, complete all as specified and directed.
S&F fan regulator stepped type electronic mini , hum free with polycarbonate body, suitable to control speed of fan from 0 to 100% and connecting electrically, complete all as specified and directed.
S&F in repair fan regulator stepped type electronic mini , hum free with polycarbonate body, suitable to control speed of fan from 0 to 100% and connecting electrically, complete all as specified and directed.
S&F fan regulator stepped type electronic delux with polycarbonate body, suitable to control speed of fan from 0 to 100% 5 to 8 step and connecting electrically, complete all as specified and directed.
S&F in repair fan regulator stepped type electronic delux with polycarbonate body, suitable to control speed of fan from 0 to 100% 5 to 8 step and connecting electrically, complete all as specified and directed.
M&L for modular point wiring for one light point / fan point / bell point controlled by one switch with 1.5 Sqmm (red or yellow or blue colour) black for neutral PVC insulated unsheathed copper conductor single core multistranded FRLS cable 1100 volts grade in and including connected non metallic rigid PVC conduit not less than 20mm dia 1.5mm thick including conduit accessaries i.e Tee, elbow, bend tee junction boxes etc fixed concealed/recessed in wall or ceiling etc and 1.5 Sqmm PVC insulated unsheathed copper conductor single core multistranded FRLS (green colour) cable 1100 volts grade as earth lead drawn in as earth continuity wire in green colour connected to common earth dolly and each terminal/joints fitted with thimble and including connected non metallic rigid PVC conduit including CI/MS box of required size including inner & outer frame plate matching with surrounding with modular surken cover including cutting chases to walls and making good the disturbed surfaces to match with the existing specifications, complete all as specified and directed.
All as per Srl item No. 27.00 here-in before but point wiring controlled by module one switch in existing PVC conduit pipe, complete all as specified and directed.
All as per Srl item No. 27.00 here-in before but point wiring controlled by module two way switch, complete all as specified and directed.
All as per Srl item No. 27.00 here-in before but for one 5 pin 5 Amps socket outlet on independent board, controlled by 5 Amps one way switches complete all as specified and directed.
All as per Srl item No. 27.00 here-in before but for one 5 pin 5 Amps socket outlet on independent board, controlled by 5 Amps one way switches in existing conduit, complete all as specified and directed.
All as per Srl item No. 27.00 here-in before but for 5 pin 5 Amps socket outlet on same board, controlled by 5 Amps one way switches complete all as specified and directed.
All as per Srl item No. 27.00 here-in before but for one 5 pin 5 Amps socket outlet on same board, controlled by 5 Amps one way switches in existing conduit, complete all as specified and directed.
All as per Srl item No. 27.00 here-in before but for one 15 Amps socket outlet using 4.00 sqmm FRLS PVC insulated multistranded copper conductor cable including 4.00 sqmm FRLS PVC insulated unsheathed multistranded copper conductor cable as earth wire, complete all as specified and directed.
All as per Srl item No. 27.00 here-in before but for one 15 Amps socket outlet using 4.00 sqmm FRLS PVC insulated multistranded copper conductor cable including 4.00 sqmm FRLS PVC insulated unsheathed multistranded copper conductor cable as earth wire in existing conduit, complete all as specified and directed.
S&F for one module switch, one way, 6 Amps, 2 module 240 Volts AC with polycarbonate body, complete all as specified and directed.
S&F for one module switch, one way, 16 Amps, 230 Volts AC with polycarbonate body, complete all as specified and directed.
S&F moduler bell push flush button, single pole, one way, 6 Amps, 230 Volts AC with polycarbonate body, complete all as specified and directed.
S&F for one module switch, two way, 6 Amps, 230 Volts AC with polycarbonate body, complete all as specified and directed.
S&F for two module socket , 6 Amps, 230 Volts 2/3 pin AC with polycarbonate body, complete all as specified and directed.
S&F for two module socket , 6/16 Amps, 230 Volts 2/3 pin AC with polycarbonate body, complete all as specified and directed.
S&F for modular fan step reguator 120W, 240 Volts 2 module AC with polycarbonate body, complete all as specified and directed.
S&F ceiling rose, surface bakelite,2 to 3 terminals, 230 Volts AC with polycarbonate body, complete all as specified and directed.
S&F in repair ceiling rose, surface bakelite,2 to 3 terminals, 230 Volts AC with polycarbonate body, complete all as specified and directed.
S&F for lamp holder insulated body of PVC / polycarbonate type with back plate suitable for Angle/ batten fittings complete all as specified and directed.
S&F in repair lamp holder insulated body of PVC / polycarbonate type with back plate suitable for Angle/ batten fittings complete all as specified and directed.
S&F bell electric, heavy duty, Ding Dong type, 230 Volts AC, single pole, complete all as specified and directed.
S&F in repair bell electric, heavy duty, Ding Dong type, 230 Volts AC, single pole, complete all as specified and directed.
Supply & fix wall mounted 1x20 watt LED 6500K tube light fittings (4 feet long),Decorative ultra slim square profile LED lighting fixture with extruded polycarbonate, environmental friendly, energy efficient with all accessories and making connection using 2 core, 0.50 Sqmm PVC insulated and overall sheathed flexible copper conductor cable from ceiling rose/PVC connector to light fitting and testing etc complete all as specified and directed.
Supply & fix in repair of wall mounted 1x20 watt LED 6500K tube light fittings (4 feet long),Decorative ultra slim square profile LED lighting fixture with extruded polycarbonate, environmental friendly, energy efficient with all accessories and making connection using 2 core, 0.50 Sqmm PVC insulated and overall sheathed flexible copper conductor cable from ceiling rose/PVC connector to light fitting and testing etc complete all as specified and directed.
Supply and fixing of LED light fittings mirror type with high out put diffuser 2 feet long .10 watt 220 volt AC decorative type with driver holder including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed.
Supply and fixing in repair of LED light fittings mirror type with high out put diffuser 2 feet long .10 watt 220 volt AC decorative type with driver holder including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed.
S & F for surface mounted LED Bulk Head luminaires 10 watts with ABS body & polycarbonate diffuser available in CCT 6000K IP 54 complete all as specified and directed.
S & F in repair of surface mounted LED Bulk Head luminaires 10 watts with ABS body & polycarbonate diffuser available in CCT 6000K IP 54 complete all as specified and directed.
S&F for Recessed LED ceiling 35/36 Watt, luminaire of size 600mm x 600mm with white light window and built-in LED lamp with all accessories and making connection using 3 core, 0.50 Sqmm PVC insulated and overall sheathed flexible copper conductor cable and testing after fixing, complete all as specified and directed.
S&F in repair Recessed LED ceiling 36 Watt, luminaire of size 600mm x 600mm with white light window and built-in LED lamp with all accessories and making connection using 3 core, 0.50 Sqmm PVC insulated and overall sheathed flexible copper conductor cable and testing after fixing, complete all as specified and directed.
S & F for energy efficient LED ceiling light 15 W of size 1x1 feet complete with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver 3 core flexible copper conductor cases of suitable size complete all as specified and directed.
S & F in repair energy efficient LED ceiling light 15 W of size 1x1 feet complete with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver 3 core flexible copper conductor cases of suitable size complete all as specified and directed.
S & F for decorative wall bracket light white in colour made up of poly carbonate suitable for and including 9 watts retrofit LED lamp complete all as specified and directed.
S & F in repair of decorative wall bracket light white in colour made up of poly carbonate suitable for and including 9 watts retrofit LED lamp complete all as specified and directed.
S&F for of building security light luminaire 30 Watt, IP 66, AC 230 volts made up of pressure dia cast iron housing complete making connection using PVC insulated and sheathed 3 core multi stranded copper conductor cable of size 0.50 Sqmm from ceiling rose including suitable size of bracket of light grade pipe for mounting of fitting along with clamps, nut bolts and washers complete all as specified and directed.
S&F in repair of building security light luminaire 30 Watt, IP 66, AC 230 volts made up of pressure dia cast iron housing complete making connection using PVC insulated and sheathed 3 core multi stranded copper conductor cable of size 0.50 Sqmm from ceiling rose including suitable size of bracket of light grade pipe for mounting of fitting along with clamps, nut bolts and washers complete all as specified and directed.
S&Ffor decorative post of lantern 40 Watt 230 volts, 50Hz, mushroom or oval shaped in sothing opal/prismatic finish made up of polycarbonate, suitable for 40 watt LED, all accessories prewired complete all as specified and directed.
S&F in repair of decorative post of lantern 40 Watt 230 volts, 50Hz, mushroom or oval shaped in sothing opal/prismatic finish made up of polycarbonate, suitable for 40 watt LED, all accessories prewired complete all as specified and directed.
Note for srl item No 49 to 64 above 1. Driver shall be potted anti-vibration types. 2. LM-79 and LM-80 test report with 1 Lakh burning hours LED life from NABL lab shall be provided. 3. CRI (Colour Rendering Index) of fixture shall be > 70. 4. CCT (Colour Co-related Temperature of fixture shall be 5700K + 300 K. 5. System Lumen Efficacy shall be > 100 Lm/W. 6. 10 KV separate Surge Protection shall be provided as a part of fitting. 7. 5 years guarantee shall be provided by contractor supported by OEM covering all parts of luminaire. 8. Lenses shall be Modular Type. 9. PCB used shall be MC PCB type. 10. The defect liability period of LED light shall be 05 years from the certified date of completion & the contractor shall replace/repair the defective fitting within 07 days after handing over to contractor for replacement/repair. 11. CA No. shall be written on each fitting before installation. 12. The name of manufacturer to be embossed on the fitting. 13. The fittings shall have arrangement so that maintenance required, if any can be carried out from Top cover.
M & L in repair for sheet metal enclosure MCB distribution board single pole and neutral with a two pin and earth plug and socket 20 amps 240 volts, complete with one single pole MCB of 20 amps complete all as specified and directed.
Supply & Fix in repair sheet metal enclosure with DB's ( grouted in walls) single pole and neutral double door type for MCB's 04 ways with 200 Amps 240 volts rated bus bar complete all as specified and directed.
Supply & Fix in repair sheet metal enclosure with DB's ( grouted in walls) single pole and neutral double door type for MCB's 08 ways with 200 Amps 240 volts rated bus bar complete all as specified and directed.
Supply & Fix in replair sheet metal enclosure with DB's ( grouted in walls) single pole and neutral double door type for MCB's 12 ways with 200 Amps 240 volts rated bus bar complete all as specified and directed.
S&F MCB single pole and neutral 63 Amps 240 volts B series complete all as specified and directed.
S&F MCB single pole and neutral 40 Amps 240 volts B series complete all as specified and directed.
S&F MCB single pole 6 to 32 Amps 240 volts B series complete all as specified and directed.
M&L for replacement of earthing complete with galvanised GI earth plate electrode of size 600x600x6mm thick, burried directly in ground (earth pit not less than 2.25 Mtr deep below normal ground level) with top edge of earth plate not less than 1.5 Mtr below normal ground level, connected to galvanised earth lead wire 4mm dia by means bolt, nuts, check nuts and washer made of galvanised iron or steel including earth work in any type of soil, charcoal dust and salt layers 15cm thick all around the earth plate as shown in electrical plate No. 03 of SSR Part-I 2009 including 20mm bore GI watering pipe 'medium grade' with funel and wire mesh and 15mm bore GI protection pipe 'light grade' from earth pit to main board including PCC pit in cement concrete 1:2:4 type B-2 (using 40mm graded stone aggregate) and including angle iron frame of size 40x40x3mm with hold fast embeded in PCC, RCC pit cover with suitable handle and earth work and removal of surplus soil to a distance not exc 50 Mtr, complete all as specified and directed.
M&L for submain wiring with two single core PVC insulated flexible FRLS copper conductor cable of size 6.0 Sqmm and one single core PVC insulated flexible copper conductor cable green colour of size 6.0 Sqmm as FRLS earth lead, drawn in existing surface/ recessed steel/ PVC conduit omplete all as specified and directed including taking down old one. Note :- Two run of cable with one run of earth wire and PVC conduit shall be measured and paid for as one unit.
M&L for submain wiring with two single core FRLS PVC insulated flexible copper conductor cable of size 6.0 Sqmm and one single core PVC insulated flexible copper conductor cable green colour of size 6.0 Sqmm as earth lead, drawn in and including concealed non metallic rigid PVC conduit, 25mm dia 1.5mm thick and making good the disturbed surfaces to match with existing specifications, including taking down exisating sub main wiring complete all as specified and directed including taking down old one. Note :- Two run of cable with one run of earth wire and PVC conduit shall be measured and paid for as one unit. Rate is inclusive of cutting chases for concealed conduit.
S&F in repair hylum sheet of size 5''x5'' including cutting for required shape for fixing of existing switches & sockets complete all as specified and directed.
S&F in repair hylum sheet of size 8''x5'' including cutting for required shape for fixing of existing switches & sockets complete all as specified and directed.
S&F in repair hylum sheet of size 10''x12'' including cutting for required shape for fixing of existing switches & sockets complete all as specified and directed.
S&F in repair hylum sheet of size 8''x10'' including cutting for required shape for fixing of existing switches & sockets complete all as specified and directed.
S&F in repair sunken steel box zinc oxide plated of size 4''x4'' including cutting the wall to required shape for fixing and making good the disturbed surfaces to match existing one complete all as specified and directed.
S&F in repair sunken steel box zinc oxide plated of size 7''x4'' including cutting the wall to required shape for fixing and making good the disturbed surfaces to match existing one complete all as specified and directed.
S&F in repair sunken steel box zinc oxide plated of size 9''x11'' including cutting the wall to required shape for fixing and making good the disturbed surfaces to match existing one complete all as specified and directed.
S&F in repair sunken steel box zinc oxide plated of size 7''x9'' including cutting the wall to required shape for fixing and making good the disturbed surfaces to match existing one complete all as specified and directed.
S&F in repair prewired VTPN distributed boards with provosion of MCCBs as incomer 63 A, 04 pole IP 54 04 ways (for incomming MCCBs and outgoing MCBs) with copper busbar for each phase with neutral bar, earth bar and cable ties for cable management fully insulated busbar & shrouded neutral bars with 63 Amps MCCB 16 KA 04 pole as incomerand SP MCB's of cap 6- 32 Amps as outgoing complete all as specified and directed. Note : Rate of MCCBs and MCBs , cutting, chases and grouting in wall are included in the quoted rates.
S&F in replacement of old u/s service cable size 6 sqmm twin core multistranded fixing or passing through pipe, 1100 volts grade heavy duty cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed complete all as specified and directed.
S&F in replacement of old u/s service cable size 16 sqmm twin core multistranded fixing or passing through pipe, 1100 volts grade heavy duty cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed complete all as specified and directed.
S&F for repair of copper strip 20 x 3 mm with saddles and insulators made out of porecelain and fixing screws etc.for roof conductors and down conductors including nut, bolt and washers threading and reviting for joints for suitable size as required at site including taking down above ground complete all as specified and directed. Note : Resin/porecelain cast insulators are to be fixed at an interwal of not more than 75 cm.
M&L in repair Earth continuity conductor or main earthing lead of 20x3 mm GI strip fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc.as required incuding taking down complete all as specified and directed.
M&L in repair Earth continuity conductor or main earthing lead 32x6 mm GI strip fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc.as required incuding taking down complete all as specified and directed.
S&F in repair of air termination, single pointed aluminium rod 12mm dia and 300mm long suitable fixing arrangement and making threading in one end of air termination rod including taking down complete all as specified and directed.
S&F in repair of air termination, single pointed copper rod 12mm dia and 300mm long suitable fixing arrangement and making threading in one end of air termination rod including taking down complete all as specified and directed.
M&L for PCC 1:2:4 type B-1 (using 20mm graded stone aggregates) in block for air termination rod etc.complete all as specified and directed.(Note : Unit rate includes for provn of form work for rough finished surfaces and finishing the exposed surfaces with 5mm thick rendering in CM 1:3 ).
S&F for GI tubes 40mm dia, 'light grade' galvanised,with all fitting and fixed complete to walls and ceilings .complete all as specified and directed.
S&F for replair of aluminium strip 25 x 3 mm with saddles and insulators made out of porecelain and fixing screws etc.for roof conductors and down conductors including nut, bolt and washers threading and reviting for joints for suitable size as required at site including taking down above ground complete all as specified and directed. Note :-Resin/porecelain cast insulators are to be fixed at an interwal of not more than 75 cm.
S&F for Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hexagonal head screw including sheet box complete with front hinged shutter with locking arrangement of size 30cmx25cmx8cm and duly painted with two coats of synthetic enamelled paint over a coat of red oxide primer complete all as specified and directed.
M&L in replacement for complete with earthing with copper earth plate electrode of size 60x60cmx3.15mm thick buried directly in ground to a depth not less than 2.25 mtr deep below normal ground level with top edge of the earth plate not less than 1.5 mtr deep below normal ground level connected to copper strip of size 20x3mm as earthing lead by means of nuts, bolts and washers of steel after welding of GI strip to earth electrode to the full lenght of earth plate,40mm dia GI tubing light grade protection pipe upto test point, 20mm dia GI watering pipe with funnel and wire mesh, PCC pit 1:3:6 with pit cover of size 30X30cm made of RCC 1:3:6 with suitable handle,angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate and filling of vegetable soil to the remaining 10%,removal of surplus soil and returning filling in all as required at site including test point made out of steel plate of size 75x75x6mm fixed to wall all as specified in plate No 3 of SSR Part-I and directed by Engr-In-Charge. Note:- (i) Item includes the cost of 7.5 metre GI pipe for protection of earth lead. (ii) Item includes the cost of 7.5 metre GI earth lead.
M&L for earthing with steel earth plate electrode of size 60x60cmx6mm thick buried directly in ground to a depth not less than 2.25 mtr deep below normal ground level with top edge of the earth plate not less than 1.5 mtr deep below normal ground level connected to galvanized iron strip of size 32x6mm as earthing lead by means of nuts, bolts and washers of steel after welding of GI strip to earth electrode to the full lenght of earth plate,40mm dia GI tubing light grade protection pipe upto test point, 20mm dia GI watering pipe with funnel and wire mesh, PCC pit 1:3:6 with pit cover of size 30X30cm made of RCC 1:3:6 with suitable handle,angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate and filling of vegetable soil to the remaining 10%,removal of surplus soil and returning filling in all as required at site including test point made out of steel plate of size 75x75x6mm fixed to wall all as specified in plate No 3 of SSR Part-I and directed by Engr-In-Charge. Note:- (i) Item includes the cost of 7.5 metre GI pipe for protection of earth lead. (ii) Item includes the cost of 7.5 metre GI earth lead.
KULBHUSHAN AGGARWAL
GOLDEN CONSTRUCTIONS
M/S SHAKTI ELECTRIC WORKS
M/S SHRI RAM BUILDERS
Bidder Name
KULBHUSHAN AGGARWAL
GOLDEN CONSTRUCTIONS
M/S SHAKTI ELECTRIC WORKS
M/S HIMANSHU BUILDERS
M/S SHRI RAM BUILDERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .