Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.9 LAccepted-AOC | ₹17.9 L | L1 | Accepted-AOC L1 Bidder |
| 2 | L2₹18.9 L+₹1.0 L (5.71%)Rejected-Finance | ₹18.9 L+₹1.0 L (5.71%) | L2 | Rejected-Finance Not being lowest |
| 3 | L3₹21.3 L+₹3.4 L (19.1%)Rejected-Finance JAISALMER | JAISALMER | RAJASTHAN | 342310 | ₹21.3 L+₹3.4 L (19.1%) | L3 | Rejected-Finance Not being lowest |
| 4 | Rejected-Technical | - | - | Rejected-Technical REQUISITE DOC NOT PRODUCE |
Tender Value
Refer Docs
EMD Value
₹44,800
Closing Date
14 Nov 2020, 6:00 pmClosed
GE Army Jaisalmer
GE Army Jaisalmer 345001
PROVN OF INSTALLATION OF 10 KW SOLAR PANEL ON GRID SYSTEM AT NACHANA UNDER AGE BR II POKARAN
2020_MES_314121_3
8854/19-20/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Pokaran
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE Army Jaisalmer
₹44,800
Yes
11 Jun 2021
26 Oct 2020
16 Nov 2020
26 Oct 2020
14 Nov 2020
2 Nov 2020
Amount
01. Solar PV Modules ≥325Wp MNRE Approved Nos. 31 02. Module Mounting Structure (50x50x5mm thick angle) Set for 31panel, (manufactured in India) 03. 10 KW String inverter, 415V AC, 50 Hz, Three phase AC, Nos - 01 04. Array Junction Box Set 4 05. Sub-main Junction Box Set, and 03 pin plug top 06. 2x2.5 Sq mm PVC Insulated Copper Cable as required at site. 07. 2x4 Sq mm PVC Insulated Copper Cable as required at site. 08. 1x6 Sq mm PVC Insulated Copper Cable as required at site. 09. Q cable to connect AC Module 10. DC Distribution Board, Set 1 11. AC Distribution Board, Set 1 12. Earthings complete with GI strip 25x3 mm, Set 3 13. Lighting Arrester, Set 3 14. Installation Accessories, Set 1 15. Spare & Tools Complete, Set 1 16. Cat Log book / Spare part Manual. 17. PCC block M-20 size 300x300x300mm for foundation of steel structure solar stand. 18. Net meter/solar meter, each 01 : Contractor responsibility for testing of meter as per JdVVNL Norms. 19. Conduit pipe/cable tie/cable clip as required.
Major Components & Technical Specification
Solar PV Module:- Poly Crystalline Silicon PV Module with efficiency > 15% and IEC 61215 & IEC 61730 MAKE - ADANI/WAAREE/KOSOL/ /Luminous or equivalen..
Module Mounting Structure :- Galvanized MS module mounting Structure with minimum thickness of galvanization 70 micron with SS nut & Bolts. Designed to withstand wind peed as per IS875 and seismic factor of the site. MAKE-TATA Steel / JSW
Junction Box :- Dust ,Vermin & waterproof made out of FRP MAKE-Fairwood-Smart Green or equivalent
Inverters : - Single -phase string inverters ideal for roof top systems complying with all requirements for IP 65 equivalent protection – their housing provides reliable protection from dust and water, including high pressure washing. With Fast MPP tracking and a wide input voltage range to ensure the high levels of efficiency Even at lower radiation, to achieve an efficiency of up to 98.2%. With integrated data-logger to send all important operating data through Internet portal. Warranty: 5 years and extendable under AMC Make-Microtek/ Luminous/ Delta/ OPS/ Keco
Distribution Boxes, Cables & Accessories : - An ACDB shall be provided in between PCU and Load/grid interface with 32A MCB of suitable rating of connection and disconnection of PCU from load. All the cables shall be supplied conforming to IS 1554 / 694 Part 1 of 1988 & shall be of 650 V/ 1.1kV grade as per requirement. Make-Delta/OPS/Keco
Earthing & Lighting Protection:- Earthing kits in adequate numbers to properly ground the array structures of the PV yard as per IEE regulation. Lighting and overvoltage protection of the SPV Plant to be provided. Total - 06 set earthing & 03 set lighting protection.
DETAILS OF THE POWER PLANTS
Solar PV modules shall be designed and manufactured to meet the same recognized standard which must have been used extensively throughout the world for more than a decade with an excellent track record of performance. SPV modules shall generate a peak power 325 Wp + 0.5 Wp or should be of higher capacity with + 0.5 Wp under STC.Each module should have two separate inter connected strings with proper by-pass diode(s). Minimum dimension of the SPV module shall be preferred.
MODULE MOUNTING STRUCTURE: Module mounting structure to be manufactured with steel angles and channels should be hot dip galvanized or spray galvanized. Size of angle 50x50x5mm angle for 31 module.
FOUNDATION: The foundation pedestals where-ever necessary shall be concrete (M-20 grade, size 300x300x300mm)
JUNCTION BOX:The junction boxes shall be made up of module cast PVC, dust and vermin proof. The terminals shall be of appropriate size; junction boxes shall have suitable cable entry with suitable glanding arrangement for both input and output cables. Suitable marking on the bus bars shall have to be provided to identify the bus bars etc.
Tools kit: Necessary maintenance tool kit (key, spanner, screwdriver), is to be provided for any immediate maintenance - two set. Make- Taparia or equivalent.
DITRIBUTION BOARDS: Distribution boards shall be used. All MCBs, Indicators, Energy Meters are to be interconnected through copper bus bar and are to be housed in a suitable sized sheet metal, enclosure. The panel board is to be grounded and for this purpose a suitable ground terminal is to be arranged. The panel board shall be coated with good quality paint. The distribution panel board shall be dust and vermin proof. The distribution panel board shall be wall mounted type and of front door opening type. The distribution panel board shall have suitable cable entry arrangement so that cable can be fastened with proper size gland loads. A distribution board shall be used for Power supply to the emergency AC from the inverter. The DB shall consist of MCB at incoming and at outgoing terminals, suitable size Copper wire are also to be supplied and installed for interconnection of DB inverter.
POWER CONDITIONING UNIT:The power conditioning unit should convert DC power produced by SPV modules, into AC power and adjust the voltage and frequency levels to suit the local grid conditions. Common Technical Specifications of the Inverter Type : IGBT based
LIGHTING PROTECTION: Each array structure of the PV yard should be grounded properly. In addition the lightening masts should also be provided inside the array field. Provision should be kept inside the array field. Provisions should be kept for shorting and grounding of the PV array at the time of maintenance work. All metal casing/shielding of the plant should be thoroughly grounded in accordance with Indian Safety Act/IEEE rules. set of 03.
LIGHTENING & OVER VOLTAGE PROTECTION: The SPV power plant should be provided with lightening and over voltage protection. The principle aim in this protection is to reduce the over voltage to a tolerable value before it reaches the PV or other subsystem components. The source of over voltage can be lightening or any other atmospheric disturbances. ESE Type lightning arrester.
JdVVNL Note :- (i) Contractor shall be fully responsible for maint of plant including all type of material required. (ii) Contractor shall be fully responsible to all type of liason with JdVVNL. Any expenditure incurred during the installation/ commissioning/ testing/ On grid connection etc included in quoted rate.
Dadhich Engineers
S K TRADER
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .