Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.1 LAccepted-AOC | ₹2.1 L Quoted ₹20.8 L | L1 | Accepted-AOC L1 |
| 2 | L2₹23.0 L+₹2.2 L (10.6%)Rejected-Finance | ₹23.0 L+₹2.2 L (10.6%) | L2 | Rejected-Finance Rejected being not L1 |
| 3 | L3₹24.8 L+₹3.9 L (18.9%)Rejected-Finance | ₹24.8 L+₹3.9 L (18.9%) | L3 | Rejected-Finance Rejected being not L1 |
Tender Value
Refer Docs
EMD Value
₹70,000
Closing Date
9 Oct 2020, 6:00 pmClosed
GE(SB) Karwar
GE (Seabird) Karwar Naval Base Karwar
REPAIR AND MAINTENANCE OF LT DISTRIBUTION NETWORK INCLUDING LT PANELS/ FEEDER PILLAR BOXES AND ALLIED WORKS AT SITE E AND NCHC AMADALLI UNDER GE(SEABIRD) KARWAR
2020_MES_376667_1
8735/E8
Open Tender
Civil Works
Item Rate
330 days
GE (Seabird) Karwar Naval Base Karwar
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE(Seabird) Karwar
₹70,000
Yes
19 Nov 2020
11 Sept 2020
12 Oct 2020
11 Sept 2020
9 Oct 2020
25 Sept 2020
Amount
Excavation in trenches not exceeding 1.5 m deep and not exceeding 1.5 m wide and getting out in hard/dense soil for all as specified and directed.
Returning filling in levelling, watering and well ramming in layers not exceeding 25 cm thick all as specified and directed.
Removal of surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point all as specified and directed.
M & L for sand filling in trenches above and below the cable as in cable protection. NOTE: Punned thickness only shall be measured and paid.
M & L for brick protection to cable using old size sub class 'B' bricks, laid flat, dry, butt jointed, laid length wise perpendicular to the axis of cable all as specified & directed.
Relaying of old serviceable bricks of any size removed from old cable trenches laid across trenches for cable protection all as specified and directed.
Supply and Laying in repairs LT UG cable 1100 Volts grade XLPE insulated PVC sheathed amoured, heavy duty, in trenches/ walls/ poles/ passing through pipes with multistranded aluminium conductor including lugs/ thimble/ ferrules connection, testing and commissioning complete including taking out old unserviceable cable for 16 sqmm 4 core. NOTE: (a) Earth work, excavation, sand cusioning, bricks for protection, GI pipe etc shall be measured separately under relevant items of this schedule. (b) Old retrieved LT cable found in serviceable condition from taking out shall be re-use/relaid in the work. (c) Item will only be operated/ executed in the condition of non availablity of sch 'B' stores with the department.
Description all as per Item No. 7.00 above but for 25 sqmm 4 core.
Description all as per Item No. 7.00 above but for 50 Sqmm 3.5 core.
Description all as per Item No. 7.00 above but for 70 sqmm 3.5 core.
Description all as per Item No. 7.00 above but for 95 sqmm 3.5 core.
Description all as per Item No. 7.00 above but for 120 sqmm 3.5 core.
M & L in repairs for straight through joints (epoxy) suitable for 3.5 core PVC insulated and PVC sheathed armoured LT underground cable with aluminium conductors including joint kits and labour complete for making joints all as specified and as directed for 3.5 core cable 25 Sq mm.
Description all as per Item No. 13.00 above but for 3.5 core cable 50 Sqmm.
Description all as per Item No. 13.00 above but for 3.5 core cable 70 to 150 Sqmm.
Description all as per Item No. 13.00 above but for 3.5 core cable 185 to 300 Sqmm.
Description all as per Item No. 13.00 above but for 3.5 core cable 400 Sqmm.
S & F in repairs MCCB 4 pole, 415 volts fixed overload & fixed short circuit setting including disconnecting the incoming/ outgoing cable connections and re-connecting with suitable aluminum lugs/ ferrules etc. after taking out the existing unserviceable and making good the disturbed surface for 100 Amps with breaking capacity 36 KA complete all as specified and directed.
Description all as per Item No. 18.00 herein above but for 125 Amps with breaking capacity 36 KA.
Description all as per Item No. 18.00 herein above but for 160 Amps with breaking capacity 36 KA.
Description all as per Item No. 18.00 herein above but for 200 Amps with breaking capacity 36 KA.
Description all as per Item No. 18.00 herein above but for 250 Amps with breaking capacity 36 KA.
Description all as per Item No. 18.00 herein above but for 315 Amps with breaking capacity 36 KA.
Description all as per Item No. 18.00 herein above but for 400 Amps with breaking capacity 36 KA.
Supply only in repairs the following items all as specified and directed:
Voltmeter digital type 0-500 Volts.
Ammeter digital type suitable to 0 - 100 Amps.
Aluminium lugs suitable for 25 sqmm to 50 sqmm cables.
Aluminium lugs suitable for 70 sqmm to 150 sqmm cables.
Aluminium lugs suitable for 150 to 300 sqmm cables.
Sheared rubber gasket suitable to LT panel board any description.
Indicator lamp LED type 'RYB'.
S & F in repairs GI tubing 'Light' grade with all fittings for cable protection fixed on poles/walls/laid under roads crossing etc and made good the disturbed surfaces/ area all as specified and directed for following sizes of pipes :-
50 mm bore.
80 mm bore.
100 mm bore.
Disconnecting all the electric connection and taking down old unserviceable Air Circuit Breaker (ACB) of any make/ description in any position from existing LT Panel and Supplying, installation, testing and commissioning of new LT Air Circuit Breaker TPN, 440 Volts, 50 Hz of capacity 1200 Amps, manual draw out type, having over current and fault protection complete fixed to existing LT Panel with all fixing arrangement as required at site complete all as specified and directed by Engr-in-Charge. MAKE: L&T or equivalent as approved by GE.
Description all as per item No. 28.00 above but Air circuit Breaker (ACB) Microprocessor based Trip Unit 440 volts, 3 Phase, 50 Hz, 800 Amps, Standard breaking capacity 500 V AC Ics.
M & L for preparation of the old deteriorated existing external and internal steel surfaces of feeder pillar boxes/ panels/ boards of any description and in any position including removal of disintegrated & deteriorated paint either by hand scrapping or by blow lamps, applying necessary filler coat and stopping as required and applying two coats of synthetic enamel paint (grey in color) with using spray machine over a coat of red oxide primer on old prepared surfaces complete all as specified and directed by Engineer-in-Charge. NOTE: Rates quoted by the contractor are deemed to include for writing the MES /SM No and other relevant details with paint in the pattern and style as approved by the Engineer-in-Charge.
M & L for earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6 mm buried directly in ground vertically to a depth not less than 4.50 meter below normal ground level (with top edge of earth plate not less than 3.25 meter below ground level) connected to GI strip 32 mm x 6 mm main earthing lead by means of galvanized bolts, nuts and washers all as shown in electrical plate no 5 of MES Schedule Part-I (1991) with connected to earth test point & to main switch board /panel etc. all as specified and testing on completion with and including necessary excavation and earth work in any type of soil, earth electrode, earthing lead from electrode to equipment/substation/panel etc, adequate quantity of charcoal dust and common salt, PCC (1:3:6) type C-1 (using 20 mm graded black trap/granite/Basalt stone aggregate) for earth pit with 40 x 40 x 6 mm mild steel angle iron frame for cover, pre cast RCC (1:2:4) type B-1 (using 20 mm graded black trap/granite/Basalt stone aggregate) 40 mm thick cover reinforced with 8 mm dia TMT bars 3 Nos both way with 12 mm dia round MS bar handle, GI light grade watering pipe 15 mm dia with funnel and wire mesh, and 40 mm dia GI light grade earth lead protection pipe, complete all as specified and directed. NOTE : Earth strip and its protection pipe upto and including 7.5 mtr only from the top of earth electrode are included under this item and additional earth strip/protection pipe etc. if any required at site shall be measured and paid for separately under appropriate item of Schedule `A’.
Description all as per item No. 31.00 above but using 4 mm dia GI earth wire complete.
S & F in repairs 32 mm x 6 mm ,GI earth strip all as specified and directed.
S & F in repairs 4.0 mm GI earth wire all as specified and directed.
M & L for testing of earthing carried out through earth testing instrument after disconnecting both end of the earthing strip or wire for LT Panels/MDSS panel/ DSS panel report should be submitted to Engineer-in-Charge all as specified and directed.
Laying only in repairs LT UG cable 1100 Volts grade XLPE insulated PVC sheathed amoured, heavy duty, in trenches/walls/poles/passing through pipes with multistranded aluminium conductor including lugs/thimble/ferules connection, testing and commissioning complete including taking out old unserviceable cable for 16 sqmm 4 core all as specified and directed. NOTE: (a) Earth work, excavation sand cusioning, bricks for protection, GI pipe etc shall be measured separately under relevant items of this schedule. (b) If old LT UG cable will found serviceable to be relaying the same.
Description all as per Item No. 36.00 above but for 25 sqmm 4 core.
Description all as per Item No. 36.00 above but for 50 Sqmm 3.50 core.
Description all as per Item No. 36.00 above but for 70 sqmm 3.50 core.
Description all as per Item No. 36.00 above but for 95 sqmm 3.50 core.
Description all as per Item No. 36.00 above but for 120 sqmm 3.50 core.
H S krishna Electricals
Raheel Enterprises
Bidder Name
Raheel Enterprises
BROTECH
H S krishna Electricals
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .