Creation of 100KVA substation alongwith HTLT network at Garar Khour and Augmentation of 100 KVA Sub station to 250 KVA at Krishna Nagar Nikkian Scheme code PDDSS2526100491 under UT Capex Budget falling under the jurisdiction of SD Jourian on Turnkey
2025_PDD_284056_1
ED-III/Jammu/26 of 2025-26
Open Tender
Electrical Works
Item Rate
45 days
Jurisdiction of Jourian
Please refer Tender documents.
7 documents required · 7 mandatory
₹1,000
Executive Engineer ED-III
₹62,000
6 Sept 2025
13 Aug 2025
4 Sept 2025
13 Aug 2025
3 Sept 2025
13 Aug 2025
Amount
Creation of 1x100 KVA Sub station at Garar Khour Providing/Supplying, Erection/Installation, Testing & commissioning comp Job)(Scheme Code PDDSS2526100491)
11/0.433 KV, 3 Phase 100 KVA Distribution Transformer with Bi-Mettalic Terminal Connectors (Energy Level-2) Aluminium wound with extremely fitted MCCB 200 amp with cable box and 4x4 mtrs. Suitable cable of ratings
Gapless Surge Arrester, 9 KV, 10 KA, Lightening Arrestor with Polymer housing Station Type
11 KV GO, AB Switch 3 Phase, 3 Pole, 200 amp, vertical type
11 KV Horn Gap Fuse Set 3 Phase, 200 amp
185 mm² Single core cable, 1.1KV Grade, PVC insulated stranded conductor FRLS type
ST Poles 9.0 Mtr long (ST -410 SP 33)
11 KV Polymeric Composite Disc Insulators 12KV, min following load 45 KN, Lightening impulse 75KV positive and 80KV negative, creepage distance 320mm with Fittings
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts & Bolts
Earthing of Sub-Station -Excavation of earth pitof diameter 650mm and deapth 3000mm, installation of earthing pipe of 40mm nominal bore and 4mm wall thickness and length 2.5m long as per IS 1239 GI Strip for neutral earthing of size 25mm into 3 mm for connection of transformer body, GO Set and lightening arrestor as per IS 2629/85, GI Nuts & Bolts, refilled with earth enhancement material
11 KV Polymeric composite Pin Insulators 12KV, 5KN,lighting inpulse 75KV positive and 80KV negative, creepage distance 320mm
Galvanized Stay Set with 50X8mm Stay clamp, Guy insulator (2 Nos), anchor plate (200X200X6mm) Nuts & Bolts, 2 nos turn buckles,1.8mm long, 16mm diameter solid GS stay rod and 7/3.15mm dia GI standard wire complete
Wedge connectors/PG Clamps
Danger Plates with Clamps
GI Barbed wire for Anti Climbing
Cement Bottoming 1:2:4 mix as per REC Standards 0.5cum/pole
Painting of Poles Red-Oxide
Painting of Poles Aluminium Paint
Sundry items like Aluminium Lugs, Jumpers, Binding Tape Aluminium Thimbles etc.
Laying of 0.80 KM 11KV line on 9 mtr PCC Poles using ACSR Weasel at Garar Khour (Scheme Code PDDSS2526100491) (Supplying, Installation, Testing & commissioning comp Job)
PCC Poles 9.0 Mtr long (WL:300Kg )
GI Channel X-arm including clamp and braces
ACSR weasel Conductor(30 mm²)
PG Clamps for 30 mm2 ACSR Conductor
11 KV Polymer composite Pin Insulators 12KV,5KN, Lighting impulse 75KV positive and 80KV negative, creepage distance 320mm
11 KV Polymeric Composite Disc Insulators 12KV, min following load 45 KN, Lightening impulse 75KV positive and 80KV negative, creepage distance 320mm with Fittings
Galvanized nuts & Bolts
Danger Plates with Clamps
Anti Climbing Device with Clamps
Earthing Complete by GI Pipe 40 mm or GI Rod 20 mm 2.5 mtr long through GI Strip
Stone Pad
Aluminium Jointing Sleeves
Galvanized Stay Set with 50X8mm Stay clamp, Guy insulator (2 Nos), anchor plate (200X200X6mm) Nuts & Bolts, 2 nos turn buckles,1.8mm long, 16mm diameter solid GS stay rod and 7/3.15mm dia GI standard wire complete
Erection of 1 no 11KV Tapping point for newly constructed sub station at Garar Khour (Scheme Code PDDSS2526100491) (Supplying, Installation, Testing & commissioning comp Job)
PCC Poles 9.0 Mtr long (WL:300Kg )
GI Channel/ Angle iron including clamp
11 KV GO, AB Switch 3 Phase, 3 Pole, 200 amp, vertical type (Providing, Erection, Testing and Commissioning.
30mm2 ACSR Weasel Conductor
PG Clamps for 30 mm2 ACSR Conductor
11 KV Polymer composite Pin Insulators 12KV,5KN, Lighting impulse 75KV positive and 80KV negative, creepage distance 320mm
11 KV Polymeric Composite Disc Insulators 12KV, min following load 45 KN, Lightening impulse 75KV positive and 80KV negative, creepage distance 320mm with Fittings (Providing, Erection, Testing and Commissioning.
Galvinized Nuts & Bolts
Danger Plates with Clamps
Anti Climbing Device with Clamps
Earthing Complete by GI Pipe 40 mm or GI Rod 20 mm 2.5 mtr long through GI Strip
Galvanized Stay Set with 50X8mm Stay clamp, Guy insulator (2 Nos), anchor plate (200X200X6mm) Nuts & Bolts, 2 nos turn buckles,1.8mm long, 16mm diameter solid GS stay rod and 7/3.15mm dia GI standard wire complete (Providing, Erection, Testing and Commissioning.
Stone Pad
Laying of 2.0Km. LT line ( 3 Phase 4 wire) on 8 meter PCC poles using ACSR weasel at Garar Khour (Scheme Code PDDSS2526100491) ( Providing/Supplying, Erection/Installation, Testing & commissioning comp Job)
PCC Poles 8.0 Mtr long (WL: 200 Kg)
GI U-Clamps for Shakle Insulators
ACSR Weasel conductor(30 mm²)
16 KN polymer shackle insulators
Galvanized nuts & Bolts
Danger Plates
Anti Climbing Device with Clamps
Earthing Complete by GI Pipe 40 mm or GI Rod 20 mm 2.5 mtr long through GI Strip
Stone Pad
Aluminium Jointing Sleeves
Galvanized Stay Set with 50X8mm Stay clamp, Guy insulator (2 Nos), anchor plate (200X200X6mm) Nuts & Bolts, 2 nos turn buckles,1.8mm long, 16mm diameter solid GS stay rod and 7/3.15mm dia GI standard wire complete
LT Line Spacers
Augmentation of 100 KVA Distribution Sub station to 250 KVA sub station at Krishna Nagar ( Nikkian) ( Scheme Code PDDSS2526100491)
11/0.433KV, 3 Phase 250KVA Distribution Transformer with Bi-MettalicTerminal Connectors ( Energy level-2) copper wound and with LV Cable Box having detachable Aluminium Gland plate
Transformer bed
LT Distribution Box for 250 KVA DTR with MCCB for incomer and switch Fuse units for outgoing circuits
Gapless Surge Arrester, 9 KV, 10 KA, Lightening Arrestor with Polymer housing Station Type
11KV GO , AB Switch 3 Phase, 3 Pole, 200 Amp, vertical type
11KV Horn Gap Fuse Set 3 Phase, 200 Amp
240mm2 Single core Cable, 11KV Grade PVC Insulated Stranded Conductor FRLS type
ST Poles 9.0 Mtr long (ST -410 SP 33)
Galvanised Nuts and bolts
Earthing of Sub-Station -Excavation of earth pitof diameter 650mm and deapth 3000mm, installation of earthing pipe of 40mm nominal bore and 4mm wall thickness and length 2.5m long as per IS 1239 GI Strip for neutral earthing of size 25mm into 3 mm for connection of transformer body, GO Set and lightening arrestor as per IS 2629/85, GI Nuts & Bolts, refilled with earth enhancement material
Danger Plates with Clamps
GI Barbed wire for Anti Climbing
Cement Bottoming 1:2:4 mix as per REC Standards 0.5cum/pole
Painting of Poles Red-Oxide
Painting of Poles Aluminium Paint
V K ELECTRICAL CONTRACTOR (BID ID -2472528)
VEENA CONSTRUCTION CO. (BID ID -2473290)
The Trikuta Engineer (BID ID -2447374)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .