Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance S 5 POST OFFICE BUILDING BATWARA SRINAGAR | SRINAGAR | SRINAGAR | JAMMU AND KASHMIR | 190004 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance DANDAMUDI ENCLAVE PETBASHEERABAD HYDERABAD 500067 | HYDERABAD | HYDERABAD | TELANGANA | 500067 | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
| 5 | Admitted-Finance | Admitted-Finance |
Tender Value
₹82.5 L
EMD Value
₹1.5 L
Closing Date
15 Oct 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE, HQ 133 WORKS ENGRS
HQ 133 WORKS ENGRS
PROVN OF 1500 KVA AUTOMATIC VOLTAGE REGULATOR AVR FOR HAWS GULMARG AND WITH ALLIED INFRA FOR URI STATION UNDER GE 969 EWS
2022_MES_552532_1
CWEK-42/2022-23
Open Tender
Electrical and Maintenance Works
Item Wise
180 days
GE 969 EWS
Class C Category b ii
7 documents required · 7 mandatory
₹1,000
GE 969 EWS
₹1.5 L
HQ 133 WORKS ENGRS
26 Oct 2022
16 Sept 2022
22 Oct 2022
16 Sept 2022
15 Oct 2022
1 Oct 2022
16 Sept 2022 - 22 Sept 2022
27 Sept 2022
Amount
Supply, installation, testing and commisioning of copper wound HT, AVR suitable for outdoor installation of capacity 1500 KVA, suitable dor HV input voltage range of 7 KV to 12 KV, HV output voltage 11 KV (+ or -) 1% with the following all standard fittings. such as silica gel breather, temperature gauge, Bucholz relay, WTI & OTI trip & alarm including by pass connections with all control cables of appropriate rating technical specifications of HT AVR. (Make: Electric Field Company / Powerware (SAI Electricals) / Indian Transformer and Electricals Pvt.Ltd (ITE Gurgaon)
(a) Ratings Rating KVA : 1500 KVA Number of phases & Frequency : 3 Ph 50 Hz Type of cooling ONAN Rated Voltage : 11 KV Input Voltage Range : 7 KV to 12 KV Input Current Range : 123.72 A to 72.17 A Output Voltage : 11 KV +1% Output Current : 78.73A Correction Rate: KV/Second : 50V/Sec Operating frequency : 50 HZ Duty Cycle : 100% Continuous Load Type of Load : More than 99% Guaranteed Over-all efficiency : 98.65% Winding : Electrolytic grade copper purity 99.08% IMPEDANCE : 1.95% (b) EFFICIENCY: AT FULL LOAD & 1.0 P.F & 75 deg C : 98.18% 3/4 : 98.47 % 1/2 : 98.66% 1/4 : 98.48% (c )TEMPERATURE RISE Ref. Ambient Degree C : 45 Oil by thermometer Degree C : 45 Winding by Resistance Degree C : 55 (d) INSULATION WITHSTAND Impulse (1.2x50 micro second wave) : 125KV Power Frequency (Dry & Wet) : 50KV for 1 Minute
4Nos Wheels Plain / Flanged /Bi-directional / Uni-directiona Explosion Vent diaphragm Silicagel Breather Valves (l) TERMINATION ARRANGEMENT H.V. SIDE (CABLE BOX) Auxiliary L.V. (Cable box) Disconnecting Chambers for HT Conservator with oil filling hole with cap & drain plug with extension of pipe. Detachable radiator with shut off valve Oil level gauge with 3 position Filter valve 25mmsize Air release valve Rating & terminal marking plate Weather proof Marshaling box with connection for above auxiliary protection with Lamp holder with Switch (m) Miscellaneous Test Required : Routine Test All routine test as per IS : 2026 Oil Pressure & Vacuum with stand test : 7 PSI Colour shade : D.A.Gary (n) GENERAL ARRANGEMENT: The unit consists of following :- (A) Stepdown Transformer- Double wound Delta/Star connected. (B) ‘ON’ Load Voltage Regulator, Auto wound Delta connected.
C) Buck-Boost Transformer, Double wound, open/open connected D) Automatic control gear consisting of :- One Electronic Voltage Relay, One Reversing Stepsyn type geared motor unit, Two limit switches in order to avoid overrunning highest and lowest positions, chain drive, coupling device and all electrical connection. (o) CONSTRUCTION: The Items (A), & (C) will be housed inside a well ventilated sheet steel tank and mounted on feet and items shall be supplied with first filing of oil, Fittings would include:- (i) Rating & Diagram Plate (ii) Silicagel breather (iii) Earthing Terminals (iv) Lifting lugs (v) Drain valve (vi) Air Release plug (vii) Oil Conservator with Oil level indicator (VIII) Filter valve (Ix) Pressure Relif Valve (x) W.T.I. & O.T.I. (xi) Buchholz Relay
(p) GENERAL FEATURES: ( I) HAND CONTROL: Hand wheel will be located on the front of the Regulator tank at convenient operative height. II) MOTOR CONTROL: Raise / Lower push button control by means of small single phase reversible geared motor of permanent capacitor type will be provided. Limit switches will be fitted to restrict the travel at extreme positions. With this arrangement, it would also be possible to provide remote control to the Regulating Unit. The reversible geared motor would be of ‘Step-Syn’ type. (III) AUTOMATIC CONTROL: For automatic correction of fluctuating supply voltage, we shall provide Electronic Relay which in its simpliest form, senses the Output Voltage and provide signal to the driving motor for necessary correction.
Supplying and laying un-reinforced precast concrete cable cover, class HVP, type 1 with peak, size 300mm x 180mm x 40mm complete all as specified and directed.
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 Sqmm complete all as specified and directed.
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185Sqmm complete all as specified and directed.
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sqmm to 300 Sqmm complete all as specified and directed.
Supply and laying in cable, XLPE insulated , screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) 11000 Volts grade with stranded aluminium conductor of size 3 Core 240 Sqmm, ISI marked complete, all as specified and as directed.
Supply and laying in cable, XLPE insulated , screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) 11000 Volts grade with stranded aluminium conductor of size 3 Core 120 Sqmm, ISI marked complete, all as specified and as directed.
Supply and laying in cable, XLPE insulated , screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 Core 95 Sqmm, ISI marked complete, all as specified and as directed.
Excavation in trenches in soft/loose soil not exceeding 1.5 mtr in width and not exceeding 1.5 mtr in depth for laying of cables up to proper level complete all as specified and directed by Engr-in-charge.
Returning, filling in including spreading, leveling, watering and well ramming in layers not exc 25 cm in soft/loose soil complete all as specified and directed by Engr-in-charge.
Removing surplus exacavated material from excavation not exc 50 meter and depositing where directed at a level not exc 1.5 meter above the starting point complete all as specified and directed.
Sand cushioning to underground cables 8 cm below the cable before laying and 15 cm above the cable after laying, complete all as specified in clause 19.75 of SSR Part-I. Note :- 1. Dry fine sand of best available quality shall be used. 2. Punned thickness shall be measured and paid.
M & L for Earthing complete with galvanised steel earth plate electrode 60x60cmx 6.3mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to copper strip 20x3mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel including PCC (concrete chamber) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate,with fair finish internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4,funnel with wire gauge of (0.68) 8 mesh per liner inch,80mm thick RCC pit cover 320 mmx320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM,JALLI and charcoal dust and common salt all as shown in electrical plate No.3 of MES SSR Part-1 and specified including provision of earth wire protected by 40 mm dia medium grade GI pipe and watering pipe shall be 20 mm bore medium graded GI pipe,and including all excavation and earth work & connecting the earthing to an earthing test point /transformer neutral/body/LT panel etc.and testing on completeion complete all as spec ified and directed. NOTE: The quoted rate of earthing shall be deemed to included cost of 7.5m long copper strip 20x3mm and protection pipe of 40 mm bore medium graded ,GI medium graded 20mm bore watering pipe
M&L for Construction of shed for suitable for 1500 KVA (AVR) including steps,plinth protection,cable duct complete all as specified and directed as shown on drawing NO CESZ/TD-1110/2011 sheet 1/2 and 2/2 Dated 01/12/2011
M/S Razdan Buildersand suppliers
Roy and Sons Infrastructers
M/S M.A. Construction
M/S KULBIR SINGH SODHI AND CO
ALCO ENGINEERSPVT LTD
KR POWER INFRA INDIA PVT LTD.
Rajindera Enterprises
CHINAR CONSTRUCTION TRADERS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .