Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
Refer Docs
EMD Value
₹50.5 L
Closing Date
12 Jan 2026, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Superintending Engineer
Office of the SE, CC, UPJNU, Prayagraj.
Augmentation of Chopan Nagar Panchayat Water Supply Scheme Dist. Sonbhadra
2025_UPJNM_1098553_1
883/AMRUT 2.0/361 dt. 10.12.2025
Open Tender
Civil Works
Percentage
NP CHOPAN
Please refer Tender documents.
3 documents required · 3 mandatory
₹23,600
EE, CD, UPJNU, Mirzapur
₹50.5 L
office of the SE, CC, UPJNU, Prayagraj.
28 Mar 2026
15 Dec 2025
13 Jan 2026
15 Dec 2025
12 Jan 2026
15 Dec 2025
23 Dec 2025
Provision for Crossing and laying of RISING MAINS pipe line of both side at State/National Highway and payment to UPSHA/PWD for permission of National/State Highway crossing:- Survey site Investigation Planning , design Drawings, excavation, dismentaling, road restoration & other all utility restoration( as per required) as per NATIONAL HIGHWAY standard as per MORTH Road manual and vetting / checked from State Road/ NH DIV. PWD/NHAI/UPSHA/ PWD/ Divisional Office and taking NOC CHARGES.(incl. noc fees, licence fees, security amount) for trenchless crossing of National highway road , Road for required dia Rising main pipe with casing pipe as required for proper completion of work also including security money deposited to State Road department and Execution of all work in the present of State Road staff / Engineers including of supply of required dia MS carrier pipe and required size of MS casing pipe as per drawing and as per (IS:3589 & made from confining to IS:2062) with 750 Micron th. food grade coating internally and 750 TH. MICRONE anti corrosive bituminous paint externally by trenchless technology method at an average depth 3.60 mtr from normal ground level up to top of casing pipe including dismentalling , restoration ,excavation & sand filling of Pit, Dewatering arrangement, Supporting system for soil, also including supply and fixing of 2 no Sluice valve ISI Mark, construction of sluice valve chamber with heavy duty MS cover etc. all complete work including supply & fixing specials in carrier pipe over main pipe, as per specification given in the bid documents including supply of all materials, labour T&P etc. for proper completion of work as per instruction of Engineer. and concerned department. (CASING- 600MM (id) MS PIPE 12 MM THICK & CARRIER PIPE (8mm th.)- AS PER REQUIRED DESIGN) INCL.3M C/C SPACER
Construction of electric power sub-station room- Survey, Planning,engineering,Drawing/ Design, vetting of drawing/ design from IIT ,Investigation, Soil Testing, Planning, Designing, Construction of electric power sub-station room (8.00m X 5.00m X 4.00m) of required size. Construction of RCC frame structure room including excavation of soil i.e. Kankar mixed morrom/soft/hard rock, PCC for bedding in lean concrete of minimum grade of M-15, R.C.C. in grade M-25 or above in footing, foundation, plinth beam, column, lintel beam, chajja, roof slab, brick work in CM 1:4 (1 cement & 4 sand) in walling, Internal plaster 12 mm thick for walls & celling in CM 1:4 (1 cement & 4 Sand), External plaster 20 mm thick in CM 1:4 (1 cement & 4 sand), providing laying hand cut polished kota stone flooring 25 mm to 30 mm thick on bed of CM 1:4 (1 cement & 4 sand) including cement float, filling jointing with neat cement slurry, curing polishing and cleaning, providing cable duct of required size, including fixing of rolling shutter, aluminium windows & ventilator with glass panels as per specifications, providing and applying white washing in two coat to new plaster surface, internal two coat snowcem painting including priming coat, external painting with apex ultima/equivalent paint including priming, painting over new iron work with one coat of primer and two coat oil paint of approved make including cost of all arrangement of shuttering, scaffolding including all materials, labours T&P etc. for proper completion of works as per direction of the Engineer. At Zone 1. FFL above 60 cm nearest road level.
PUMP HOUSE - Survey, Investigation, Planning, Designing, Construction, Commissioning of Pump houes of required size to accommodate required nos of pumps. For the construction of Pump House above CWR, minimum 6 m height is to be kept with suitable arrangements to install and dismantle VT/HSC pumps and installation of Fire Extinguishers, Power wiring & earthling system, rubber resistance sheets, spares for motors & switchgear, internal & external electrifications and adequate LED lighting, 23 cm. thick brickwork 1:4 (one cement and four sand), plasterwork 1:4 (one cement and coarse sand). Steel and cement to be used as per approved by Engineer-in charge / IS code. Reinforced Cement Concrete minimum M-25 to be used including fixing of doors, windows, shutters, glass panels with gantry girder arrangement with supply and fixing of suitable sizes of steel girder including snowcem painting two coat over one priming coat using approved Colour and shade and whitewashing three coat of ceiling of pump house and painting over new ironwork with one coat of primer and two coat of approved paint including cost of all arrangement of staircase, balcony with medium G.I pipe 20 mm size three row railing, shuttering, scaffolding and water with supply of all materials, labours T&P etc. required for proper completion of works as per direction of the Engineer. FFL above 60 cm nearest road level.
Construction of LCS Room size of 6m x 4m x 4m including Supply all materials, labours T&P etc. all complete work including Excavation, PCC(M-15), RCC(M-25), Brick work(1:4), plaster(1:3), painting, door window, collapsible steel shutters, electric wayring etc. all complete work. Cement and steel should be as per approved by the Employer/IS code. Collapsible MS steel doors and aluminium windows to be provided including of three-coat whitewashing, internal two coat putty with acrylic painting, external painting with apex ultima/equivalent paint, all steelwork must be painted with red oxide paint and two coat of anticorrosive paint etc. and internal and external electrification with adequate LED lights for the compound. FFL above 60 cm nearest road level.
DISTRIBUTIONS SYSTEM :- Supply of following sizes (D.I.) pipes for rising main system confo
Supply , carting, laying, jointing & fixing in pipe of following size of CI D/F SLUICE VALVES IS-780-1960 tested to 16Kg / Cm2f trenches, jointing and testing etc. complete.
In Ordinary soil
In Moorum /Kankar / Shingle etc. (with replace loose soil)
In Soft/Medium rock. (with replace loose soil)
Supply of all materials, labours T&P etc. and construction of masonary type sluice valve chamber. With extra heavy duty MS cover.
Thrust Block
Supply of all materials,labour, and T & P etc. and construct R.C.C.(M-25 grade) thrust blocks. Including mild steel (1%)works all complete as per design for following size and instructions of Engineer ‐in ‐ charge.
350 mm (size 1.25m x 1.25m x 1.25m)
300 mm (size 1.15m x 1.15m x 1.15m)
200 mm (size 0.85m x 0.85m x 0.85m)
150 mm (size 0.70m x 0.70m x 0.70m)
Dismantling of following type of road surface including stacking of serviciable material and disposal of unservicable material within the limit of npp upto 8km distance including supply of all labour T&P etc. required for proper completion of the work as per instructions of Engineer ‐in ‐charge.
Bituminous Road
C.C. Road
Interlocking Road
Re-instatement of following type of road surface of PWD/ UPJN specifications including supply of all materials, labour, T&P etc. required for proper completion of the work as per instructions of Engineer ‐in ‐charge.
Bituminous surface (20cm sand, 20cm GSB, 20cm WMM, 5 cm to 8 cm DBM, 3cm to 4 cm B.C.) payment made upto WMM- 50%, DBM- 30% and BC with testing in NABL aprooved lab/PWD- 20%
C.C. Road in M25 grade, minimum thickness 15cm on 15cm sand & 20cm GSB filling base.
Interlocking Road (50% new Interlocking bricks M-30 grade, 80 mm thick on 10cm sand & 10cm GSB filling base)
Providing and laying of GSB for reinstatement of earthen road (Shoulder) including dressing, watering, ramming etc. complete.
Rising Main :- Supply of following sizes (DI K-
Rising Main :- Supply of following sizes (DI K-
For Zone-1 (1350 KL/22 m stagging)
For Zone-4 (450 KL/22 m stagging)
Supply of all materials labour T&P etc. for complete construction of R.C.C. (M30 Grade) Over Head Tank of following capatity and staging min 1m above ground level with main components, soil testing and assuming bearing capacity of soil as 8MT including cost of supply of design and drawings. all the water
Repair of RCC Over Head Tank 350 KL/16 m Staging and allied works in water campus including Providing and fixing double scaffolding system (cup lock type) on the exterior side of OHT, upto 25 metre height, above ground level, including additional rows of scaffolding in stepped manner as per requirement of site, For sealing cracks and faulty construction joints, routed out/making U-shape groove size 25x25mm and then primed the area with integral crystalline slurry @ 0.05kg/running metre and while the suface is tacky filled the groove up to surface with crystalline mortar @1.50kg/running metre. Once crystalline mortar is touch dry then finally applied two coats of integral crystalline slurry @1.50kg/running metre. 18 mm cement plaster in two coats under layer 12 mm thickcement plaster 1:5 finished with a top layer 6mm thick cementplaster 1:6. Providing and injecting approved grout (OHT tank body) in proportion recommended by the manufacturer into cracks/honey-comb area of concrete/ masonry by suitable gun/pump at required pressure including cutting of nipples after curing etc. complete as per directions of Engineer-inCharge. Stirrer mixed Acrylic Polymer of approved make @ 2% of weight of cement used) modified Cement slurry made with non shrink compound in concrete/RCC work. Stirrer mixed SBR Polymer (of approved make) modified Cement slurry made with Shrinkage Compensating Cement in concrete/RCC work. Epoxy injection grout in concrete/RCC work of approved make. Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures. For vertical surface one coat @1.40 kg per sqm., Cone wall, wall inner, column inner, For horizontal surface one coat @1.10 kg per sqm for Bottom Dom including repairing of MS ladder, 1 m vide RCC balcony, railing, ventilater of top Dome, Water Lever Indicator, CI Mainhole., Sluice valve and Construction of S.V. Chamber, Cleaning of OHT and Removing dry or oil bound distemper, water proofing cement paint and the like by scrapping, sand papering and preparing the surface smooth including necessary repairs to scratches etc. complete., Finishing of all Wall/concrete surface in two coat premium acrylic smooth exterior paint with silicon addive, with one coat of exterior primer over smooth base of white cement. cement based wall putty and steel pipe works with three coats of approved cement paint and anticorrosive paints.,foodgrade epoxy painting internal part of water containe with 3 coat, Painting of all m.s./ steel pipe works with three coats of approved cement paint and anticorrosive paints and disposal of water from overflow and washout chamber to suitable point outside the water works compound, painting of all concrete surface and steel pipe works with three coats.
retaining components of OHT shall be casted in M-30 grade cement concrete and minimum grade of concrete of foundation and staging should be M-25 with approved cement, coarse sand and stone grit as per I.S. 11682 and I.S. 456 seismic effects and wind load should be taken into consideration as per I.S. 1893 for earthquake resistance and I.S. 875 Part-III for wind load on structure and including 1M wide RCC doglegged staircase with separate columns, 1m wide R.C.C. M30 balcony, M.S. ladder made of 50x50x6mm angle section and 20mm plain M.S. bars with hand rails of 20mm medium class G.I. pipes, one aluminum ladder inside the tank from top dome to bottom dome, R.C.C. railling with 20mm dia medium class G.I.pipe (in 3 rows) on both sides of stair case, supported on 50x50x6mm M.S. angle section, spaced at intervals not more than 1.5m, proper ventilator at top dome in circular shape of 1.5m dia, Ultra Sonic Water Level Indicator fabricated with sensor connecting to automation, lightening conductor as per I.S.S. 2309 or its latest amendments of latest electricity rules, consisting of proper elecation rod with 5 or more fork points as prescribed in ISS 2309-1969 and ISS 3013-1966 C.I. manhole of min 60x60cm size with locking arrangement, supply, fixing, jointing of D.I.D/F Pipes of appropriate size with D.I.D/F specials conforming to IS 8329/2000 as vertical pipes for all required no of inlet (200mm OR as designed), all required no of outlet (250mm or as designed for each DMA), overflow and washout as per latest/relevant I.S. specification with all jointing materials for proper completion of work along with NRV Sluice valves with actuators construction of bed blocks in 1:2:4 PCC with cement, coarse sand and approved stone grit, construction of inlet, outlet, washout, overflow chamber with extra heavy duty MS cover and chambers for sluice / butter fly valves as per departmental type design and drawings, supply of 300mm dia DI K-7 pipe as per I.S.-4985/2000 for disposal of water from overflow and washout chamber to suitable point outside the water works compound, painting of all concrete surface and steel pipe works with three coats. For bidding purpose, bearing capacity of soil shall be considered as 8 t/sqm. working design shall be based on the SBC determind after soil investigation /8 tonne/sqm including requird earthfilling for maintaining FGL as per level of nearest road cost of earth required for filling not to be paid extra. Note :- The bid price of over head tanks is to be submitted considering net safe allowable bearing capacity as 8 t/m2, keeping the minimum foundation depth to be 2.5 m below existing ground level at the site of work, layout as ground level of over head tank consider from 100 cm above than near of road surface to be finalized by the engineer in charge including, campus cleaning, removal of debries, bush cutting and disposal with in municipal limt and filling ogf earth if required as per direction of Engineer in charge. The successful bidder will be required to investigate the soil bearing capacity. If not safe allowable bearing capacity is found to be equivalent or more than 8 t/m2, the design of OHT will be based on 8 t/m2 capacity. However in case the net safe allowable bearing capacity is found to be below 8 t/m2, then the design of OHT will be based on the actual bearing capacity.
Making House Connection should be done from distribution pipe line to outer wall of house or 2.0 m inside the boundary wall with provision of tap including supply of 7.0 m HDPE Pipe(is code 4984 with latest amendments) 20mm dia, PN- 12.5, PE-100, SDR-11 (0.6m depth below ground level), and 4.0m 15mm dia (ID) G.I. Pipe, Class-B and keeping the G.I. pipe atleast 1.0m in height above the G.L. as per department type design and Drowing including supply of specials, saddle, clamps etc. of suitable size, ISI mark 6mm BRASS FERRULE conforming to latest/relevant I.S. 2692/1989 or their latest amendments, Heavy BRASS Tap, all Materials, labours, T&P etc. complete, Dismentelling of all type of road surface, breaking of all type of floor, wall, and disposal of unserviceable materials up to 8km. Excavation pit/trench, cutting of pipe, Bailing out of water, carting and lowering them unto the already prepared trenches, fixing in position and jointing them with pipelines and testing etc, Grounting by CC 150mm x 150mm x 150mm size in M20, Restoration of pit, trench/Road (as site condition NON PAVED, BOE, CC, INTERLOCKING BRICKS, Bituminous road, RAMP, DRAIN, WALL, FLOOR etc.) as per PWD/UPJN SPECIFICATION and 3 nos GPS location colour photographs submitted after complition of work. Also including GIS Based Survey to collect all required data in projected area Nagar Panchayat Chopan for proper complition of work as per drawing and. As per Instruction of Engineer in charge as per drawing. Payment make after completion of work up to household 70%, RETORATION & GROUTTING-10% and 10% submitted of photographs after Testing and Commisioning,5%after GIS based all collected required data and 3 NOS GPS using colour photographs & geo tagging on google maps - 5% after handover to NP Chopan of all remaining work.
DI pipe Class K-7 (IS-8329/2000)
rming to latest/relevant I.S. 8329/2000 Specifications with all jointing materials such as MJ joints, tee ,bends, all required mild steel fabrication works (if MS fabrication used, its proper protection treatment against corossion must be done) and all DI specials conforming to latest /relevant I.S. specifications, suitable for D.I pipes, as per IS‐1239 /2000 and IS 8329/2000 or their latest amendment & CPHEEO latest amendments including F.O.R. destinations rate per metre in Rs., anywhere in U.P. including cost of SBR Rubber Gasket per pipe length & iniclusive of all Taxes & Duties, Third Party Inspection Charges, Packing & Forwarding Charges, Transit Insurance Charges, Road Transportation Charges etc. with loading, unloading and Carting up to store,HYDRAULIC TESTING AS PER CPHEEO MANUALS latest amendments also including specials, carting, laying & jointing in proper trench for these pipes all complete as per instructions of Engineer ‐in ‐ charge. Note- Only SBR Rubber Gaskets to be used as per IS- 5382 and IS- 12820.
Supply of all types of materials and construct following chambers with extra heavy duty ms cover grade-35as per type design with supply of all labour, T&P etc. completed.
Provision for NALLA/CULVERT CROSSING from250mm to 350MM DIA PIPE CROSSING including all material, for casing etc. all complete work. With concreting thrust block M20 grade using inlcuding supply of DI K-9 Pipe and laying with MS Fabrication and DI Specals.
Shifting of Utility as a water supply pipe line, sewer line, drainage pipe,brick drainage nali,Telephone line/pole, Electric pole/ cable, tree cutting etc. all complete work including all material, Labour, T&P etc for whole project. (all overhead / underground utility)
Crossing of Road Laying of pipe line 8mm thick MS carrier pipe 200mm to 300mm dia and 12 mm thick MS Casing pipe 600 mm dia by trenchless technology (Auger Boring Method) For highway. Provision for Crossing and laying of pipe line of both side at State/National Highway and payment to state/NHAI Authority for permission of National Highway crossing:- Survey site Investigation Planning , design Drawings, excavation, dismentaling, road restoration & other all utility restoration( as per required) as per NATIONAL HIGHWAY standard as per MORTH Road manual and vetting / checked from State Road/ NH DIV. PWD/NHAI/UPSHA/ PWD/ Divisional Office and taking all NOC CHARGES.(incl. noc fees, licence fees, security amount) for trenchless crossing of National highway road , Road for required dia Rising main pipe with casing pipe as required for proper completion of work also including security money deposited to State Road department and Execution of all work in the present of State Road staff / Engineers including supply of required dia MS carrier pipe and required size of MS casing pipe as per drawing and as per (IS:3589 & made from confining to IS:2062) with 750 Micron th. food grade coating internally and 750 TH. MICRONE anti corrosive bituminous paint externally by trenchless technology method at an average depth 3.60 mtr from normal ground level up to top of casing pipe including excavation & sand filling of Pit, Dewatering arrangement, Supporting system for soil, also including supply and fixing of 2 no Sluice valve ISI Mark, construction of sluice valve chamber etc. all complete work including supply & fixing specials in carrier pipe over main pipe, as per specification given in the bid documents including supply of all materials, labour T&P etc. for proper completion of work as per instruction of Engineer. and concerned department. (CASING- 600MM (id) MS PIPE 12 MM THICK & CARRIER PIPE- AS PER REQUIRED DESIGN) INCL.3M C/C SPACER
In Ordinary Soil
In Moorum /Kankar / Shingle etc & incl. replace of ordinary soil.
In Soft/Medium rock. & incl. replace of ordinary soil.
Supply of following types of fittings including railway freight, cartage from store to site of work,lowering, carting, fixing , jointing all taxes and duties etc. complete. CI D/F Sluice Valves, Scour Valve Class-I as per IS 780 (1969) & CPHEEO MANUALS latest amendments suitable for a working pressure of 16 Kg / Sq.Cm. (using without galendori valves)
rming to latest/relevant I.S. 8329/2000 Specifications with all jointing materials such as MJ joints, tee ,bends, all required mild steel fabrication works (if MS fabrication used, its proper protection treatment against corossion must be done) and all DI specials conforming to latest /relevant I.S. specifications, suitable for D.I pipes, as per IS‐1239 /2000 and IS 8329/2000 or their latest amendment & CPHEEO latest amendments including F.O.R. destinations rate per metre in Rs., anywhere in U.P. including cost of SBR Rubber Gasket per pipe length & iniclusive of all Taxes & Duties, Third Party Inspection Charges, Packing & Forwarding Charges, Transit Insurance Charges, Road Transportation Charges etc. with loading, unloading and Carting up to store,HYDRAULIC TESTING AS PER CPHEEO MANUALS latest amendments also including specials, carting, laying & jointing in proper trench for these pipes all complete as per instructions of Engineer ‐in ‐ charge. Note- Only SBR Rubber Gaskets to be used as per IS- 5382 and IS- 12820.
Supply of all types of materials and construct following chambers with extra heavy duty ms cover grade-35as per type design with supply of all labour, T&P etc. completed.
Provision for NALLA/CULVERT CROSSING from250mm to 350MM DIA PIPE CROSSING including all material, for casing etc. all complete work. With concreting thrust block M20 grade using inlcuding supply of DI K-9 Pipe and laying with MS Fabrication and DI Specals.
Shifting of Utility as a water supply pipe line, sewer line, drainage pipe,brick drainage nali,Telephone line/pole, Electric pole/ cable, tree cutting etc. all complete work including all material, Labour, T&P etc for whole project. (all overhead / underground utility)
Crossing of Road Laying of pipe line 8mm thick MS carrier pipe 200mm to 300mm dia and 12 mm thick MS Casing pipe 600 mm dia by trenchless technology (Auger Boring Method) For highway. Provision for Crossing and laying of pipe line of both side at State/National Highway and payment to state/NHAI Authority for permission of National Highway crossing:- Survey site Investigation Planning , design Drawings, excavation, dismentaling, road restoration & other all utility restoration( as per required) as per NATIONAL HIGHWAY standard as per MORTH Road manual and vetting / checked from State Road/ NH DIV. PWD/NHAI/UPSHA/ PWD/ Divisional Office and taking all NOC CHARGES.(incl. noc fees, licence fees, security amount) for trenchless crossing of National highway road , Road for required dia Rising main pipe with casing pipe as required for proper completion of work also including security money deposited to State Road department and Execution of all work in the present of State Road staff / Engineers including supply of required dia MS carrier pipe and required size of MS casing pipe as per drawing and as per (IS:3589 & made from confining to IS:2062) with 750 Micron th. food grade coating internally and 750 TH. MICRONE anti corrosive bituminous paint externally by trenchless technology method at an average depth 3.60 mtr from normal ground level up to top of casing pipe including excavation & sand filling of Pit, Dewatering arrangement, Supporting system for soil, also including supply and fixing of 2 no Sluice valve ISI Mark, construction of sluice valve chamber etc. all complete work including supply & fixing specials in carrier pipe over main pipe, as per specification given in the bid documents including supply of all materials, labour T&P etc. for proper completion of work as per instruction of Engineer. and concerned department. (CASING- 600MM (id) MS PIPE 12 MM THICK & CARRIER PIPE- AS PER REQUIRED DESIGN) INCL.3M C/C SPACER
Scour Valve 100mm dia
Fire Hydrant 80mm Dia
Air Valve 25mm Dia
Construction of 1.8 m high and 115mm thick boundary wall ( Zone-1 , Zone-4) with 230 mmx 230 mm RCC BEAM, 230 mmx230 mm thick pillar, 50*50*6mm size MS angle FIXING IN RCC PILLAR with 3 Layer barbed bars made in RCC in 1:1.5:3 the spacing between two pillar should not be more than 2.0 m c/c and depth of rcc footing (1.2*1.2*.3)m not less than 1.2m , and the depth of foundation should not be less than 0.60m below N.G.L. and plinth height should be kept 0.60m above nearest road level, Brick Work in 1:4 and 12mm thick plaster with cement and coarse sand in the ratio of 1:4, painting with weatherproof approved paint, at the site of water works as per departmental type design and drawing, as per specifications given in the bid document and pwd/upjn, including supply of all materials, labour T&P etc.for proper completion of the all work as per instructions of Engineer ‐in ‐ charge.
S.V. Chamber (Surface Box Type)
S.V. Chamber (Masonary Type)
Air Valve Chamber
Fire Hydrant Chamber
Dismantling of following type of road surface including stacking of serviciable material and disposal of unsericeable material within the limit of npp upto 8km distance including supply of all labour T&P etc. required for proper completion of the work as per instructions of Engineer ‐in ‐charge.
Bituminous Road
C.C. Road
Interlocking Road
Re-instatement of following type of road surface of PWD/ UPJN specifications including supply of all materials, labour, T&P etc. required for proper completion of the work as per instructions of Engineer ‐in ‐charge.
Bituminous surface (20cm sand, 20cm GSB, 20cm WMM, 5 cm to 8 cm DBM, 3cm to 4 cm B.C.) payment made upto WMM- 50%, DBM- 30% and BC with testing in NABL aprooved lab/PWD- 20%
C.C. Road in M25 grade, minimum thickness 15cm on 15cm sand & 20cm GSB filling base.
Interlocking Road (50% new Interlocking bricks M-30 grade, 80 mm thick on 10cm sand & 10cm GSB filling base)
Providing and laying of GSB for reinstatement of earthen road (Shoulder) including dressing, watering, ramming etc. complete.
Construction of RCC Common CWR 925 KL under Zone-1 for Water Demand of Zone-1/2/3 & 4 - Survey, Investigation, Soil Testing, Planning, Designing, Construction, Commissioning of CWR of 925 KL. The Concrete in a minimum grade of M-30 and steel to be used as per IS code and approved by Employer. Seismic effects and wind load with earthquake resistance should be taken into account in the design. CWR should be provided with a ventilator, manhole of adequate size. An aluminium ladder minimum of 0.45 m wide in manhole should be provided. Ultrasonic water level indicator should be provided along with lighting conductor as per IS 2309. PCC of M-10 grade to be used in bed blocks. Inlet, Outlet, washout, desilting and Overflow arrangement with the supply & installation of pressure pipe of the suitable dia, for taking overflow water to a suitable low lying area. Painting of all steel and concrete pipes with 3 coats of approved cement plaster and 3 coat food grade epoxy & anticorrosive paint including all labour, material, T & P etc., all required for proper completion of works as per the direction of the Engineer.
Rising Main :- Supply of following sizes (DI K-
THRUST BLOCK
Supply of all materials,labour, and T & P etc. and construct R.C.C.(M-25 grade) thrust blocks. Including mild steel works(1% ) all complete as per design for following size and instructions of Engineer ‐in ‐ charge.
80mm ( Size 0.45m x 0.45m x 0.45m)
100mm ( Size 0.55m x 0.55m x 0.55m)
125mm ( Size 0.60m x 0.60m x 0.60m)
150mm ( Size 0.70m x 0.70m x 0.70m)
200mm ( Size 0.85m x 0.85m x 0.85m)
250mm ( Size 1.00m x 1.00m x 1.00m)
Provision for NALLA/CULVERT CROSSING UP TO 200MM DIA PIPE CROSSING including all material, for casing
etc. all complete work. With concreting thrust block M20 grade using inlcuding supply of DI K-9 Pipe and laying with MS Fabrication and DI Specals.
Crossing of Railway Line Laying of pipe line 8mm thick MS carrier pipe 200mm to 300mm dia and 12 mm thick MS Casing pipe 600 mm dia by trenchless technology (Auger Boring Method) For Railway. Provision for Railway Crossing:- Survey site Investigation, Planning , design Drawings as per Railway Divisional Office and taking NOC & permission with all fee/ security/ liecence fee/ for NOC from RBCS PORTAL for trenchless crossing of Railway track, required dia DISTRIBUTION main pipe with casing pipe ( 600 MM DIA (ID) MS PIPE TH. 12MM) as required for proper completion of work also including security money deposited to Railway department and Execution of all work in the present of Railway staff / Engineers including of supply of required dia MS carrier pipe and required size of MS casing pipe as per drawing and as per (IS:3589 & made from confining to IS:2062) with min 750 microne th. foodgrade epoxy coating internally & anti corrosive bituminous paint externally by trenchless technology method at an average depth 5.00 mtr. from normal ground level up to top of casing pipe including excavation &sand filling & restoration of Pit, Dewatering arrangement, Supporting system for soil, also including supply and fixing of 2 no Sluice valve ISI Mark, construction of sluice valve chamber with frame extra heavy duty MS cover etc. all complete work including supply & fixing specials in carrier pipe over main pipe, as per specification given in the bid documents including supply of all materials, labour T&P etc. for proper completion of work as per instruction of Engineer. all works excution as per guidlines of ministry of RAILWAY (CASING- 600MM (id) MS PIPE 12 MM THICK & CARRIER PIPE (8mm th.)- AS PER REQUIRED DESIGN) INCL.3M C/C SPACER
Dismantling joint 200 mm dia or suitable size for common header - 1 No.Reflex valve 200mm dia or suitable size 1 No.
New Connections with New pipe line.
Shifting of Existing House Connection from Old Pipe line to New Pipe Line
Supply and fixing of 3.6 m x 1.80 m MS gate including fabrication and supply of steel and construction of RCC pillars of size 1.8m x 0.23m x 0.23m in M25 grade with ornamental brick work 115mm thick around RCC pillers with elctrification and lighting arrangement, brick work in foundation 1:4 cement & fine sand upto plinth, as per departmental type design and drawing and as per specifications of pwd/upjn and laid down in the bid document, including supply of all material, labour,T&P etc.required for proper completion of the work as per instructions of Engineer‐in‐charge.
MS Gate (size 3.60 m X 1.80 m) minimum weight 1.60 Qtl
MS Wicket gate (size 1.20 m X 1.80 m) minimum weight 0.50 Qtl
Provision for arboriculture/ greeneries/ plantation for development of water works, including earth filling ( REQUIRED all nonusing area) with pipe sprinkling arrengments. For ZONAL WATER WORKS
Construction of Cement Concrete USING 20 CM TH. M25 grade using concrete type & 30 cm GSB BASE approach road including supply of all materials, labour, tools and plants etc. complete.
Supply and Construction of roof top rain water & ground water harvesting system including all required materials, labour, tools and plants etc. complete. (150 MM DIA PVE PIPE PN6 boring depth 2nd layer strata)
PUMPING PLANT AT INTAKE WELL Supply of vertical turbine oil lubricated raw water pump set along with V.H.S. squairal cage induction motor with shaft, 30 meter column pipe, (tentative it will be decided as per site required) thrust bearing, motor stool foundation bolt etc. suitable to operate 415 volt, 3 phase, 50Hz, AC Supply (2 W+ 1 S). LPM - 2350 Head-35 M with all other accessories complete in all respect.
CE/UL certified PLC/RTU with redundant CPU and power supply in IP 54 enclosure suitable to communicate with GSM based modem unit with redundant CPU and power supply with analog /digital parameter and features as specified for each zps/oht to store and trasmitt data on GSM backbone , RTU/PLC designed with logic to transfer data at multiple station specified in tender document
GSM/GPRS based wireless communication system for RTU capable to transfer and gather data from remote sites to control stations. All accessories included with signal enhancer, antennan etc.
Intelegent Energy meter with memory RTC and 2 serial parts integrated with RTU
Motor operated sluice valve with actuator complete in all respect
Electric motor operated sluice valve 200mm dia or suitable size along with actuator for delivery pipe of pump.
Electric motor operated sluice valve 250mm or suitable size dia along with actuator for common header.
Auto phase reversal unit suitable with inbuilt time delay & enclose of 100 Amp or suitable rating.
Radar type level with RTU communication at Intakewell.
Pressure Transmitter with manual pressure gauge at common header for each pump - 4 Nos
Isolation transformer & surge arrestor.
CE/UL certifiedd 7 inch HMI touch screen suitable to communication with PLC/RTU for local display and control.
Control cabling for intake well including all power and control cable for all equipment (1.5sq mm, 10cx1sq mm, 2cx1sq mm other required items for pump set.
Security serveilliance camera IP with recorder
ELECTRO MAGNETIC FLOW METER
Provision of Electro magnetic flow meter suitable to measure the water discharge and to be fitted in common header of 250mm dia. Or suitable size
FLOW SENSOR
Type - Pulsed DC
End connection- Flanged of Carbon steel
Flange rating - PN 16 size 250 mm./ suitable size
Electrode - SS 316
Lining Material - Hard rubber
Protection category - IP 68
Measuring Accuracy- + 5% of measured
Valve inclusive of linearity repeatability pressure effect and Hystrusues between 1 to 3 meter per second.
Sensor Housing - SS 304 with fully welded construction
Connection/ Junction Box - SS 304
Earthing only grounding rings required
FLOW TANSMITTER CONVERTOR
Type - Micro processor based modular desing
Display - 3 line back lit LDC for indication of actual flow rate forward reverse sum totolizer.
Protection category - IP 65
Enclosure - DI - Cast Aluminium with poly urethan with glass window.
Programming- Through three key pad as front facia.
Power Supply - 230 volt 50 HZ AC
Cable Gland - ½ NPT
Mounting - Wall mounted
Maximum Sepration - Upto 300 m between sensor and transmeter without any signal boosters.
Terminals - shock-Hazard-protected push lock terminal.
Error Indetification : 0.3, 6/22 MA
Flow Indicator Totalizer - 3½ digit IED display with 6 digit electro mechanical Totalizer.
MAIN PIPING & VALVES INCLUDING COMMON HEADER :-
Size of Delivery of pump 200mm dia length or as per site requirement
Size of Common header of 250mm dia. Length or as per site requirement
Supply of following
CI D/F Reflux Valve 200 mm dia or suitable size -3 Nos.
CI D/F Tee 250x250x200 mm dia or suitable size. -3 Nos.
D/F distance piece 200 mm dia. or suitable size 1.00 m. long - 3 Nos.
D/F distance piece 250 mm dia or suitable size . 1.50 m. long - 3 Nos.
D/F distance piece 250 mm dia or suitable size 3.00 m. long - 3 Nos.
Dismantling joint 200 mm dia or suitable size - 3 Nos.
Dismantling joint 250 mm dia or suitable size for common header - 1 No.Reflex valve 250mm dia or suitable size 1No.
Nut-bolts, bend,rubber packing (as required)
Any other Item required for proper installation of above pumps. - 1 Job.
CABLE FOR INCOMING PANEL & PUMPS :-
Suitable size P.V.C. Armoured Alluminium conductor cable from outgoing of transformer to L.T. incoming Panel and for power wring of pumping plant.
EOT crane
Provision of E.O.T. crane of 3 Ton capacity along with gantry girder and chainpully block and geared trolly suitable for span and 12 meter or suitable higher capacity clear lift complete in all respect for circular pump house, suitable for travelling length.
POWER WIRING :
Power wiring complete for L.T. panel, starter and for 3 No. pump set etc all complete.
EARTHING :
Provision for double plate earthing for 3 nos. of electric motors, starters, panels etc. excavation of earthing pit of required size supply and burrying of 600 mm x600 mm size 3mm thick copper earth plate vertically errected for earthing with its top at least 3 meter from ground level completed with 32 mm G.1. perforated pipes and funnel for watering, laying and fetting of earthing strip, CI boxes hinged cover masonary, laying alternate layers of characoal / coak and salt at least 150 mm thick each layer complete in all respect.
PAINTING
Provision for painting of all the pumps set, main piping and valves, panels etc. installed in the pump house with three coats by enamel paint.
INSTALLATION OF " SCADA"
Installation of SCADA system, to control the 3 set of pumping plant including testing and commissioning etc.
INSTALLATION AND COMMISSIONING
Installation and commissioining of all 3 no.pumping plants along with L.T. panels distribution boards, switch gear control panels,
starter etc laying & jointing of column pipes, delivery pipes, common header also commissioning of pumping plant.
Electrification for pump house and premises.
Electrification of pump house and campus with copper conductor wire concealed with the all material laboure etc.
Fire Extinguisher capasity 4.5 Kg co2
12.5 mm thick electric resistance rubber sheet as per BIS for LT Panels
Supply and fixing of exhaust fans of 18" size 1450rpm of GEC/equivalent make complete in all respect.
Pole mounted solar based LED light (As per SOR 2018)
PUMPING PLANT Supply of Desilting pump set,nut bolt ,rubber packing etc. LPM - 250 Head - 40,(1W+1S)
SWITCH GEAR WITH starter
Supply of suitable capacity stater for above pump set
supply of 1100 volt grade copper submersible cable 3x16mm
MS column pipe 100mm Dai or suitable size.
CI/DF Sluice valve 100mm Dai or suitable size
CI/DF Reflex valve 100mm dai or suitable size
CI/DF Bend 100 mm dai or suitable size
SS guide pipe of 40mm dai. or suitable size
Dismentaling joint 100 mm
Pressure gauge with stop cock.
Installation ,testing and commissioning of pumping plant.
Meter
PUMPING PLANT Supply of submerged VT/ submerged pumping plant along with suitable motor 415 volt ± 10%, 3phase,50 Hz AC supply with required size and lenghth, Column pipe, Foundation, guide pipe, Auto coupling arrangement if required and other necessary accessories to complete the work, capacity LPM - 2200 Head-50 M (both tentative it will be decided as per site condition)
GSM/GPRS based wireless communication system for RTU capable to transfer and gather data from remote sites to control stations. All accessories included with signal enhancer, antennan etc.
Intelegent Energy meter with memory RTC and 2 serial parts integrated with RTU
CE/UL certified PLC/RTU with redudant CPU and power supply in IP 54 enclosure suitable to communicate with GSM based modem unit with redudant CPU and power supply with analog /digital parameter and features as specified for each zps/oht to store and trasmitt data on GSM backbone , RTU/PLC designed with logic to transfer data at multiple statins as specified in tender document
Motor operated sluice valve with actuator complete in all respect-
Electric motor operated sluice valve 150 mm dia or suitable size along with actuator for delivery pipe of pump.
Electric motor operated sluice valve 250mm dia or suitable size along with actuator for common header.
Auto phase reversal unit suitable with inbuilt time delay & enclose of 100 Amp rating or suitable rating.
Rador type level sensor for CWR.
CE/UL certifiedd 7 inch HMI touch screen suitable to communication with PLC/RTU for local display and control.
Security serveilliance camera IP with recorder
Pressure Transmitter with manual pressure gauge at each pump and common header.
Isolation transformer & surge arrestor.
CE/UL certified Radar type Level Transmitter for OHT
ELECTRO MAGNETIC FLOW METER
Cable (1.5sq mm, 10cx1sq mm, 2cx1sq mm other required itmes for installation of SCADA system.
FLOW SENSOR
Type - Pulsed DC
End connection- Flanged of Carbon steel
Provision of Electro magnetic flow meter suitable to measure the water suitable discharge be fitted in common header of 250 mm dia or suitable size having following specification
Electrode - SS 316
Lining Material - Hard rubber
Protection category - IP 68
Measuring Accuracy- + 5% of measured
Sensor Housing - SS 304 with fully welded construction
Connection/ Junction Box - SS 304
Earthing only grounding rings required
FLOW TANSMITTER CONVERTOR
Type - Micro processor based modular desing
Display - 3 line back lit LDC for indication of actual flow rate forward reverse sum totolizer.
Protection category - IP 65
Enclosure - DI - Cast Aluminium with poly urethan with glass window.
Programming- Through three key pad as front facia.
Power Supply - 230 volt 50 HZ AC
Cable Gland - ½ NPT
Mounting - Wall mounted
Maximum Sepration - Upto 300 m between sensor and transmeter without any signal boosters.
Terminals - shock-Hazard-protected push lock terminal.
Error Indetification : 0.3, 6/22 MA
Flow Indicator Totalizer - 3½ digit IED display with 6 digit electro mechanical Totalizer.
MAIN PIPING & VALVES INCLUDING COMMON HEADER :-
Flange rating - PN 16 size 250 mm. or suitable size
Size of Common header of 250mm dia. Length or as per site requirement
Supply of following
Size of Delivery of pump 150mm dia length or as per site requirement
CI D/F Reflux Valve 150 mm dia or suitable size - 3 Nos.
CI D/F Tee 250x250x150 mm dia or suitable size. - 3 Nos.
D/F distance piece 150 mm dia. 1.00 m. long - 3 Nos.
D/F distance piece 250 mm dia. 1.50 m. long - 3 Nos.
D/F distance piece 250 mm dia. 3.00 m. long - 3 Nos.
Dismantling joint 150 mm dia or suitable size - 3 Nos.
Dismantling joint 250 mm dia or suitable size for common header - 1 No.,Reflex valve 250mm dia 1No.
Any other Item required for proper installation of above pumps. - 1 Job.
Nut-bolts, rubber packing (as required)
POWER WIRING CABLE FOR INCOMING PANEL & PUMPS :-
EARTHING :
EOT crane
Provision for double plate earthing for 3 nos. of electric motors, starters, panels etc. excavation of earthing pit of required size supply and burrying of 600 mm x600 mm size 3mm thick copper earth plate vertically errected for earthing with its top at least 3 meter from ground level completed with 32 mm G.1. perforated pipes and funnel for watering, laying and fetting of earthing strip, CI boxes hinged cover masonary, laying alternate layers of characoal / coak and salt at least 150 mm thick each layer complete in all respect.
PAINTING
Provision for painting of all the pumps set, main piping and valves, panels etc. installed in the pump house with three coats by enamel paint.
INSTALLATION OF " SCADA"
Provision of E.O.T. crane of 2 Ton capacity along with gantry girder and chainpully block and geared trolly suitable for span and 6 meter or suitable highter clear lift complete in all respect for circular pump house, suitable for travelling length.
INSTALLATION AND COMMISSIONING
Installation of SCADA system, to controle the 3 set of pumping plant including testing and commissioning etc.
Installation of all 3 pumping plants along with L.T. panels distribution boards, switch gear control panels, starter etc laying & jointing of column pipes, delivery pipes, common header also commissiong of pumping plant.
Pole mounted solar based LED light For WTP Campus (As per SOR 2018)
C.W.R. ZONE-1 to OHT Zone-1
CE/UL certified PLC/RTU with redundant CPU and power supply in IP 54 enclosure suitable to communicate with GSM based modem unit with redundant CPU and power supply with analog /digital parameter and features as specified for each zps/oht to store and trasmitt data on GSM backbone , RTU/PLC designed with logic to transfer data at multiple station specified in tender document
PUMPING PLANT Supply of submerged VT/ submerged pumping plant along with suitable motor 415 volt ± 10%, 3phase,50 Hz AC supply with required size and lenghth, Column pipe, Foundation, guide pipe, Auto coupling arrangement if required and other necessary accessories to complete the work, capacity LPM - 3100 Head-40 M (both tentative it will be decided as per site condition)
Intelegent Energy meter with memory RTC and 2 serial parts integrated with RTU
CE/UL certified PLC/RTU with redudant CPU and power supply in IP 54 enclosure suitable to communicate with GSM based modem unit with redudant CPU and power supply with analog /digital parameter and features as specified for each zps/oht to store and trasmitt data on GSM backbone , RTU/PLC designed with logic to transfer data at multiple statins as specified in tender document
GSM/GPRS based wireless communication system for i RTU capable to transfer and gather data from remote sites to control stations. All accessories included with signal enhancer, antennan make for abbove ITRU.
Electric motor operated sluice valve 200 mm dia along with actuator for delivery pipe of pump.
Electric motor operated sluice valve 250mm dia or suitable size along with actuator for common header.
Electric motor operated sluice valve 200 mm dia along with actuator for common header.
CE/UL certifiedd 7 inch HMI touch screen suitable to communication with PLC/RTU for local display and control.
Security serveilliance camera IP with recorder
Isolation transformer & surge arrestor.
Rador type level sensor
Pressure Transmitter with manual pressure gauge at each pump and common header - 3 Nos
ELECTRO MAGNETIC FLOW METER
Complete cabling for 8 no. pump set and other required itmes .
FLOW SENSOR
Type - Pulsed DC
End connection- Flanged of Carbon steel
Provision of Electro magnetic flow meter suitable to measure the water discharge to be fitted in common header of 200 mm dia or suitable size having following specification
Electrode - SS 316
Lining Material - Hard rubber
Protection category - IP 68
Measuring Accuracy- + 5% of measured
Valve inclusive of linearity repeatability pressure effect and Hystrusues between 1 to 3 meter per second.
Sensor Housing - SS 304 with fully welded construction
Connection/ Junction Box - SS 304
Earthing only grounding rings required
FLOW TANSMITTER CONVERTOR
Type - Micro processor based modular desing
Display - 3 line back lit LDC for indication of actual flow rate forward reverse sum totolizer.
Protection category - IP 65
Enclosure - DI - Cast Aluminium with poly urethan with glass window.
Programming- Through three key pad as front facia.
Power Supply - 230 volt 50 HZ AC
Cable Gland - ½ NPT
Mounting - Wall mounted
Maximum Sepration - Upto 300 m between sensor and transmeter without any signal boosters.
Terminals - shock-Hazard-protected push lock terminal.
Error Indetification : 0.3, 6/22 MA
Flow Indicator Totalizer - 3½ digit IED display with 6 digit electro mechanical Totalizer.
MAIN PIPING & VALVES INCLUDING COMMON HEADER :-
Size of Delivery of pump 200mm dia length or as per site requirement
Flange rating - PN 16 size 200 mm.
Supply of following
Size of Common header of 200mm dia. Length or as per site requirement
CI D/F Reflux Valve 200 mm dia or suitable size - 2 Nos.
CI D/F Tee 200x200x200 mm dia or suitable size. - 2 Nos.
D/F distance piece 200 mm dia or suitable size. 1.00 m. long - 2 Nos.
D/F distance piece 200 mm dia or suitable size. 1.50 m. long - 2 Nos.
D/F distance piece 200 mm dia or suitable size. 3.00 m. long - 2 Nos.
Dismantling joint 200 mm dia or suitable size. - 2 Nos.
Any other Item required for proper installation of above pumps. - 1 Job.
CABLE FOR INCOMING PANEL & PUMPS :-
Suitable size P.V.C. Armoured Alluminium conductor cable from outgoing of transformer to L.T. incoming Panel and for power wring of pumping plant.
EARTHING :
Nut-bolts, Bend ,rubber packing (as required)
PAINTING
Provision for painting of all the pumps set, main piping and valves, panels etc. installed in the pump house with three coats by enamel paint.
INSTALLATION OF " SCADA"
Provision for double plate earthing for 2 nos. of electric motors, starters, panels etc. excavation of earthing pit of required size supply and burrying of 600 mm x600 mm size 3mm thick copper earth plate vertically errected for earthing with its top at least 3 meter from ground level completed with 32 mm G.1. perforated pipes and funnel for watering, laying and fetting of earthing strip, CI boxes hinged cover masonary, laying alternate layers of characoal / coak and salt at least 150 mm thick each layer complete in all respect.
INSTALLATION AND COMMISSIONING
Installation of SCADA system, to controle the 4 set of pumping plant including testing and commissioning etc.
Installation of all 2 pumping plants along with L.T. panels distribution boards, switch gear control panels, starter etc laying & jointing of column pipes, delivery pipes, common header also commissiong of pumping plant.
Pole mounted solar based LED light For Campus (As per SOR 2018)
CWR ZONE 1 FOR OHT ZONE-2
CE/UL certified PLC/RTU with redudant CPU and power supply in IP 54 enclosure suitable to communicate with GSM based modem unit with redudant CPU and power supply with analog /digital parameter and features as specified for each zps/oht to store and trasmitt data on GSM backbone , RTU/PLC designed with logic to transfer data at multiple statins as specified in tender document
PUMPING PLANT Supply of submerged VT/ submerged pumping plant along with suitable motor 415 volt ± 10%, 3phase,50 Hz AC supply with required size and lenghth, Column pipe, Foundation, guide pipe, Auto coupling arrangement if required and other necessary accessories to complete the work, capacity LPM - 900 Head-40 M (both tentative it will be decided as per site condition)
Size of Delivery of pump 100mm dia length or as per site requirement
Rador type level sensor
Electric motor operated sluice valve 200 mm dia along with actuator for common header.
ELECTRO MAGNETIC FLOW METER
Size of Common header of 100mm dia. Length or as per site requirement
FLOW SENSOR
Type - Pulsed DC
End connection- Flanged of Carbon steel
Provision of
Electrode - SS 316
Lining Material - Hard rubber
Protection category - IP 68
Measuring Accuracy- + 5% of measured
Valve inclusive of linearity repeatability pressure effect and Hystrusues between 1 to 3 meter per second.
Sensor Housing - SS 304 with fully welded construction
Connection/ Junction Box - SS 304
Earthing only grounding rings required
FLOW TANSMITTER CONVERTOR
Type - Micro processor based modular desing
Display - 3 line back lit LDC for indication of actual flow rate forward reverse sum totolizer.
Protection category - IP 65
Enclosure - DI - Cast Aluminium with poly urethan with glass window.
Programming- Through three key pad as front facia.
Power Supply - 230 volt 50 HZ AC
Cable Gland - ½ NPT
Mounting - Wall mounted
Maximum Sepration - Upto 300 m between sensor and transmeter without any signal boosters.
Terminals - shock-Hazard-protected push lock terminal.
Error Indetification : 0.3, 6/22 MA
Flow Indicator Totalizer - 3½ digit IED display with 6 digit electro mechanical Totalizer.
MAIN PIPING & VALVES INCLUDING COMMON HEADER :-
PUMPING PLANT Supply of submerged VT/ submerged pumping plant along with suitable motor 415 volt ± 10%, 3phase,50 Hz AC supply with required size and lenghth, Column pipe, Foundation, guide pipe, Auto coupling arrangement if required and other necessary accessories to complete the work, capacity LPM - 900 Head-40 M (both tentative it will be decided as per site condition)
Size of Delivery of pump 100mm dia length or as per site requirement
Supply of following
Electro magnetic flow meter suitable to meassure the sutabile discharge to be fitted in common header of suitable size having following specification complete in all respect.
Flange rating - PN 16 size 100 mm.
CI D/F Reflux Valve 100 mm dia or suitable size - 2 Nos.
CI D/F tee 100x100x100 mm dia or suitable size. - 2 Nos.
D/F distance piece 100 mm dia or suitable size. 1.00 m. long - 2 Nos.
D/F distance piece 100 mm dia or suitable size. 1.50 m. long - 2 Nos.
D/F distance piece 100 mm dia. or suitable size 3.00 m. long - 2 Nos.
Dismantling joint 100 mm dia or suitable size. - 1 Nos.
Any other Item required for proper installation of above pumps. - 1 Job.
Dismantling joint 100 mm dia. or suitable size - 1 No.Reflex valve 150mm dia 1No.
Nut-bolts, bend,rubber packing ( as required)
Accessories for pump house :
Fire extingushier cinfirming to BIS of 3 Kg Co2 gas type
12.5 mm/25mm thich electric resistance rubber sheet as per BIS for LT Panels
CABLE FOR INCOMING PANEL & PUMPS :-
Suitable size P.V.C. Armoured Alluminium conductor cable from outgoing of transformer to L.T. incoming Panel and for power wring of pumping plant.
EARTHING :
E.O.T CRANE
starter etc laying & jointing of column pipes, delivery pipes, common header also commissioning of pumping plant.
Provision of E.O.T. crane of 2 Ton capacity along with gantry girder and chainpully block and geared trolly suitable for span and 6 meter or highter rating clear lift complete in all respect for circular pump house, suitable for 6 meter travelling length.
12.5 mm thick electric resistance rubber sheet as per BIS for LT Panels
PAINTING
Provision for painting of all the pumps set, main piping and valves, panels etc. installed in the pump house with three coats by enamel paint.
INSTALLATION AND COMMISSIONING
Installation of SCADA system, to controle the 4 set of pumping plant including testing and commissioning etc.
Provision for double plate earthing fo2 nos. of electric motors, starters, panels etc. excavation of earthing pit of required size supply and burrying of 600 mm x600 mm size 3mm thick copper earth plate vertically errected for earthing with its top at least 3 meter from ground level completed with 32 mm G.1. perforated pipes and funnel for watering, laying and fetting of earthing strip, CI boxes hinged cover masonary, laying alternate layers of characoal / coak and salt at least 150 mm thick each layer complete in all respect.
Electrification of pump house and campus with copper conductor wire concealed with the all material.
CE/UL certified PLC/RTU with redudant CPU and power supply in IP 54 enclosure suitable to communicate with GSM based modem unit with redudant CPU and power supply with analog /digital parameter and features as specified for each zps/oht to store and trasmitt data on GSM backbone , RTU/PLC designed with logic to transfer data at multiple statins as specified in tender document
At CWR ZONE 1 FOR OHT ZONE-3
PUMPING PLANT Supply of submerged VT/ submerged pumping plant along with suitable motor 415 volt ± 10%, 3phase,50 Hz AC supply with required size and lenghth, Column pipe, Foundation, guide pipe, Auto coupling arrangement if required and other necessary accessories to complete the work, capacity LPM - 850 Head-40 M (both tentative it will be decided as per site condition)
Rador type level sensor
Electric motor operated sluice valve 200 mm dia along with actuator for common header.
ELECTRO MAGNETIC FLOW METER
Electric motor operated sluice valve 100mm dia or suitable size along with actuator for delivery pipe of pump.
FLOW SENSOR
Type - Pulsed DC
End connection- Flanged of Carbon steel
Provision of
Electrode - SS 316
Lining Material - Hard rubber
Protection category - IP 68
Measuring Accuracy- + 5% of measured
Valve inclusive of linearity repeatability pressure effect and Hystrusues between 1 to 3 meter per second.
Sensor Housing - SS 304 with fully welded construction
Connection/ Junction Box - SS 304
Earthing only grounding rings required
FLOW TANSMITTER CONVERTOR
Type - Micro processor based modular desing
Display - 3 line back lit LDC for indication of actual flow rate forward reverse sum totolizer.
Protection category - IP 65
Enclosure - DI - Cast Aluminium with poly urethan with glass window.
Programming- Through three key pad as front facia.
Power Supply - 230 volt 50 HZ AC
Cable Gland - ½ NPT
Mounting - Wall mounted
Maximum Sepration - Upto 300 m between sensor and transmeter without any signal boosters.
Terminals - shock-Hazard-protected push lock terminal.
Error Indetification : 0.3, 6/22 MA
Flow Indicator Totalizer - 3½ digit IED display with 6 digit electro mechanical Totalizer.
MAIN PIPING & VALVES INCLUDING COMMON HEADER :-
Provision of Electro magnetic flow meter suitable to meassure the discharge upto 850 lpm and to be fitted in common header of 100 mm dia having following specification complete in all respect.
Supply of following
Size of Delivery of pump 100mm dia or suitable size.Lenght 6.0 Mtr. for each pump. as per site requirement
Size of Common header of 100mm dia or suitable size, length as per site requirement
CI D/F Reflux Valve 100 mm dia or suitable size - 2 Nos.
CI D/F tee 100x100x100 mm dia or suitable size. - 2 Nos.
D/F distance piece 100 mm dia or suitable size. 1.00 m. long - 2 Nos.
CI D/F Reflux Valve 100 mm dia or suitable size - 2 Nos.
CI D/F tee 100x100x100 mm dia. or suitable size - 2 Nos.
Dismantling joint 100 mm dia or suitable size. - 1 Nos.
Any other Item required for proper installation of above pumps. - 1 Job.
CABLE FOR INCOMING PANEL & PUMPS :-
Suitable size P.V.C. Armoured Alluminium conductor cable from outgoing of transformer to L.T. incoming Panel and for power wring of pumping plant.
EARTHING :
E.O.T CRANE
PAINTING
Provision for painting of all the pumps set, main piping and valves, panels etc. installed in the pump house with three coats by enamel paint.
INSTALLATION AND COMMISSIONING
Installation of SCADA system, to controle the 4 set of pumping plant including testing and commissioning etc.
Dismantling joint 100 mm dia. - 1 Nos.
Dismantling joint 100 mm dia. - 1 No.Reflex valve 100mm dia 1No.
CE/UL certified PLC/RTU with redudant CPU and power supply in IP 54 enclosure suitable to communicate with GSM based modem unit with redudant CPU and power supply with analog /digital parameter and features as specified for each zps/oht to store and trasmitt data on GSM backbone , RTU/PLC designed with logic to transfer data at multiple statins as specified in tender document
At CWR ZONE 1 FOR OHT ZONE-3
CWR ZONE 1 FOR OHT ZONE-4
PUMPING PLANT Supply of submerged VT/ submerged pumping plant along with suitable motor 415 volt ± 10%, 3phase,50 Hz AC supply with required size and lenghth, Column pipe, Foundation, guide pipe, Auto coupling arrangement if required and other necessary accessories to complete the work, capacity LPM - 1000 Head-40 M (both tentative it will be decided as per site condition)
Electric motor operated sluice valve 100mm dia or suitable size along with actuator for common header-2 Nos
ELECTRO MAGNETIC FLOW METER
Pressure Transmitter along with manual pressure gauge
FLOW SENSOR
Type - Pulsed DC
End connection- Flanged of Carbon steel
Provision of
Electrode - SS 316
Lining Material - Hard rubber
Protection category - IP 68
Measuring Accuracy- + 5% of measured
Valve inclusive of linearity repeatability pressure effect and Hystrusues between 1 to 3 meter per second.
Sensor Housing - SS 304 with fully welded construction
Connection/ Junction Box - SS 304
Earthing only grounding rings required
FLOW TANSMITTER CONVERTOR
Type - Micro processor based modular desing
Display - 3 line back lit LDC for indication of actual flow rate forward reverse sum totolizer.
Protection category - IP 65
Enclosure - DI - Cast Aluminium with poly urethan with glass window.
Programming- Through three key pad as front facia.
Power Supply - 230 volt 50 HZ AC
Cable Gland - ½ NPT
Mounting - Wall mounted
Maximum Sepration - Upto 300 m between sensor and transmeter without any signal boosters.
Terminals - shock-Hazard-protected push lock terminal.
Error Indetification : 0.3, 6/22 MA
Flow Indicator Totalizer - 3½ digit IED display with 6 digit electro mechanical Totalizer.
MAIN PIPING & VALVES INCLUDING COMMON HEADER :-
Ultrasonic level sensor of 5 mtr. For RTU communication
Provision of Electro magnetic flow meter suitable to meassure the discharge upto be fitted in common header of 100 mm dia or suitable size having following specification complete in all respect.
Supply of following
Electro magnetic flow meter suitable to meassure the sutabile discharge to be fitted in common header of suitable size having following specification complete in all respect.
Size of Common header of 100mm dia or suitable size, length as per site requirement
CI D/F Reflux Valve 100 mm dia or suitable size - 2 Nos.
Size of Delivery of pump 100mm dia or suitable size Lenght 6.0 Mtr. for each pump.
Size of Common header of 100mm dia., or suitable size length as per site requirement
D/F distance piece 100 mm dia. 1.50 m or suitable size. long - 2 Nos.
D/F distance piece 100 mm dia. 3.00 m. or suitable size long - 2 Nos.
Dismantling joint 100 mm dia or suitable size. - 1 Nos.
Any other Item required for proper installation of above pumps. - 1 Job.
CABLE FOR INCOMING PANEL & PUMPS :-
Suitable size P.V.C. Armoured Alluminium conductor cable from outgoing of transformer to L.T. incoming Panel and for power wring of pumping plant.
EARTHING :
E.O.T CRANE
PAINTING
Provision for painting of all the pumps set, main piping and valves, panels etc. installed in the pump house with three coats by enamel paint.
INSTALLATION AND COMMISSIONING
Installation of SCADA system, to controle the 4 set of pumping plant including testing and commissioning etc.
Dismantling joint 100 mm dia. or suitable size - 1 Nos.
Dismantling joint 100 mm dia. or suitable size - 1 No.Reflex valve 100mm dia 1No.
DMA Equipment At OHT Zone 1,
Motor operated Actuators with sluice valve for OHT delivery
SITC of plunger type flow control Valve 250 mm or suitable size.
SITC of Double Solenoid Flow control Valve 250 mm or suitable size.
CE & UL certified Radar type level transmitter for OHT
CE/UL Certified pressure Transmitter
SITC of CE & UL certified Electomagnetic Flowmeter for OHT line size 250 mm. dia or suitable size as per size condition.
SITC of CE & UL certified Electomagnetic Flowmeter for OHT line size 200 mm. dia or suitable size as per size condition.
SITC of Chlorine Analyzer with MODBUS RTU having following specifications- (a) FRC Sensor (Senssit make), range- 0-5 PPM (electrolyte with membrane cap), tytpe-Amperometric. (b) Analyzer with RS 485O/P. suitable to OHT distribution line size & compatible with SCADA system .
SITC of SCADA Compatible Automatic type chlorinating plant solenoid driven dosing pump of capacity 0-10 LPH ( pressure 4kg/cm2 with ORP sensor to check and regulate the dosing along with 200 ltr capacity HDPE tank (02 nos., 1W+1S) ,standard fittings, wall/floor mountings MS bracket for dosing pump with GM Valve ,cock valve & sodium hydro chloride solution.,chlorine test kit with O.T. Solution complete with all respect.( suitable for 100-220V and 30-60 Hz , suction lift- 1.5 m., injection pressure 4 bars, steadt state accuracy +-3% repeatability +-3%) with RS 485 Port O/P having facility of interface with PLC SCADA system.
Coplete cabling of all equipment at OHT including power and control cable.
Dismantling joint 100 mm dia. or suitable size - 1 No.Reflex valve 100mm dia 1No.
Installation ,commissioning and testing .
SITC of plunger type flow control Valve 250 mm or suitable size.
SITC of Double Solenoid Flow control Valve 250 mm or suitable size.
DMA Equipment At OHT Zone -2
SITC of CE & UL certified Electomagnetic Flowmeter for OHT line size 250 mm. dia or suitable size as per size condition.
SITC of CE & UL certified Electomagnetic Flowmeter for OHT line size 200 mm. dia or suitable size as per size condition.
SITC of plunger type flow control Valve of suitable size.
SITC of SCADA Compatible Automatic type chlorinating plant solenoid driven dosing pump of capacity 0-10 LPH ( pressure 4kg/cm2 with ORP sensor to check and regulate the dosing along with 200 ltr capacity HDPE tank (02 nos., 1W+1S) ,standard fittings, wall/floor mountings MS bracket for dosing pump with GM Valve ,cock valve & sodium hydro chloride solution.,chlorine test kit with O.T. Solution complete with all respect.( suitable for 100-220V and 30-60 Hz , suction lift- 1.5 m., injection pressure 4 bars, steadt state accuracy +-3% repeatability +-3%) with RS 485 Port O/P having facility of interface with PLC SCADA system.
SITC of CE & UL certified Electomagnetic Flowmeter for OHT line size 200 mm. dia or suitable size as per site condition.
Complete cabling of all equipment at OHT including power and control cable.
DMA Equipment At OHT Zone -3
Dismantling joint 100 mm dia. or suitable size - 1 No.Reflex valve 100mm dia 1No.
Installation ,commissioning and testing .
SITC of plunger type flow control Valve 250 mm or suitable size.
SITC of Double Solenoid Flow control Valve 250 mm or suitable size.
CE & UL Certified PLC/ RTU in IP 54 enclosure suitable to communicate with GSM based modem unit with CPU & Power supply with analog & digital parameter & features as specified, for each tubewell/ OHT & stand alone OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations
SITC of CE & UL certified Electomagnetic Flowmeter for OHT line size 250 mm. dia or suitable size as per size condition.
SITC of CE & UL certified Electomagnetic Flowmeter for OHT line size 200 mm. dia or suitable size as per size condition.
SITC of Chlorine Analyzer with MODBUS RTU having following specifications- (a) FRC Sensor (Senssit make), range- 0-5 PPM (electrolyte with membrane cap), tytpe-Amperometric. (b) Analyzer with RS 485O/P. suitable to OHT distribution line size & compatible with SCADA system .
SITC of SCADA Compatible Automatic type chlorinating plant solenoid driven dosing pump of capacity 0-10 LPH ( pressure 4kg/cm2 with ORP sensor to check and regulate the dosing along with 200 ltr capacity HDPE tank (02 nos., 1W+1S) ,standard fittings, wall/floor mountings MS bracket for dosing pump with GM Valve ,cock valve & sodium hydro chloride solution.,chlorine test kit with O.T. Solution complete with all respect.( suitable for 100-220V and 30-60 Hz , suction lift- 1.5 m., injection pressure 4 bars, steadt state accuracy +-3% repeatability +-3%) with RS 485 Port O/P having facility of interface with PLC SCADA system.
SITC of CE & UL certified Electomagnetic Flowmeter for OHT line size 250 mm. dia. or suitable size
Complete cabling of all equipment at OHT including power and control cable.
DMA Equipment At OHT Zone -3
Dismantling joint 100 mm dia. or suitable size - 1 No.Reflex valve 100mm dia 1No.
Installation ,commissioning and testing .
SITC of plunger type flow control Valve 250 mm or suitable size.
SITC of Double Solenoid Flow control Valve 250 mm or suitable size.
CE & UL Certified PLC/ RTU in IP 54 enclosure suitable to communicate with GSM based modem unit with CPU & Power supply with analog & digital parameter & features as specified, for each tubewell/ OHT & stand alone OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations
SITC of CE & UL certified Electomagnetic Flowmeter for OHT line size 250 mm. dia or suitable size as per size condition.
SITC of CE & UL certified Electomagnetic Flowmeter for OHT line size 200 mm. dia or suitable size as per size condition.
SITC of Chlorine Analyzer with MODBUS RTU having following specifications- (a) FRC Sensor (Senssit make), range- 0-5 PPM (electrolyte with membrane cap), tytpe-Amperometric. (b) Analyzer with RS 485O/P. suitable to OHT distribution line size & compatible with SCADA system .
SITC of SCADA Compatible Automatic type chlorinating plant solenoid driven dosing pump of capacity 0-10 LPH ( pressure 4kg/cm2 with ORP sensor to check and regulate the dosing along with 200 ltr capacity HDPE tank (02 nos., 1W+1S) ,standard fittings, wall/floor mountings MS bracket for dosing pump with GM Valve ,cock valve & sodium hydro chloride solution.,chlorine test kit with O.T. Solution complete with all respect.( suitable for 100-220V and 30-60 Hz , suction lift- 1.5 m., injection pressure 4 bars, steadt state accuracy +-3% repeatability +-3%) with RS 485 Port O/P having facility of interface with PLC SCADA system.
DMA Equipment At OHT Zone -4
Master Control Station (MCS)
CE & BIS approved manufacturer's industrial grade LCD monitor with latest configuration as per specification of size 65"
Desktop/PC with i7 processor for as per spec mentioned in technical bid documents.
CE/UL approved manufacturer's 3 KVA UPS with batteries as spec. mentioned for WTP and Computer as per requirement
Full development version of required TAGS SCADA Software with costomization of software for MCS as per required as per spec mentioned in technical bid documents.
CE & UL approved manufacturer's control room PLC with CPU & power supply at MCS in IP65 enclosure as per spec. mentioned
CE/UL certified field gateway agent for transfering data from MCS to control room
GSM based wireless / broadband/Equipment communication system for PLC capable to transfer and gather data from remote sites to control stations, including all accessories complete
CE/UL approved manufacturer's Firewall for network protection
Lightning surge protector for ethernet communication protection
CE/UL approved manufacturer's industrial grade ethernet switch
Mobile App facility system architecture complete.
Supply and Install
ation 1.5 Ton AC with stabilizer and other required item for installation
Canon/HP 1018/equivalent Laser printer with chair and table.
Security Survelliance IP camera
Installation, testing and commissioning with required furniture,Air Conditioner etc
Test and trial run
Sub station at Intake well
HT Control Panel
2mm thick M.S. sheet fabricated factory wired dust and vermin proof cubical and floor mounting type SCADA Compatible control panel comprising of following items.
Incoming panel-1No.
11 KV/800 Amp. 3 Phase 3 wire 50 Hz. HT incoming panel with a short circuit breaking current up to 18.4 KVA capacity in draw out version vaccum circuit breaker fitted with-
3 Nos. single phase double core epoxy bar primary time current transformer of suitable ratio of class I accuracy and 5p 10 for protection core with burden of 15 VA per core.
1 no. 3 phase resin cast draw out type PT of ratio 11 KV/110 volt of class I accuracy and 100 VA burden.
1 set of closing & tripping coil suitable for 30 Volt DC.
Mechanical indicator for ON/OFF.
Emergency Mechanical tripping through push lever.
Rear/Side entry cable box to accommodate suitable size cable.
Energy Analyzer of measuring parameters such as voltage, current, KW, KWH, KVA & Power factor.
Indicating lamp assembly for breaker ON/OFF trapping spring, charge.
Over current and earth fault relay, C.D.G. 31 having elements for over current and one for earth fault etc.
Incoming panel will be followed by a battery charge unit having specification as under
The Cabinet of Suitable thickness shall be enclosed type to ensure the atmosphere is absolutely acid free. It shall be provided with cover for ventilation and shall have steel hinged doors equiped with battery & battery charger.
Outgoing panel 2 No.
H.T. out going panels for feeding two transformers of suitable capacity similar to incoming panel but without following accessories.
KWH meter with M.D.I.
Potential transformers
Outgoing battery charger
month
Incoming Panel-2No.For Transformer and 1 No. DG
Reputed make cubical floor mounting extensible type panel complete with T.P. air insulated aluminium Bus bar of suitable size with neutral of reduced section, system voltage 415/440 volts 3 phase 4 wire 50 Hz indoor installation type and comprising of suitable size T.P. M.C.C.B. housed in sheet steel cubical panel fitted with following.
One set of Mechanical On/Off Indicator
One no. shunt trip oil
One set of T.P.I.D. M.T. Non-directional combined over current and earth fault relay having setting 50-200% for over current and 20-80% for earth fault or equivalent.
Two CTs of suitable ratio and class for protection and indication.
One no. neutral link
One no. 96 Sq.mm. Ammeter of and suitable range
One set of red green indicating lamp
Cable connection arrangments
Suaitable size APFC pannel for maintaning power factor and Inter locking arrangements.
Required No. of Soft starter/VFD Of suitable Size
Bus coupler
Bus coupler complete with internal wiring aluminium bus bar comprising of following.
Extensible type 630 Amp or suitable Capacity Aluminium bus bar arrangement for phase and neutical
600 Amp. or suitable size 3 pole M.C.C.B. fitted with over load under voltage shunt trip short circuit release with safety shutter etc. for pumps and spare MCCB - 2 Nos.
Electrical and mechanical inter locking arrangement
M.C.C.B On/Off indicating lamp.
HRC Fuses
Auxilliary contractors
Breaker control switch
Load Distribution Panel
Supply and laying of cable
Supply of 11 KV XLPE cable 3 x 70mm sq./ suitable size
Supply of 3.50 core 185 Sq.mm /suitable size aluminium PVC cable 1100 V grade.
Supply of Jointing cable
i) HT Indoor joint
ii) HT outdoor joint
Supply of earthing materials and earthing arrangement.
Erection, testing and commissioning of Sub-Station including testing at work also.
Approval of electrical inspector, electric safety.
Foundation & bolder for Transformers
25 thick electric resistance rubber sheet as per BIS
Installation, testing and commissioning with required furniture,Air Conditioner etc
Test and trial run
Fencing work
HT Control Panel
2mm thick M.S. sheet fabricated factory wired dust and vermin proof cubical and floor mounting type SCADA Compatible control panel comprising of following items.
Incoming panel-1No.
11 KV/800 Amp. 3 Phase 3 wire 50 Hz. HT incoming panel with a short circuit breaking current up to 18.4 KVA capacity in draw out version vaccum circuit breaker fitted with-
3 Nos. single phase double core epoxy bar primary time current transformer of suitable ratio of class I accuracy and 5p 10 for protection core with burden of 15 VA per core.
1 no. 3 phase resin cast draw out type PT of ratio 11 KV/110 volt of class I accuracy and 100 VA burden.
1 set of closing & tripping coil suitable for 30 Volt DC.
Mechanical indicator for ON/OFF.
Emergency Mechanical tripping through push lever.
Rear/Side entry cable box to accommodate suitable size cable.
Energy Analyzer of measuring parameters such as voltage, current, KW, KWH, KVA & Power factor.
Indicating lamp assembly for breaker ON/OFF trapping spring, charge.
Internal Electrification with concealed conduct wiring including all materials and labour complete in all respect of controlling room and staff Quarter.
Sub station at WTP for WTP and main CWR.
The Cabinet of Suitable thickness shall be enclosed type to ensure the atmosphere is absolutely acid free. It shall be provided with cover for ventilation and shall have steel hinged doors equiped with battery & battery charger.
Outgoing panel 2 No.
H.T. out going panels for feeding two transformers of suitable capacity similar to incoming panel but without following accessories.
Incoming panel-1 No.
Potential transformers
Outgoing battery charger
Outgoing panel-2No
H.T. out going panels for feeding two transformers of similar to incoming panel but without following accessories.
month
Incoming Panel-2No.For Transformer and 1 No. DG
Reputed make cubical floor mounting extensible type panel complete with T.P. air insulated aluminium Bus bar of suitable size with neutral of reduced section, system voltage 415/440 volts 3 phase 4 wire 50 Hz indoor installation type and comprising of suitable size T.P. M.C.C.B. housed in sheet steel cubical panel fitted with following.
One set of Mechanical On/Off Indicator
One no. shunt trip oil
One set of T.P.I.D. M.T. Non-directional combined over current and earth fault relay having setting 50-200% for over current and 20-80% for earth fault or equivalent.
Two CTs of suitable ratio and class for protection and indication.
One no. neutral link
One no. 96 Sq.mm. Ammeter of and suitable range
One set of red green indicating lamp
Cable connection arrangments
Suaitable size APFC pannel for maintaning power factor and Inter locking arrangements.
Provision for oil immersed natural air cooled step down transformer suitable for out door installation of 200 KVA or higher as per site requirement and design in best engineering manner., 11/0.4KV and as per I:S 2020/1972 with all accessories. The transformer should be provided with off load tap changer ± 7.5% voltage varialtion on L.T. side. These tapping should be connected by and externally separated tap changing switch. The temp side in oil by thermometer should not exceed 50oC and of winding by measuring resistance should not exceed 55oC over an ambient of 45oC maximum. The transformer should have cable box on HT/LT side for termination of cables.
Incoming Panel- 2 No For Transformer and 1 No. DG
Bus coupler complete with internal wiring aluminium bus bar comprising of following.
Extensible type 630 Amp or suitable Capacity Aluminium bus bar arrangement for phase and neutical
600 Amp. or suitable size 3 pole M.C.C.B. fitted with over load under voltage shunt trip short circuit release with safety shutter etc. for pumps and spare MCCB - 2 Nos.
Electrical and mechanical inter locking arrangement
M.C.C.B On/Off indicating lamp.
HRC Fuses
Reputed make cubical floor mounting extensible type panel complete with T.P. air insulated aluminium Bus bar of 800 Amp. or suitable size with neutral of reduced section, system voltage 415/440 volts 3 phase 4 wire 50 Hz indoor installation type and comprising of 630 Amp. T.P. M.C.C.B. housed in sheet steel cubical panel fitted with following.
Breaker control switch
Load Distribution Panel
Supply and laying of cable
Supply of 11 KV XLPE cable 3 x 70mm sq./ suitable size
Supply of 3.50 core 185 Sq.mm /suitable size aluminium PVC cable 1100 V grade.
Supply of Jointing cable
i) HT Indoor joint
ii) HT outdoor joint
Extensible type suitable Capacity Aluminium bus bar arrangement for phase and neutical
suitable 3 pole M.C.C.B. fitted with over load under voltage shunt trip short circuit release with safety shutter etc.
Approval of electrical inspector, electric safety.
Foundation & bolder for Transformers
Installation, testing and commissioning with required furniture,Air Conditioner etc
Test and trial run
Foundation and bolder for Transformers
HT Control Panel
2mm thick M.S. sheet fabricated factory wired dust and vermin proof cubical and floor mounting type SCADA Compatible control panel comprising of following items.
Incoming panel-1No.
11 KV/800 Amp. 3 Phase 3 wire 50 Hz. HT incoming panel with a short circuit breaking current up to 18.4 KVA capacity in draw out version vaccum circuit breaker fitted with-
3 Nos. single phase double core epoxy bar primary time current transformer of suitable ratio of class I accuracy and 5p 10 for protection core with burden of 15 VA per core.
1 no. 3 phase resin cast draw out type PT of ratio 11 KV/110 volt of class I accuracy and 100 VA burden.
1 set of closing & tripping coil suitable for 30 Volt DC.
Mechanical indicator for ON/OFF.
Emergency Mechanical tripping through push lever.
Rear/Side entry cable box to accommodate suitable size cable.
Energy Analyzer of measuring parameters such as voltage, current, KW, KWH, KVA & Power factor.
Indicating lamp assembly for breaker ON/OFF trapping spring, charge.
25mm thick electric resistance rubber sheet as per BIS
Sub station at Zone -1
The Cabinet of Suitable thickness shall be enclosed type to ensure the atmosphere is absolutely acid free. It shall be provided with cover for ventilation and shall have steel hinged doors equiped with battery & battery charger.
Outgoing panel 2 No.
H.T. out going panels for feeding two transformers of suitable capacity similar to incoming panel but without following accessories.
Incoming panel-1No
Outgoing panel- 2 No
Outgoing battery charger
H.T. out going panels for feeding two transformers of similar to incoming panel but without following accessories.
month
Incoming Panel-2No.For Transformer and 1 No. DG
Reputed make cubical floor mounting extensible type panel complete with T.P. air insulated aluminium Bus bar of suitable size with neutral of reduced section, system voltage 415/440 volts 3 phase 4 wire 50 Hz indoor installation type and comprising of suitable size T.P. M.C.C.B. housed in sheet steel cubical panel fitted with following.
One set of Mechanical On/Off Indicator
One no. shunt trip oil
One set of T.P.I.D. M.T. Non-directional combined over current and earth fault relay having setting 50-200% for over current and 20-80% for earth fault or equivalent.
Two CTs of suitable ratio and class for protection and indication.
One no. neutral link
One no. 96 Sq.mm. Ammeter of and suitable range
Provision for oil immersed natural air cooled step down transformer suitable for out door installation of 160 KVA or suitable as per size condition and design and best engineering manner, 11/0.4KV and as per I:S 2020/197
One set of red green indicating lamp
Cable connection arrangments
Suaitable size APFC pannel for maintaning power factor and Inter locking arrangements.
2 with all accessories. The transformer should be provided with off load tap changer ± 7.5% voltage varialtion on L.T. side. These tapping should be connected by and externally separated tap changing switch. The temp side in oil by thermometer should not exceed 50oC and of winding by measuring resistance should not exceed 55oC over an ambient of 45oC maximum. The transformer should have cable box on HT/LT side for termination of cables.
Incoming Panel- 2 No For Transformer and 1 No. DG
Bus coupler complete with internal wiring aluminium bus bar comprising of following.
Extensible type 630 Amp or suitable Capacity Aluminium bus bar arrangement for phase and neutical
600 Amp. or suitable size 3 pole M.C.C.B. fitted with over load under voltage shunt trip short circuit release with safety shutter etc. for pumps and spare MCCB - 2 Nos.
Electrical and mechanical inter locking arrangement
M.C.C.B On/Off indicating lamp.
HRC Fuses
Main L.T. Panel WITH APFC PANNEL
Breaker control switch
Reputed make cubical floor mounting extensible type panel complete with T.P. air insulated aluminium Bus bar of 1000 Amp or suitable capacity. with neutral of reduced section, system voltage 415/440 volts 3 phase 4 wire 50 Hz indoor installation type and comprising of 630 Amp. T.P. M.C.C.B. housed in sheet steel cubical panel fitted with following.
Suitable size of APFC pannel to maintaning power factor and Inter locking arrangements
Supply and laying of cable
Supply of 11 KV XLPE cable 3 x 70mm sq./ suitable size
Supply of 3.50 core 185 Sq.mm /suitable size aluminium PVC cable 1100 V grade.
Supply of Jointing cable
i) HT Indoor joint
ii) HT outdoor joint
Extensible type suitable Capacity Aluminium bus bar arrangement for phase and neutical
suitable 3 pole M.C.C.B. fitted with over load under voltage shunt trip short circuit release with safety shutter etc.
Approval of electrical inspector, electric safety.
Foundation & bolder for Transformers
Extensible type suitable. Capacity Aluminium bus bar arrangement for phase and neutical
Supply of 11 KV XLPE cable . 3 x 70mm sq./ suitable size
Supply of 3.50 core 120 Sq.mm /suitable size aluminium PVC cable 1100 V grade.
DIESEL GENERATING SET AT INTAKE WELL
Provision for supply Installation,Testing and commissing of salient type suitable capacity DG set as per C.P.C.B. Latest guide line powered with complete in all respect-
Deiesel Engine ( goverining as per BS - 5114)
Type- Vertical
Method of coolling- Radiator
Method of aspiration- Turbo charged after . cooled
Method of Starting- 24 Volt Electric
Alternator
3 phase, 50 C/S, self regulated, self excited, Screen protected, 415 volts 4 wire alternator of rated capacity at 0.8 power factor. The alternator would generally confirm to relevant BS/IS standard.
Base Plate
The above diesel engine will be directly coupled alternator through a flexible coupling on a sturdy channel section steel base frame.
Control Panel
The control panel will be dust and varmin proof of sheet metal construction, floor mounting type, suitable for indoor use in IP-41 enclosure. The control panel will comprise of -
Frequency meter
K.W.A. meter
Kilowatt meter
MCCB with overload, shart cercuit and under voltage protection.
Starting push button and Key switch ( ON/OFF)
Audio/Visual alarm with shut down for engine protection for low oil pressure and high coolant temperature.
Indicating lamps for low lub-oil pressure, high coolant temperature, set running and load on set be control on.
Instrument fuses.
1.5 class CTs of suitable ratio.
Bus bars- Alumimum.
Supply of 11 KV XLPE cable . 3 x 70mm sq./ suitable size
Supply of 3.50 core 120 Sq.mm /suitable size aluminium PVC cable 1100 V grade.
DIESEL GENERATING SET AT INTAKE WELL
Provision for supply Installation,Testing and commissing of salient type suitable capacity DG set as per C.P.C.B. Latest guide line powered with complete in all respect-
Cable entry gland plate without cable gland
Type- Vertical
Method of coolling- Radiator
Method of aspiration- Turbo charged after . cooled
Method of Starting- 24 Volt Electric
Alternator
3 phase, 50 C/S, self regulated, self excited, Screen protected, 415 volts 4 wire alternator of rated capacity at 0.8 power factor. The alternator would generally confirm to relevant BS/IS standard.
Base Plate
The above diesel engine will be directly coupled alternator through a flexible coupling on a sturdy channel section steel base frame.
Control Panel
The control panel will be dust and varmin proof of sheet metal construction, floor mounting type, suitable for indoor use in IP-41 enclosure. The control panel will comprise of -
Frequency meter
K.W.A. meter
Kilowatt meter
MCCB with overload, shart cercuit and under voltage protection.
Starting push button and Key switch ( ON/OFF)
Audio/Visual alarm with shut down for engine protection for low oil pressure and high coolant temperature.
Indicating lamps for low lub-oil pressure, high coolant temperature, set running and load on set be control on.
Power cable of 150 sqmm size/suitable size of 1100 volts grade 3½ core Alluminium armoured PVC seathed
DIESEL GENERATING SET AT WTP AND MAIN CWR
Provision for supply Installation,Testing and commissing of salient type suitable rating DG set as per C.P.C.B. Latest guide line powered with complete in all respect-
Supply of 11 KV XLPE cable . 3 x 70mm sq./ suitable size
Supply of 3.50 core 120 Sq.mm /suitable size aluminium PVC cable 1100 V grade.
DIESEL GENERATING SET AT INTAKE WELL
Provision for supply Installation,Testing and commissing of salient type suitable capacity DG set as per C.P.C.B. Latest guide line powered with complete in all respect-
Cable entry gland plate without cable gland
Type- Vertical
Method of coolling- Radiator
Method of aspiration- Turbo charged after . cooled
Method of Starting- 24 Volt Electric
Alternator
3 phase, 50 C/S, self regulated, self excited, Screen protected, 415 volts 4 wire alternator of rated capacity at 0.8 power factor. The alternator would generally confirm to relevant BS/IS standard.
Base Plate
The above diesel engine will be directly coupled alternator through a flexible coupling on a sturdy channel section steel base frame.
Control Panel
The control panel will be dust and varmin proof of sheet metal construction, floor mounting type, suitable for indoor use in IP-41 enclosure. The control panel will comprise of -
Frequency meter
K.W.A. meter
Kilowatt meter
MCCB with overload, shart cercuit and under voltage protection.
Starting push button and Key switch ( ON/OFF)
Audio/Visual alarm with shut down for engine protection for low oil pressure and high coolant temperature.
Indicating lamps for low lub-oil pressure, high coolant temperature, set running and load on set be control on.
Instrument fuses.
Method of aspiration- Turbo charged after . cooled
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.59 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 3.23 MB
CHOPANBID883.pdf
Tender Documents • 9.80 MB
BOQ_2023493.xls
BOQ • 1.37 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .