Loading…
Loading…
Tender Value
₹80.1 L
EMD Value
₹1.6 L
Closing Date
7 Jan 2026, 11:00 amClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
45 days
Expenditure
Revenue
Above/Below/Par
TECHNICAL
15 conditions · 4 needing a document upload
The tenderer must have minimum average annual contractual turnover of [V/N or 'V' whichever is less; where V = Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-VIB, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet.
Tenderer must have to submit valid Electrical Contractor license as per Indian Electricity Rules for the respective category of works issued by Government Electrical License Board on or before the closing date of tender. Copy of the electrical contractor license should be submitted along with the tender offer, otherwise, the tender will be summarily rejected.
The Similar nature of works for this instant tender shall be "Supply, installation, testing and commissioning of any LT/HT electrical work." The tenderer should have executed the similar nature of works in Central /State Government department or PSUs of Central /State Government."
51 conditions · 4 needing a document upload
Whether the cost of earnest money deposited
Migration to GST regime - Special Tender Conditions: The rates should clearly indicate the rate of applicable duties and taxes included in the prices quoted by them. Any variation in tax structure/ rate due to introduction of GST, shall be dealt with under Statutory Variation Clause. It should be ensure that bidders/tenderers are GST compliant and quoted tax structure/rates are as per GST Law.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Contractor should submit the GSTIN number and same should be mentioned in the bills along with a copy of GSTIN registration certificate while submitting the bills to accounts for audit and payment, As GST is scheduled to implemented wef 01.07.2017. Without GSTN, no bill will be accepted w.e.f. 01.07.2017
From 01.07.2017 GST has been implemented but the detail guideline is still not clear. Hence, new tax structure on materials and labour will be applicable to both Railway & contractor after getting proper notification
Payment of Earnest Money deposit (EMD) , in respect of e- tendering,should be accepted through net banking or online payment gateway only
Electrical works associated with renovation, repair, rewiring work and upgradation of Railway Institute (RICP) Pandu, and Brahmaputra Officers Rest House, Guwahati.
EL-LM-25-26-40~NFR
EL-LM-25-26-40
Open
Works - General
90 Days
Hojai, Assam
₹0
₹1.6 L
7 Jan 2026
15 Dec 2025
24 Dec 2025
159 items across 2 schedules
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 45,79,854.37 | ||
| — | 1.00 | — | — | ||
| Supply, Installation, testing and commissioning of Outdoor Cast Resin Oil Type11KV/433V 500 KVA transformer, (BIS Level-1 as per Amendment 4 ) 3Phase,50Hz, Dyn11, copper wound, Class A insulation associated with windingtemperature indicator / controller, having cable termination on the HV & LV sidesand all accessories and conforming to IS 2026 part 11. Technical specification as per enclosed | — | — | — | 10,23,060 | |
| — | 40.00 | — | — | ||
| — | — | — | 2,42,388.4 | ||
| , installation of free for Transformer switchyard locking arrangement. TheFencing using components made FRP and shall becorrosion latest IS-6746.FRP fencing ready to use type. The fencing and tools. The DetailsTechnical of Engineer incharge at beresponsibility of contractor of those items. | Supply Doorand manufactured of the be of hardware direction inclusive | — | fencing, fencing violet andIS (Low foronsite entire have been items.However | ||
| — | 40.00 | — | — | ||
| Supply and erection of CC foundation (for transformer) in ratio 1:2:4 cement, sand and good quality chips of size 19 mm and down size as per direction at site Engineer in-charge of Railway. | — | — | — | 78,177.6 | |
| — | 1.00 | — | — | ||
| Construction of 2 pole structure by supply, erection,fixing of the following MS channel and angle clamp with pole by 50 x 5 mm MS flat with 50x16 mm diameter bolt and nut including making of hole by drill as per requirement of site (i) MSChannel (100 x 50 x 50 x 5)mm x 2200 mm=1 No.conductor bracket. (ii) MSAngle (50x50x6) mm x2200mm=2 nos. bracing(iii) MS Channel (75 x 40 x 40x 4.8) mm x 2200mm= 1No.guard wire (iv)MS Angle (50x50x6) mm x3200mm=2nos. cross bracing. | — | — | — | 3,305.54 | |
| — | 2.00 | — | — | ||
| Supply of galvanized tubular pole 9 mtr longtype 410 SP-33 with steplength 5.00- 2.00-2.00 mtrsectional dia165.1X139.7X114.3 mtrsectional thickness5.4X4.5X3.65 mm as perIS 2713/1980 includingsuitable size base plateand cap on top. | — | — | — | 16,629.72 | |
| — | 2.00 | — | — | ||
| Erection of rail/tubular pole to 1/5 th of its height with CCfoundation from base block (30 cm x 30 cm x 15 cm)including digging & refilling of earth to a height of 30 cmabove ground level as per drawing no.CEE/OH@ 47'40@FGA)in ratio 1:3:6 by cement sand & Chips 19 mm & downincluding excavation of earth (Rail pole will be supplied byRailway) | — | — | — | 2,749.36 | |
| — | 1.00 | — | — | ||
| Supply, installation , testing and commissioning of Triple pole Air- break Gang Operating air break off load disconnecting switch (GOS) 11 KV 400 Amp. complete with drop out fuses, 3 insulator triple pole each pole consist of galvanize steel base HT insulator as per BIS non ferrous knife and spring loaded contact arcing horn of adequate section to break magnetizing current of the transformer horizontal GI shaft/ pipe of adequate length for phase separator, adequate length for operation from ground level and operation handle complete with locking arrangement in both OFF & ON position. All ferrous part heavily tinned with stand weather . Fuse shall be conforming to IS:9385 part-I/1979, GOS shall be conforming to IS: 9921 Part-I/1981&9921 Part III/1982.complete with operating rod , drop out fuse and locking arrangement etc. conforming to IS: 1811 1992 or latest including provision of mounting arrangement for GOS as req.The whole work shall be executed as per direction of Engineer in charge at site. | — | — | — | 8,802.23 | |
| — | 9.00 | — | — | ||
| Supply & laying of 100 mm dia medium class GI pipe | — | — | — | 8,559 | |
| — | 400.00 | — | — | ||
| Laying, commissioning of LT/HT cable XLPEinsulated power cables with armoured aluminum conductors of different sizes partly along the pole andpartly through ground in cable trench.Loading, unloading & carrying of cable toactual work site by contractor own arrangement as per instruction of Engineer incharge at site. (Cable will be supplied by Railway.) | — | — | — | 16,372 | |
| — | 250.00 | — | — | ||
| Excavation of cable trench 1.0 m x 0.5 m below the GL with laying of armored cable and refilling the same by supply of Brick, Sand and Soil after digging the earth as per direction of Engineer at site & connection of armored Cable by supply and fixing of crimping lugs etc. | — | — | — | 30,447.5 | |
| — | 1.00 | — | — | ||
| Design, fabrication, supply, installation, testing and commissioning of LT control panel outdoor type of double door construction, FORM-3b as per IEC 60439-1 standards with IP 54/55 and 415 V 3phase & 4 wire system, rear access type. The panel colour shall be RAL 7035 structured finish. cable entry incoming=bottom,outgoing=bottom. Horizontal 630 Amp, busbar will be running at the top throughout the panel Enclosure shall be of CRCA steel sheet type. load bearing parts shall have 2mm thickness & non-loading parts shall have 1.6mm thickness. Gland plate shall be 3mm of GI type. the busbar system shall have heat shrinkable colored PVC sleeve. main busbar (power bus) is TPN electrolytic copper busbar size (50x6)mm. Doors and covers shall be gasketed by Neoprene gaskets. Control wires shall be 1.1KV grade Copper Flexible conductors. Panel should have short circuit strength at 100KA for 1 seconds as per IS:8623 part-I and temperature rise test at 6300 A as per IS:8623 part-1.The panel shall also consist of digital multifunction meter, CT, LED indicating lamps, auxiliary contractors, selector switches, cam switches etc as per manufacturer specification /recommendation & Cable alley also. the panel shall be provided with 3nos bus bar for phases made of electrolytic grade of copper bar of each (50x6) mm. the incoming switches shall beconnected with bus bar by crimping sockets on bus bar of panel side. the bar shall be connected by on either side by porcelain insulator and sufficient clearance shall be maintained inside the bus bar doe easy maintenance. Drawing would be submitted by the contractor and approved by competent authority. the panel has to built & inspected in OEM factory. inspection has to be carried out in presence of Rly's authorized representative. the control panel should be designed and manufactured by the CPRI and ISI.ISO approved manufacturer. The panel shall be fabricated from 2 mm thick consisting of . (i) Onload Change Over Switch 630 A, 4Pole (Manual-Transfer-Swicth ) = 1 no.(ii) MCCB 400 Amps 4pole 50 KA = 2 nos.(iii) MCCB 125 Amps 4pole 25 KA = 2 nos. Ics=100%Icu with adjustable thermal magnetic setting confirming to IEC 60947-2. | — | — | — | 3,07,185 | |
| — | 2.00 | — | — | ||
| "Supply fixing, testing and commissioning of 6 way TPN MCCB incomer Vertical DB and outgoing module (6+6+6) Conforms to IS 8623-1 & 3,IEC 61439-1 & 3,IK 08 single door, in CRCA Sheet steel, RAL 9003, Powder Coated Board IP43 with i) 63 amps 4P MCCB, 25 KA, Ics=100%Icu with adjustable thermal magnetic setting confirming to IEC 60947-2. - 1 no. (ii) 40 amps DP C series MCB - 6 nos (iv) 20 amps DP C series MCB - 2 nos. The TPN MCCB incomer Vertical DB whole arrangement should be properly concealed on wall as per direction of engineer in charge at site. The all other necessary items required for proper execution of the work should be supplied by contractor. | — | — | — | 78,580 | |
| — | 2.00 | — | — | ||
| "Supply, fitting, fixing of 4 way TPN DB box with incomer 4 module & outgoing (4+4+4) modules and also consisiting of main 63 A 4P C curve MCB- 1 no.,40 amp DP MCB, C curve = 1 no., 32 amp DP MCB, C curve = 2 nos. The TPN MCCB incomer Vertical DB whole arrangement should be properly concealed on wall as per direction of engineer in charge at site. The all other necessary items required for proper execution of the work should be supplied by contractor. | — | — | — | 21,410 | |
| — | 1200.00 | — | — | ||
| Supply and wiring of sub- main line concealed by 2x6 sq.mm. PVC insulated unsheathed and multi stranded FRLSCopper Cable confirming to IS 694/1990 through suitablesize of PVC conduit pipe with 1sq. mm unsheathed coppercable as earth continuity wire. | — | — | — | 1,19,616 | |
| — | 400.00 | — | — | ||
| Supply and wiring of sub- main line by 2x4 sq.mm. PVC insulated unsheathed and multi stranded FRLSCopper Cable confirming to IS 694/1990 through suitablesize of PVC conduit pipe with 1sq. mm unsheathed coppercable as earth continuity wire. | — | — | — | 30,808 | |
| — | 400.00 | — | — | ||
| Supply and wiring of sub- main line by 2x2.5 sq.mm. PVC insulated unsheathed and multi stranded FRLSCopper Cable confirming to IS 694/1990 through suitablesize of PVC conduit pipe with 1sq. mm unsheathed coppercable as earth continuity wire. | — | — | — | 25,068 | |
| — | 100.00 | — | — | ||
| Supply and wiring of light point through good quality hard PVC casing with associated accessories for surface type wiring by 1.5 mm sq single core PVC insulated flexible coppercable and flush type 5/6 amp controlling switch to be providedon hard plastic moulded board.Casing shall be fixed on the wall/ ceiling by MS screw (6x40 mm)at an interval not more than 300 mm | — | — | — | 15,858 | |
| — | 30.00 | — | — | ||
| Supply and wiring of ceiling fan point through good quality hard PVC casing with associated accessories for surface type wiring by 1.5 mm sqsingle core PVC insulated flexible copper cable withearth continuity by 16SWG bare copper wire andflush type 5/6 amp controlling switch to be provided on hard plastic moulded board including 300W box type stepped electronic fan regulator.Ceiling fan connection shallbe done through ceilingrose. Casing shall be fixedon the wall / ceiling by MS (6x40 mm) screw at an interval not more than300mm. | — | — | — | 7,977.9 | |
| — | 250.00 | — | — | ||
| Supply, fitting and laying of Single core 2.5 sqmm Flame Retardant PVC insulated industrial grade multistrand copper conductor(unsheathed) flexible cable voltage grade upto1100 Volt.(Conforming to IS 694:2010). | — | — | — | 8,867.5 | |
| — | 30.00 | — | — | ||
| Supply, fitting, fixing, testing and commissioning of recess mounting pressure die cast 12 watts LED round downlight fitting complete with lamp having separate replaceable electronic driver including flexible connecting cable, ceilingrose etc. as per site requirement and as per direction of site engineer in-charge. LED driver's efficiency should be minimum 90%, Power factor of complete fitting should begreater than 0.90, Input operating voltage: 140V to 277VAC. | — | — | — | 17,490 | |
| — | 6.00 | — | — | ||
| Supply, installation, testing & commissioning of 24W RGBW LED LinearWall Washer with following technical features: Aluminium Die-casting body with Surface anodic oxidation and UV stabilized toughened glass front cover ,luminary should be linear shaped suitable for illumination of wall facade lighting, Tilt :asper requirement,IP-66 or greater ingressprotection for outdoor application suitability, secondary optical lensesprovided on each LED of fitting withsuitable narrow beam angle, DMX compatibility with inbuilt decoder .Control Mode :DMX512, DMX Controller canachieve 16.7Mcolors, Rated Input Supplyof LED: Highly reliable DC24V constantvoltage power supply which drives the RGBWLEDs High Power LED ,Power Consumption : 24W(approx.) per fixture however as per requirement wattage maybe increased /decreased to meet thedesired effect of Facade. Power Efficiency :>85%,Power factor : >0.95,Operating Frequency: 50 Hz, Operating temperature: -10 to+55 degree centigrade, Life Span:>50000 hours, Warranty : 5 Years,Electrical Safety Class : Class 1. (The workto be executed as per direction of engineering charge at site. If any other items have been omitted but required for efficient working for facade lighting it would be responsibility of contractor to supply and provide such items. However the quotedrate shall be inclusive of those items). | — | — | — | 30,124.26 | |
| — | 8.00 | — | — | ||
| Supply, installation, testing& commissioningof 120 watt RGBW/Warm White Floodlight upexterior wall facade of Railway Institute with following features: Aluminium Die-casting body with surface anodic oxidation and UV stabilized toughened glass on the front, Rectangular shaped luminary suitable for wallfacade application, adjustable tilt as per siterequirement, Suitable beam angle as per siterequirement, IP66 ingress protection, PowerConsumption: 120W per fixture however asper requirement wattage may be increased/decreased to meet the desired effect ofFacade. Input Voltage: AC 220V,PowerEfficiency :>85%, Power factor: >0.95, Operating Frequency : 50 Hz, Output Color :RGBW/Warm White, Life Span :>50000hours, Warranty : 5 Years, Electrical SafetyClass : Class 1. (The work to be executed asper direction of engineer in charge at site. Ifany other items have been omitted butrequired for efficient working for facadelighting it would be responsibility ofcontractor to supply and provide such items.However the quoted rate shall be inclusive ofthose items). | — | — | — | 54,260.88 | |
| — | 4.00 | — | — | ||
| Supply, installation, testing & commissioning of 30 W LED movable light warm white, 3240 lm, & color temp. 3000K, CRI should be above 80. The work to be executed as per direction of engineer in charge at site. | — | — | — | 9,900 | |
| — | 4.00 | — | — | ||
| Supply, installation, testing, commissioning & Programming of RGB/ DMX Controller System with following features :Stand alone interfaces, Input Connector, MiniUSB-including mini USB Cable,Output Connector,XLR3/XLR5, DMX Output-512 & 1024 Channels, PC DMX In triggering capability, Master/Slave connection capability, DMX speed - 1 to 45 Hz,MaB/Vk, internal clock and internal calendar enabled]inbuilt internal memory,data display system, system compatibilitywith Windows/MAC/LINUX with 32/ 64 bitCPU technology to be installed in IP65 Waterproof Junction Box with necessary connection. Warranty: 5 Years (The work tobe executed as per direction of engineer incharge at site. If any other items have been omitted but required for efficient working of projector light for facade lighting it would be responsibility of contractor to supply, to employ technicallysound software professionals/Engineer to programming the same during execution/commissioning as well as during maintenance & fault under warranty period and provide such items. However the quoted rate shall be inclusive of those items). | — | — | — | 2,38,670.2 | |
| — | 20.00 | — | — | ||
| Supply, fitting, fixing and testing of indoor 2x5Watt watts LED wallbracket light fitting having chrome finish with opal glass complete with lamp and other accessories along with connection of flexible copper cable etc. as per direction of site engineer in-charge. | — | — | — | 28,095.6 | |
| — | 40.00 | — | — | ||
| Supply & erection of Foot Lamp light 3 watt, 300 lm,Total Power Consumption:1.5 W, Sufficient to illuminate stairs or pathways without glare for use on staircases, walkways, or any low- level illumination areas. | — | — | — | 23,200 | |
| — | 20.00 | — | — | ||
| Supply, fitting, fixing,connection & commissioning of 18/20 watt LED indoor fitting complete set with LED tube and other accessories. The fitting shall be connected by 1.5sq mm flexible copper wire through pvc pipes/casing as required at site. | — | — | — | 6,284 | |
| — | 1.00 | — | — | ||
| Supply, installation, fitting, fixing, testing & commissioning of 2 KW hybrid solar system with technical specification System Capacity 2 kW System Type Hybrid (Solar + Battery + Grid) Solar PV Module type Mono/Polycrystalline silicon, IEC 61215 & IEC 61730 certified, Module Capaci-400 Wp (or above) per panel, total 2 kW, No. of Panels 5 Nos. of 400 Wp each (or equivalent), Inverter Type Hybrid inverter (MPPT-based) with inbuilt charge controller, Inverter Capacity 2 kVA / 2 kW, Input Voltage Range 230 V ± 20% (Single Phase AC), Battery Bank 48 V DC (e.g. 4 Nos. x 12 V 150 Ah SMF/Lead-acid/Li-ion batteries), Backup Duration 4-6 hours (approx., depending on load), Mounting Structure Hot-dip galvanized MS structure suitable for RCC/ground mounting, Cables & Protection UV-resistant DC cables, MCBs, MCCBs, surge protection devices (SPD), earthing and lightning protection as per IS/IEC standards, Monitoring Provision for remote monitoring (optional IoT-based/online data logging) Standards & Compliance MNRE-approved components, IEC/IS standards, CEA safety regulations, Operating Temperature -10 °C to +55 °C, Efficiency System efficiency 85% overall | — | — | — | 2,23,000 | |
| — | 30.00 | — | — | ||
| Supply, erection, testing & commissioning of heavy duty 400 mm sweep Wall Bracket Fan suitable for single phase 230 volt AC supply including fixing arrangement by allied engineering works as per direction at site Engineer. | — | — | — | 39,159 | |
| — | 20.00 | — | — | ||
| Supply and wiring of 5/6 amp, 5 pin plug point through good quality hard PVC casing with associated accessories for surface type wiring by 1.5 mm sq single core PVC insulated flexible copper cable with earth continuity by 16 SWG bare copper wire and flush type 5/6 amp controlling switch to be provided on hard plastic moulded board.Casing shall be fixed on the wall / ceiling by MS (6x40 mm) screw at an interval not more than 300mm. | — | — | — | 3,375.4 | |
| — | 6.00 | — | — | ||
| Supply and wiring of 15/16 amp, 6 pin plug point through good quality hard PVC casing with associated accessories for surface type wiring by 4 mm sq single core PVC insulated flexible copper cable with earth continuity by 16 SWG bare copper wire and flush type15/16 amp controlling switch to be provided on hard plastic moulded board. Casing shall be fixed on the wall / ceiling by MS (6x40mm) screw at an interval not more than 300mm. | — | — | — | 1,793.28 | |
| — | 10.00 | — | — | ||
| — | 10.00 | — | — | ||
| — | 500.00 | — | — |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
EL-LM-25-26-40works.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .