| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹26.1 LAccepted-AOC | 1 | Accepted-AOC L1 | |
| 2 | Rejected-Technical A 17 1ST FLOOR TRIBENI COMMERCIAL COMPLEX G S ROAD ULUBARI KAMRUP ASSAM 781007 | KAMRUP METRO | ASSAM | 781007 | - | Rejected-Technical Relevant Completion certificate not submitted as per NIT. |
Tender Value
₹24.5 L
EMD Value
₹49,071
Closing Date
21 Aug 2023, 6:00 pmClosed
AGM (E-E), Barapani Airport, Shillong
O/o, Engg-Electrical, Barapani Airport, Shillong
Procurement of trolley mounted DG set and DG operated trolley mounted Lighting Tower at Barapani Airport, Shillong.
2023_AAI_162250_1
AAI/ENGG(E)/SHL/Trolley mounted DG/2023-24
Open Tender
Electrical Works
Item Rate
90 days
AGM (E-E), Barapani Airport, Shillong
As per NIT
5 documents required · 5 mandatory
₹1,180
₹49,071
27 May 2024
29 Jul 2023
22 Aug 2023
29 Jul 2023
21 Aug 2023
29 Jul 2023
29 Jul 2023 - 12 Aug 2023
Amount
Supply of 4 wheel driven portable standard trolly mounted Diesel Generating Set having Prime power rating of 125KVA, 415 volts at 1500 RPM, 0.8 lagging power factor at 415V , 50 Hz, 3 Phase AC supply system and for 0.85 load factor consisting of the following: a) Diesel Engine: 4 stroke, radiator cooled, electric start, of suitable BHP at 1500 RPM suitable for 125 KVA output of alternator at 40 degree C at normal RH, 50 meters (approx.) above MSL and conforming to BS 5514, BS 649, IS 10000, capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be fitted complete with all the required accessories. b) Engine mounted Instrument Panel fitted with Start-stop switch with key and having digital display for following: (i) Water temperature indication (ii) Lubrication oil pressure indication. (iii) Battery charging indication (iv) RPM indication (v) Over speed indication (vi) Low lub. Oil trip indication (vii) Engine Running Hours indication (viii) Inbuild Control Panel: As per Specification of DG Set para 2.4 of NIT. c) Alternator: Synchronous alternator rated at 125KVA, 415 volts at 1500 RPM, 3 phase 50 Hz. AC supply with 0.8 lagging power factor at 40 degree C normal RH. The alternator shall be having SPDP enclosure, brushless, continuous duty, self- excited and self-regulated through AVR conforming to IS: 4722/BS with class H insulation. d) Base frame & foundation: Both the engine and alternator shall be mounted on suitable base frame made of MS channel which shall be installed on suitable capacity trolly with AVM pads as per recommendations of manufacturer. e) Exhaust System: Dry exhaust manifold with residential exhaust silencer. f) Starting System: 12 V DC starting system comprising of starter motor: voltage regulator and arrangement for initial excitation complete with suitable nos. of batteries. g) Accoustic enclosure: Accoustic and weather proof enclosure of suitable size with arrangement. for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air into the atmosphere as per upto date specifications of CPCB. h) Fuel tank: In built fuel tank suitable for 8 hrs of operation, fabricated from 14 SWG MS sheet as per manufacturers standards complete with drain. valve, air vent, inlet and outlet connection & level. indicator. i) Suitable capacity Trolley: Four wheeled trolley, with turn table, towing eye, axel, brake, 4 jacks, as per standard specification of DG set manufacturers and as per specification in NIT etc.
Supply testing and commissioning of 4 KW,230 V,50 hz mobile Lighting Tower Diesel Generator set air cooled manually operated panel, with enclosure as per latest CPCB guidelines, , 8 mts high Lightmast capable of 360 degree rotation, Single axle 2 wheeled trailer and towing eyebollt, fuel tank 15 Ltrs. , wind stability upto 80Km/hr , 4x250 W LED @ 135 Lumens/Watt efficacy and 50000Hrs Life etc, as per specifications.
Supplying of Changeover Switch 4 Pole 630 Amp 415 Volt 50Hz with SS enclosure as per preferred makes.
AMC Works: Repair and Maintenance Contract of 125 KVA DG Sets after completion of DLP which includes quarterly visit for checking the Engine and Alternator including attending fault / breakdown calls as and when required. During the period of the contract agency shall carry out the periodical maintenance of Engine i.e. A Check, B check & C check Alternator side i.e., vibration, diode, bearings, terminals including supply & replacement of required spares as specified and recommended by manufacturer. 1st Year
AMC Works: Repair and Maintenance Contract of 125 KVA DG Sets after completion of DLP which includes quarterly visit for checking the Engine and Alternator including attending fault / breakdown calls as and when required. During the period of the contract agency shall carry out the periodical maintenance of Engine i.e. A Check, B check & C check Alternator side i.e., vibration, diode, bearings, terminals including supply & replacement of required spares as specified and recommended by manufacturer. 2ndYear
AMC Works: Repair and Maintenance Contract of 125 KVA DG Sets after completion of DLP which includes quarterly visit for checking the Engine and Alternator including attending fault / breakdown calls as and when required. During the period of the contract agency shall carry out the periodical maintenance of Engine i.e. A Check, B check & C check Alternator side i.e., vibration, diode, bearings, terminals including supply & replacement of required spares as specified and recommended by manufacturer. 3rd Year
AMC Works: Repair and Maintenance Contract of 125 KVA DG Sets after completion of DLP which includes quarterly visit for checking the Engine and Alternator including attending fault / breakdown calls as and when required. During the period of the contract agency shall carry out the periodical maintenance of Engine i.e. A Check, B check & C check Alternator side i.e., vibration, diode, bearings, terminals including supply & replacement of required spares as specified and recommended by manufacturer. 4th Year
AMC Works: Repair and Maintenance Contract of 125 KVA DG Sets after completion of DLP which includes quarterly visit for checking the Engine and Alternator including attending fault / breakdown calls as and when required. During the period of the contract agency shall carry out the periodical maintenance of Engine i.e. A Check, B check & C check Alternator side i.e., vibration, diode, bearings, terminals including supply & replacement of required spares as specified and recommended by manufacturer. 5th Year
Carrying out D-Check maintenance of 125 KVA DG set including supplying and replacement of required spares & consumables as specified/as per manufacturer recommendations, as and when required during the five years of contract period.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .