| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.8 LAccepted-Finance | L1 | Accepted-Finance ACCEPTED | |
| 2 | L2₹10.5 L+₹1.7 L (19.5%)Accepted-Finance | L2 | Accepted-Finance ACCEPTED | |
| 3 | L3₹10.6 L+₹1.8 L (21.0%)Accepted-Finance | L3 | Accepted-Finance ACCEPTED | |
| 4 | L4₹12.9 L+₹4.1 L (47.1%)Accepted-Finance | L4 | Accepted-Finance ACCEPTED | |
| 5 | Rejected-Technical | - | Rejected-Technical Not submitted tender document and electrical licence is only authorized for electrical work carry out in Karnataka state |
Tender Value
₹14.4 L
EMD Value
₹29,000
Closing Date
17 Jul 2023, 1:30 pmClosed
HOS, Maintenance
IPM Section, IIT Guwahati
Replacement, Repairing and Re conditioning of the defective outdoor feeder pillar along with development of area lighting and street lighting at D, E and F type residential quarter Sector 1 at IIT Guwahati Campus
2023_IITG_760539_1
IITG/IPM/NIT/R/2023-24/05
Open Tender
Electrical Works
Works
60 days
IIT Guwahati
Please refer Tender documents.
2 documents required · 2 mandatory
₹2,000
IIT Guwahati
₹29,000
Yes
8 Feb 2024
7 Jul 2023
18 Jul 2023
7 Jul 2023
17 Jul 2023
7 Jul 2023
Amount
PART-A: Outdoor feeder pillar
Design fabrication supply installation of following floor mounted oudoor type, free standing, dust and vermin proof 3 phase 4 wire 415V AC supply fabricated with 2 mm thick CRC sheet finish with power coatings paint after chemical treatment & providing TPN 150 aluminium bus bar & wiring considering of floowing feeder-
As Incomer
125 A TP 36KA MCCB =1 no
Spreader link for 125A 4P MCCB ( set of 6 Pcs) =1 no
LED indicator lamp RYB = 3 nos
6 A SP MCB =3 nos
As Outgoing
63A TP 10KA MCB instead C Series =8 no
32A SP 10KA MCB C Series =3
Earthling bus =1 no
Design fabrication supply installation of following floor mounted oudoor type, free standing, dust and vermin proof 3 phase 4 wire 415V AC supply fabricated with 2 mm thick CRC sheet finish with power coatings paint after chemical treatment & providing TPN 150 aluminium bus bar & wiring considering of floowing feede-r
As Incomer
125 A TP 36KA MCCB =1 no
Spreader link for 125A 4P MCCB ( set of 6 Pcs) =1 no
LED indicator lamp RYB = 3 nos
6 A SP MCB =3 nos
As Outgoing
63A TP 10KA MCB instead C Series =7 no
32A SP 10KA MCB C Series =2 Nos
Earthling bus =1 no
Design fabrication supply installation of following floor mounted oudoor type, free standing, dust and vermin proof 3 phase 4 wire 415V AC supply fabricated with 2 mm thick CRC sheet finish with power coatings paint after chemical treatment & providing TPN 150 aluminium bus bar & wiring considering of floowing feeder-
As Incomer
125 A TP 36KA MCCB =1 no
Spreader link for 125A 4P MCCB ( set of 6 Pcs) =1 no
LED indicator lamp RYB = 3 nos
6 A SP MCB =3 nos
As Outgoing
63A TP 10KA MCB instead C Series =6 no
32A SP 10KA MCB C Series =2
Earthling bus =1 no
Repaparing and Reconditioning of existing external feeder pillar alongwith Painting and locking arragement as required
Enamel Paint
lock Arragement
Gasket Arragement
Hinging Arragement
Welding Arragement
Supply and installation of SMC box sizes 295x195x100 mm (syntax/devipolymer/hensel with terminal loop out terminal strips MCBs make Sintex
PART-B : External lighting system
Supply and installation of 4 pole connector suitable for cable connection required
Supply and fixing 5amps to 32amp 240/415V 10KA C curve miniatutre ckt braker suitable for inductive load of following poles in the existing MCB DB complete with connection testing and commissioing etc as required
Triple pole
Suuply and laying 16sqmm ISI marked FRLS PVC insulated single core copper conductor cable.
Wiring of submain wiring with the following size of PVC insulated copper conductor ,single core cable in existing PVC cassing capping
3x1.5 sqmm wire (for light point)
Supply of following types and sizes of 1.1 kV grade PVC/XLPE insulated aluminium conductor unarmourd underground cable make Havells/RR Kabel/KEI/Finolex
4Cx 6 sqmm
Laying one 1100V power cables of following sizes direct in ground including excavation, sand cushioning, protective brick covering and refilling etc. as required
Up to 35 sqmm
Supply of 50mm dia GI pipe (medium class) as required
Erection of metalic pole of following length in cement concrete 1:3:6 cement: 3 coarse sand : 6 graded stone aggregate 40mm nominal size) foundation including plastering , painting , excavation and refiling etc as required
Above 4.5 mtr and up to 6.5 mtr
Supply of SMC Box dimenson-230mm X 170mm X 105mm, Door Fixing-Hinged.(Make-Sintex)
Supply of LED post top lantern with die cast aluminum graphite grey power quoted spigot acrylic diffuser having minium efficacy more than 90lument/wat operating voltage range 140-280V AC ( Make Bajaj/Philips/Havells/jauar/Syska/CG
Replacement of SMC box and other accessories
Suplly and drawing following sizes of FR PVC insulated copper conductor,single core cable in the existing surface/recess/pVC conduit as required make Havells/Finolex/RR Kabel or equvalent
2 x 1.5 sqmm + 1x 1.5sqmm earth wire
Supply and fixing 5amps to 32 amp rating 240/415V C curve miniature ckt breaker suitable for inductive load of following poles in the existing MCB DB complete connection testing and commissioing etc as required
Single pole
Supply and making end termination with brass compression gland and alluminium lug for following sizes of PVC insulated and PVC sheated/XLPE aluminum conductor cable of 1.1KV grade as required
6 sq.mm 3 core cable
TRADE PALACE
Mudoi Enterprise
M/S ANUSHREE CONSTRUCTIONS & ASSOCIATES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .