Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.9 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹2.4 L+₹58,760 (31.7%)Rejected-AOC | L2 | Rejected-AOC L2 | |
| 3 | L3₹2.5 L+₹61,710 (33.3%)Rejected-AOC | L3 | Rejected-AOC L3 | |
| 4 | L4₹2.5 L+₹68,660 (37.1%)Rejected-AOC | L4 | Rejected-AOC L4 |
Tender Value
₹4.8 L
EMD Value
₹4,750
Closing Date
16 Mar 2020, 3:00 pmClosed
SE EUDC-II, GHAZIABAD
33/11 KV S/S KALA PATHAR, INDIRAPURAM, GHAZIABAD
Increasing cap of Transformer from 250 KVA to 400 KVA and Installation of New 250 KVA Transformer under EUDD XI KHORA
2020_PVVNL_439910_1
32/W/2019-20/D-XI/EUDC-II/GZB
Open Tender
Electrical Works
Item Rate
60 days
under EUDD XI KHORA
As per Tender Documents
2 documents required · 2 mandatory
₹1,180
SUPERINTENDING ENGINEER EUDC-II GHAZIABAD
₹4,750
17 Sept 2020
27 Feb 2020
17 Mar 2020
27 Feb 2020
16 Mar 2020
27 Feb 2020
Amount
fo|qr uxjh; forj.k e.My&f}rh;] xkft;kckn ds vUrxZr fo|qr uxjh; forj.k [k.M&X;kjg] xkft;kckn ds dk;Z{ks= esa uouhr fogkj [kksM+k esa 250 ds0oh0,0 ifjorZd dh {kerko`f) dj 400 ds0oh0,0 djuk] nhid fogkj ¼fu;j yscj pkSd½ ,oa vktkn fogkj] [kksM+k esa 1&1 ux 250 ds0oh0,0 ds u;s ifjorZd LFkkfir djus dk dk;ZA
Carrige of 08 No. PCC Pole, Line material, 08 No. Stay Rod, ACSR conductor, Earthing Rod, Cross arms, 06 No. 11KV Pin Insulator with pin, 06 No. Disc fitting, 20 Meters MS Channel, MS Angle, Clamps etc all complete material etc. from store Center Ghaziabad /Sahibabad /JE store to site of work including loading and unloading at both end.
Carriage of 900 Meter 3x120+1x195+1x16 mm2 and 450 Meter 3x95+1x70+1x16 mm2 Cable from store Center Ghaziabad /Sahibabad /JE store to site of work including loading and unloading at both end.
Carrige of Transformer from store center Ghaziabad/ Sahibabad/JE store to site of work including loading and unloading at both end. i) 250 KVA Transformer
ii) 400 KVA Transformer
Erection, Grouting & Foundation of Double Pole Structure 8.5/9/11/13 meter long PCC pole including the work of complete H.T. fittings as per RESPO manual and required for proper completion of work.
Installation and grouting of stay set including the work of nozelling etc. as per RESPO manual required for proper completion of work.
Laying sagging stringing, binding and jumpering etc of ACSR dog conductor on the newly erected pole as per RESPO manual and required for proper completion of work. (A) ACSR Dog Conductor
(B) LT, ABC 3x120+1x195+1x16 mm2
(C) LT ABC Cable 3x95+1x70+1x16sq mm2
Fixing of earthing rod as per RESPO manual and required for proper completion of work.
Construction of plinth of size 2MX2MX2.5M above ground level and one ft. below the ground level of 9”. After excavation of 4” earth, brick ballast shall be provided and rammering will be done properly after that a retaining wall of 9” width by first class brick in ratio 1:4 of cement and sand shall be made. The earth shall be filled upto one ft. below the top of the plinth. After this brick ballast shall be provided upto 6” from the earth level and froper rammering shall be done. One no. jaal of 12mm MS Tor shall be fixed in the hollow of the plinth and one ft. thick RCC in 1:2:4 ratio of cement , sand and stone ballast shall be laid on the of the plinth. The 12mm thick plastering shall be done all around the plinth in ratio 1:4 ratio of cement and sand. The contractor shall be responsible to complete the work as per direction of supervising Engineer. It includes the cost of labour, T&P, carrier etc. required for proper completion of the work (This material will be provided by the Contactor)
Fabrication of wire mesh Fencing Frames of different size fabricate out of MS angle iron of size 35X35X5mm². Each frame duly welded and fixing with wire mesh of size 25mmX25mmX10SWG hot dipped galvanized within the frame pressed under MS flats of size 40X5mm inside the angle on all four side with help of approx. 20NO Bolts &Nuts of 10mm diameter 45cm legs of frame will be grouted in 1:2:4 cement coarse send and 20mm gauge stone blast in the size of 0.22X0.22X0.45meter, Each will be painted with one coat of red oxide and two coat Aluminum paint of approved mark after proper cleaning. Fixing of wire mess fencing around on plinth of T/F with wire gauge 25X25mm, MS angle 35X35X5 mm with gate.
Proper Installation of 250/400 KVA Distribution Transformer & existing plinth/MS chair/ with the help of crane or manual at site. i) 250 KVA Transformer
ii) 400 KVA Transformer
Making of connection at both side of T/F with conductor & PVC Cable.
Providing and fixing of suspension/ holding Clamp made of MS Flat size 50X6mm suitable for pole as per RESSPO specification M.S clamps all sizes (This material will be provided by the Contactor)
Fixing LT distribution box 1/3 phase as per RESPO Specification.
Providing and fixing of MS bolt & Nuts of size (16X150mm, 4”X1/2” Ench, 1.5”X1/2” Ench, 1”X1/2” Ench) with 2No Bolts & Nuts size 16X100mm & off size half threaded of good quality. (This material will be provided by the Contactor)
Providing and fixing of Pircing Clamp as per RESSPO specification (piercing clamp)
Dismantling of OLD/Damaged Transformer from existing site (250KVA)
Dismantling of 140 Meter OLD/Damaged LT ABC 3x95+1x70+1x16sq mm2 cable from existing line.
Carrige of Old/Damaged 250 KVA Transformer and 140 meter AB Cable of 3x95+1x70+1x16sq mm2from site of work to store/JE store including loading and unloading at both end.
Providing and fixing of danger board.
MITTAL BROTHERS
Intelligent Smart Grid Pvt.Ltd
R. P. T. Electrical
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .