GE (AF) Bamrauli
GE (AF) Bamrauli
REPAIR MAINT OF EARTHING WORKS CHIMNEY UPS OF VARIOUS CAPACITY SENSOR GATE STORAGE TYPE WATER HEATERS SOLAR WATER HEATING SYSTEM AND VARIOUS TYPES OF ELECTRICAL APPLIANCES SUCH AS CEILING FANS EXHAUST FANS VENTILATION FANS INCL CERTAIN MISC EM WORKS
2026_MES_769498_1
8044/E8
Open Tender
Civil Works - Others
180 days
GE (AF) Bamrauli
As per tender documents
7 documents required · 7 mandatory
₹500
GE (AF) Bamrauli
₹70,000
3 Jun 2026
3 Jun 2026
24 Jun 2026
3 Jun 2026
22 Jun 2026
17 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Carrying out earth resistence test with digital earth resistence tester at various location in Airforce station Bamrauli,taking reading & noting down in register in the presence of user including tightening of nuts bolts,pouring of water in earth pit to reduce the resitivity of the soil,cleaning around the earth pit,proper checking of earth continuty conductor,replacement of epoxy based insulator,aluminium strip,copper strip,GI strip, pouring of chemical to enhace the conductivity of the soil.
Note- (i) Material used in repair/maint of earthing will be measured & Paid saperately Like Nutsbolts,insulator,strip,chemical.(ii) Earth record register to be provided by contractor.(iii) Testing to be carried out by skilled electrician.(iv) Earth result to be written with synthatic enamel paint on display board near earth pit.(v) Earth record register to be produced before Engr-In-Charge for checking at regular interval.(vi) Required T&P will be provided by contractor for carrying out earth resistence test. | 200 | Each Job | - | - |
| 2 | Taking down corroded Earth continuity GI/Aluminium/Copper strip fixed to wall on batten or any other indicated situation with porcelain vitreous white seperators, complete all as specified and directed. | 120 | RM | - | - |
| 3 | Supply & fixing of Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4mm dia galvanised iron or steel wire, complete all as specified and directed. | 30 | RM | - | - |
| 4 | Supply & fixing of Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 20x3 mm dia Copper strip, complete all as specified and directed. | 30 | RM | - | - |
| 5 | Supply & fixing of Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 32x6 mm dia GI strip, complete all as specified and directed. | 30 | RM | - | - |
| 6 | Supply & fixing of Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 25x3 mm dia aluminium strip, complete all as specified and directed. | 30 | RM | - | - |
| 7 | Supply and fixing of cast iron pitcover of existing size on earth pit with carring handle, complete all as specified and directed. | 6 | Each | - | - |
| 8 | Supply and pouring earth resistance lowering gel to reduce the earth resitsivity without excavating the soil, high viscosity in nature to be absorved by soil which creates bondage between electrode and soil, 6 kg contain in bucket Make Acculec power or other equivelent, complete all as specified and directed. | 10 | Each Set | - | - |
| 9 | Material and labour for repair of chemical earth pit by using liquid chemical earthing solution (not less than 10 Kg) and mixing with water and filling into the chemical earth pit to achieve the result less than 01 Ohm, complete all as specified and directed. | 10 | Each Job | - | - |
| 10 | Supply and lay 16 sqmm single core multistranded, PVC insulated copper conductor cable as earth continuty from strip to highly sensitive equipment which reqire zero voltage in neutral to earth, complete all as specified and directed. | 50 | RM | - | - |