Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.9 LAccepted-AOC BLD NO 2 BLOCK NO 6 PATEL COLONY LAXMI BAI LAD ROAD DAHISAR EAST 400068 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400068 | L1 | Accepted-AOC Lowest offer Accepted | |
| 2 | L2₹28.4 L+₹50,175 (1.80%)Rejected-Finance | L2 | Rejected-Finance Not lowest one | |
| 3 | Rejected-Technical | - | Rejected-Technical Documents not submitted as per NIT |
Tender Value
₹31.1 L
EMD Value
₹31,200
Closing Date
5 May 2025, 12:00 pmClosed
Superintending Engineer Mumbai
Office of the Superintending Engineer Mumbai MIDC HQ Udyog Sarathi Building Mahakali Caves
MBP M and R to MBP Annual Maintenance contract for maintenance of fire hydrant system with fire pump and maintenance of fire alarm system 2nd Call
2025_MIDC_1172716_1
MIDC/Mahape/Tender/2025-26/1
Open Tender
Civil Works
Item Rate
365 days
TTC Indl Area MBP Navi Mumbai
Please refer Tender documents.
2 documents required · 2 mandatory
₹10,030
₹31,200
30 Jul 2025
25 Apr 2025
6 May 2025
25 Apr 2025
5 May 2025
29 Apr 2025
28 Apr 2025 - 30 Apr 2025
Amount
SE.I Repairs / upgradation of existing Fire hydrant system & fire alarm system.
Supplying and erecting 12 V/180Ah Tubular battery with battery terminal wire, duly charged complete with 36 months warranty complete
Supplying and erecting 12 V/7Ah -7.5Ah SMF battery with battery terminal wire, duly charged complete with 12 months warranty complete
Supplying, erecting & terminating FR XLPE insulated, galvanised steel wire armoured (round) cable 1100 V, 2 core 2.5 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating FR XLPE insulated, galvanised steel wire armoured (round) cable 1100 V, 4 core 4 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, installation, testing and commissioning of booster fire pump [BP] suitable for water discharge of 450 LPM at 35 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 5.5 kW or of suitable kW capacity for manual/automatic operation and consisting of following : (a) Horizontal/vertical type, single/multi stage, centrifugal casing pump of cast iron body & bronze/CI impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520. (b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/BP
Supplying, installation, testing and commissioning of main fire pump (MFP/DP) suitable for water discharge of 1600 to 1800 LPM at 70 to 50 m head driven by 45 HP or suitable HP capacity diesel engine at required working speed suitable for manual/automatic operation and consisting of following : (a) Horizontal type, single stage, centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520. (b) Water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12/24 volts DC electric starting equipment with battery of required AH capacity with necessary charger suitable to work on 230v, 50Hz AC supply, diesel tank of minimum 150ltr capacity with first filling of diesel up to 100% level with necessary piping with valves up to engine, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications etc. as required. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with engine assembly and accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/SSC/DP
Supplying and erecting G.I. pipe ‘C’ class ERW 25 mm dia with necessary fittings duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete as per specification no. FF-PP
Supplying and erecting G.I. pipe ‘C’ class ERW 75/80 mm dia with necessary fittings duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete as per specification no. FF-PP
Supplying and erecting G.I. pipe ‘C’ class ERW 100 mm dia with necessary fittings duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete as per specification no. FF-PP
Supplying and erecting G.I. pipe ‘C’ class ERW 150 mm dia with necessary fittings duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete as per specification no. FF-PP
Supplying and erecting 80 mm dia cast iron foot valve ball type/flap type with strainer for negative suction complete as per specification no. FF-VL/FV
Supplying and erecting 200 mm dia cast iron foot valve ball type/flap type with strainer for negative suction complete as per specification no. FF-VL/FV
Supplying and erecting 75/80 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying and erecting 100 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying and erecting 150 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying and erecting stainless steel single outlet hydrant valve fitted with necessary accessories complete as per specification no. FF-VL/HV
Supplying and erecting 25 mm Ball Valve complete with PN16 pressure rating, as per specification no. FF-VL/BV
Supplying and installing wall mounting swinging hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene (Polyhose) alongwith necessary accessories complete as per specification no. FF-FFA/HV
Supplying and erecting 63mm dia, reinforced rubber lined (R.R.L.) hose pipe, 15m in length, fitted with necessary accessories complete as per specification no. FF-FFA/RRL
Supplying and erecting gun metal branch pipe of 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle complete as per specification no. FF-FFA/NZ
Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, erected with provided G.I. pipe, elbow etc. complete as per specification no. FF-FFA/PG
Supplying and erecting 63mm dia, controlled percolation (C.P.) hose pipe, 15m in length, fitted with necessary accessories complete as per specification no. FF-FFA/CPH
Supplying, erecting testing and commissioning Optical Type Smoke Detector on suitable back box with necessary connections complete as per specification no. FF-FAS/SD
Supplying, erecting, testing and commissioning hooters having high (100dB @ 1m) and low (94dB @ 1m) volume setting, group addressing facility allowing multiple sounders to be activated with CRCA enclosure complete as per specification no. FF-FAAS/HTR
Supplying, installing, testing and commissioning remote response indicators suitable to operate on 5 - 28 V dc supply having FR Polymer ABS Housing complete as per specification no. FF-FAAS/RRI
Supplying, installing, testing and commissioning of addressable manual call points ( break glass type/pull station type), made of addressable break glass plastic square in shape surface/flush mounted with "Break Glass" massage embedded on the glass, complete erected with mounting base and required accessories, Module shall conform to EN 54/VdS / UL & FM approved with 3 years equipment replacement warranty, as per specification no FF-AFAS/MCP.
Making trench in Hard murum/Tar road having 0.75m depth and minimum 0.3m width for laying provided cables up to voltage level 1.1kV cable complete as per specification no. CW-EXN-CTR
Supply & installation of PVC blank cap with chain to suit existing hydrant valve.
Supply & installation of Ring Washer, Spindle Washer & servicing of hydrant valve.
Supply & Installation of Hose Box Glass
Supply & Installation of Rubber Gasket for Hose Box.
Supply & Installation of Hose Box Key Glass.
Supplying, installation, testing & commissioning of Heavy duty Ball Type Foot Valve for Jockey Pump including supply of Nut Bolts Gasket etc. complete. (Make Normex
Providing and applying primer and one coat of red oxide of iron paint externally including cleaning the surface of the pipes with steel scrappers, wire brushes, and metal cleaning solution, etc
Supply & Installation of Single Door Hose Box.
PCC / RCC for Road Crossing.
Supply & Installation of Structural Steel support for Pipe line, Supports etc.
Supplying, installing, testing and commissioning of 8 Zone Microprocessor based, conventional fire alarm control panel (FACP) with standard accessories , 16x2 Character LCD Display, provision for zone wise contact and beep sound alarm, suitable to operate on 120-220 V AC, complete as per specification no. FF-FAAS/FACP
Supplying, installing, testing and commissioning of 16 Zone Microprocessor based, conventional fire alarm control panel (FACP) with standard accessories , 16x2 Character LCD Display, provision for zone wise contact and beep sound alarm, suitable to operate on 120-220 V AC, complete as per specification no. FF-FAAS/FACP
Supplying and erecting female coupling.
Repairing and commissioning of existing diesel engine fire pump.
Varnishing of hydrant main fire pump motor of fire fighting system and servicing of pump & motor including changing of bearing, bushing, oil, seal, rubber packing, etc. as per requirement. The scope of work including dismantling of existing pump & motor and re-installation of the same as per site condition.
Varnishing of Jockey / booster pump motor of fire fighting system and servicing of pump & motor including changing of bearing, bushing, oil seal, rubber packing, etc. as per requirement. The scope of work including dismantling of existing pump & motor and re-installation of the same as per site condition.
Servicing of Diesel Engine of Fire Fighting System with top overhauling of Diesel Engine Driven Pump including Changing of Engine Oil, Oil Filter, Fuel Filter, Coolant & Replacement of Piston Ring & Injector , Calibration of Fuel Pump, Servicing of Starter Alternator , Replacement of liner & Starter Panel , Repairing Cylinder head etc. complete. The scope of work including dismantling of existing pump & motor and re-installation of the same as per site condition.
Supply of diesel for day to day maintenance and operation of diesel Engine driven pumps including transportation.
Sub Estimate -II: AMC for Maintenance of Fire Hydrant System & Fire Alarm System
Annual maintenance contract for the work of 'Fire Hydrant System with Fire Pump' consist of provision for skilled technical staff, semi skilled / unskilled workers if required, electrician, plumber, including day to day maintenance; entire maintenance of Fire pump, maintenance of electrical panels, relays, electrical motors; Providing field testing and giving demonstration by every 15 days to allottees in the park; running of Fire pump every saturday minimum 1 Hr.; maintenance of Fire Hydrant, wet risers, including their other accessories like sluice valve; maintenance of electrical data history sheets including every type of maintenance in the fire hydrant system including jocky pumps / booster pumps including safety, security, insurance etc. complete. The agency has to maintain the Fire Hydrant System of total 19 buildings. The item is excluding all the maintenance material & spare parts required for the above mentioned works and machinaries . The same shall be paid separately if required.
Annual maintenance contract for the maintenance of fire alarm system provided in the buildings including regular checking, deployment of fire safety engineer along with skilled technicians, supervision includes report of systems function conditions, maintenance of smoke detector, Repairing of existing Fire Alarm Panel, fixing of new fire extinguisher as per requirment , demonstration of safety measures to be adopted for prevention of fire & use of fire hydrants in case of fire etc once in a week etc. complete. The agency has to maintain the Fire Alarm System of total 9 buildings. The item also includes round the clock for monitoring of fire system. The agency has to monitor & take appropriate action immediately during any fire hazard including buildings mentioned in item No.1.
Jagraj Construction Co. (BID ID -6644823)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .