85897 PREVENTIVE MAINTENANCE AND SERVICING TO CENTRAL AIR CONDITIONING PLANT AND OTHER CONNECTED AREA OF AGE E/M-II UNDER GE SOUTH PUNE
2024_MES_643180_1
85897 CWE PUNE
Open Tender
Electrical and Maintenance Works
Item Rate
333 days
GE (SOUTH) PUNE
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹1,000
GE (SOUTH) PUNE
₹1.9 L
Yes
13 Apr 2024
20 Feb 2024
28 Mar 2024
20 Feb 2024
26 Mar 2024
13 Mar 2024
Amount
Comprehensive maintenance, preventive/ periodical, routine and corrective (break down), maintenance, servicing, cleaning, inspection and testing of VRF Type AC Plant and Treated Fresh Air Unit at new CMDC including repair/ replacement of defective components/ parts/ fittings/ sensors /control & power wiring, gas charging and leakage detection including pressure testing of VRF/TFA copper pipes including replacement of defective copper pipes as and when required of indoor and outdoor unit of VRFTFA System through OEM- Daikin or their authorised dealer, comprising of following equipment of following capacity all as specified and directed. (i) VRF type AC Plant of capacity 18 HP (Make - Daikin, Model No -RXQ18ARY6) - 04 Nos (ii) VRF type AC Plant of capacity 14 HP (Make - Daikin, Model No-RXQ14ARY6) - 02 Nos (iii) Treated Fresh Air Unit 4 TR (Make - Daikin, Model - RGF48CRY16) - 4 Nos
Note No-1 :- (a) Dismantling of out door unit covers of VRF/TFA unit of any capacity completely by disconnecting/ covering all electrical/ electronic boards and wiring and servicing condensor coils completely and servicing by using approved chemicals by OEM and replace all defective /unserviceable parts of units through OEM M/S Daikin or their authorised dealer, re-assembling setting all parameters by using softwares by an OEM Engineer. (b) Dismantling of any types of indoor unit covers of VRF/TFA unit of any capacity completely by disconnecting/covering all electronics boards and wiring and servicing cooling coils, expansion valves, indoor drainage pumps, drainage lines completely and servicing by using approved chemicals and replace all defective/unserviceable parts of units through OEM by using tray jackets including cleaning the surface after servicing testing all as directed by Engineer-in-Charge. (i) Contractor should prepare breakdown servicing report card & kept on record duly signed by Engineer-in-Charge. (ii) All types of spare spare parts if defective / unserviceable of indoor and outdoor units are included in Comprehensive maintenance and replaced by contractor through OEM (Cost of the same is included in quoted rate & no extra cost admissible in this regard):-
(iii) Out door units (Make: Daikin) of capacity mentioned below:- Total number of outdoor unit - 06 Nos and total capacity of outdoor units - 18 HP and 14 HP. TFA Unit 4 TR - 04 Nos (iv) Indoor units (Make: Daikin) of capacity upto 3 TR- 16 Nos, 2 TR - 28 Nos, 1.5 TR - 02 Nos, AHU 800 C (v) Cost of refrigerant gas, pressure switch, pressure sensor, operation switch, thermostat, fuse, thermistor, fusible plug, expansion valve, pressure relief valve, stop valve, adjust valve, economizer assembley, compressor, fan motor, magnetic switch, overcurrent relay auxiliary switch, hour meter, solenoid valve oil heater current sensor, main PCB, noise PCB and compressor oil will be included in quoted rate. (vi) The rate for replacement of damage communication cable will also included in quotated rate. (vii) The contractor is liable to maintain 21 degree centigrade temperature (plus/minus 2 degree C) and 50 % relative humidity (plus/minus 5%) in the rooms.FM - 04 Nos. The cost of spares and labour for any minor or major repairs of VRF type Air Conditiong plants/ TFA Unit and connected Casset type Unit or split type unit or upto 3 TR as and when required (as recommended by the OEM during inspection/analysis report) shall be provided by the contractor at no extra cost and rate for the same are deemed to be included in the unit rates of item as above
2) Scope of Comprehensive Maintenance is as follows :- (a) Diagnose the fault and rectify the defects detected in reasonable time. (b) Repair /replace the faulty minor and major parts etc. of the equipments. (c) All periodical and preventive maintenance shall be carried out through OEM (Daikin) or OEM authorised personnel or their authorised dealer (d) Attend all break down as and when required. (e) The cost of spares parts for repairs of oudoor/indoor units as and when required for smooth reliable operation with high efficiency (as recommended by the OEM during inspection/analysis report) shall be provided by the contractor at no extra cost and rate for the same are deemed to be included in the unit rates of item as above.
(f) The Contractor has to attend the unscheduled service calls as and when required for locating the faults and rectify the same within 04 hours. In case of any fault in the machineries due to which the plant is put off more than 04 hours the following penalties shall be recovered from the contractor : (i) Rs. 5000/- Per hours will be recovered from the contractor for non rectification of defect/replacement of any unserviceable spares after 04 hours from lodging of complaint telephonically or verbaly. (ii) Thereafter Rs. 10000/- will be added every day till rectification of fault/replacement of unserviceable spares as directed by the Engineer-in-Charge. (h) The service Engineer from M/S Daikin (OEM) will visit the TFA unit/VRF AC plant every two month in contract period for inspection and servicing of all indoor/oudoor units and will submit inspection and servicing report to the Engineer-in-charge (g) Necessary repair action of urgent nature should be taken immideately whether it is working hours or holidays if/as required and no additional charges will be payable. (h) Before completion, one leakage test to be done by contractor in the presence of Engineer of OEM and certificate submitted to Engr-in-charge. (j) During comprehensive maintenance period if any indoor VRF/TFA unit and any outdoor VRF/TFA unit any type/any model/capacity unserviceable then contractor should replace the same with new one without extra cost.
Preventive, Scheduled maintenance and attending breakdown round the clock for AC Plant at Main Hospital Building at new CHSC for Centrifugal Water Cooled Chilling M/C of 500 TR with R - 134 A refrigerant, open / semihermatic / hermatically sealed centrifugal compressor, direct / gear driven by suitable KW Sq. Cage induction motor complete with variable speed drive, water-cooled shell & tube condenser, insulated shell and tube flooded chiller, flow switches at condenser & chiller outlet, refrigerant piping, Refrigerant and Oil (First Charge), flexible pipe connector at condenser & chiller inlet / outlet, integral lubrication system, Microprocessor based control panel, chiller / floor mounted VSD & accessories etc. all mounted on M.S. frame suitable for 415 volts ± 10%, 50Hz ± 5 %, three phase A.C. supply. specifications & having interface card compatible with BMS system maintaining following parameters: Condenser : CDW IN - 32.22º C. / CDW OUT - 36.39º C./ FLOW - 7560 LPM / Fouling Factor (MKS) - 0.0002 / Pressure Drop Max - 8.5 Meter Chiller : CHW IN - 12.22º C. / CHW OUT - 6.67º C./ FLOW - 4536 LPM /Fouling Factor (MKS) - 0.0001/Pressure Drop Max - 7.5 Meter
Details of equipment installed: (a)500 TR centrifugal water cooled chillers=4 Nos.(Mcquay make) (b)Chilled Water Pumps (Primary)= 3 Nos. (c) Chilled Water Pumps (Secondary)=3 Nos. (d) Condenser Water centrifugal Pumpsets 55KW/75HP,7560LPM=4 Nos. (e) Primary chilled water centrifugal pump sets 25HP,4536LPM =04 nos (f) Secondary Chilled water centrifugal pump,TEFC 40 HP,4536 LPM=04 Nos (g) variable speed pumping system for secondary pumps(h)FRP induced draft Cooling Tower 550TR =04Nos(j) VFD systems for cooling tower10 HP=8 machines.(h) Hot water generator of 500KW =03 nos(k) HW monoblock pump set 7.5HP,522 LPM=04 Nos (l) double skin Floor Mounted AHU’s 2000 to 16000CFM = 70 Nos.(m) Ceiling suspended AHU 3000CFM=06 Nos (n) supervisory controllers for BMS,DDC,CHW,CDW,CT,HWG,AHU(g)AHU Blower variable speed drive (VFD)=10 Nos. (o) 200mm Air Separator=1 No. (p) inline fan300 to 2000 CFM= 46No. (q) HRV units =5 Nos. (r) Closed vessel expansion tank complete With all accessories=1No. (s)Jet diffusers=130 Nos. (t) Smoke Extraction Fan= 22 Nos. (u)Inline Fan & Propeller Fans=1 Nos. (v) Electrical Control Panel in AC Plant, Control Console Panel & AHU Room Panels (w)Associated work such as piping, valves and (x) Fan coil units 1 TR to 2.5TR=175 nos (y) Floor mounted air washer 25000 to 30000CFM=03 Nos (z)Pressure fans 10000 to 15000CFM=28 Nos
Preventive, Scheduled maintenance and attending breakdown round the clock for AC Plant at MDTC at new CHSC for Centrifugal Water Cooled Chilling M/C of 100 TR with R - 134 A refrigerant, open / semihermatic / hermatically sealed centrifugal compressor, direct / gear driven by suitable KW Sq. Cage induction motor complete with variable speed drive, water-cooled shell & tube condenser, insulated shell and tube flooded chiller, flow switches at condenser & chiller outlet, refrigerant piping, Refrigerant and Oil (First Charge), flexible pipe connector at condenser & chiller inlet / outlet, integral lubrication system, Microprocessor based control panel, chiller / floor mounted VSD & accessories etc. all mounted on M.S. frame. suitable for 415 volts ± 10%, 50Hz ± 5 %, three phase A.C. supply. Condenser : CDW IN - 32.22º C. / CDW OUT - 36.39º C./ FLOW - 1512 LPM / Fouling Factor (MKS) - 0.0002 / Pressure Drop Max - 6.5 Meter Chiller : CHW IN - 12.22º C. / CHW OUT - 6.67º C./ FLOW - 907 LPM /Fouling Factor (MKS) - 0.0001/Pressure Drop Max - 6.0 Meter
Details of equipment installed: (a)100 TR centrifugal water cooled chillers = 2Nos. (Mcquay make) (b) Chilled Water Pumps = 2 Nos. (c) Condenser Water centrifugal Pumpsets 15HP=2 Nos. (d) FRP induced draft Cooling Tower 125TR =02 Nos (e) Hot water generator of 75KW =02 nos (f) HW monoblock pump set 3HP=02 Nos (g) double skin Floor Mounted AHU’s 3000 to 8000CFM = 8 Nos. (h) Ceiling suspended AHU 3000CFM=01 Nos (j) Electrical Control Panel in AC Plant & AHU Room Panels (k) Associated work such as piping, valves and (l) Floor mounted air washer 25000 to 30000CFM=02 Nos
(iii) Contractor has to maintain all the equipments by regular preventive maintenance for troublefree operation by deputing suitable manpower on demand at one hour notice otherwise Compensation will be recovered @ Rs. 10000 per day from the FB/RAR of the contractor for non-functioning of HVAC system with no payment for comprehensive maintenance and operation on pro-rata basis for the day. (iv) The agency has to do balancing and motor alignment as and when required and nothing extra shall be paid on this account. (v) The firm shall maintain history cards of each equipment maintained under their control. There shall be checklist for preventive & comprehensive maintenance schedule including de-scaling servicing, general cleanliness & checking etc. which will be carried out monthly. (vi) Contractor will depute 1xAC technician with minimum five years experience in repairing 500 TR capacity chiller plants, 1x Electrician with minimum five years experience in repairing of VFD, ACB, LT panel and MCC Panels and 2x Helpers with working knowledge in Ref &AC and Electric Supply for repair works.
Disconnecting electrically and mechanically defective/burnt squirrel cage induction motor, shifting to civil workshop, opening for inspection, removing of unserviceable ball bearings, gaskets etc, cutting of old burnt winding, cleaning of slots, fixing of insulated material, winding with new super enemelled copper winding wire of suitable gauge, varnishing, re-assembling, transporting to site, re-fixing at existing location, connecting mechanically, electrical connections, testing to entire satisfaction of Engineer-in-charge all as directed at site for capacity 1 HP to 2 HP. (Note: - (i) Shifting of Motor and transportation cost shall included in quoted rates. (ii) Cost of spares will be measured and paid seperately under relevant items.)
All as per Item No. 05 here-in-above but 3 HP capacity.
All as per Item No. 05 here-in-above but 5 HP capacity.
All as per Item No. 05 here-in-above but 7.5 HP capacity.
All as per Item No. 05 here-in-above but 10 HP capacity.
All as per Item No. 05 here-in-above but 12.5 HP capacity.
All as per Item No. 05 here-in-above but 15 HP capacity.
All as per Item No. 05 here-in-above but 20 HP capacity.
All as per Item No. 05 here-in-above but 25 HP capacity.
All as per Item No. 05 here-in-above but 40 HP capacity.
All as per Item No. 05 here-in-above but 75 HP capacity.
Disconnecting mechanically centrifugal pump of capacity 1 HP to 2 HP, shifting to civil workshop, opening for inspection, removing of unserviceable parts like ball bearings, impellers, impeller nut, 'O' ring, eye ball, shaft, bearing housing, gland packing, gasket set etc & replacement of old unserviceable spares with new ones, re-assembling, shifting to site, re-fixing at existing location, connecting mechanically, testing to entire satisfaction of Engineer-in-charge all as directed. [Note: - (i) Shifting of Motor and transportation cost shall included in quoted rates. (ii) Cost of spares will be measured and paid seperately under relevant items.]
All as per Item No. 16 here-in-above but 3 HP capacity.
All as per Item No. 16 here-in-above but 5 HP capacity.
All as per Item No. 16 here-in-above but 7.5 HP capacity.
All as per Item No. 16 here-in-above but 10 HP capacity.
All as per Item No. 16 here-in-above but 12.5 HP capacity.
All as per Item No. 16 here-in-above but 15 HP capacity.
All as per Item No. 16 here-in-above but 20 HP capacity.
All as per Item No. 16 here-in-above but 25 HP capacity.
All as per Item No. 16 here-in-above but 40 HP capacity.
All as per Item No. 16 here-in-above but 75 HP capacity.
Supply only ball bearing model 6202 of size (Pump and motor 1 HP to 2 HP). Make-SKF/TATA/NBC/HMT.
All as per Item No. 27 here-in-above but 6203 (Pump and motor 3 HP).
All as per Item No. 27 here-in-above but 6204 (Pump and motor 5 HP).
All as per Item No. 27 here-in-above but 6205 (Motor 7.5 HP).
All as per Item No. 27 here-in-above but 6306 (Motor 10 HP).
All as per Item No. 27 here-in-above but 6205 (Pump 10 HP).
All as per Item No. 27 here-in-above but 6306 (Motor 12.5 HP).
All as per Item No. 27 here-in-above but 6307 (Motor 15 HP).
All as per Item No. 27 here-in-above but 6311 (Motor 20 HP).
All as per Item No. 27 here-in-above but 6206/6207 (Pump and motor 25 HP).
All as per Item No. 27 here-in-above but 6308/6309 (Pump and motor 40 HP).
All as per Item No. 27 here-in-above but 6312/6313 (Pump and motor 75 HP).
M&L for lathe work/machining work for shaft of centrifugal pump set of capacity 1 HP to 2 HP, grinding, polishing and matching to reqiured size/shape all as directed by the Engr-in-Charge.
All as per Item No. 39 here-in-above but for pump set of capacity 3 HP complete all as specified and as directed
All as per Item No. 39 here-in-above but for pump set of capacity 5 HP complete all as specified and as directed
All as per Item No. 39 here-in-above but for pump set of capacity 7.5 HP complete all as specified and as directed.
All as per Item No. 39 here-in-above but for pump set of capacity 10 HP complete all as specified and as directed to 12.5 HP complete all as specified and as directed.
All as per Item No. 39 here-in-above but for pump set of capacity 15 HP complete all as specified and as directed.
All as per Item No. 39 here-in-above but for pump set of capacity 20 HP complete all as specified and as directed.
All as per Item No. 39 here-in-above but for pump set of capacity 25 HP complete all as specified and as directed.
All as per Item No. 39 here-in-above but for pump set of capacity 40 HP complete all as specified and as directed.
All as per Item No. 39 here-in-above but for pump set of capacity 75 HP complete all as specified and as directed.
Supply only gun metal impeller suitable for 1 to 2 HP capacity centrifugal pump set as per existing model and make for Kirloskar make pump set.
All as per Item No. 49 here-in-above but for pump set of capacity 3 HP complete all as specified and as directed.
All as per Item No. 49 here-in-above but for pump set of capacity 5 HP complete all as specified and as directed to 7.5 HP complete all as specified and as directed.
All as per Item No. 49 here-in-above but for pump set of capacity 10 HP complete all as specified and as directed to 15 HP complete all as specified and as directed.
All as per Item No. 49 here-in-above but for pump set of capacity 20 HP complete all as specified and as directed to 25 HP complete all as specified and as directed.
All as per Item No. 49 here-in-above but for pump set of capacity 40 HP complete all as specified and as directed.
All as per Item No. 49 here-in-above but for pump set of capacity 75 HP complete all as specified and as directed.
Supply only V belt or link belt of size A26, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size A29, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size A30, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size A31, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size A36, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size A37, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size A38, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size A39, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size A43, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size A44, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size A45, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size A46, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size A47, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size A48, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size A51, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size A61, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size A63, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size A64, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size B25, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size B28, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size B29, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size B30, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size B31, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size B32, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size B33, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size B36, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size B38, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size B39, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size B49, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size B58, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size B60, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size B61, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size B63, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size B72, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size B73, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size B92, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size B94, Make : Fenner or equivalent as approved by GE.
Supply only V belt or link belt of size B102, Make : Fenner or equivalent as approved by GE.
Supply only flexible tyre coupling of size TC-015 including , nuts, bolts and washers suitable for centrifugal motor pump set 30/40HP capacity match with existing one complete all as specified and as directed
All as per Item No. 94 here-in-above but of size TC-014 complete all as specified and as directed.
All as per Item No. 94 here-in-above but of size TC-013 complete all as specified and as directed.
All as per Item No. 94 here-in-above but of size TC-012 complete all as specified and as directed.
All as per Item No. 94 here-in-above but of size TC-011 suitable for pump set of capacity 10 HP complete all as specified and as directed.
Supply of PVC fills suitable for cooling tower 550 TR (1995840 Kcal/hr) of existing size and thickness not less than 0.2 mm complete all as specified and as directed.
Supply of PVC fills suitable for cooling tower 125 TR (362880 Kcal/hr) of existing size and thickness not less than 0.2 mm complete all as specified and as directed.
Descaling AHU’s cooling coil of capacities 2000 to 5000CFM, by opening of cooling coil, circulating acid / suitable chemical for removing all foreign material gathered in the coil, cleaning of all filters, re-fixing and testing complete all as specified and directed by Engineer-in-Charge.
All as per Item No.101 here-in-above but 5500 to 9000 CFM complete all as specified and as directed.
All as per Item No.101 here-in-above but 10000 to 15000 CFM complete all as specified and as directed.
Supply only prefilter of non woven synthetic media of 10 micron particle size with an efficiency of 90% complete all as specified and as directed.
Supply only Fine filter of non woven synthetic media of 5 micron particle size with an efficiency of 90% complete all as specified and as directed.
Supply only PU foam of 23mm thick and 36 Kg/cum complete all as specified and as directed.
Supply only PU foam of 48mm thick and 36 Kg/cum complete all as specified and as directed.
Supply only Pressure Independant Balancing Cum Two Way Control Valve in a single body equipped with electronic modulating actuator working on 2-10 V DC, 4- 20 mA electric signal. The minimum close off Pressure of actuator must be 1.5 times shut off head of pump as per specifications of following sizes:
20 mm Dia, Maximum 6 GPM
25 mm Dia, Maximum 8 GPM
32 mm Dia, Maximum 17 GPM
40 mm Dia, Maximum 26 GPM
50 mm Dia, Maximum 50 GPM
65 mm Dia, Maximum 72 GPM
80 mm Dia, Maximum 132 GPM
Supply only digital display type thermostat & humidistat for various OT Air Handling Units including temperature and humidity sensor. The thermostat shall have provision of setting of space temperature and space RH as per requirement. Unit controller shall be installed in OT Room.
M&L for replacement of Proportional cooling / heating type digital display type thermostat at air-handler.
M&L for replacement of Snap Acting digital display type Humidistat at air-handler.
M&L for automatic control for Fan Coil Units consisting of pressure independant balancing cum two way control valve & digital thermostat, which will have provision of setting of room temperature, setting of fan speed (High, Medium, Low).
M&L for repair of Inline fans with motor incl rewinding with superenamelled copper wire of existing gauge incl appropriate class of insulation, incl replacement of bush , ball bearing and inbuilt speed controller complete in all respect & of following capacities.
300 CFM (8mm static pressure, single phase)
500 CFM (10mm static pressure, single phase)
600 CFM (10mm static pressure, single phase)
700 CFM (10mm static pressure, single phase)
800 CFM (12mm static pressure, single phase)
900 CFM (12mm static pressure, single phase)
1000 CFM (15mm static pressure, single phase)
1200 CFM (15mm static pressure, single phase)
1500 CFM (15mm static pressure, single phase)
1800 CFM (15mm static pressure, three phase)
2000 CFM (15mm static pressure, single phase)
Supply only Laminar air flow pattern perforated plenum made of 16 G aluminium sheet, Aluminium VCD, DOP tested with Hepa filters of efficiency 99.97 % down to 0.3 micron particle size & suitable for operation theatre with all accessories as required & to suit site condition of size 2.4 x 2.7 m² complete all as specified and as directed.
Supply only bare chilled / condenser / Hot water piping of M.S 'Heavy' Class complete with fittings like elbows, tees, reducers, bends, MS flanges, supports, welding, painting etc. but excluding valves as required conforming to IS:1239 / 3589 & technical specification. All outdoor condenser water piping shall be treated with Zinc Cromate Primer plus two coats of Epoxy Paints.
25 mm dia pipe
32 mm dia pipe
40 mm dia pipe
50 mm dia pipe
65 mm dia pipe
80 mm dia pipe
100 mm dia pipe
125 mm dia pipe
150 mm dia pipe
200 mm dia pipe
250 mm dia pipe
300 mm dia pipe
400 mm dia pipe
450 mm dia pipe
Supply only motorised on / off butterfly valves with modulating motor in return chilled & condenser water line of each chiller, condenser & cooling tower operated through BMS & of following sizes:
250 mm dia (For Chillers)
400 mm dia (For Condenser & Cooling Towers)
450 mm dia (For Condenser & Cooling Towers)
Supply only automatic balancing valves in return chilled and condenser water line of each chiller, condenser and cooling tower per existing of following sizes:
250 mm dia (For Chillers)
400 mm dia (For Condenser & Cooling Towers)
450 mm dia (For Condenser & Cooling Towers)
Supply only of following sizes CI butterfly valves in chilled / condenser water line as specified and directed
50 mm dia
65 mm dia
80 mm dia
100 mm dia
125 mm dia
150 mm dia
200 mm dia
250 mm dia
300 mm dia
350 mm dia
Supply only of following sizes CI globe valves in chilled / condenser water line as specified and directed :-
25 mm dia
32 mm dia
40 mm dia
Supply only of following sizes CI Check valves in chilled / condenser water line as specified and directed
250 mm dia
100 mm dia
Supply only of following sizes Y strainers in chilled / condenser water line MS construction as specified and directed
25 mm dia
32 mm dia
40 mm dia
50 mm dia
65 mm dia
80 mm dia
200 mm dia
250 mm dia
Supply only alcohol fitted 'V' form thermometer of approved make . (For Floor Mounted AHU, Chiller & Condenser)
Supply only pressure guage of approved make of dia 150 mm (For Floor Mounted AHU, Chiller, Condenser & All Pumps)
Supply only condensate drain water piping of GI 'Medium' class complete with fittings like elbows, tees, reducers, bends, MS flanges, supports, welding, painting etc. as required , specified and directed and of following sizes.
25 mm dia pipe
32 mm dia pipe
40 mm dia pipe
50 mm dia pipe
65 mm dia pipe
80 mm dia pipe
100 mm dia pipe
Supply only chilled water piping with Closed Cell Elastomeric Nitrile Rubber of specified thickness and suitable for indoor application. Outdoor pipe from AC Plant shall run in pucca concrete trench & shall be insulated as per indoor application for the following complete all as specified and directed :-
25 mm dia
32 mm dia
40 mm dia
50 mm dia
65 mm dia
80 mm dia
100 mm dia
125 mm dia
150 mm dia
200 mm dia
250 mm dia
350 mm dia
400 mm dia
300 mm dia
S&F Insulation on valves with Closed Cell Elastomeric Nitrile Rubber of existing thickness & suitable for indoor application for Motorised Butterfly Valves of following sizes:
250 mm dia (For Chillers)
100 mm dia (For Hot Water Generator)
All as per item no 126 but Butterfly Valves of following sizes :-
50 mm dia
65 mm dia
80 mm dia
100 mm dia
125 mm dia
150 mm dia
200 mm dia
250 mm dia
300 mm dia
350 mm dia
400 mm dia
All as per item No. 126 but Globe Valves of following sizes
25 mm dia
32 mm dia
40 mm dia
All as per item no 126 but Check Valves of following sizes
250 mm dia
100 mm dia
All as per item no 126 but Automatic Balancing Valves of following sizes
250 mm dia (For Chillers)
100 mm dia (For Hot Water Generator)
All as per item no 126 but Y-strainer of following sizes
25 mm dia
32 mm dia
40 mm dia
50 mm dia
65 mm dia
80 mm dia
100 mm dia
250 mm dia
M&L for replacement of auto air vent valve of following sizes:-
10 mm dia auto air vent valve
19 mm dia auto air vent valve
25 mm dia auto air vent valve
M&L for butt welded joint for joining circumferential pipe to itself, fittings, flanges, Valves, and other equipment all as specified and directed.
M & L for painting of MS Pipes or Steel surfaces after preparing of old painted surfaces and priming with one coat of Red oxide primer and painting with two coat synthetic enamel paint colour as approved by Engr-in-charge.
M&L for replacement of acoustic insulation on four walls & ceiling of AHU Rooms with 50 mm thick fibre glass of density 32 Kg/m³ fixed in square frame box of size 610 x 610 mm, frame made of 24 G GI sheet of size (25 - 50 - 50 - 50 - 25 mm) coverd with fibre glass tissue paper and finally finished with 0.5mm thick perforated aluminium sheet & conforming specification. All vertical & horizontal joints to be sealed with 25 mm wide 1.0 mm thick aluminium beading.
M&L for replacement of multiblade box type Galvanized Sheet Steel construction damper for ducts to be provided with suitable links and quadrants for control of volume of air complete all as specified and as directed.
M&L for replacement of multiblade box type Aluminium Sheet construction damper for ducts to be provided with suitable links and quadrants for control of volume of air complete all as specified and as directed. (For OT Only)
M&L for replacement of insulated Flexible ducting made of double lamination of Metalized Polyster Film permanentaly bounded to a coated spring steel wire helix & resistant construction to tear & puncture branch & collar wherever suitable & of following sizes:
200 mm dia.
250 mm dia.
300 mm dia.
M&L for replacement of Aluminium sheet metal ducting duly polysulphide sealed complete with Spliter Damper, vanes etc. as required for OT and as per ISI specifications and as per approved shop drawings.
M&L for replacement of following acoustic lining of duct with fibre glass rigid board of density 48 Kg/m³ sealed in fibre glass tissue paper and covered with 0.5 mm thick perforated aluminium sheet and conforming to specification given in the tender.
12 mm thick fibre glass rigid board.
25 mm thick fibre glass rigid board.
M&L for replacement of external thermal insulation on ducts with Cross Linked Closed Cell Polyethylene FR-XPE insulation, tape & adhesive (pidilite SR -998) as required of following thickness.
6 mm thick
9 mm thick
13 mm thick
M&L for replacement of Duct / Wall mounted GI Fire Dampers actuated with the help of 24 V electric actuator and as per specifications excluding actuator.
M&L for replacement of Motorised Spring Return Actuator for devices upto 0.8 sq. metre with with control panel & temperature sensor.
M&L for replacement of Immersion Temperature sensor for Chilled water system all as specified and directed.
M&L for replacement of Ambient air temperature and humidity sensor all as specified and directed.
M&L for replacement of Current relay for pumps all as specified and directed.
M&L for replacement of Differential pressure switch for various vent. fans all as specified and directed.
M&L for replacement of Differential pressure switch for AHU blower status all as specified and directed.
M&L for replacement of Differential pressure switch for AHU pre, fine & hepa filter status all as specified and directed.
M&L for replacement of Temperature sensor for return temperature monitoring all as specified and directed.
M&L for replacement of Digital electronic multimeter all as specified and directed.
M&L for replacement of Pressure Transducer all as specified and directed.
M&L for replacement of Ultrasonic Type Water flow meter (5,400 USGPM For Header) all as specified and directed.
M&L for replacement of ICU pressure monitor system with the following specifications :- High precision ICU pressure monitor system fitted at entrance of the ICU to view positive pressure inside the ICU. Positive and negative pressure cubical shall be fitted with separate ICU pressure monitoring system. (Make/Manufacturer :- Western India Electromedical systems pvt. ltd. model No PS-066 or any other equivalent model in Hospedia medicare/Becon Meades/Penlon/CMS)
Supply only Laminar air flow pattern perforated plenum made of 16 G aluminium sheet, Aluminium VCD, DOP tested with Hepa filters of efficiency 99.97 % down to 0.3 micron particle size with all accessories as required & to suit site condition of size 2.1 m x 2.1 m
Supply, installation & testing of HEPA filter made of media microfiber glass protected with aluminium mesh, flange type, Al frame efficiency 99.97% down to 0.3 micron particle size, filter size 610x610x75mm including rubber gasket, rivets and other accessories including submission of test report from authorised NABL Lab.
M&L for Servicing /Caliberation / Repairs to Air circuit Breaker Model UW1-20 N ,800-2000A, Four pole incl cleaning of Fixed and moving contacts,shut release coil and operating mechanism. Spares reqd for replacement will be measured and paid separately all as specified and directed.
Spares for Air circuit breaker Model: UW1-20N,2000A, Make L&T or equivalent as approved by GE.
Supply only draw out ACB's terminal adapters frame 1,2000A N (vertical/Horizontal) all as specified and directed.
Supply only operation counter all as specified and directed.
Supply only door interlock all as specified and directed.
Supply only Electrical Position indication (EPI) all as specified and directed.
Supply only Microswitch for Ready to close indication all as specified and directed.
Supply only micro switch for Common fault Indication (CFI) all as specified and directed.
Supply only micro switch for Shunt release all as specified and directed.
Supply only micro switch for Under Voltage release all as specified and directed.
Supply only micro switch for Spring Charging Indication all as specified and directed.
Supply only Electrical charging device (ECD) 110VAC/110-125V AC all as specified and directed.
Supply only Closing release (CR) 110VAC/110-125V AC all as specified and directed.
Supply only Shunt Release (SR)110VAC/110-125V AC all as specified and directed.
Supply only Under Voltage Release (UVR) with time delay (0-1-3-5)110VAC/110-125V AC all as specified and directed.
Supply and installation of Refrigerant copper piping insulated with Nitrile Rubber Tubular Insulation complete all as specified and directed by Engr-in-charge
54.1 mm with 19 mm thick insulation
41.3 mm with 19 mm thick insulation
28.6 mm with 19 mm thick insulation
25.4 mm with 19 mm thick insulation
22.2 mm with 13 mm thick insulation
15.9 mm with 10 mm thick insulation
12.7 mm with 10 mm thick insulation
Supply only POT strainer MS construction of size 350 mm as specified and directed
M&L for complete robotic cleaning of ducts by using HEPA filtered vaccum unit to create negative pressure in the duct system from AHU to Plenum and return duct to AHU room, by placing the same outside the occupied space by using variety of tools to agitate and loosen the dust, which shall be then drawn into the vaccum unit and contained therein. the cleaning should be done by using robotic tool ,monitored & operated remotely video camera for cleaning the hard to reach areas, which are out of reach for most duct cleaning equipments. Access cutting can be made, if required and shall later be refitted with screw and sealant. All floors and furnishing where the work will be carried on shall be covered and complete care shall be taken to avoid minimum amount of cross- contamination. upon completition of work the system shall be sanitized by fogging the ducts to ensure all mold and bacteria spores and foul smell is eradicated the entire process shall be caried out with Air compressor with bib, pneumatic air whips and power jobs, Rotary brush Drum vaccum wit pipe.
Item No. 161 Contd..... Negative machine HEPA and 10" hose pipe and Robo camera with control unit. All clening agents/chemicals used shall be inaccordance with the regulation and shall be certified for use in the respective system .During the inspection process collect particulate samples from the duct interior to provide with a complete laboratory analysis of the particulate content to identify hazards such as asbestos. Microbial samples are also taken to evaluate the duct surface for bacteria and mould growth as directed and specified by Engr-in Charge. : PVC sheets or protective covers for installed medical equipment and accessories reqd for ingress Protection of medical equipments will be arranged by the contractor and its cost is included in unit rate
S&F in replacement MCCB, 400A, 3 Pole, Thermal magnetic release 320-400A, breaking capacity 36KA Model DN3B-400D Make L&T or equivalent as approved by GE.
S&F in replacement MCCB 125A, 3 Pole Thermal magnetic release 100-125A, breaking capacity 36KA Model DN0-125D Make L&T or equivalent as approved by GE.
S&F in replacement MCCB 125A, 3 Pole Thermal magnetic release 100-125A, breaking capacity 25KA Model DN1-250C Make L&T or equivalent as approved by GE.
S&F in replacement MCCB TP, 63A, Thermal magnetic release 50-63A, breaking capacity 25KA,Model DN0-100C Make L&T or equivalent as approved by GE.
S&F in replacement MCCB TP, 40A, Thermal magnetic release 32-40A, breaking capacity 25KA Model DN0-100DMake L&T or equivalent as approved by GE.
Supply only MCB FP 40 to 100A,C Curve, 415V all as specified and directed. Make : L&T or equivalent as approved by GE.
Supply only MCB SP 6A - 32A,C Curve, 240V all as specified and directed Make : L&T or equivalent as approved by GE.
Supply electronic Timer for star delta Timer 3Sec to 120Sec, 240VAC model, 2ASDTO of Make – L & T or equivalent as approved by GE complete all as directed.
M&L for replacement of Thermal overload relay with current range 8.5A to 12.5A Type RTO-1 suitable for MO contactor Make L&T or equivalent as approved by GE.
M&L for replacement of Thermal overload relay with current range 17A to 25.5A Type RTO-1 suitable for MO contactor Make L&T or equivalent as approved by GE.
M&L for replacement of Thermal overload relay with current range 47A to 62A Type RTO-3 suitable for MO contactor Make L&T or equivalent as approved by GE.
M&L for replacement of Thermal overload relay with current range 9A to 15A suitable for MNX contactor Make L&T or equivalent as approved by GE.
M&L for replacement of single phase preventor Make Minilec Model VSP2 or equivalent as approved by GE.
M&L for replacement of Push button as per sample Make-L&T or equivalent as approved by GE.
M&L for replacement of indicator lamps LED type with holder suitable for panel control functions Make-L&T or equivalent as approved by GE.
M&L for front mounting add-on aux contact block 2NO + 2NC for MNX contactors all as specified and directed. Make-L&T or equivalent as approved by GE.
M&L for front mounting add-on aux contact block 2NO + 2NC for MO contactors all as specified and directed. Make-L&T or equivalent as approved by GE.
M&L for replacement of power contactor MO25 CONFIRMING TO IS/IEC 60947-4-1 Make-L&T or equivalent as approved by GE.
M&L for replacement of power contactor MO140 Conforming to IS/IEC 60947-4-1 Make-L&T or equivalent as approved by GE.
M&L for replacement of power contactor MO45 CONFIRMING TO IS/IEC 60947-4-1 all as specified and directed Make-L&T or equivalent as approved by GE.
M&L for replacement of power contactor MNX25 confirming to IS/IEC 60947-4-1 Make-L&T or equivalent as approved by GE.
M&L for replacement of power contactor SC025 with Thermal Overload relay confirming to IS/IEC 60947-4-1 Make-Salzer or equivalent as approved by GE.
M&L for replacement of Single Function meter, Single phase LED Voltmeter accuracy class 1, 0-520VAC, flush mounting 96x96mm Model :WL1120, Make L&T or equivalent as approved by GE.
Supply only E-box for Chiller having part number SACS160297-1 (Make: Daikin) all as specified and directed.
Supply only central remote controller for VRF Type AC Plant. Make Daikin DCS302CA61 or equivalent as approved by GE.
Supply only Variable frequency drive unit complete capacity 7.5KW/10HP, all as specified and directed Make Danfoss Model No : 134F2929 or equivalent as approved by GE.
Supply only power supply unit input 100-240V,1.4A output DC 12V,4.2A all as specified and directed Model: S8JX-G05012CD Make OMRON or equivalent as approved by GE.
Supply Only Isolation Transformer 100VA,50-60Hz all as specified and directed make McQuay International or equivalent as approved by GE.
Supply Only Isolation Transformer 15VA,50-60Hz all as specified and directed make McQuay International or equivalent as approved by GE.
Supply only motor winding sensor (GDB) 24VAC, 50/60Hz, Cut off at 4000 Ohm, Cut in 700 Ohm as per sample all as specified and directed.
Supply only capacitor 60 micro farad,440VAC,50Hz all as specified and directed.
Supply only noise Filter , 30A, 50/60hZ, 250V, 55 degree,25/100/21 Model SUPF-EX30-ER-6 complete all as specified and directed.
M&L for updation of BMS system software through OEM or OEM authorised personnel including updation of Operating system and any other software and replacement of faulty components of CPU or UPS as directed by Engr-in-charge.
Supply only PLC based unit compressor Controller, input24VAC,50/60Hz/24VDC max power 40VA, all as specified and directed Make DAIKIN or equivalent as approved by GE.
Supply only BAC net Router all as specified and directed Make Siemens Model PXG3.L,S55842-Z105-A100 or equivalent as approved by GE.
Supply only Compact room automation station for HVAC all as specified and directed Make Siemens Model DXR2.M18-101A or equivalent as approved by GE.
Supply only data/Communication Cable 2 core x 1.0 Sqmm tinned copper shield unarmoured Cable, Fusion polymer, 1100V grade all as specified and directed.
Supply only Dinkle assembly DK6N10 gang box Connector for 14 way,8-20AWG,50A,1100V.
Supply only cat 6 UTP PVC FR (with separator) communication Cable 6 core as per sample.
somnath engineering corporation
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .