Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.8 LAccepted-AOC | ₹32.8 L Quoted ₹32.9 L | L1 | Accepted-AOC Lowest |
| 2 | L2₹33.3 L+₹36,870 (1.12%)Rejected-Finance GURUDWARA LANE PORT BLAIR 744101 | SOUTH ANDAMANS | ANDAMAN AND NICOBAR ISLANDS | 744101 | ₹33.3 L+₹36,870 (1.12%) | L2 | Rejected-Finance Not Lowest |
Tender Value
₹34 L
EMD Value
₹68,000
Closing Date
31 Dec 2021, 6:00 pmClosed
Garrison Engineer Haddo
GARRISON ENGINEER HADDO Military Engineer Services Haddo Post Port Blair Andaman and Nicobar 744102
ADDITION / ALTERATION OF FIRE PROOF LIGHT AT NAVAL STORE II (P-46), III (P-47) AND IV (P-260) OF MO (PBR) AND OTHER E/M WORKS IN OTHER AREA UNDER GE HADDO, PORT BLAIR
2021_MES_492546_1
8592/GE/H/PB
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE Haddo Port Blair
D b (i)
9 documents required · 9 mandatory
₹500
GE Haddo
₹68,000
Yes
25 Jan 2022
4 Dec 2021
4 Jan 2022
4 Dec 2021
31 Dec 2021
18 Dec 2021
4 Dec 2021 - 13 Dec 2021
Amount
Supply and install vertical pack type split AC units indoor / outdoor complete with cordless remote control unit, twin rotary compressor, single phase units 220V - 240V, 50Hz of capacity 2.5TR including 3 mtr copper suction and discharge pipe line complete with proper insulation complete all as specified and directed. Note: All connected pipes must be covered by insulation material. The drain out water pipe connection should be connected upto ground level. Make : LG / Whirlpool / Blue Star
FIXING ONLY outdoor and indoor units of Split type air conditioner of any capacity, make and model, including copper suction and discharge pipe line of suitable size and length by making necessary holes/ chases in the walls and making good disturbed surfaces to match with surrounding existing surface and testing after installation complete all as specified and as directed NOTE : 1. Fixing only items shall be collected from store yard of AGE E/M Sub division. 2. Unit price quoted shall deemed to be include for cost of transportation of material from store yard to installation site. 3. The contractor's authorised persons for collecting items from store yard shall ensure that material issued is in perfect condition and any damage occured during transportation and installation shall be the sole responsibility of the contractor for replacement and no claim whatsoever shall not be entertained at a later stage.
S&F Electronic voltage stablizer of 4 KVA capacity, wall mounting type having features such as Intelligent time delay system of 2 to 4 minutes, low and high voltage cut-off protection, latest IC technology to protect from power fluctuations, thermal over load protection, wide input variation between 165 Volts to 295 Volts with output voltage stablized at 200 Volts to 240 Volts, with accuracy of +2.5% suitable for split type airconditioner complete all as specified and as directed. MAKE: V-GUARD / PREMIER
S&F Electronic voltage stablizer of 5 KVA capacity, wall mounting type having features such as Intelligent time delay system of 2 to 4 minutes, low and high voltage cut-off protection, latest IC technology to protect from power fluctuations, thermal over load protection, wide input variation between 165 Volts to 295 Volts with output voltage stablized at 200 Volts to 240 Volts, with accuracy of +2.5% suitable for split type airconditioner complete all as specified and as directed. MAKE: V-GUARD / PREMIER
S&F starter switch of capacity 25 Amps working on 240 Volts, AC supply suitable for split type airconditioner complete all as specified and as directed. MAKE: CRAB TREE Cat part No. ACTO252504 or equivalent in ANCHOR/HAVELLS/L&T
M&L for Sub main wiring complete with two runs (1P+1N) of 6.0 Sqmm single core, PVC insulated unsheathed, FRLS cable, 1100 volts grade, multistranded copper conductor (with colour coding of Red/Blue/Yellow for phase and Black for neutral) and one run of 6.0 Sqmm single core, PVC insulated unsheathed, FRLS cable, 1100 volts grade, multistranded copper conductor as earth wire green in colour including lugs, drawn through and including 32mm wide rigid non-metallic PVC casing and capping and its accessories (OR) 25mm dia PVC conduit and conduit accessories fixed on surface of wall/ceiling/roof/ floor complete all as specified and as directed. NOTE: Two runs of 6.0 Sqm copper conductor, One run of 6.0 Sqmm copper conductor as earth wire and one run of PVC casing and capping / PVC conduit shall be measured as one unit length.
M&L for HDPE DWC (Double wall corrugated) pipe of size 77mm (Outer diameter) x 63mm (Inner diameter) along with connected accessories like couplers, bends, end caps etc., laid in trenches/floors/ducts or fixed on poles/walls for as in protection of LT/ HT cable complete all as specified and as directed.
M&L for LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 1100 volts grade, cross sectional area 3½ core, 50 Sqmm laid in trenches/floors/ducts or fixed on poles/walls with suitable clamps/saddles or drawn through pipes etc., including connecting up with suitable size of lugs, glands and jointing material including taking out old unserviceable cable complete all as specified and as directed. NOTE: 1. Cable test results like continuity test, megger test shall be submitted to Engr-in-charge before the cable is laid. 2. Necessary excavation and earth work shall be measured and paid separately under relevant items of this schedule.
S&F TPN DB sheet metal enclosure double door suitable (IP-43) Protection, 4 Way with 200 Amp rated standard bus bar of suitable size plate and common neutral link all enclosed in standard steel sheet flush mounting type factory fabricated complete. Make : Havells/L&T/Indo Asian/Legrand/Schneider. Note : Distribution box should be concealed in wall and disturbed surface area making good plastering.
S&F MCCB, 4 pole, 16KA rupturing capacity, 240 Volts with thermal and magnetic release complete all as specified and as directed. Make : Havells/ L&T/ Indo Asian/ Legrand
S&F MCB, TP, 240 volts, 40 Amps, 10 KA rupturing capacity complete all as specified and as directed. Make : Havells/ L&T/ Indo Asian/ Legrand
S&F MCB, SPN, 240 volts, 40 Amps, 10 KA rupturing capacity complete all as specified and as directed. Make : Havells/ L&T/ Indo Asian/ Legrand
S&F rigid non metallic PVC conduit exclusive of boxes (junction / terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipehooks, etc. complete all as specified and as directed.
M&L for fixing of 5/8" flare size additional copper tubing confirming to relevant IS with proper insulation complete all as specified and as directed.
M&L for fixing of 1/2" flare size additional copper tubing confirming to relevant IS with proper insulation complete all as specified and as directed.
M&L for fixing of 3/8" flare size additional copper tubing confirming to relevant IS with proper insulation complete all as specified and as directed.
M&L for fixing of 1/4" flare size additional copper tubing confirming to relevant IS with proper insulation complete all as specified and as directed.
M&L for taking down carefully ceiling/wall fan, sealing cables end dismantling blades and removing fan and blades to store and FIXING only ceiling/wall fan and connecting up including provision of cable from ceiling rose or connector to fan complete all as specified and directed.
M&L for Point wiring complete with 1.5 Sqmm (nominal area) single core, PVC insulated unsheathed, FRLS cable, 1100 volts grade, multistranded copper conductor (with colour coding of Red/Blue/Yellow for phase and Black for neutral), drawn through and including rigid non metallic PVC casing and capping of suitable size (not less than 20mm) and accessories fixed on walls/ceilings etc., including provision of PVC insulated 1.5 Sqmm FRLS cable with copper conductor green in colour for earth continuity and connected to common earth dolly and sunk in CI boxes/pressed steel terminal boxes 60mm deep made out of 1.6mm thick MS sheet duly painted with two coats of anti-corrosive paint outside and with two coats of aluminium paint inside and laminated sheet cover of 3mm thick on top for housing the switches, socket outlet etc, all as specified and as directed for ONE LIGHT/FAN point controlled by one, one way 5 Amps switch. MAKE: Anchor/Polycab/ Finolex/ Havells
M&L for Point wiring flame proof complete with 1.5 Sqmm (nominal area) single core, PVC insulated unsheathed, HRFR cable, 1100 volts grade, multistranded copper conductor, drawn through and including rigid non metallic stove enamelled steel conduit (ISI marked) and conduit accessories suitable for flame proof wiring concealed in walls/ceilings/roofs/steel sections etc., including provision of PVC insulated 1.5 Sqmm (nominal area) single core, PVC insulated unsheathed, HRFR cable, 1100 volts grade, multistranded copper conductor green in colour for earth continuity connected to common earth dolly and flame proof switches etc., all as specified and as directed for one light/ fan point controlled by one flame proof switch including taking down old unserviceable point wiring complete all as specified and directed. MAKE: Anchor/Polycab/ Finolex/ Havells
M&L for Point wiring flame proof complete with 1.5 Sqmm (nominal area) single core, PVC insulated unsheathed, HRFR cable, 1100 volts grade, multistranded copper conductor, drawn through and including rigid non metallic stove enamelled steel conduit (ISI marked) and conduit accessories suitable for flame proof wiring concealed in walls/ceilings/roofs/steel sections etc., including provision of PVC insulated 1.5 Sqmm (nominal area) single core, PVC insulated unsheathed, HRFR cable, 1100 volts grade, multistranded copper conductor green in colour for earth continuity connected to common earth dolly and flame proof switches etc., all as specified and as directed for ONE 3 pin 5/6A SOCKET OUTLET point controlled by one, one way 5/6 Amps modular switch on independent board.
S&F switch flame proof, rotary type with cable termination box in LM6, 16A, single pole, 250V complete all as specified and as directed. MAKE: SUDHIR SWITCH GEAR Cat part No. RI/M/1010-2A or equivalent in SHYAAM/BALIGA
S&F flame proof, switch socket & plug combined in LM6 cable termination box in LM6, 16A, 250V, 2P+ earth complete all as specified and as directed. MAKE: SUDHIR SWITCH GEAR Cat part No. RI/M/1010-2A or equivalent in SHYAAM/BALIGA
S&F exhaust fan, flame proof, 300mm (12") sweep, 0.25 HP motor, 1400 RPM speed, 1120 CFM, single pole, 250 V fixed at a height of 4.0 m above floor complete all as specified and as directed. MAKE: SUDHIR SWITCH GEAR Cat part No. EF/140 or equivalent in Havells / CG
S&F light fitting, flame proof in aluminium alloy LED tube light fittings 20W made prewired including connecting with FRLS 1100 volts grade confirming to IS 694 to the fitting complete all as specified and as directed. MAKE: Crompton Greaves cat part No. EXTN2LT8-16/20 or equivalen in Sudhir/Philips/Bajaj/Havells Note: The rate shall be including necessary fitting arrangement for light fiting on ceiling.
M&L for mild steel framed brackets fabricated made out of angles or tees for fixing exhaust fan of any sweep with web and flanges cut to shape, drilled and countersunk for screw, including bending and welding angles, as necessary, gusset plates, riveting, etc., weight of each bracket not exceeding 10 kg and conforming to Fe-290 Gde E-165 including fabrication and fixing complete all as specified and as directed.
M&L for Sub main wiring complete with two runs (1P+1N) of 6.0 Sqmm single core, PVC insulated unsheathed, FRLS cable, 1100 volts grade, multistranded copper conductor and one run of 6.0 Sqmm single core, PVC insulated unsheathed, FRLS cable, 1100 volts grade, multistranded copper conductor as earth wire green in colour including lugs, drawn through and including 32mm wide rigid non-metallic PVC casing and capping and its accessories (OR) 25mm dia PVC conduit and conduit accessories fixed on surface of wall/ceiling/roof/ floor complete all as specified and as directed. NOTE: 3 length of cable and one length steel shall be measured as one unit length. Make: Polycab / Anchor / Havells / Finolex
S&F modular switch, one way, one module, single pole, 6 Amps complete all as specified and as directed.
S&F decorative light fittings clear curving glass mushroom strip beaded with class A clear crystal including LED bulb complete all as specified and directed. Make : Philips Model No. 581864 or equivalent in Havells / CG / Bajaj
S&F 33W decorative light fittings mirror stainless steel & clear crystal inccluding LED bulb complete all as specified and directed. Make : Philips Model No. 581850 or equivalent in Havells / CG / Bajaj
S&F round shape / square shape recessed mounted 18 watts, downlight with with die-cast aluminium housing finished in premium with white powder coating LED panel light fitting with ultra bright luminaire comprises of thermal conductive material, pre wired with high effeciency electronic driver with high translucent frosted diffuser gets glare free, smooth light distribution complete all as specified and directed. Make : CG Cat Part No. LSRCM-18W-CDL/NW/WW/Philips Cat Part No. Astra Max Mental Panel (Worm White) or equivalent in Havells.
S&F (CRYSTA COB SWIVEL) energy efficient 1 x 9W 3000K (white / yellow colour) LED spotlight for low ceiling height applicationsround in shap, pressure die-cast aluminium housing, spring loaded clips for easy mounting complete all as specified and directed. Make :Havells (Model No. LHEEGEPBIE1W009) /Philips (7W COB PRO) or equivalent in CG / C&S.
S&F IP-20 modern Chalice crescent Chandeliar of colour mirror stainless steel clear crystal & cognac glass 6 x 42 watt maximum including bulbs and all fixing arrangement complete all as specified and directed. Make :Philips Model No. 581841 or equivalent in CG / C&S.
M&L for earthing complete with GI earth plate electrode of size 600mmx600mmx6mm thick buried directly in ground (earth pit not less than 2.25m deep below the normal ground level) with top edge of the earth plate not less than 1.5m below normal ground level connected to 4mm dia GI earth wire as earth lead connected by means of bolts, nuts, washers and check nuts made out of galvanised iron or steel all as shown on electrical plate No. 3 of SSR Part-I connected to common earth dolly including testing on completion complete all as specified and directed. NOTES: 1) The unit rate shall also include for earth work in any type of soil, PCC (1:3:6) type C1 chamber, pre-cast RCC (1:2:4) type B-1 using 20mm graded stone aggregate cover 50mm thick reinforced with TMT bars 8mm dia @ 100mm c/c both ways, funnel with watering pipe 20mm dia medium grade, GI protection pipe light grade 40mm dia and wire mesh complete in addition to item No. 1(a) to (e) of preamble (notes) under sub-heading earthing, specified on Sl. Page Nos. 422 & 423 of SSR Part-II. 2) Earthing lead and GI protection pipe beyond 7.5m will be measured and paid separately.
B S Grewal
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .