EE_KCED_PWD
Khadya_Bhawan_11A_Mirza_Ghalib_Street_Block_A_3rd_Floor_Kokata_700087
SITC of Fire Detection system at Govt college of Engineering and Ceramic Technology 73 Abinash Chandra Banerjee Lane Kolkata 700010
2019_PWDE_229743_1
WBPWD/EE/07/IR/T/KCED/II of 2019-20
Open Tender
Electrical Work/ Equipment
Item Rate
150 days
Govt college of Engineering and Ceramic Technolo
Please refer Tender documents.
4 documents required · 4 mandatory
₹65,000
27 Sept 2021
24 Jun 2019
22 Jul 2019
24 Jun 2019
20 Jul 2019
25 Jun 2019
Amount
Supply, Installation,Testing & Commisioning of Microprocessor based Intelligent, addressable 7/8 Loops fire alarm control panel having expandable features ( VDS / UL / FM /LPCB approved ) fully networkable with each loop capable of taking minimum 120 devices, 1/4 VGA display character alpha-numeric liquid crystal display.The panel shall be soft addressable type.The panel shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered.The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emargency condition, with integral battery charger complete as required. The panel shall have extra loop card to serve as stand by in case of burntout or malfunctioning of any operating loop cards. The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 bus.The FACP shall have provision for interfacing with the ON LINE 1 KVA UPS public address system and BMS( RS 485 )The system must be preloaded with licenced software.( Approved Make: Esser/Cerberus Pro/Secutron/ Notifer / Edward / Bosch / Apollo / Morley / System Sensor / Johnson Controls ).
SITC of Analog addressable intelligent Fire Alarm Control & Panel shall be following loop capacity fully Networkable with minimum 120 devices per loop. The panel shall be soft addressable type . The panel shall be able to give pin point location of all fire conditions. Integral SMF lead acid batteries with sealed cells of 24V capable for running a minimum of 8 hours with integral battery charger complete as required and as per specification incl. all accessories as required with ON LINE 1 KVA UPS (make- Notifier/ Siemens/Esser) 4 Loop Fire Alarm Panel
SITC of Repeater Panel ( VDS / UL / FM / ULC approved )which will act as an add-on device for remote display of FACP status information of the FDA operating front related to the detectors and decetors zones.Event messages are displayed via LED collective indicators and on the 2-Line LCD display with the associated detecors zone number and a programmable additional text. Each message is signalled via the built-in buzzer. The buzzer can be acknowledged by pressing a button. Upto 31 LCD indicator panel can be operated on as RS 485 bus. (Approved Make: Esser/Cerberus Pro/Secutron/ Notifer / Edward / Bosch / Apollo / Morley / System Sensor / Johnson Controls ).
Supply, Installation,Testing & Commisioning of Analog Addressable Intelligent multisensor detector ( VDS / UL / FM / ULC/LPCB approved ) with backward & forward scattering light angles as well as additional heat detector sensor with decentralise intelligence, addressable Photothermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard.(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost).(Approved Make: Esser/Cerberus Pro/Secutron/ Notifer / Edward / Bosch / Apollo / Morley / System Sensor / Johnson Controls )
Supplying, installation, testing and commissioning of Addressable Heat Detector (Fixed temperature cum rate of rise) with twist lockable removal base, built - in fault isolator, drift compensation feature etc including connections as per specifications complete as reqd and having IP as per recommended standard(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost)...(Approved Make: Esser/Cerberus Pro/Secutron/ Notifer / Edward / Bosch / Apollo / Morley / System Sensor / Johnson Contros )
Supply & installation of Addressable Beam Detector (Make: Notifer / Siemens / System Sensor / Johnson Contros). (VDS / UL / FM / ULC/LPCB approved)
Supply, Installation,Testing & Commisioning of Addressable Manual Call Point ( VDS / UL / FM / ULC approved ) addressable type complete as required. (Approved Make: Esser/Cerberus Pro/Secutron/ Notifer / Edward / Bosch / Apollo/ Morley / System Sensor / Johnson Controls ).
Supply, Installation, Testing & Commissioning of Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe complete ( VDS / UL / FM / ULC approved). (Approved Make: Esser/Cerberus Pro/Secutron/ Notifer / Edward / Bosch / Apollo / Morley / System Sensor /Johnson Controls ).
Supply, Installation, Testing & Commissioning of Addressable transponder/ Monitor Modules ( VDS / UL / FM / ULC approved ) for monitoring flow switches/Fire exit doors / AHU / Lift etc complete as required. ( Approved Make: (Approved Make: Esser/Cerberus Pro/Secutron/ Notifer / Edward / Bosch / Apollo / Morley / System Sensor / Johnson Controls ).
Supplying, installation, testing and commissioning of LED type Response Indicator ( VDS / UL / FM / ULC approved) having 2 Nos. red coloured LED lamps including connections etc.( Approved Make: Esser/Cerberus Pro/Secutron/ Notifer / Edward / Bosch / Apollo / Morley / System Sensor /Johnson Controls ).
Supply, Installation, Testing & Commissioning of Power supply 230 V AC to 12/24 V DC with all other accessories. (Make: Reputed)
Supply & Laying of 3 Core 1.5 sq.mm FRLS shielded round copper Cable (For Loop) (Make. Finolex / KEI ) with 20 mm NB PVC rigid conduit pipe(Make: Precisson-Medium) on the surface of the wall.
Supply of 40mm UPVC pipe
Supply of 40mm GI pipe
Supply & Laying of 3 Core 2.5 sq.mm FRLS shielded round copper Cable (For Loop) (Make. Finolex / KEI ) with 20 mm NB PVC rigid conduit pipe(Make: Precisson-Medium) on the surface of the wall. NOTE : 1. The Fire Alarm system shall comply with latest requirements of -- 1. National Fire Protection Association (NFPA) Standards. 2. IS 2189 3. NFPA 70 National Electric Code 4. NFPA 72 National Fire Alarm Code 5. local Statutory Regulations 6. Manufacturer Recommendation. TESTS:1.The system shall be tested and commissioned by a qualified competent,trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation and other tests as per above standards must be done.
GLYPTIC
JAYSHWAL ENTERPRISES
Fire Guard Syndicate
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .