| Sl No | Description | Qty | Unit | M/S STAR NEOTECH ENGINEERS L1 | COMPLETE COOLING SOLUTIONS LLP L2 |
|---|---|---|---|---|---|
| 1.00Supply, Installation, testing & commissioning of Variable refrigerant flow modular type air-conditioning system suitable to operate from 415+10% volt, 50 Hz,3 phase AC power supply for Cooling & Heating by using inverter driven capacity control compressors complete with individual controller and fittings with necessary wiring, connection & termination, painted MS frame for outdoor unit etc. as per quantity given below including full charging of refrigerant gas in ODU as per recommendaion by OEM complete as per specifications. The outdoor unit shall be factory assembled, weather proof casing (Material of construction of casing shall be vendor's standard design), constructed from heavy gauge GI sheets steel panels and coated with baked enamel finish. The outdoor unit shall be completely factory wired, tested with all necessary controls & filled with first charge of refrigerant before delivering at site. The inverter technology based D.C Twin/Single Rotary / Scroll compressor modular type VRF equipment should be designed, so that refrigerant piping between outdoor units and furthest indoor unit shall be extendable up to a length >= 160m. Allowable level difference between outdoor & indoor unit shall be 50m in case of outdoor unit on top & 40m in case of outdoor unit at bottom. Allowable level difference between two indoor units connected to same outdoor unit shall be upto 15m. All the outdoor units comprising of multiple modules should have 100% inverter type compressor in each module. The units should comply with minimum COP of 3.65 at 100% load (Heating mode) and minimum 6.5 at 50% load in cooling mode at following conditions: 0 Deg C to 40 Deg C in cooling mode and -20 Deg C to 15 Deg C in heating mode. IEER not less than 6.5. Anti Ice Circuit/ Auto defrost kit if required to operate at this temperature in winter to be provided in ODU. It should also be provided with duty cycling for D.C inverter Twin Rotary/Scroll compressors capable of changing the rotating speed of compressor by inverter controller to follow variation in cooling & heating loads & switching starting sequence for better stability and prolonging equipment life or similar features. The unit shall be provided with its own microprocessor control panel with provision for integration with the building management system/Centralized Per HP remote controller for Air-conditioning system. The machine must have a sub cool feature to use coil surface more effectively through proper circuit/ bridge so that it prevents the flushing of refrigerant from long piping due to this effect thereby achieving energy savings. The outdoor unit should be fitted with low noise level and should not be more than 67 db (A) at normal operation when measured at a point 1 mtr in front of the unit at a height of 1.5 mtrs. The outdoor unit should be fitted with low noise aero spiral design fan with aero fitting grill for spiral discharge airflow to reduce pressure loss and should be fixed with DC/AC fan motor for better efficiency. The outdoor unit shall have refrigerant cool PCB chamber for better operation at high ambient temperature. The outdoor unit shall have feature to change the evaporative temperature with respect to load for better comfort and energy efficiency. The systems shall be equipped with free phase technology & operation shall be continuous in case of phase reverse in supply electricity. The system shall have automatic refrigerant charge function for optimal charging for additional refrigerant. The fan static pressure of the outdoor unit shall be above 78 Pa to avoid hot air recirculation. The compressor is inverter based D.C Twin/single/ Rotary / Scroll compressor system shall be highly efficient. The system should response efficiently in accordance to the variation in cooling or heating load requirement. All outdoor units shall have multiple steps of capacity control to meet load fluctuation and indoor unit individual control. All parts of compressor shall be sufficiently lubricated stock. Forced lubrication may also be employed. Oil heaters shall be provided in the compressor casing. Unit shall be equipped with an oil recovery system to ensure stable operation with long refrigeration piping lengths. The system shall have oil recovery cycle of 8 or more hours or as per recommendation of OEM. The system must be provided with oil balancing circuit to avoid poor lubrication. Final Configuration/ selection of module for ODUS based on piping circuit to provide sufficient redundancy in system shall be done as per floor & project requirement as per OEM recommendations. The job includes fabrication of L-shaped GI duct of suitable guage along with power scanner for individual out door units. The job also includes earthing of the equipment as recommended by OEM. | |||||
| 2.00 | 18 HP | 1 | Job | 4,06,000 ₹4,06,000 Lowest | 4,60,737 ₹4,60,737 |
| 3.00 | 28 HP | 1 | Job | 6,72,000 ₹6,72,000 | 6,56,179 ₹6,56,179 Lowest |
| 4.00 | 42 HP | 1 | Job | 9,35,000 ₹9,35,000 Lowest | 9,99,399 ₹9,99,399 |
| 5.00 | 46 HP | 2 | Jobs | 10,35,000 ₹20,70,000 Lowest | 10,81,611 ₹21,63,222 |
| 6.00 | 48 HP | 1 | Job | 10,78,000 ₹10,78,000 Lowest | 11,20,195 ₹11,20,195 |
| 7.00 | 58 HP | 1 | Job | 13,00,000 ₹13,00,000 Lowest | 13,43,376 ₹13,43,376 |
| 8.00 | 60 HP | 4 | Jobs | 14,30,000 ₹57,20,000 | 13,74,395 ₹54,97,580 Lowest |
| 9.00Supply, Installation, testing & commissioning of Ceiling Mounted Round/4way flow cassette type Unit of suitable capacity suitable to operate from 230+10% volt, 50 HZ, 1 phase power supply with cordless remote control, fittings & required cable to connect indoor unit to socket.Refrigerant Pipe size and gas quantity should suit to the copper pipe length at actual. The capacity guarantee should be ensured by the contractor/manufacturer. Each unit shall have high lift drain pump, and Low gas detection system. The job includes dismantelling of false cieling where ever installed and reinstallation of the same after making provisions for indoor units | |||||
| 10.00 | 1.28 TR | 4 | Jobs | 36,500 ₹1,46,000 Lowest | 42,114 ₹1,68,456 |
Tender Value
₹3.7 Cr
EMD Value
₹7.3 L
Closing Date
20 Aug 2024, 12:00 pmClosed
Executive Engineer MHD Sgr
Office of the Executive Engineer MHD Sgr
Supply, Installation, Testing and Commissioning of HVAC System at Multiple Facility Centre (MFC) for Economically Weaker Section (EWS) including CMC for 02 years Post Normal Warranty Period at Govt. Medical College, Srinagar
2024_PWDJK_255906_1
MHDS/TS/2024-25/69/e-tendering Dt 08.08.2024
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
120 days
govt medical college srinagar
As detailed in NIT
6 documents required · 6 mandatory
₹15,000
Superintending Engineer, MHC, Kmr
₹7.3 L
24 Aug 2024
8 Aug 2024
20 Aug 2024
8 Aug 2024
20 Aug 2024
8 Aug 2024
Amount
Supply, Installation, testing & commissioning of Ceiling Mounted Round/4way flow cassette type Unit of suitable capacity suitable to operate from 230+10% volt, 50 HZ, 1 phase power supply with cordless remote control, fittings & required cable to connect indoor unit to socket.Refrigerant Pipe size and gas quantity should suit to the copper pipe length at actual. The capacity guarantee should be ensured by the contractor/manufacturer. Each unit shall have high lift drain pump, and Low gas detection system. The job includes dismantelling of false cieling where ever installed and reinstallation of the same after making provisions for indoor units
Supply & Installation of interconnecting suitable sizes of one end expanded refrigerant copper pipe work, insulated with 13mm thick ( pipe size upto 19.1mm dia) & 19mm thick (pipe size above 19.1mm dia) with XPLE Class O tubular closed cell electrometric nitrile rubber tubular insulation sleeves sections of specified thickness between each set of indoor & outdoor units with outer mechanical protection for all exposed pipes as per specification detailed later. All piping inside the room shall be properly fixed/supported with suitable size of clamp/ M.S. hanger and all external piping shall run in M.S. painted cable tray etc. as required. Piping vaccumiazation and Nitrogen testing to be done by contractor and price for the same to be included thickness of pipes should be as per VRF recommendation. The job includes dismantelling of false cieling where ever installed and reinstallation of the same after making provisions for piping circuit.
41.3 mm dia with 19mm thick insulation
34.9 mm dia with 19mm thick insulation
28.6 mm dia with 19mm thick insulation
22.2 mm dia with 19mm thick insulation
19.1 mm dia with 13mm thick insulation
15.9 mm dia with 13mm thick insulation
12.7 mm dia with 13mm thick insulation
9.5 mm dia with 13mm thick insulation
6.4 mm dia with 13mm thick insulation
Supply Instalaltion, testing & commissioning of Yjoints for various size of Refrigerant pipe including insulation.
Cost on account of charging of refrigerant in the piping circuit so as to attain optimum operating conditions of the compressor (both HP & LP side) of the respective outdoor unit after proper pressure testing of refrigerant piping circuit at a pressure of atleast 1.5 times the working pressure of the compressor.
Providing & fixing of heavy duty PVC Pipe (Drain Pipe for VRF IDUs)complete with fittings, supports as per specifications and duly insulated with 9 mm thickness of XPLE Class-O tubular/ closed cell tubular nitrile rubber as required & as per specifications.
50 mm dia with 9 mm thick insulation
40 mm dia with 9 mm thick insulation
32 mm dia with 9 mm thick insulation
Supplying, installation, testing & commissioning of cubical type wall mounted power distribution panels suitable for 415V, 3 Phase, 4Wire 50 Hz AC supply system fabricated in compartmentalized design from CRCA sheet steel of 2mm thick for frame work and covers, 3 mm thick for gland plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having suitable capacity extensible type FP Aluminium Alloy bus bars of high conductivity, DMC/ SMC bus bar supports, with short circuit withstand capacity of 31 MV A for I Sec. with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al. bus bars and control wiring with 1.5 sq.mm. Incomer 1No. Following capacity Four Pole, MCCB with thermal & magnetic relays with 3 Nos. R,Y,B Indication Lamps with 2A back up SP MCB with ON indication.MCCB shall be provided with spreader link and direct rotary handle. Busbar: TPN aluminium bus bars of minimum of following capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. Outgoings: Supplying and fixing following outgoing MCCB/MCB including connection, inter-connection etc. with suitable size of wires complete as required. (Each MCCB to be provided with ON indiation with 2A backup SP MCB)
200 Amp (01 No) MCCB having Breaking capacity of 36KA; 250 Amp Bus Bars (TPN) ; 04 Pole MCCB having Breaking capacity of 25KA with RCCB 63 Amp (04 No); Double Pole MCB 06 Amp ( Minimum 17 No)
200 Amp (01 No) MCCB having Breaking capacity of 36KA; 250 Amp Bus Bars (TPN) ; 04 Pole MCCB having Breaking capacity of 25KAwith RCCB 63 Amp (03 No); Double Pole MCB 06 Amp ( Minimum 17 No)
160 Amp (01 No) MCCB having Breaking capacity of 36KA; 200 Amp Bus Bars (TPN) ; 04 Pole MCCB having Breaking capacity of 25KA with RCCB 63 Amp (03 No); Double Pole MCB 06 Amp ( Minimum 17 No)
125 Amp (01 No) MCCB having Breaking capacity of 36KA; 200 Amp Bus Bars (TPN) ; 04 Pole MCCB having Breaking capacity of 25KA with RCCB 63 Amp (03 No); Double Pole MCB 06 Amp ( Minimum 17 No)
100 Amp (01 No) MCCB having Breaking capacity of 36KA; 125 Amp Bus Bars (TPN) ; 04 Pole MCCB having Breaking capacity of 25KA with RCCB 63 Amp (03 No); Double Pole MCB 06 Amp ( Minimum 17 No)
Centralised Remote Controller:- Supply, installation, testing & commissioning of touch screen type centralised remote controller along with control wiring etc all complete cabable of monitoring parameters of all Indoor units and Outdoor units.
Electric Cables:-Providing and fixing of electric power cabling from distribution panel to floor panel and from floor panels to outdoor units suitable for 415v, 3 phase, 50 Hz and from floor panels to individual indoor units suitable for single phase supply. The job includes dismantelling of false cieling where ever installed and reinstallation of the same after making provisions for cabling.
3.5 Core, 25 Sq.mmAluminium armoured
3.5 Core, 70 Sq.mmAluminium armoured
3.5 Core, 120 Sq.mmAluminium armoured
4 Core 16 sq.mm copper cable
3 Core 1.5 Sq.mm coper cable
2 Core 1.5 Sq.mm copper cable
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth melectrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Cable Trays:- Providing and fixing of hot dip galvanised perforated/ladder cable Trays of sizes 150mm in width and 50mm depth (16SWG) perforated type
Cost on account of Providing, fabricating and supplying and fixing panels of aluminium composite panel (ACP) cladding of thickness 4mm to completely conceal the refrigerant piping circuit including cable trays etc.
Providing and laying of stone soling (Crushed) including watering, ramming etc complete
Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering. All work upto plinth level with: 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size)
Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering. All work upto plinth level with: 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size)
Centering and shuttering including strutting, propping etc. and removal of form for: Foundations, footings, bases of columns etc. for mass concrete.
Structural steel work welded in built up sections trusses and framed work, including cutting, hoisting, fixing in positions and applying a priming coat of approved steel primer all complete.
Providing and fixing precoated galvanized iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+ 0.05 %) total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required.
COMPLETE COOLING SOLUTIONS LLP
stage.html
html • 0.03 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.72 MB
Tendernotice_2.pdf
PDF • 0.76 MB
BOQ_744970.xls
BOQ • 0.33 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .