Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance 00 OPP RASHMI HOSPITAL RAYA ROAD LAXMI NAGAR MATHURA UTTAR PRADESH 281204 | MATHURA | UTTAR PRADESH | 281204 | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
₹15.5 L
EMD Value
₹15,510
Closing Date
8 Aug 2024, 12:00 pmClosed
SE EWCL
MVVNL, TIPE IV/3, TRANSMISSION STAF COLONY, DEVA ROAD, CHINHAT, Lucknow
Increasing Capacity of 33 11 KV Substation Barai Jalalpur from 1x10 MVA to 1x10 1x5 MVA and Construction of Associated 11 KV Line at Distt Sitapur Under Business Plan 2024 25
2024_MVVNL_943142_1
17/EWCL/2024-25
Open Tender
Electrical Works
Item Wise
90 days
SITAPUR
AS PER PQR
2 documents required · 2 mandatory
₹3,540
SE EWCL
₹15,510
14 Aug 2024
3 Aug 2024
8 Aug 2024
3 Aug 2024
8 Aug 2024
3 Aug 2024
Amount
Safe loading, carriage and unloading & proper stacking of following store materials from any Electy. Store of Lucknow Zone to 33/11 KV S/S site (work site).
Cost of 33 KV Bus Isolator
Cost of Post Insulator
Cost of 33 KV Lightening Arrester
Cost of 33/11 KV 05 MVA Transformer
Cost of 33 KV VCB 800 Amp., 750 MVA
Cost of 33 KV CT 200/100/1 Amp.
Cost of 33 KV Single T/F Control Pannel with structure.
600/300/5 AMP, 350 MVA Incoming
200/100/5 AMP, 350 MVA Outgoing
11 KV 3x300 SQ MM XLPE
11 KV 3x185 SQ MM XLPE
MS Channel 125x65, 3.2Mtr. Long 1,2,3,4 No Pieces for Top channel. 13.10 Kg/Mtr.+wastage.
MS Angles 50x50x6mm for bracing type members of T.G./B.G./Trench
MS Angles 75x75x8, 2.6mtr long, total 5.2 @ 8.9 Kg/Mtr.
MS Angles 75x75x6mm (6.8 Kg/Mtr.) for Neutral/Cable Stand
Cost of ACSR Panther Conductor
PCC Pole 8.5m long.
Rail Pcs of 90 Lbs 3.46M long 2 No. Pcs 6.92M @ 44.61 Kg./M
MS Channel 100x50 mm (9.6 Kg/Mtr.) for Cable Stand
MS Channel 100x50x2028 mm (Dropper for Fuse Set)
MS Channel 100x50x2240m Top Channel
MS Angle 40x40x5 mm (3.0 Kg/Mtr)
11 KV Polymeric Disc Insulator T & C type 4500 Kg.
11 KV Disc fitting T & C type 4500 Kg.
11 KV Polymeric Pin Insulator
MS Channel 100x50x2028m for TPMO
Earthing of pole by MS Earthing rod 20x2500 mm & 6 SWG earthing wire etc Complete
MS Angle 65x65x6mm 2028 mm Mtr long for cable hoisting support
Stay Complete
11 KV 3x300 SQ MM XLPE Cable Outdoor
11 KV 3x300 SQ MM XLPE Cable Indoor
11 KV 3x185 SQ MM XLPE Cable Outdoor
11 KV 3x185 SQ MM XLPE Cable Indoor
Single Core PVC Cable, 1x630 sq.mm.
ST Pole 11 Mt Long-SP-55
8.5 Mtr. Long PCC Pole
V-type cross arm 65x65x6 mm (5.8 Kg/Mtr.)
Polymeric 11KV Disc Insulator T&C Type 4500 Kg.
Disc Fittings Dog/ Racoon 4500 Kg
Polymeric 11KV Pin Insulator
M.S. Angle Iron 65x65x6mm, 2700 mm long 2/6/8 no. Bracing, with 4/12/16 clamps (5.8 kg./m)
M.S. Angle Iron 65x65x6, 2240mm long, 5.8 Kg/Mtr. for cable with clamp
Top chanel 100X50mm, 2240 mm long (9.6 Kg./m) with clamp
MS Channel 100x50 mm (9.6 Kg/Mtr.)
GI wire 8 SWG for guarding along the line
GI wire 8 SWG for guarding across the line
Guarding Angle 65x65x6mm (2500/1600 mm long)
Earthing of pole by MS earthing rod 20x2500 mm and 6 SWG earthing/GI wire etc
Complete Stay (GI Stay rod 16x1800 mm, Stay 7/10 SWG 5 Kg.)
ACSR Weasel Conductor
Erection and Installation of 33/11KV 10 MVA T/F:- Earthing for power T/F by way of boring and lowering of 40mm dia, 2.9 mm thick GI Pipe B class from ground upto the water level (minimum 60 feet deep) as per standard practice as per RESPO/REC Drg with making of earth pit of 300x300 mm & 1 feet deep with Cover. (All materials to be provided by Contractor).
Plinth of 5MVA 33/11KV T/F: Construction of plinth of size 3.46 x4.46 Mtr. For 5MVA T/F having 0.4 Mtr. above ground level. The work includes excavation of foundation, base concretion of CC 1:4:8 ratio (cement, fine sand & brick ballast) first class brick work in cement morter of rtio1:4 foundation CC in 1:4:8 ratio(cement, find sand & brick ballast) and RCC work in ratio 1:2:4 (cement, coarse sand and stone grit of 20mm gauge using MS bar of 10mm dia(tor) in reinforcement including its cutting, bending & binding in required shape. The work also includes laying of 2 No. 3.46 mtr. long rail pieces complete with cutting, welding & proper fitting etc. The plinth will be made as per drawing and shall be plastered/ finished on top and sides of the plinth.
Lightening Arrestor, P.I. & CT Structure : Fabrication of Lightening Arrestor, P.I. & CT Structure 3.5 mtr. in height as per Drg. digging of two no pits of size 1.075x0.9x0.3 mtr. providing stone pad at the bottom of the pit and grouting of two legs of the Structure in CC(cement coarse sand and stone grit of 20mm gauge) of the ratio 1:4:8 in block of 1.075x0.3 mtr. including all civil material, T&P complete in all respect. The work includes dragging, shifting up to 40 Mtr., raising and erecting the two legs with runner on proper alignment and level and plumb. Both plinths of the structure shall be properly finished with smoothing of edges.
Isolator Structure: Fabrication of Isolator Structure 3.5 mtr in height as per Drg. digging of two no. pits of size 1.075x0.9x0.3 mtr. providing Stone Pad at the bottom of the pit and grouting of two legs of the isolator structure in CC(cement coarse sand and stone grit of 20mm gauge) of the ratio 1:4:8 in block of 1.075x0.3 mtr. including all civil material, T&P complete in all respect. The work includes dragging, shifting up to 40 Mtr., raising and erecting the two legs with runner on proper alignment and level and plumb. Both plinths of the isolator structure shall be properly finished with smoothing of edges.
Plinth of VCB : Construction of Plinth of size 2.0 mtrx1.5mtrx0.9mtr. suitable for erection of upper structure of 33KV VCB including grouting of anchor bolts in proper alignment and level. Scope of work includes excavation of foundation base concreting in CC 1:3:6 (cement, find sand & brick ballast) 1st class brick work in cement mortor ratio 1:4:8 (cement, coarse sand and stone grit of 20mm gauge).
Fabrication and grouting (1:4:8) of MS Angle 75x75x6mm in L Shape & in proper size and alignment to provide support through GI earthing strips (50x6)mm size for power transformer neutral including supply & fixing of flexible copper bonds for neutral earthing as per RESPO Drg. (All decentralised materials to be provided by Contractor).
Fabrication and erection of cable support made of two pieces of MS channel 100x50mm, 3.0 mtr. long joined to each other by means of 5 no. MS Flat 50x6mm pieces of size 150mm long each by welding at equal intervals as per drawing and grouting in block of size 300x300x700mm (1:4:8) complete. This includes providing of required MS Clamp made of MS Flat holding the cable including nuts & bolts and fixing of XLPE cable.
Installation of Lightening Arrestors and Post Insulator : Assembling, installation & mounting of 3 No.(1set) L.A. and Post Insulator (12 nos.) on the L.A Structure/ Post Insulator /complete with making earth connections (separate) with GI Strip 50x6mm. The work includes fabrication for fixing if required. (All decentralised materials to be provided by Contractor).
Installation of Switchgears in Control Room:
Shifting carefully & installation safely 11KV Outgoing switchgears from outside the switchgear room placing and fixing of switchgear on foundation providing G.I. Bolt & Nuts of proper size in proper position and alignment. This includes checking, complete work with proper testing, connetion of earthing & commissioning of switchgears.
Fixing and making Bus Bar connections in between all switchgears after cleaning and tapping with H.T. Tape, empire tape and PVC tape properly, providing and fixing of 6 mm thick Bakelite separators and plugging of all opening & holes with plastic compound complete work as per required.
Shifting carefully and installation of 33KV Single Transformer Control Panel in Control Room including fixing, bolting & grouting of above as per required and testing, commisioning complete work as per required.
Earthing of 11 KV Switchgears: Earthing of 11 KV Switchgears by lowaring and boring of Chemical Earthing outside of switchyard and connecting through G.I. Strip 50x6mm with indoor/outdoor equipments with making of earth pit of 300x300 mm & 1 feet deep with Cover. (All the material provided by the contractor)
Installation of CT: Installation of 3 No.(1 set) CT on the CT Structure along with CT Junction Box. The work includes fabrication for proper fixing of C.T. If required and proper commissioning & testing.
Installation of VCB: Installation of 33KV VCB complete work including commissioning & testing.
Installation of Isolator: Installation of 3 No.(1 set) Isolator on the Isolator Structure. The work includes fabrication for proper fixing of Isolator . If required and proper commissioning. .
Painting of all structures and equipments with good quality ISI Mark one coat of red oxide primer & two coats of Aluminium Paint. (All materials to be provided by Contractor).
Construction of Cable trench of size 300x300mm including brick work 1:4 in wall of the trench, brick ballast work in 1:5:10 on foundation plaster 12mm thick with coarse sand 1:4 and surface finishing with cement, providing MS Strip at an interval of 0.5 Mt. and MS Angle (25x25x5mm) running on both the edges of trench.
Construction of welded frame type control cable trench cover 0.5 Mt. long suitable for trench including cost of MS/Tor Bar.
Earthing for power T/F by way of boaring and lowering of 40mm dia, 2.9 mm thick GI Pipe from ground upto the water level (minimum 60 feet deep) as per standard practice as per REC Drg.
HT Cable Laying :
Laying & dressing of 11KV 3x300 Sq.mm XLPE cable from 5MVA T/F to 11KV incoming Switchgear by excavation of trench in the ground of size 450mm wide, 900mm deep providing 150mm fine sand cushion below the cable. The cable shall be duly protected by bricks, sand & stone slab and refilling & ramming of the left out soil. Spare cable shall be left and buried in the trench in the shape of rings at both ends. Cable laying work includes unrolling, cutting, making ring and sealing both ends of the cable. (All decentralised materials to be provided by Contractor).
Laying & dressing of 11KV 3x185 Sq.mm XLPE cable from 11KV O/G VCB Switchgear To Double Pole Feeder by excavation of trench in the ground of size 450mm wide, 900mm deep providing 150mm fine sand cushion below & above the cable. The cable shall be duly protected by bricks, sand & stone slab and refilling & ramming of the left out soil. Spare cable shall be left and buried in the trench in the shape of rings at both ends. Cable laying work includes unrolling, cutting, making ring and sealing both ends of the cable. (All decentralised materials to be provided by Contractor).
Hoisting of 11KV Cable with 100 mm dia 3 Mtr. long GI Pipe on the feeder cable before mounting the cable on the double pole, lifting, mounting and clamping of 11KV feeder cable boxes on the feeder double pole structure and making connection including supply of cable mounting clamps. The work includes the sealing of GI Pipes, lower end of the pipe is to be buried into the earth by about one foot.(All decentralised materials to be provided by Contractor).
Hoisting of 11KV XLPE Cable for 11 KV switchgears & 33/11KV T/F of requried size.
Supply and laying of following size Copper Control Cable through underground/cable trench/trenching SGR interlinking through proper connections to T/F Control panel/protection board/Battery and Battery Charger/Bunch joints, Relay 33/11KV T/F junction Box/33KV VCB, CTs etc. as per site conditions:
2x2.5 Sq.mm
4x2.5 Sq.mm
6x2.5 Sq.mm
Supply and fixing of Control Cable Trey
Providing and Fixing of Single Core PVC Cable, 1x240/400/630 sq.mm. & fixing between Transformer incoming 3x300 Sq.mm XLPE Cable and Transformer 11 KV/LV Side Bushing connector for reducing of tension at LV Side Bushing.
Construction of 11 KV feeders : (a) Excavation of foundation pit in mix soil/normal soil, soft & hard rock and its back filling and levelling etc. The size of the pit will be 800x900 mm and having a depth of 1/6 of the full length of the support. Erection of supports by providing stone pad, fixing all clamps and other accessories such as No. Plate, Danger Board, Barbed Wire (2Kg.), Painting (one coat red oxide primer & two coats of red& Aluminium paint at required height). as per relevant RESPO/ RES. drawing . This includes any fabrication, if required. (b) Grouting of above supports with cement, concrete (CC will be of cement coarse sand & Stone Grit) Grouting will be done with the help of wooden/steel formers in a block of size 450 mm x 450 mm x 1/6 of the full length of the support in the CC 1:4:8 ratio as per RESPO/ RES. drawing including back filling and proper ramming. (c) Making plinth of STP 300 mm, dia & 300 mm above ground level in CC of 1:4:8 & plastering of the same with 12 mm thick plaster of cement & sand in 1:4 ratio. (d) Earthing of supports with Earth Electrode 2.5 mtr. length including excavation of pit and driving M.S. Rod upto proper depth and connecting the earth electrode with the help of 6/8 SWG G.I. Wire and earthing lugs. RESPO/ RES. drawing.
Double Support for Outgoing Feeder on 8.5 mtr PCC Pole with complete all accessories. (11 KV TPMO, 11 KV Fuse set with clamps to be provided by Contractor)
(a) Grouting of stay rods 1800x16 mm including all works of excavation grouting by, cement concrete in size 0.60x0.60x0.3 mtr. with ratio 1:4:8 as per relevant drawing including back filling of earth and proper ramming. (b) Fixing, making of loop insulator, tightening & nuzzling of stay with the poles and required tension as per RESPO/ RES. drawing.
(a) Excavation of foundation pit in mix soil/normal soil, soft & hard rack and its back filling and levelling etc. The size of the pit will be 800x900 mm and having a depth of 1/6 of the full length of the support. Erection of supports by providing stone pad, fixing all clamps and other accessories such as No. Plate, Danger Board, Barbed Wire (2Kg.), Painting etc. as per relevant RESPO/ RES. drawing . This includes any fabrication, if required. (b) Grouting of above supports with cement, concrete (CC will be of cement coarse sand & brick ballast) Grouting will be done with the help of wooden/steel formers in a block of size 450 mm x 450 mm x 1/6 of the full length of the support in the CC 1:4:8 ratio as per RESPO/ RES. drawing including back filling and proper ramming. (c) Making of plinth of STP 300 mm, dia & 300 mm above ground level in CC of 1:4:8 & plastering of the same with 12 mm thick plaster of cement & sand in 1:4 ratio. (d) Earthing of supports with Earth Electrode 2.5 mtr. length including excavation of pit and driving M.S. Rod upto proper depth and connecting the earth electrode with the help of 8 SWG G.I. Wire and earthing lugs. RESPO/ RES. drawing.
For O/G Double Support 8.5 Mtr. PCC :
For Single Support Section Pole on 11 Mtr STP
For Single Support Section Pole on 8.5 Mtr Pcc
For Single Support 8.5 mtr PCC :
For Single Support 11 mtr STP :
For End Type Section Double Support 8.5 Mtr. PCC:
For Section Double Support 8.5 Mtr. PCC :
For Stud Pole Support 8.5 Mtr. PCC :
For Making Single/Double Section Pole on Over head line 8.5 Mtr PCC
(a) Grouting of stay rods 1800x16 mm including all works of excavation grouting by , cement concrete in size 0.60x0.60x0.3 mtr. with ratio 1:4:8 as per relevant drawing including back filling of earth and proper ramming. (b) Fixing, tightening & nuzzling of stay with the poles and required tension as per RESPO/ RES. drawing.
Laying, spreading, lifting, Stinging, jointing and final sagging of ACSR Dog Conductor in accordance with profiles and sag chart including binding, jumpering and fixing of all accessories in 3 nos. conductor in parallel with PG Clamp binding wire etc requested for job.
Painting of following supports with one coat of red oxide primer and two coats of aluminum white paint of ISI mark and top danger portion of each support must be painted by providing two coat of Post Office Red Paint (1.5mtr upper portion of support.) Paint and material would be given by contractor to complete of job.
Painting Single Pole of 11 M S.T.P
Painting Single Section Pole of 11 M S.T.P
Providing & Fixing of 33 KV SMC Danger board ( as per GTP)with Clamp & Nut Bolt
Providing & Fixing of 33 KV SMC Number Plate ( as per GTP) with Clamp & Nut Bolt
Providing & Fixing of G.I. Barbed wire (2 Kg./pole)
Providing & Fixing of Stone Pad (300x300x75 mm)
Concreting of supports in 1:4:8 ratio and plinthing of supports upto 300mm above ground level by using cement ,Concrete ,Corase ,and sand in ratio 1:4:8 as per RESSPO drawing with watering/curing properly upto proper setting of plinthing.All matrial would be provided by the contractor.
Earthing of STP/PCC supports with Earth Electrode 2.5 mtr. length including excavation of pit and driving M.S. Rod upto proper depth and connecting the earth electrode with the help of 6 SWG G.I. Wire and earthing lugs. RESPO/ RES. drawing.Earthing of each section pole is also to be done. All type of nut & bot would be given by the contractor.
Cradle type Guarding of HT/LT/Telephone line/ road/river crossing etc. by providing GI wire No. 6/8 and making net with difference of 1.00 Mtr. Completely including fixing of channel/angle etc. with proper locking at each support. All type of nut bolt ,clamp to be provied by the contractor.
Dismentaling , Misc, & Extra Civil Works
Supply and fixing of Rubber mat 8/10mm, 2x4mtr.
Supply and Fixing Of 24 Volt Battery & Charger .
Replacement of Old Bus Bar into Panther Conductor (PG Clamp & Connector provided by the Contractor)
Repairing ,Overhauling and Removing Leakage /Sepage of Old & Used Nos.5 MVA Power T/F .Change OTI & WTI of Power T/F if Required.(OTI&WTI Be Provided By the Contractor.)
Tree cutting compensation
M/s Shubham Traders
NATIONAL CONTRACTOR & GENERAL ORDER SUPPLIER
Bidder Name
M/s Shubham Traders
NATIONAL CONTRACTOR & GENERAL ORDER SUPPLIER
HARE KRISHNA ENERGY PROJECTS
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .