Tender Value
₹49 L
EMD Value
₹98,000
Closing Date
20 Jun 2025, 6:00 pmClosed
GE(I R AND D RCI, HYDERABAD
GE(I) RND RCI, MILITARY ENGINEER SERVICES, VIGNYANAKANCHA, RCI, HYDERABAD
REPAIRS REPLACEMENT OF HT UG CABLES LT UG CABLES LT PANELS APFC PANELS ETC AT RCI HYDERABAD
2025_MES_711354_1
8283
Open Tender
Electrical and Maintenance Works
Item Rate
335 days
GE(I) R AND D RCI
MES enlisted Class D category b ii Un enlisted Meeting enlistment criteria of D class in MES and having no recovery pending. For further details ref NIT
8 documents required · 8 mandatory
₹500
Yes
GE(I) R AND D RCI HYDERABAD
₹98,000
Yes
26 Jun 2025
30 May 2025
23 Jun 2025
30 May 2025
20 Jun 2025
13 Jun 2025
Amount
Disconnecting and cutting down the existing unserviceable /burnt out HT cable end joints, S& F in repairs for outdoor type (Heat shrinkable) 11kV grade suitable for XLPE cables of size 120 Sqmm,3 core all as specified and as directed.
All as per item no 01 above but suitable for XLPE cables of size 95 Sqmm,3 core
Checking of APFC panels / capcitors bank panels, carrying out necessary servicing, cleaning of the switch gears, busbars with CTC and removing the carbon deposits, checking of the connections, functioning the components such as capacitors, contactors, switch gears etc ,disconnecting and removing burnt out cable end portions, crimping with new suitable lugs of the same size, removing burnt out thyristors, reconnecting and testing complete for maintaining efficient power factor at the Sub station all as directed.
Taking down the unserviceable power factor capacitors of different capacities from the capacitor panel board after disconnecting the electric supply, Supply and fixing of power factor correction capacitors, All Poly Propelene (APP) Box type, rectangular in shape, heavy duty, with over current withstand capability 3 x In, operating losses 0.35 W/kVAr, peak inrush current withstand capability 500 x In, number of switching operations per year : 20000, maximum ambient temperature 70 degree celcious, minimum operating life 300000 hours, various KVAR rating, 440 V, with suitable fixing arrangement including connection with suitable copper cables and testing complete all as specified and directed. Note : (i) Capacitors shall conform to IEC 831-1, with total losses not more than 0.25W / KVAR. (ii) Copper cables, thimbles will be measured and paid for seperately under respective items. Make : Cat No LTXL (Box series : LTBCU) of make L&T or equivalent model in SIEMENS/GE.
All as per Sl Item No 4 above but cylindrical type (LT CCU).
Supply and fix in repairs power factor control relay (APFC) 12 step including necessary electric connections and testing complete all as specified and directed. Make : L&T/HPL/Neptune
All as per Sl Item No 6 above but 8 step relay
All as per Sl Item No 6 above but 4 step relay
Supply and fix 4 pole 800 Amps, 50KA ruppturing capacity MCCBs with adjustable thermal and magnetic settings, 50 Hz at 415 volt, conforming to IEC -60947-II/ IS-13947-II including provision of copper cable / extended terminals of suitable ratings from MCCBs to busbar and connection of LT cables with MCCBs with suitable size aluminium lugs complete all as specified and directed for maintaining the APFC panels. Make : Havells / Schneider / Standard / GEC / Legrand / L&T
All as per Sl Item No 9 above, but 250 Amps, 36 KA capacity
All as per Sl Item No 9 above, but 125 Amps, 10 KA capacity
All as per Sl Item No 9 above, but for 63 to 100 Amps, 10 KA capacity
Supply and fix 3 pole 63 Amps, 10 KA ruppturing capacity MCBs, 50 Hz, conforming to IEC -60947-II/ IS/IEC-60898 complete all as specified and directed for maintaining the APFC panels. Make : Havell's / Schneider /Legrand / L&T
All as per Sl Item No 13 above, but SP, 2 Amps capacity
Disconnecting and removing of the unserviceable switch fuse unit (SFU) 63 Amps front operated from the existing position, supply and fixing new switch fuse unit (SFU) 63 Amps with HRC fuse links of 63 Amps all as directed . Make : Havell's / Schneider / Standard / GEC / Legrand / L&T
Disconnecting and removing of the unserviceable CT, Ratio 150/5 A (ID 75 mm) from the existing position, supply and fixing new CT, Ratio 150/5 A (ID 75 mm) all as specified and directed by Engr-in-Charge. Make : Havell's / Schneider / Standard / GEC / Legrand / L&T
Disconnecting and removing of the unserviceable 200 Amps HRC DIN type fuse link size 1 from the existing position, supply and fixing new 200 Amps HRC DIN type fuse link size 1 all as specified and directed by Engr-in-Charge. Make : Havell's / Schneider / Standard / GEC / Legrand / L&T
All as per Sl Item No 17 above, but for 16 / 32 Amps HRC bolted fuse link size A 2
All as per Sl Item No 17 above, but for 63 Amps HRC bolted fuse link size A 3
All as per Sl Item No 17 above, but for 63 / 100 Amps fuse link size 00
All as per Sl Item No 17 above, but for 125 Amps fuse link size 00
All as per Sl Item No 17 above, but for 63 Amps cylindrical type fuse link size 14x51
All as per Sl Item No 17 above, but for 20 Amps fuse base
Dismantling unserviceable/ burnt electric cables connected with capacitors, supply and replacement following size PVC insulated, unsheathed, single core industrial copper cable (flexible), 2.5 / 4.0 / 6.0 / 10 / 25 / 35 Sqmm, 1100 Volt grade, conforming to IS : 694, ISI marked, matching with the existing size, provision of suitable copper lugs, bolts, nuts, washers etc. complete including electric connections and testing complete all as specified and directed. Make : KEI/ Finolex / Legrand.
Dismantling unserviceable push buttons (start/stop button) from the power factor capacitor panel boards after disconnecting the power supply, supply and fix push buttons with 1 No + 1 NC, screw type for operation of capacitors all as per sample available at sub stations including necessary electric connections and testing complete all as specified and directed.
Opening of LT panel board, disconnecting and removing of the burnt out cable end terminations, cutting and reterminating of the cable end portions with proper size of lugs and decarbonising of panel busbar and cleaning with CTC, replacing of cable glands, connecting back cable end termination properly, opening of the busbar chambers, cutting removing of the cable connections, reterminating with proper size of lugs, tightening of the bus bar nuts, bolts including wrapping of the busbar with colour codes, checking of all switches, MCCBs all isolators, tightening of the loose connections replacing of burnt out fuse, cut out fuses with new ones complete all as directed by Engineer-in-Charge.
Dismantling unserviceable/ burnt thyristors / power contactors from the power factor capacitor panel boards after disconnecting the electric supply, supply and fix capacitor duty contactors suitable for following ratings of capacitors including necessary electric connections and testing complete all as specified and directed. Make : L&T / HPL / Neptune / GE / ABB
Supply MNX 185 power contactor
Supply MNX 70 power contactor
Supply MOC 50 power contactor
Supply MNX 32 power contactor
Supply MOC 25 power contactor
Dismantling unserviceable add on block for MNX / MOC series (Right or Left) from the power factor capacitor panel boards after disconnecting the electric supply, supply and fix new Add on block for MNX / MOC series (Right or Left) including necessary electric connections and testing complete all as specified and directed. Make : L&T / HPL / Neptune / GE / ABB
All as per Sl item No. 28 above but for 2 NO 2 NC
Taking out unserviceable analoge / digital type single phase ammeter / voltmeter, square type from LT panel boards, supply and fixing single phase analog / digital type ammeter / voltmeter, square type suiitable for three phase supply with suitable capacity CTs including electric connection and testing complete all as specified and directed
All as per Sl item No. 30 above but three phase
Taking out unserviceable LED type indicator lamp unit from the panel boards, supply and fixing LED type indicator lamp unit of red/ yellow / blue / green / Amber with bulb including connection and testing complete all as specified and directed. Make : AE / IMP / KAYCEE / C&S / L&T
PASAYDAN ELECTRICALS (BID ID -3323384)
jmd engineers (BID ID -3325629)
ELEVATORS MAINTENANCE ENGINEER WORKS (BID ID -3329816)
M.R.ENTERPRISES (BID ID -3328475)
omsai thermax engineers (BID ID -3330240)
hari enterprises (BID ID -3329296)
S.S.ENGINEERING CORPORATION (BID ID -3327380)
BHAGYARAM ENTERPRISES (BID ID -3327198)
vvcenterprises (BID ID -3329568)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .