Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Accepted-Technical | Accepted-Technical Technically accepted |
Tender Value
₹94.2 L
EMD Value
₹1.9 L
Closing Date
23 Mar 2026, 3:00 pmClosed
DIRECTOR CSIR NAL BENGALURU 560017
DIRECTOR CSIR NATIONAL AEROSPACE LABORATORIES KODIHALLI PBNo177 BENGALURU 560017
Round the clock operation and minor maintenance of 2 x 10 MVA 66 11 KV sub-station and other allied sub-stations and their associated HT and LT switchgears control panels batteries Operation of DG sets UPS systems and lab maintenance contract for E
2026_CSIR_268832_1
ESD - NAL / 08 / E of 2025 - 2026
Open Tender
Electrical Works
Item Rate
365 days
CSIR NAL NWTC BELUR BENGALURU
Please refer to the Tender Documents
11 documents required · 11 mandatory
₹1,000
THE DIRECTOR CSIR NAL
₹1.9 L
6 Apr 2026
26 Feb 2026
24 Mar 2026
26 Feb 2026
23 Mar 2026
26 Feb 2026
PART - A (66/11kV Sub station) Round the clock operation and minor maintenance of 2 x 10 MVA, 66 / 11 KV sub-station and other allied sub-stations and their associated HT& LT switchgears, control panels, batteries, Operation of DG sets, UPS systems, operations of Roof top SOLAR plants during emergency and etc,. by deploying qualified personnel including reliever as per the detailed scope of work and terms & conditions indicated / enclosed in tender document.
PART - B ( Maintenace of Laboratory) Day to Day Maintenance for attending breakdowns, servicing and repairing of electrical installations, preventative maintence and arranging power supply for newly installded scientific equipments etc., shown in Annexure -1. The work shall be complied as per detailed scope of work and other terms & conditions specified in the tender document on all CSIR-NAL working days from 8:30 hours and 17.00 hours (General shift).
PART - C ( Electrical consumables for maintenace works) Note: Supply of the light fixtures for entire period of contract as and when required. (Labour portion for fixing / replacement included in item No.2)
Supplying of Street light LED fixture, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4- 5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP66,IK-10, CRI >80 , under voltage and over voltage protection,EMIEMC as per CISPR-15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report , CCT 6000°K / 6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) 135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C).
Supplying of Flood Light, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP-66,IK-10, CRI >80 , under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg120deg as per the application and the project requirement deg., suitable tilt able fitting, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report , CCT 6000°K / 6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) 135 lm/Watt output LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C).
Supplying of Panel light 2x2 ft., of 40 watt body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends ,CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C).
Supplying of LED surface square SMD type of following body material with PMMAand prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range - 15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), life time of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K / 6000°K /6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) < 3. Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark / Name Engraved / Embossing / Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast / Extruded aluminum Body including trim..
stage.html
html • 0.02 MB
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.24 MB
TenderDocument08.pdf
Tender Documents • 2.11 MB
BOQ.xls
Other Document • 0.53 MB
ApprovedMakes.pdf
Other Document • 0.11 MB
tools.pdf
PDF • 0.10 MB
20260306154431.pdf
PDF • 0.56 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .