| 1 | 1₹25.0 LAccepted-AOC | ₹25.0 L Quoted ₹25.9 L | 1 | Accepted-AOC Being lowest |
| 2 | 2₹26.7 LRejected-Finance 65 MATA KA MANDIR RAM NAGAR COLONY SHAHJAHANPUR 242001 UP | SHAHJAHANPUR | SHAHJAHANPUR | UP | 242001 | ₹26.7 L | 2 | Rejected-Finance Not being lowest |
| 3 | 3₹28.3 LRejected-Finance | ₹28.3 L | 3 | Rejected-Finance Not being lowest |
| 4 | 4₹30.1 LRejected-Finance SHIV NIWAS DHANDA P O TOTU DISTT SHIMLA HP 171011 | SHIMLA | SHIMLA | HIMACHAL PRADESH | 171011 | ₹30.1 L | 4 | Rejected-Finance Not being lowest |
| 5 | 5₹34.1 LRejected-Finance MOH HATHITHAN NIGOHI ROAD SHAHJANPUR UP 242001 | SHAHJAHANPUR | UTTAR PRADESH | 242001 | ₹34.1 L | 5 | Rejected-Finance Not being lowest |
| Sl No | Description | Qty | Unit | M/S CHAUHAN ELECTRIC WORKS L2 | M/S J.B.AND SONS L3 | Vishvani Electricals L1 | SHYAM AND SONS ENTERPRISES L6 | M/S SRI JAGDAMBE TRADERS L7 | avon electric engineering woks L5 | M/S BEE ESS ENTERPRISES L8 | M/s Dinesh Kumar L4 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Taking down copper/aluminium point wiring of any description and any position (light, fan, socket or power point) complete, including fixture and fittings such as switches,socket, ceiling rose,lamp holder,pendants, bracket and regulator etc and removing material from site including making good disturbed surface to match with the existing surface complete all as specified. | 1,420 | Per Point | 5 ₹7,100 | 10 ₹14,200 | 3 ₹4,260 | 20 ₹28,400 | 10 ₹14,200 | 25 ₹35,500 | 19 ₹26,980 | 20 ₹28,400 |
| 2.00 | Taking down Aluminium sub main wiring and making good disturbed surfaces to match with the existing surface roof/wall/floor complete all as specified and as directed | 1,460 | RM | 2 ₹2,920 | 2 ₹2,920 | 1 ₹1,460 | 25 ₹36,500 | 5 ₹7,300 | 25 ₹36,500 | 19 ₹27,740 | 10 ₹14,600 |
| 3.00M&L for point wiring with 1100 volt grade PVC insulated and unsheathed 1.5 Sq mm (FRLSH) multistranded copper conductor cable with continuous earth wire of 1.5 Sq mm (FRLSH) multistranded copper conductor cable PVC insulated and unsheathed, drawn in & including concealed/surface with PVC rigid conduit medium grade with fittings (ISI marked) not less than 20 mm dia & 1.6 mm thick sunken pressed steel galvanised terminal boxes with top cover ISI marked plastic laminated hylam sheet for housing/ fixing switches etc complete all as specified and directed for the following- Note- (i) The quoted rete is deemed to be included for the chases cutting. (ii) Cutting chases for concealed shall be made good using CM 1:4 and surface finished to match the existing surface & colour. | |||||||||||
| 3.01 | One light/ holder/fan/exhaust/bell point controlled by one switch. | 900 | Per Point | 300 ₹2.7 L | 300 ₹2.7 L | 350 ₹3.1 L | 360 ₹3.2 L | 380 ₹3.4 L | 360 ₹3.2 L | 539 ₹4.9 L | 370 ₹3.3 L |
| 3.02 | One 5 pin 5 Amp switch socket combination point on an same board. | 100 | Per Point | 80 ₹8,000 | 60 ₹6,000 | 100 ₹10,000 | 125 ₹12,500 | 90 ₹9,000 | 170 ₹17,000 | 539 ₹53,900 | 180 ₹18,000 |
| 3.03 | One 5 pin 5 Amp switch socket combination point on an independent board. | 320 | Per Point | 300 ₹96,000 | 300 ₹96,000 | 350 ₹1.1 L | 360 ₹1.2 L | 380 ₹1.2 L | 360 ₹1.2 L | 539 ₹1.7 L | 370 ₹1.2 L |
| 4.00 | All as per item 3 here in before but for one 15 Amp 5/6 Pin switch socket combination independent with 2.5 Sqmm FRLSH unsheathed copper conductor single core multistranded complete all as specified and directed. | 100 | Per Point | 400 ₹40,000 | 400 ₹40,000 | 400 ₹40,000 | 450 ₹45,000 | 500 ₹50,000 | 390 ₹39,000 | 549 ₹54,900 | 490 ₹49,000 |
| 5.00 | S&F of Modular switch one way 6A, 1 module complete all as specified and directed. | 20 | Each | 70 ₹1,400 | 35 ₹700 | 100 ₹2,000 | 35 ₹700 | 110 ₹2,200 | 50 ₹1,000 | 39 ₹780 | 75 ₹1,500 |
| 6.00 | S&F of Switch Piano flush type 5 Amp single pole one way complete all as specified and directed. | 1,100 | Each | 25 ₹27,500 | 22 ₹24,200 | 20 ₹22,000 | 27 ₹29,700 | 28 ₹30,800 | 22 ₹24,200 | 19 ₹20,900 | 28 ₹30,800 |
| 7.00 | S&F of Modular Socket, 6A - 2/3 pin combined 2 module complete all as specified and directed. | 20 | Each | 95 ₹1,900 | 90 ₹1,800 | 120 ₹2,400 | 70 ₹1,400 | 170 ₹3,400 | 80 ₹1,600 | 59 ₹1,180 | 90 ₹1,800 |
Updated dates
Tender Value
₹40.4 L
EMD Value
₹80,740
Closing Date
11 Dec 2025, 6:00 pmClosed
HQ CWE Agra
112, Taj Road, Agra Cantt
REPAIR, RENEWAL, MAINT INTERNAL ELECTRIFICATION INCL FITTING, WINTER APPLIANCES AND CERTAIN ALLIED WORK AT FATEHGARH
2025_MES_739551_1
86260/E8
Open Tender
Electrical and Maintenance Works
180 days
Fatehgarh
MES contractors enlisted for Class D and above and category b(i) for unenlisted contractors meeting the enlistment criteria corresponding to value class and category of work
8 documents required · 8 mandatory
₹500
AGE (I) Fatehgarh
₹80,740
21 Jan 2026
13 Nov 2025
18 Dec 2025
13 Nov 2025
11 Dec 2025
27 Nov 2025
13 Nov 2025 - 20 Nov 2025
Amount
Taking down copper/aluminium point wiring of any description and any position (light, fan, socket or power point) complete, including fixture and fittings such as switches,socket, ceiling rose,lamp holder,pendants, bracket and regulator etc and removing material from site including making good disturbed surface to match with the existing surface complete all as specified.
Taking down Aluminium sub main wiring and making good disturbed surfaces to match with the existing surface roof/wall/floor complete all as specified and as directed
M&L for point wiring with 1100 volt grade PVC insulated and unsheathed 1.5 Sq mm (FRLSH) multistranded copper conductor cable with continuous earth wire of 1.5 Sq mm (FRLSH) multistranded copper conductor cable PVC insulated and unsheathed, drawn in & including concealed/surface with PVC rigid conduit medium grade with fittings (ISI marked) not less than 20 mm dia & 1.6 mm thick sunken pressed steel galvanised terminal boxes with top cover ISI marked plastic laminated hylam sheet for housing/ fixing switches etc complete all as specified and directed for the following- Note- (i) The quoted rete is deemed to be included for the chases cutting. (ii) Cutting chases for concealed shall be made good using CM 1:4 and surface finished to match the existing surface & colour.
One light/ holder/fan/exhaust/bell point controlled by one switch.
One 5 pin 5 Amp switch socket combination point on an same board.
One 5 pin 5 Amp switch socket combination point on an independent board.
All as per item 3 here in before but for one 15 Amp 5/6 Pin switch socket combination independent with 2.5 Sqmm FRLSH unsheathed copper conductor single core multistranded complete all as specified and directed.
S&F of Modular switch one way 6A, 1 module complete all as specified and directed.
S&F of Switch Piano flush type 5 Amp single pole one way complete all as specified and directed.
S&F of Modular Socket, 6A - 2/3 pin combined 2 module complete all as specified and directed.
S&F of switch socket combination 2 in 1 flush type 5 Amp 5 Pin complete all as specified and directed.
S&F of Modular Socket 6A/16A - 2/3 pin combined 2 module complete all as specified and directed.
S&F of switch socket combination 5 in 1, 15 Amp flush type complete all as specified and directed.
S&F of modular type Fan step regulator, 120W - 2 module complete all as specified and directed.
S&F of electronic fan regulator 5 stepped type complete all as specified and directed
S&F of ceiling rose PVC/Poly carbonate isolated body three terminal AC 230 volts complete all as specified and directed.
S&F of MODULAR white or Ivory cover plate with frame, 3 module complete all as specified and directed.
S&F of MODULAR white or Ivory cover plate with frame, 4 module complete all as specified and directed.
S&F of MODULAR white or Ivory cover plate with frame, 8 module complete all as specified and directed.
S&F of Metal Flush box 3 module complete all as specified and directed.
S&F of Metal Flush box 4 module complete all as specified and directed.
S&F of Metal Flush box 8 module complete all as specified and directed.
S&F of Lamp holder, PVC/Polycarbonate type with back plate suitable for batten fittings complete all as specified and directed.
S&F of Call Bell Ding Dong AC 230 volts complete all as specified and as directed.
S&F of Bell Push AC 230 volts complete all as specified and as directed.
M&L for sub main wiring with two single core 6.0 Sqmm FRLSH copper conductor PVC insulated and unsheathed cable including PVC conduit medium grade (appropriate size) concealed in wall for sub main connection including 6.0 Sqmm FRLSH insulated multistranded unsheathed copper conductor used as a earth wire to common earth and connection to earth dolly all as specified. (Note :- Two runs of 6.0 sqmm FRLSH and one run of 6.0 sqmm FRLSH copper conductor shall be measured as one unit length.)
M&L for sub main wiring with two single core 4.0 Sqmm FRLSH copper conductor PVC insulated and unsheathed cable including PVC conduit medium grade (appropriate size) concealed in wall for sub main connection including 4.0 Sqmm FRLSH insulated multistranded unsheathed copper conductor used as a earth wire to common earth and connection to earth dolly all as specified. (Note :- Two runs of 4.0 sqmm FRLSH and one run of 4.0 sqmm FRLSH copper conductor shall be measured as one unit length.)
S&F in replacement of VTPN DB 12 way suitable for Mounting MCCB as Incomer of rating 200 Amp Vertical distribution board with suitable rated bus bar having IP-43 protection and double metal door concealed in wall including connection as required complete all as specified & directed.
S&F in replacement of MCB distribution board SPN 240 Volt 12 way with 200 Amp rated bus bar having IP-43 protection and double metal door concealed in wall including connection as required complete all as specified & directed.
S&F in replacement of MCB distribution board SPN 240 Volt 8 way with 200 Amp rated bus bar having IP-43 protection and double metal door concealed in wall including connection as required complete all as specified & directed.
S&F in replacement of MCCB 160 Amp, 16KA, 4 Pole including complete electrical connection complete all as specified and directed
S&F in replacement of MCCB 100 Amp, 16KA, 4 Pole including complete electrical connection complete all as specified and directed
S&F in replacement of MCB SPN 32-40 Amp, 10 KA, 240 volt 'C' curve complete all as specifed and directed.
S&F in replacement of MCB of MCB SP 6 to 32 Amp 240 Volt 'C' curve 10 KA complete all as specified and directed.
S&F of Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 amps complete all as specified and directed.
S&F in repair of LED lights fitting 4 Ft, 20W, 220V, AC, batten type, including LED tube light connecting up with two core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed.
S & F in repair LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC batten type including connecting up with two core flexible copper conductor cable of suitable size complete all as specified and directed
S&F in repair LED luminaire 600 mm x 600 mm, 36/ 40 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and directed.
S&F in repair round shape 15 watt 220 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed.
S & F in repair Building security LED Light 30/35 Watt made up pressure die-cast aluminium housing with high power LED as lighting source and lens embedded PC having top opening separate driver compartment with IP-66 protection and impact resistance of IK 07 for building secuity purpose with bracket size made of GI pipe medicum grade 32 mm dia 1.5 mtr long bend to shape as required and fixing with two nos MS Clamp of size 40x6 mm for fixing of builiding security light fittings completed all as specified and directed.
S & F in repair of LED lamp 9 watt B22 completed all as specified and directed.
S&F in repair of LED decorative wall light fixture made up of Polycarbonate, suitable for 09W TU retrofit CFL (B-22 base) including LED bulb 09 Watt of colour temp 3000K & luminaire lumen >1000 lm complete all as specified and directed.
S & F in replacement LED light fitting 1x9W / 1X10W bulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed.
M&L for earthing complete with galvanised steel earth plate electrode 600 x 600 x 6 mm thick, burried directly into the ground (earth pit not less than 2.25 mtr below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to GI earth wire 4 mm dia by means of bolts, nuts, check nuts, and washers of galvanised iron or steel all as shown in electrical plate No - 3 connected to earthing test point all as specified or indicated including excavation and connected earth work, PCC chamber and cover, watering pipe, funnel wire mesh but without earth lead protection pipe and test on completion after dismantling unserviceable erthing (above GL only) complete all as directed incl dismantling of exsisting earthing. ( Note :- On testing after completion if desired earth resistence is not obtained, the earthing will be redone at no extra cost.)
Supply and Laying cable XLPE Insulated screened PVC bedded, galvanized steel strip armoured service cable pole to building electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 Sqmm 3.5 Core incl dismentaling complete all as specified and directed.
All as per item 42.00 here in before but of size 50 Sqmm 3.5 Core
S & F in of 40 mm bore GI Tubing light grade with all fittings laid across road, in trenches or across PCC drain, along electric pole or floor/wall for cable protection with suitable size of MS Clapms and nut and bolts/washer complete all as specified and directed.
M & L Sand cushioning for cables complete all as specified and directed .
M & L for old size brick well burnt, laid flat, for cable protection complete all as specified and directed.
Excavation in trenches not exceeding 1.5 mtrs wide and not exceeding 1.5 mtrs in depth for laying of cables including getting out in any type of soil complete all as specified and directed.
Returning filling in including spreading, leveling ,and well ramming, in layers not exceeding 25 cm each layer of any type of soil complete all as specified and directed
Removing surplus excavated material from site not exceeding 50 mtrs from starting point and depositing where directed at level not exceeding 1.5 mtr above the starting point complete all as specified and directed
S&F in replacement of 3 phase multi-function meter LCD display 3x240V, 3X (20100)Amp, 50 Hz, 3200 Imp/kWh, class - 1.0, ISI mark (20100) Amps with cover box including necessary connection complete as directed. Make : Genus/HPL/L&T. The contractor should deposit the Old U/S meter to E/M store yard.
Taking down carefully storage type water heater (Geysers) of any make of 50 litrs capacity at any height opening for inspection complete including heating element inner copper tank etc de-scaling cleaning and re-assembling of Geysers after necessary repairs carrying out and re-fixing in same position (spares parts as required for repair/replacement geyser are measured and paid separately under supply only item) including making good to walls with CM (1:3) or PCC (1:2:4) and plastering the wall surfaces with CM 1:6 and replacement of old nuts, bolts and rubber gasket etc all as specified & directed. Note:- Spares replaced shall be measured and paid seperately under respective items of this Schedule as supply only.
All as per item No.51 above but of capacity 25 ltrs
Supply only of 1.5 KW Heating Element, Push/ Screw type with ‘O’ ring complete all as specified and directed.
Supply only of 2.0 KW Heating Element, Push/ Screw type with ‘O’ ring complete all as specified and directed.
Supply only of 2.0 KW Heating Element, Push/ Screw type with ‘O’ ring with and including aparatus plate assembly suitable for Racold Make geyser as per sample complete all as specified and directed.
Supply only of Geyser assembly suitable for 25 ltr capacity ISI marked complete all as specified & directed.
Supply only of Geyser assembly suitable for 50 ltr capacity ISI marked complete all as specified & directed.
Supply only of thermostate suitable for 50 Ltr Geyser ISI marked complete all as specified & directed.
Supply only of thermostate suitable for 25 Ltr Geyser ISI marked complete all as specified & directed.
Supply only of inner tank made of steel suitable for 25 Ltr geyser complete all as specified & directed.
Supply only outer tank made of steel suitable for 25 Ltr geyser complete all as specified & directed.
Supply only LED indicating lamp 230 volts 50 HZ AC suitable for geyser any type (round,squire or rectangular type) any capacity complete all as specified & directed.
S&F in replacement hot water supply CPVC/PVC connection pipe of size 450mm long heavy duty with check nut for 15 mm dia pipe ISI marked complete all as specified and directed.
Supply in replacement safety pressure/air lock valve suitable for geyser 25/50 Ltrs capacity complete all as specified and directed.
M&L for sub main wiring with two single core 4 Sqmm (FRLSHH) copper conductor PVC unsheathed cable medium grade in existing PVC conduit concealed in wall for sub main connection including 4 Sqmm (FRLSH) PVC insulated multistranded unsheathed copper conductor used as a earth wire to common earth and connection to earth dolly including dismantling and resurfacing the disturbed surface all as specified & directed. (Note :- Two runs of 4 sqmm (FRLSH) and one run of 4 sqmm (FRLSH) copper conductor shall be measured as one unit length.)
Dismantling complete solar water heating system of capacity 300 LPD per day including hot & cold water pipes and hot water tank complete. Repairing the system fixing back in position and testing complete all as specified and as directed. Note:- Rates quoted by the contractor shall deemed to be included for:- (a) Making good the worn out missing nuts bolts, washers, union sockets, flanges and screws etc. (b) Cleaning hot and cold water tanks.
All as per item No.66 above but for 200 LPD
S &F in repair of 15 mm bore GI tubing medium grade with screw, socket joints with all fittings/fixtures like bends, sockets, unions, nipples etc on wall or floor including making alterations in existing /new pipes as required complete all as specified and as directed.
S&F in repair 15mm dia bib taps fancy type, cast copper alloy with crutch or butterfly handle, screwed down, screwed for iron pipe complete all as specified and as directed.
Supply and fixing in repair of Angle stop valves of any colour high pressure screwed for iron pipe and fixed for 15-20 mm bore pipes.
M/S CHAUHAN ELECTRIC WORKS (BID ID -3488973)
M/S J.B.AND SONS (BID ID -3489093)
M/s Dinesh Kumar (BID ID -3495406)
avon electric engineering woks (BID ID -3495377)
SHYAM AND SONS ENTERPRISES (BID ID -3489694)
M/S SRI JAGDAMBE TRADERS (BID ID -3494714)
M/S BEE ESS ENTERPRISES (BID ID -3484105)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.12 MB
BOQ_828094.xls
BOQ • 11.52 MB
TENDER.pdf
Tender Documents • 0.37 MB
AppxG.pdf
Additional Documents • 0.06 MB
Download all tender documents and submit your bid