| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.1 LAccepted-Finance | ₹9.1 L | L1 | Accepted-Finance LOWEST BIDDER |
| 2 | L2₹9.3 LRejected-Finance 22B RABINDRA SARANI ROOM NO SM 27 KOLKATA KOLKATA 700073 | KOLKATA | WEST BENGAL | 700073 | ₹9.3 L | L2 | Rejected-Finance NOT LOWEST BIDDER |
| 3 | L3₹9.5 LRejected-Finance | ₹9.5 L | L3 | Rejected-Finance NOT LOWEST BIDDER |
| Sl No | Description | Qty | Unit | PRADHAN ENGINEERING L2 | SARKAR ENTERPRISES L1 | ALTECH ELECTRO L3 |
|---|---|---|---|---|---|---|
| 1.01 | TOTAL | 1 | Nos | 9,27,244.24 ₹9.3 L | 9,14,110.6 ₹9.1 L | 9,49,937.3 ₹9.5 L |
Tender Value
Refer Docs
EMD Value
₹18,500
Closing Date
28 Jan 2026, 1:00 pmClosed
D.G. S_D
OFFICE OF THE DG S_D Kolkata Municipal Corporation 5, S.N. Banerjee Road Kolkata-700 013
Complete rewinding of stator with replacement of cable of 80 KW 415 volt motor of submersible pump unit no. A at MMPS under BDPS.
2026_KMC_988675_1
KMC/DG(S_D)/BDPS/ES-14/25-26
Open Tender
Electrical Work/ Equipment
10 days
BDPS
Please refer Tender documents.
4 documents required · 4 mandatory
₹0
₹18,500
30 May 2026
16 Jan 2026
30 Jan 2026
16 Jan 2026
28 Jan 2026
16 Jan 2026
TOTAL
Item Rate BoQ
BoQ_Ver3.0
Name of the Bidder/ Bidding Firm / Company :
PRICE SCHEDULE (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only )
NUMBER #
Enagement of specialised technician to overview the situation under the sump
Cutting out the column pipe and bring it to the top along with cleaning the well properly to to fix the new column pipe
Lifting the pump with special attachment after disconnecting the power supply and removing top cover.
Dismantling the motor by separation of stator and rotor carefully without damaging the both and all the rotating components to be placed on the wooden block separately in the working place and dismantling the pump unit part by part such as draining out of oil from oil chamber, motor shaft, mechanical seals, bearings, diffuser, bell mouth, impeller etc. by using special tools and tackles.
Removal of the bearing housing and the bearing without damaging and mechanical seal with special attachments and hydraulic puller
Complete re-winding the stator with new conductor as per original shape and size with class insulation. winding to be baked up to proper temperature, vanish and cured properly. high pressure testing measurement of ir of winding resistance to be done as per direction of engineer-in- charge
After thorough cleaning of the rotor winding by proper heating, final cleaning to be done by ctg. The rotor winding is to be varnished by dr. beck's make vanish after heat.
Trueness checking of rotor shaft and dynamic balancing of rotor (balancing certificate to be produced)
Testing with measuring of IR value and all other relevant test and electric H.P test.
Thorough check up the power and control cable arrangement of socketing with supply of copper socket as required size by crimping and soldering.
Modification of cable gland enclosure by sealing of one side cable gland properly with high graded sealing materials and making a new enclosure cover after arranagement by machining & drilling the unit.
Supply of 4 core 50 Sq mm copper flexible cable.
Finishing end terminal leads by S & F dowells copeer sockets properly supplying tapes, petroleum jelly etc 6 nos.
Repairing the 3 nos. bearing housings
Servicing of 3 number of bearing and fitting
Supply and replacement of damaged Mechanical seals 80/75 upper and lower (1 set).
Metalizing the diffuser to minimize the distance betweeen impeller and diffuser
Filling the oil chamber with specified graded oil and pressure testing for confirming the leakage.
Assembly the entire pump motor unit part by part with tact and tools with necessary gasket, nitrile rubber o- ring, nut , bolts & washer, high temperature grease etc.
Thorough painting the whole pump motor with two coats of approved quality paint after necessary scrapping and cleaning.
Transportation charge from pumping station to party's work shop and back same including loading
Lower down the finished column pipe in the well part by part and assemble by fastening it in the well by SS Bolt by maintaining proper alignment
Lower down the pump motor set and commissioning after complete assembly and provide electrical connection in the starter panel board and trail run.
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.28 MB
TD.pdf
Tender Documents • 0.63 MB
BOQ_2415405.xls
BOQ • 0.39 MB
Download all tender documents and submit your bid