Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.3 CrAccepted-AOC 15 402 ASHOKA RATAN SHANKAR NAGAR DISTT RAIPUR CG | RAIGARH | CHHATTISGARH | 492007 | ₹9.3 Cr | L1 | Accepted-AOC Award value is inclusive of GST at the rate of 18 percent |
| 2 | L2₹9.6 Cr+₹33.6 L (3.62%)Rejected-Finance | ₹9.6 Cr+₹33.6 L (3.62%) | L2 | Rejected-Finance Rejected not being L1 |
| 3 | L3₹10.6 Cr+₹1.3 Cr (13.9%)Rejected-Finance C O VOLTAS LIMITED SPARE PARTS DEPOT OLD HUTMENT COLONY NCL NIGAHI SINGRAULI M P 486884 | SINGRAULI | SINGRAULI | MADHYA PRADESH | 486884 | ₹10.6 Cr+₹1.3 Cr (13.9%) | L3 | Rejected-Finance Rejected not being L1 |
| 4 | Rejected-Technical | - | - | Rejected-Technical Does not meet the requirement of NIT as per Clause no 8(c). |
Tender Value
₹11.4 Cr
EMD Value
₹14.2 L
Closing Date
17 Apr 2024, 5:00 pmClosed
GM (CMC)/ HoD, SECL
Office of GM (CMC)/ HoD, SECL
Planning, Design, Engineering, Construction, Fabrication, Supply, Erection, Trial Run and Commissioning of 2X2.5 MVA, 33kV/3.3kV Substation including Operation and Maintenance during DLP of 60months on Turnkey Basis at KANCHAN OCP, JOHILLA AREA, SECL
2024_SECL_303208_1
SECL/BSP/CMC/e-Tender-TK/JHL /605 dt. 29.02.2024
Turnkey
Electrical and Maintenance Works
Item Rate
2190 days
KANCHAN OCP, JOHILLA AREA, Dist- Umaria(MP)
Please refer Tender documents.
6 documents required · 6 mandatory
₹14.2 L
Office of GM (CMC)/ HoD, SECL
18 Feb 2025
1 Mar 2024
19 Apr 2024
1 Mar 2024
17 Apr 2024
18 Mar 2024
1 Mar 2024 - 10 Apr 2024
11 Mar 2024
Amount
DESIGN AND ENGINEERING COST (for 2X2.5 MVA, 33kV/3.3kV Substation)
Design and Engg on PLANT & MACHINERY ( P&M - Electrical) to be supplied by bidder inlcusive of Overhead constuction cost, Contigencices, but excluding GST
Design and Engg on Civil & Structural work
CIVIL CONSTRUCTION AND STRUCTURAL WORKS for 2X2.5 MVA, 33kV/3.3kV Substation on Turnkey Basis at SHIWANI UG, BHATGAON AREA inclusive of Insurance,Contingencie but excluding GST
Sub-station Building
Outdoor steel structures
Foundation of outdoor structures including Transformer foundation
Cable Trench
Barbed wire fencing
Boundary wall
Surface dressing
Stone laying
Anti weed treatment
Bore well with submersible pump
Path way
Security Room
RCC sump and Pump House
Shed for DG & oil filter unit
Drain along boundary wall
Parking Shed
Oil Overflow Chamber
Oil Drain Pipe
Survey & Soil testing
SUPPLY OF PLANT & MACHINERY inclusive of Overhead Construction cost, Insurance, Contingencies , but excluding GST for substation ( 2X2.5 MVA, 33kV/3.3kV Substation )
Isolators, 33 kV (nominal),3 poles, pole mounted, 630A(min.), suitable fault current rating, arrangement for interlocking with 33 kV Vacuum Circuit breaker ( Min. 8 sets)
Isolators, 33 kV (nominal), 3 poles, pole mounted, 630A(min.), suitable fault current rating, arrangement for interlocking with 33 kV Vacuum Circuit breaker with Earthing switch ( Min. 2 sets)
Isolators, 33 kV (nominal), 3 poles, pole mounted, 630A(min.) ,suitable fault rating, with D.O. Fuses. (Min. 4 sets)
Lightning Arrestors, station class, 30 kV,10 kA, suitable for 33kV, solidly earthed (each set consists of 3 nos.) with counters/surge monitors (Min. 6 sets)
Single phase current transformer ,outdoor type with required CT ratio for 33 kV system for metering and protection (1 set consists of 3 units for 3 phase supply) Min 5 sets
Potential transformer ,outdoor type 33kV, 100 VA each (each set consists of 3 nos. single phase PT) 33/√ 3 kV/ 110/ √ 3 V for metering and protection each for three phase system (Min. 2 sets)
Vacuum Circuit Breaker, 33kV,630 A/800 A/1250A, outdoor type, 25 kA min with remote control panel having IDMTL relay for O/L and E/F protection,,Digital type microprocessor based power meter, ammeter etc (Min. 5 sets)
Power Transformer outdoor type plinth mounted 33/3.3kV, 2.5 MVA, ONAN cooled, DYn-11 conforming to IS:2026 (current) having OFF-LOAD tap changer on HV side and LV neutral restricted earthed ( with NGR) with all accessories including 33 kV remote control panel for on load tap changer as per IS:3639 (Current) with the rating as given below: Rated kVA: 2500 Rated Voltage(primary):33000V Rated Voltage(secondary):3.3kVV Connection and vector group:Dyn11 (Min. 2 Nos.)
18 - Panels, 3.3 kV switch-board, indoor type with 18 nos. VCB panels, 630 A for incomer and sectionaliser , 630 A for outgoing , 150 MVA symmetrical breaking capacity. All panels will conform to IS:3427 (current) and relevent parts to IS:2516. These will be provided with cable end boxes. The incoming panels will be provided with restricted earth fault Protection. All panels will be provided with IDMTL relays for over current and earth fault protection. All incoming control circuit breaker shall be provided with Digital type microprocer based Power meter and outgoing control circuit breaker shall be provided with Digital type ammeter & energy meter.
Station Transformer , Outdoor Type . 160 kVA , 33kV/0.433kV , Cu wound , plinth wound
Lighting Transformer , Outdoor Type . 100 kVA , 33kV/0.230kV(L-L) , Cu wound , plinth wound
230V(L-L) Main Lighting Distribution Board
415V 3 Ph-N, switchboard , indoor type with 4 nos. MCCB having O/L , S/C, and E/L protection , 25 MVA symmetrical breaking capacity ( All outgoing panels will be provided with ammeter and incoming panel with ammeter and voltmeter). The function of panels will be as follows:- 1 no. , required rating MCCB , required CTR , as controller for incoming feered. 3 nos. , required rating MCCB , required rating CTR , as controller for outgoing feeders.
Capacitor bank, 3.3kV indoor type (600KVAR) Suitable Rating kVAR including APFC. (Min. 2 nos.)
Battery (110 V) lead Acid type, 200 AH and battery charging (with one stand bye battery charging unit) equipment, control panels, wooden racks including DCDB etc.
Earthing system (Safe Earth Electrode type) including earth pits, required galvanised strips/flats,MS Rod for inter connection etc.
Lightning protection system consisting of spikes, earth pits, galvanised strips/flats, shield conductors etc.
LUMINARIES
Decorative, LED (Suitable rating) light fittings
Suitable rating LED Bulbs for indoor lighting
Tubular steel poles,11m height along with 90 W LED lamps with fittings ( minimum 7 nos.)
Lighting masts, 15m height (Min) along with required nos. of 200 W LED lamps with fittings.(min. one number mast) and Luminaires for Lightning cum Lighting Mast
90 W LED fitted on substation building (min. 4 nos.)
Emergency lighting system suitable for operation on 110 V DC supply in substation building.
Accessories such as lighting distribution boards, sub lighting distribution boards, junction boxes, individual control cables, PVC conduits/ casings, back up fuses, switches, sockets, ceiling roses, single core PVC cable with copper conductors, flexible wire etc.
CABLE AND ACCESSORIES
HT Power Cable , 3.3kV , Copper Cable
LT Power cable, 1100V grade, PVCSWA, 10 sq. mm.(minimum),3/4 core copper stranded conductors
Outdoor Lighting cable, 1100V, PVCSWA , 2 cores, 10 sq mm (minimum) stranded Al conductors
Outdoor and indoor Control cables, 1100V grade, PVCSWA, not less than 2.5 sq mm , copper conductors of with required number of cores
Wires for internal wiring of ,of illumination, ceiling fans, power sockets etc. 1.5 sq mm and 6 sq mm size, PVC insulated copper conductor cable of 1100 V grade.
Cables for internal control wiring for circuit breakers, CT’s, PT’s, PVC insulated cable 2.5 sq mm size, PVC insulated copper conductor of 1100 V grade
Cable trays, cable racks, binding materials, cable glands/lugs, cable jointing kit, bolts, nuts, washers, termination kit, other accessories etc.
Overhead conductors,Insulators, poles, string bus, ACSR conductors, clamps, terminal connectors, other steel hardware etc for 33 kV sides in the out door yard and 2 pole structure fitted with gang operated AB switch, lightning arrester etc for out going feeders
FIRE FIGHTING SYSTEM
Fire fighting equipment consisting of fire hydrants hose cabinets, hose reels, valves, pipes, fire detection alarming system, High velocity Water spray system for power transformers,diesel pump, electric pump with electricals and cables , jockey pump etc
Supply of portable fire extinguisher system
Sand buckets with stand
MISCELLANEOUS ITEMS
Room air conditioners, min. 1.5 t capacity ( 5 star rating inverter compressor type ) including servo stabilizer
Supply of 63/62.5 kVA Diesel Generator set (silent type) with 3 ph, 50 Hz ,415 V output supply with cable, change over switch and earthing etc (Min. 1 no.)
Exhaust fans
BLDC Ceiling fan ,1200 mm sweep along with electronic regulator (5 star rating)
Water cooler with water purifier r (min 20 Ltr storage & 20 LPH cooling capacities) Min. 1 no.
Vacuum Cleaner Set (Min. 1 no.)
LOTO station system/kit-1 no. , Electrical Layout/Single Line Diagram Board , Electrical shock treatment Chart , Do's & Don’t Chart , Earth pit connection diagram with retro refractive radium type display , Danger plates , Furniture & fittings and insulating mat, First Aid chart & box, tool box, caution board, keyboard etc
Erection and commissioning of Plant and Machinary for substation to be suplied by bidder as above inclusive of Overhead Construction cost, Insurance, Contingencies , but excluding GST
Training of O&M staff
Store cost for maintenance of P&M during Defect Liability Period (DLP) of five years.
Cost of Operation & Maintenace during during Defect Liability Period (DLP) of five years.
Total impact of GST for the purpose of CTC
Konstelec Engineers Limited
Universal MEP Projects & Engineering Services Limited
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
BOQ_314100.xls
BOQ Document • 0.31 MB
140937087.pdf
Tender Document • 0.54 MB
140937089.html
Tender Document • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .