SPECIAL REPAIR OF EXISTING LT PANELS AND IMPROVEMENT IN CONNECTED ACCESSORIES AT RAMGARH UNDER GE (AF) JAISALMER
2026_MES_784241_1
8470/GE/E8
Open Tender
Miscellaneous Works
Item Rate
180 days
GE (AF) Jaisalmer
As per tender documents
7 documents required · 7 mandatory
₹500
GE (AF) Jaisalmer
₹95,040
Yes
13 Aug 2026
13 Aug 2026
4 Sept 2026
13 Aug 2026
2 Sept 2026
26 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing & commissioning in replacement of LT panel Outdoor type, CPRI All type test certificate and Design Verification with switchgears (MCCB) conforming to IS/IEC: 61439/2011 Part-1 & 2 shall be submitted by the contractor before execution of work, weather/vermin proof, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system, made out of 3.15 mm thick CRCA sheet with Rain Canopy and Outlet filter with Hood, factory assembled cubicle pattern modular and compartmentalized construction with front and backside hinged double door with locking arrangement, floor mounted free standing type with Angle iron of size 50 x 50 x 6 mm, provided with gasket for all the doors & removable covers, duly powder coated, 3 phase and neutral 400 Amps current carrying capacity aluminium bus bar with heat shrinkable PVC sleeve insulated coating with colour code and insulated support with aluminium earth bus of size 25 x 6 mm with inter connecting bus bar connection comprising of following switch gears and mounting panel board on ground with PCC (1:3:6) bedding upto a height of 30 cm above gorund level connecting existing LT Cables with panel board complete all as specified and directed :- NOTES: [i] The Panel shall be purchased from the (OEM) / authorized license partner of the OEM i.e. ABB, Siemens, Havells, L&T or equivalent as approved by GE.
(Note: LT Panel shall be mounted on floor with suitable size fasteners and cost of the same shall be deemed to be included in the unit rate quoted for the item)
Location : HQ Main Panel
Incoming :(a) MCCB 250 Amp 415 Volts, 36 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release -01 No
Outgoing :(a) MCCB 160 Amp 415 Volts, 25 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release-01 No
(b) MCCB 125 Amp 415 Volts, 25 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release-01 No
(c) MCCB 100 Amp 415 Volts, 25 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release-01 No
(d) Digital Voltmeter 0-500 Volts with inbuilt selector switch -01 No
(e) Digital Amp meter 0-250 Amp with inbuilt selector switch -01 No
(f) Indicating Light RED 220V AC -01 No
(g) Indicating Light Yellow 220V AC -01 No
(h) Indicating Light Green 220V AC -01 No
(j) Protection MCB 6 Amp SP-03 Nos
(k) CT 250/5A-03 Nos
(l) Automatic Phase Sequence Corrector -01 No
(m) Danger Plate-01 No
(n) Enclosure of Suitable Size | 1 | Each Job | - | - |
| 2 | Supply, installation, testing & commissioning in replacement of LT panel Outdoor type, CPRI All type test certificate and Design Verification with switchgears (MCCB) conforming to IS/IEC: 61439/2011 Part-1 & 2 shall be submitted by the contractor before execution of work, weather/vermin proof, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system, made out of 3.15 mm thick CRCA sheet with Rain Canopy and Outlet filter with Hood, factory assembled cubicle pattern modular and compartmentalized construction with front and backside hinged double door with locking arrangement, floor mounted free standing type with Angle iron of size 50 x 50 x 6 mm, provided with gasket for all the doors & removable covers, duly powder coated, 3 phase and neutral 400 Amps current carrying capacity aluminium bus bar with heat shrinkable PVC sleeve insulated coating with colour code and insulated support with aluminium earth bus of size 25 x 6 mm with inter connecting bus bar connection comprising of following switch gears and mounting panel board on ground with PCC (1:3:6) bedding upto a height of 30 cm above gorund level connecting existing LT Cables with panel board complete all as specified and directed :- NOTES: [i] The Panel shall be purchased from the (OEM) / authorized license partner of the OEM i.e. ABB, Siemens, Havells, L&T or equivalent as approved by GE.
(Note: LT Panel shall be mounted on floor with suitable size fasteners and cost of the same shall be deemed to be included in the unit rate quoted for the item)
Location : L/In Billet (Front side)
Incoming :(a) MCCB 250 Amp 415 Volts, 36 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release -01 No.
Outgoing :(a) MCCB 160 Amp 415 Volts, 25 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release-01 No
(b) MCCB 100 Amp 415 Volts, 25 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release-02 Nos
(c) Digital Voltmeter 0-500 Volts with inbuilt selector Switch -01 No
(d) Digital Amp meter 0-250 Amp with inbuilt selector Switch -01 No
(e) Indicating Light RED 220V AC-01No
(f) Indicating Light Yellow 220V AC-01No
(g) Indicating Light Green 220V AC-01No
(h) Protection MCB 6 Amp SP-03 Nos
(j) CT 250/5A-03 Nos
(k) Automatic Phase Sequence Corrector -01No
(l) Danger Plate-01 No
(m) Enclosure of Suitable Size | 1 | Each Job | - | - |
| 3 | Supply, installation, testing & commissioning in replacement of LT panel Outdoor type, CPRI All type test certificate and Design Verification with switchgears (MCCB) conforming to IS/IEC: 61439/2011 Part-1 & 2 shall be submitted by the contractor before execution of work, weather/vermin proof, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system, made out of 3.15 mm thick CRCA sheet with Rain Canopy and Outlet filter with Hood, factory assembled cubicle pattern modular and compartmentalized construction with front and backside hinged double door with locking arrangement, floor mounted free standing type with Angle iron of size 50 x 50 x 6 mm, provided with gasket for all the doors & removable covers, duly powder coated, 3 phase and neutral 200 Amps current carrying capacity aluminium bus bar with heat shrinkable PVC sleeve insulated coating with colour code and insulated support with aluminium earth bus of size 25 x 6 mm with inter connecting bus bar connection comprising of following switch gears and mounting panel board on ground with PCC (1:3:6) bedding upto a height of 30 cm above gorund level connecting existing LT Cables with panel board complete all as specified and directed :- NOTES: [i] The Panel shall be purchased from the (OEM) / authorized license partner of the OEM i.e. ABB, Siemens, Havells, L&T or equivalent as approved by GE.
(Note: LT Panel shall be mounted on floor with suitable size fasteners and cost of the same shall be deemed to be included in the unit rate quoted for the item)
Location : Gym (Front side)
Incoming :(a) MCCB 160 Amp 415 Volts, 25 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release -01 No.
Outgoing :(a) MCCB 100 Amp 415 Volts, 25 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release-01 No.
(b) MCCB 63 Amp 415 Volts, 25 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release-02 Nos.
(c) Digital Voltmeter 0-500 Volts with inbuilt selector Switch -01 No
(d) Digital Amp meter 0-200 Amp with inbuilt selector switch -01 No
(e) Indicating Light RED 220V AC-01 No
(f) Indicating Light Yellow 220V AC-01 No
(g) Indicating Light Green 220V AC-01 No
(h) Protection MCB 6 Amp SP-03 Nos
(j) CT 160/5A-03 Nos
(k) Automatic Phase Sequence Corrector-01 No
(l) Danger Plate -01 No
(m) Enclosure of Suitable Size | 1 | Each Job | - | - |
| 4 | Supply, installation, testing & commissioning in replacement of LT panel Outdoor type, CPRI All type test certificate and Design Verification with switchgears (MCCB) conforming to IS/IEC: 61439/2011 Part-1 & 2 shall be submitted by the contractor before execution of work, weather/vermin proof, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system, made out of 3.15 mm thick CRCA sheet with Rain Canopy and Outlet filter with Hood, factory assembled cubicle pattern modular and compartmentalized construction with front and backside hinged double door with locking arrangement, floor mounted free standing type with Angle iron of size 50 x 50 x 6 mm, provided with gasket for all the doors & removable covers, duly powder coated, 3 phase and neutral 250 Amps current carrying capacity aluminium bus bar with heat shrinkable PVC sleeve insulated coating with colour code and insulated support with aluminium earth bus of size 25 x 6 mm with inter connecting bus bar connection comprising of following switch gears and mounting panel board on ground with PCC (1:3:6) bedding upto a height of 30 cm above gorund level connecting existing LT Cables with panel board complete all as specified and directed :- NOTES: [i] The Panel shall be purchased from the (OEM) / authorized license partner of the OEM i.e. ABB, Siemens, Havells, L&T or equivalent as approved by GE.
(Note: LT Panel shall be mounted on floor with suitable size fasteners and cost of the same shall be deemed to be included in the unit rate quoted for the item)
Location : Near Guest Room No : 01
Incoming :(a) MCCB 160 Amp 415 Volts, 25 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release -01 No.
Outgoing :(a) MCCB 125 Amp 415 Volts, 25 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release-01 No.
(b) MCCB SPN 32-40 Amp 240 Volts, 10 KA, C curve - 02 Nos
(c) MCCB TPN 32 Amp 415 Volts, 10 KA, C curve - 01 No
(d) Digital Voltmeter 0-500 Volts with inbuilt selector switch -01 No
(e) Digital Amp meter 0-150 Amp with inbuilt selector switch -01 No
(f) Indicating Light RED 220V AC-01 No
(g) Indicating Light Yellow 220V AC-01 No
(h) Indicating Light Green 220V AC-01 No
(j) Protection MCB 6 Amp SP-03 Nos
(k) CT 160/5A-03 Nos
(l) Automatic Phase Sequence Corrector -01 No
(m) Danger Plate-01 No
(n) Enclosure of Suitable Size | 1 | Each Job | - | - |
| 5 | Supply, installation, testing & commissioning in replacement of LT panel Outdoor type, CPRI All type test certificate and Design Verification with switchgears (MCB/MCCB) conforming to IS/IEC: 61439/2011 Part-1 & 2 shall be submitted by the contractor before execution of work, weather/vermin proof, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system, made out of 3.15 mm thick CRCA sheet with Rain Canopy and Outlet filter with Hood, factory assembled cubicle pattern modular and compartmentalized construction with front and backside hinged double door with locking arrangement, floor mounted free standing type with Angle iron of size 50 x 50 x 6 mm, provided with gasket for all the doors & removable covers, duly powder coated, 3 phase and neutral 50 Amps current carrying capacity aluminium bus bar with heat shrinkable PVC sleeve insulated coating with colour code and insulated support with aluminium earth bus of size 25 x 6 mm with inter connecting bus bar connection comprising of following switch gears and mounting panel board on ground with PCC (1:3:6) bedding upto a height of 30 cm above gorund level connecting existing LT Cables with panel board complete all as specified and directed :- NOTES: [i] The Panel shall be purchased from the (OEM) / authorized license partner of the OEM i.e. ABB, Siemens, Havells, L&T or equivalent as approved by GE.
(Note: LT Panel shall be mounted on floor with suitable size fasteners and cost of the same shall be deemed to be included in the unit rate quoted for the item)
Location : Parade Ground
Incoming :(a) MCCB TPN 32 Amp 415 Volts, 10 KA, C curve, - 01 No
Outgoing :(a) MCB SPN 32 Amp 240 Volts, 10 KA, C curve - 06 Nos
(b) Digital Voltmeter 0-500 Volts with Selector Switch -01 No
(c) Digital Amp meter 0-50 Amp with Selector Switch -01 No
(d) Indicating Light RED 220V AC-01 No
(e) Indicating Light Yellow 220V AC-01 No
(f) Indicating Light Green 220V AC-01 No
(g) Protection MCB 6 Amp SP-03 Nos
(h) CT 32/5A-03 Nos
(j) Automatic Phase Sequence Corrector -01 No
(k) Danger Plate-01 No
(l) Enclosure of Suitable Size | 1 | Each Job | - | - |
| 6 | Supply, installation, testing & commissioning in replacement of LT panel Outdoor type, CPRI All type test certificate and Design Verification with switchgears (MCCB) conforming to IS/IEC: 61439/2011 Part-1 & 2 shall be submitted by the contractor before execution of work, weather/vermin proof, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system, made out of 3.15 mm thick CRCA sheet with Rain Canopy and Outlet filter with Hood, factory assembled cubicle pattern modular and compartmentalized construction with front and backside hinged double door with locking arrangement, floor mounted free standing type with Angle iron of size 50 x 50 x 6 mm, provided with gasket for all the doors & removable covers, duly powder coated, 3 phase and neutral 250 Amps current carrying capacity aluminium bus bar with heat shrinkable PVC sleeve insulated coating with colour code and insulated support with aluminium earth bus of size 25 x 6 mm with inter connecting bus bar connection comprising of following switch gears and mounting panel board on ground with PCC (1:3:6) bedding upto a height of 30 cm above gorund level connecting existing LT Cables with panel board complete all as specified and directed :- NOTES: [i] The Panel shall be purchased from the (OEM) / authorized license partner of the OEM i.e. ABB, Siemens, Havells, L&T or equivalent as approved by GE.
(Note: LT Panel shall be mounted on floor with suitable size fasteners and cost of the same shall be deemed to be included in the unit rate quoted for the item)
Location : Sargent Block
Incoming :(a) MCCB 160 Amp 415 Volts, 25 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release-01 No.
Outgoing :(a) MCCB 125 Amp 415 Volts, 25 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release-01 No.
(b) MCCB 100 Amp 415 Volts, 25 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release-01 No.
(c) MCB TPN 32 Amp 415 Volts, 10 KA, C curve - 01 No
(d) MCB TPN 40 Amp 415 Volts, 10 KA, C curve - 01 No
(e) Digital Voltmeter 0-500 Volts with Selector Switch - 01 No
(f) Digital Amp meter 0-150 Amp with Selector Switch - 01 No
(g) Indicating Light RED 220V AC- 01 No
(h) Indicating Light Yellow 220V AC- 01 No
(j) Indicating Light Green 220V AC- 01 No
(k) Protection MCB 6 Amp SP- 03 Nos
(l) CT 160/5A- 03 Nos
(m) Automatic Phase Sequence Corrector -01 No
(n) Danger Plate-01 No
(o) Enclosure of Suitable Size | 1 | Each Job | - | - |
| 7 | Supply, installation, testing & commissioning in replacement of LT panel Outdoor type, CPRI All type test certificate and Design Verification with switchgears (MCCB) conforming to IS/IEC: 61439/2011 Part-1 & 2 shall be submitted by the contractor before execution of work, weather/vermin proof, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system, made out of 3.15 mm thick CRCA sheet with Rain Canopy and Outlet filter with Hood, factory assembled cubicle pattern modular and compartmentalized construction with front and backside hinged double door with locking arrangement, floor mounted free standing type with Angle iron of size 50 x 50 x 6 mm, provided with gasket for all the doors & removable covers, duly powder coated, 3 phase and neutral 250 Amps current carrying capacity aluminium bus bar with heat shrinkable PVC sleeve insulated coating with colour code and insulated support with aluminium earth bus of size 25 x 6 mm with inter connecting bus bar connection comprising of following switch gears and mounting panel board on ground with PCC (1:3:6) bedding upto a height of 30 cm above gorund level connecting existing LT Cables with panel board complete all as specified and directed :- NOTES: [i] The Panel shall be purchased from the (OEM) / authorized license partner of the OEM i.e. ABB, Siemens, Havells, L&T or equivalent as approved by GE.
(Note: LT Panel shall be mounted on floor with suitable size fasteners and cost of the same shall be deemed to be included in the unit rate quoted for the item)
Location : Parameter Panel
Incoming :(a) MCCB 125 Amp 415 Volts, 25 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release -01 No.
Outgoing :(a) MCCB 100 Amp 415 Volts, 25 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release-01 No.
(b) MCCB 63 Amp 415 Volts, 25 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release-01 No.
(c) Digital Voltmeter 0-500 Volts with inbuilt selector Switch -01 No
(d) Digital Amp meter 0-150 Amp inbuilt selector Switch -01 No
(e) Indicating Light RED 220V AC-01 No
(f) Indicating Light Yellow 220V AC-01 No
(g) Indicating Light Green 220V AC-01 No
(h) Protection MCB 6 Amp SP-03 Nos
(j) CT 125/5A-03 Nos
(k) Automatic Phase Sequence Corrector -01 No
(l) Danger Plate-01 No
(m) Time switch astro type (having longitude and latitude of Indian cities in memory) 415 Volt three phase of 20 Amp rating with contactor fitted inside steel enclosure - 01 No.
(n) Enclosure of Suitable Size | 1 | Each Job | - | - |
| 8 | Supply, installation, testing & commissioning in replacement of LT panel Indoor type, CPRI All type test certificate and Design Verification with switchgears (MCCB) conforming to IS/IEC: 61439/2011 Part-1 & 2 shall be submitted by the contractor before execution of work, weather/vermin proof, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system, made out of 2.00 mm thick CRCA sheet factory assembled cubicle pattern modular and compartmentalized construction with front and backside hinged door with locking arrangement, floor mounted free standing type with Angle iron of size 50 x 50 x 6 mm, provided with gasket for all the doors & removable covers, duly powder coated, 3 phase and neutral 150 Amps current carrying capacity aluminium bus bar with heat shrinkable PVC sleeve insulated coating with colour code and insulated support with aluminium earth bus of size 25 x 6 mm with inter connecting bus bar connection comprising of following switch gears and mounting panel board on ground with PCC (1:3:6) bedding upto a height of 30 cm above gorund level connecting existing LT Cables with panel board complete all as specified and directed :- NOTES: [i] The Panel shall be purchased from the (OEM) / authorized license partner of the OEM i.e. ABB, Siemens, Havells, L&T or equivalent as approved by GE.
(Note: LT Panel shall be mounted on floor with suitable size fasteners and cost of the same shall be deemed to be included in the unit rate quoted for the item)
Location : Pump House Panel
Incoming :(a) MCCB 100 Amp 415 Volts, 25 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release-01 No.
Outgoing :(a) MCCB 32 Amp 10 KA SPN 'C' Curve-03 Nos
(b) MCCB 16 Amp 10 KA SPN 'C' Curve-02 Nos
(c) Digital Voltmeter (0-500 V) with Selector Switch-01 No
(d) Digital ammeter (0-100 A) with Selector Switch-01 No
(e) Indicating Light RED 220 V AC-01 No
(f) Indicating Light Yellow 220 V AC-01 No
(g) Indicating Light Green 220 V AC-01 No
(h) Protection MCB 6 Amp SP-03 Nos
(j) CT 100/5A-03 Nos
(k) MPCB 22-32 Amp 415 Volts, 50 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release - 02 Nos
Fully automatic Star Delta Starter 15 HP (Centrifugal Pumpset):- (i) Power Contactor 22 A TP (Main & Delta) -04 Nos (ii) Power Contactor 18 A TP (Star) -02 Nos (iii) Bi metal over load relay 9-15A -02 Nos (iv) Star Delta timer Micon Series -02 Nos (v) Aux. Blocks -06 Nos (vi) Push Button Start / Stop 220 V -04 Nos (vii) Auto manual Selector Switch -02 Nos (viii) Indicating light on/off/trip 220 V-06 Nos (ix) Control MCB SP 6 A 10 KA-02 Nos (x) Single Phase Preventer-02 Nos (xi) Digital ammeter with Selector switch -02 Nos
(l) Automatic Phase Sequence Corrector-01 No
(m) CT 100/5A-03 Nos
(n) Danger Plate-01 No
(o) Enclosure of Suitable Size | 1 | Each Job | - | - |
| 9 | Supply, installation, testing & commissioning in replacement of LT panel Indoor type, CPRI All type test certificate and Design Verification with switchgears (MCCB) conforming to IS/IEC: 61439/2011 Part-1 & 2 shall be submitted by the contractor before execution of work, weather/vermin proof, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system, made out of 2.00 mm thick CRCA sheet factory assembled cubicle pattern modular and compartmentalized construction with front and backside hinged door with locking arrangement, floor mounted free standing type with Angle iron of size 50 x 50 x 6 mm, provided with gasket for all the doors & removable covers, duly powder coated, 3 phase and neutral 1000 Amps current carrying capacity aluminium bus bar with heat shrinkable PVC sleeve insulated coating with colour code and insulated support with aluminium earth bus of size 25 x 6 mm with inter connecting bus bar connection comprising of following switch gears and mounting panel board on ground with PCC (1:3:6) bedding upto a height of 30 cm above gorund level connecting existing LT Cables with panel board complete all as specified and directed :- NOTES: [i] The Panel shall be purchased from the (OEM) / authorized license partner of the OEM i.e. ABB, Siemens, Havells, L&T or equivalent as approved by GE.
(Note: LT Panel shall be mounted on floor with suitable size fasteners and cost of the same shall be deemed to be included in the unit rate quoted for the item)
Location : Power House Panel
Incoming :(a) MCCB 630 Amp 415 Volts, 36 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release-01 No.
Outgoing :(a) MCCB 250 Amp 415 Volts, 25 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release-01 No
(b) MCCB 125 Amp 415 Volts, 25 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release-03 Nos
(c) MCCB TPN 32-40 Amp 415 Volts, 10 KA, C curve - 4 Nos
(d) MCCB SPN 32 Amp 240 Volts, 10 KA, C curve - 02 Nos
(e) Digital Voltmeter 0-500 Volts with Selector Switch -01 No
(f) Digital Amp meter 0-600 Amp with Selector Switch -01 No
(g) Indicating Light RED 220V AC-01 No
(h) Indicating Light Yellow 220V AC-01 No
(j) Indicating Light Green 220V AC- 01 No
(k) Protection MCB 6 Amp SP-03 Nos
(l) CT 630/5A-03 Nos
(m) Automatic Phase Sequence Corrector -01 No
(n) Time switch astro type (having longitude and latitude of Indian cities in memory) 415 Volt three phase of 20 Amp rating with contactor fitted inside steel enclosure - 01 No.
(o) Danger Plate-01 No
(p) Enclosure of Suitable Size | 1 | Each Job | - | - |
| 10 | Supply, installation, testing & commissioning in replacement of LT panel Indoor type, CPRI All type test certificate and Design Verification with switchgears (MCCB) conforming to IS/IEC: 61439/2011 Part-1 & 2 shall be submitted by the contractor before execution of work, weather/vermin proof, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system, made out of 2.00 mm thick CRCA sheet factory assembled cubicle pattern modular and compartmentalized construction with front and backside hinged door with locking arrangement, floor mounted free standing type with Angle iron of size 50 x 50 x 6 mm, provided with gasket for all the doors & removable covers, duly powder coated, 3 phase and neutral 150 Amps current carrying capacity aluminium bus bar with heat shrinkable PVC sleeve insulated coating with colour code and insulated support with aluminium earth bus of size 25 x 6 mm with inter connecting bus bar connection comprising of following switch gears and mounting panel board on ground with PCC (1:3:6) bedding upto a height of 30 cm above gorund level connecting existing LT Cables with panel board complete all as specified and directed :- NOTES: [i] The Panel shall be purchased from the (OEM) / authorized license partner of the OEM i.e. ABB, Siemens, Havells, L&T or equivalent as approved by GE.
(Note: LT Panel shall be mounted on floor with suitable size fasteners and cost of the same shall be deemed to be included in the unit rate quoted for the item)
Location : RO Plant Panel (Motor Starter Panel)
Incoming :(a) MCCB 125 Amp 415 Volts, 25 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release -01 No.
Outgoing :(a) MCCB 100 Amp 415 Volts, 25 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release-01 No
(b) MCCB 63 Amp 415 Volts, 25 KA, 4 pole, 50 Hz, with adjustable thermal magnetic release-01 No
(c) Digital Voltmeter (0-500 V) with Selector Switch -01 No
(d) Digital ammeter (0-100 A) with Selector Switch-01 No
(e) Indicating Light RED 220 V AC-01 No
(f) Indicating Light Yellow 220 V AC-01 No
(g) Indicating Light Green 220 V AC -01 No
(h) Protection MCB 6 Amp SP -03 Nos
(j) CT 125/5A-03 Nos
DOL Starter 2 HP (Monoblock pumpset) (i) Power Contactor 9 Amp TP -02 Nos (ii) Bi metal over load relay 3-5A-02 Nos (iii) Star Delta timer Micon Series -02 Nos (iv) Aux. Blocks-02 Nos (v) Push Button Start / Stop 220 V-04 Nos (vi) Auto manual Selector Switch-02 Nos (vii) Indicating light on/off/trip 220 V-06 Nos (viii) Control MCB SP 6 A 10 KA-02 Nos (ix) Single Phase Preventer-02 Nos
(k) Automatic Phase Sequence Corrector -01 No
(l) CT 125/5A -03 Nos
(m) Danger Plate-01 No
(n) Enclosure of Suitable Size | 1 | Each Job | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.49 MB
BOQ_878717.xls
BOQ • 0.30 MB
8470tenderdocu.pdf
Tender Documents • 0.99 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].