Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.5 LAdmitted-Finance | L1 | Admitted-Finance | |
| 2 | L2₹7.1 L+₹60,800 (9.31%)Admitted-Finance | L2 | Admitted-Finance | |
| 3 | L3₹10.3 L+₹3.8 L (58.4%)Admitted-Finance | L3 | Admitted-Finance | |
| 4 | Rejected-Technical | - | Rejected-Technical As per enclosed sheet | |
| 5 | Rejected-Technical C 1 G 1 138 SRI GANGANAGAR SRI GANGANAGAR SRI GANGANAGAR SRI GANGANAGAR RAJASTHAN 335001 | GANGANAGAR | RAJASTHAN | 335001 | - | Rejected-Technical As per enclosed sheet |
| Sl No | Description | Qty | Unit | JK ENGINEERING WORKS L1 | M/S S.S. Engineering Enterprises L2 | ATCORP MARKETING L3 |
|---|---|---|---|---|---|---|
| 1.00 | SITC of MGPS pipe of medically grade as per BSEN-13348 with third party certification from Lloyds/TUV degreased (ie free from oil, grease and particulate matters) seamless copper pipe confirming to ASTM B88 and all copper joining done by brazing with AWSA5.8, classification BCuP-5 or BS 1845 following procedure in accordance with ASTM B828 after purging with nitrogen. All pipe cutting shall be carried out with a radial pipe cutter and copper pipe fitting's shall comply with B4 alloy designation. Adequate support shall be provided while laying pipeline testing shall be done at 17 Bar and after testing pipe shall be painted with two coat of enamel paint as per colour codification as per ISO 7396-Part-I 2016. Third party test report shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with P.W.D. Electrical BSR 2021 | 180 | KG | 1,800 ₹3,24,000 | 2,100 ₹3,78,000 | 1,764 ₹3,17,520 Lowest |
| 2.00SITC of non lubricated ball type Nickel Coated Isolation Valve with adapter & PTFE Seat having quarter turn/Butterfly handle opening of following sizes suitable for flow capacity of required LPM as per the size of valve at 4.7 bar with maximum allowable pressure of 30 bar and suitable for working temperature ranging - 20°C to 130°C. Appropriate Test certificate/report of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021 | ||||||
| 2.01 | For 12 MM OD Pipe | 62 | Set | 600 ₹37,200 | 500 ₹31,000 Lowest | 1,427 ₹88,474 |
| 2.02 | FOR 15 MM OD Pipe | 12 | Set | 800 ₹9,600 | 700 ₹8,400 Lowest | 1,595 ₹19,140 |
| 2.03 | FOR 22 MM OD Pipe | 6 | Set | 1,200 ₹7,200 Lowest | 1,800 ₹10,800 | 2,565 ₹15,390 |
| 2.04 | FOR 28 MM OD Pipe | 6 | Set | 1,400 ₹8,400 Lowest | 2,250 ₹13,500 | 3,797 ₹22,782 |
| 3.00 | SITC of Gas outlet points Oxy, N2O, (AR-4), (AR-7) and Vaccum (8.7 psig) for dispensing medical gases (oxygen/air/vaccum) at point of use confirming to BSEN ISO 9170-1:2008. The gas outlet are quick connect type , it should have color coding for different gas source and should accept only repective adapters as required.Appropriate Test Certificate/report of product/accessories from OEM shall be submitted. The product should be CE Certified/CE Marked. All as per pre approved by Engineer in charge. For additional echnical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021 | 80 | Each | 1,200 ₹96,000 | 1,050 ₹84,000 Lowest | 1,833 ₹1,46,640 |
| 4.00 | SITC of BPC (back pressure compensated) flow meter with humidifer made of nickel plated body, double jacketed with flow gradations CE Marked on it. Desired flow will be setteled through rotary knob. Flow range should be between 0 to 15 lpm & work should be executed as per direction of engineer in charge. Appropriate Test Certificate/report of product/accessories from OEM shall be submitted. The product should be CE Certified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021. | 31 | Set | 600 ₹18,600 Lowest | 750 ₹23,250 | 1,212 ₹37,572 |
| 5.00 | SITC of ward suction unit (Suction controller and collection Jar-600 ml capacity) with posibility to configure required capacity collection jar and should meets the requirements as per BSEN ISO 10079-3:2009. The unit must designed to operate with the vaccum line of MGPS. The collection jar must accumpained with Vaccum regulator suitable for 0-14.7 psig with flow rate 0-55 Lmp (min) for operating temperature- 18°C to 50°C with ON/OFF facility. The collection jar should be transparent, made of high quality polycarbonate that can be autoclaved at 121°C for 20 minutes for reuse and provided with auto stop to avoid over spill and contaminatin of the suction source when the jar collection reached optimized level. The complete unit supplied with filter to protect the source and pipe line from bacterial contamination. Appropriate Test certificate/report of product/accessories from OEM shall be submitted. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021. | 31 | Set | 1,200 ₹37,200 Lowest | 1,450 ₹44,950 | 3,712 ₹1,15,072 |
| 6.00SITC of valve box made of CRCA sheet duly powder coated with transparent window which is installed in the MGPS for oxygen and vaccum line and should comply with BSEN ISO5211:2001 complete with ball type valves and gauges as required for oxygen compressed air and vaccum line. Appropriate Test certificate/report of product/accessories from OEM shall be submited. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021. | ||||||
Tender Value
₹10 L
EMD Value
₹20,000
Closing Date
29 Oct 2025, 6:00 pmClosed
Executive Engineer M and H, Dn. 2 Jaipur
Executive Engineer M and H, Dn. 2 Jaipur
SITC of MGPS work in Trauma Center Khivsar, Distt Nagaur.
2025_MEDIC_508537_3
NIT No.22/2025-26 EEM and HDiv 2 Jaipur/
Open Tender
Electrical Works
Percentage
60 days
Nagaur
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
RTGS/NEFTRTGS/NEFT/Any other money Transfer System
₹20,000
13 Nov 2025
18 Oct 2025
30 Oct 2025
18 Oct 2025
29 Oct 2025
18 Oct 2025
Amount
SITC of MGPS pipe of medically grade as per BSEN-13348 with third party certification from Lloyds/TUV degreased (ie free from oil, grease and particulate matters) seamless copper pipe confirming to ASTM B88 and all copper joining done by brazing with AWSA5.8, classification BCuP-5 or BS 1845 following procedure in accordance with ASTM B828 after purging with nitrogen. All pipe cutting shall be carried out with a radial pipe cutter and copper pipe fitting's shall comply with B4 alloy designation. Adequate support shall be provided while laying pipeline testing shall be done at 17 Bar and after testing pipe shall be painted with two coat of enamel paint as per colour codification as per ISO 7396-Part-I 2016. Third party test report shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with P.W.D. Electrical BSR 2021
SITC of non lubricated ball type Nickel Coated Isolation Valve with adapter & PTFE Seat having quarter turn/Butterfly handle opening of following sizes suitable for flow capacity of required LPM as per the size of valve at 4.7 bar with maximum allowable pressure of 30 bar and suitable for working temperature ranging - 20°C to 130°C. Appropriate Test certificate/report of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021
For 12 MM OD Pipe
FOR 15 MM OD Pipe
FOR 22 MM OD Pipe
FOR 28 MM OD Pipe
SITC of Gas outlet points Oxy, N2O, (AR-4), (AR-7) and Vaccum (8.7 psig) for dispensing medical gases (oxygen/air/vaccum) at point of use confirming to BSEN ISO 9170-1:2008. The gas outlet are quick connect type , it should have color coding for different gas source and should accept only repective adapters as required.Appropriate Test Certificate/report of product/accessories from OEM shall be submitted. The product should be CE Certified/CE Marked. All as per pre approved by Engineer in charge. For additional echnical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021
SITC of BPC (back pressure compensated) flow meter with humidifer made of nickel plated body, double jacketed with flow gradations CE Marked on it. Desired flow will be setteled through rotary knob. Flow range should be between 0 to 15 lpm & work should be executed as per direction of engineer in charge. Appropriate Test Certificate/report of product/accessories from OEM shall be submitted. The product should be CE Certified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
SITC of ward suction unit (Suction controller and collection Jar-600 ml capacity) with posibility to configure required capacity collection jar and should meets the requirements as per BSEN ISO 10079-3:2009. The unit must designed to operate with the vaccum line of MGPS. The collection jar must accumpained with Vaccum regulator suitable for 0-14.7 psig with flow rate 0-55 Lmp (min) for operating temperature- 18°C to 50°C with ON/OFF facility. The collection jar should be transparent, made of high quality polycarbonate that can be autoclaved at 121°C for 20 minutes for reuse and provided with auto stop to avoid over spill and contaminatin of the suction source when the jar collection reached optimized level. The complete unit supplied with filter to protect the source and pipe line from bacterial contamination. Appropriate Test certificate/report of product/accessories from OEM shall be submitted. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
SITC of valve box made of CRCA sheet duly powder coated with transparent window which is installed in the MGPS for oxygen and vaccum line and should comply with BSEN ISO5211:2001 complete with ball type valves and gauges as required for oxygen compressed air and vaccum line. Appropriate Test certificate/report of product/accessories from OEM shall be submited. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
Three Gas Service
SITC of microprocessor based auto alarm (digital type) suitable for medical gas service provided with audible and visual alarm for MGPS zoning. It should monitors the current status of oxygen / compresssed air pressure in distribution pipeline of central medical supply system and trigger the alarm to alert. The system should comply BSEN ISO:7396-I:2007 Appropriate Test certificate/report of product /accessories from OEM Shall be submitted. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
Three Gas Service
SITC of Bed Head Panel of 900-1500 MM long made out from high strength extruded aluminium with powder coating with at least 4 Nos 6/16 Amp switch socket and provision for required number of gas outlet points as suggested by the client. Appropriate Test Certificate/Report of product/accessories from OEM shall be submitted. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
SITC of Emergency Oxygen / Nitrous Oxide Manifold System (2+2) with tail pipes NRV and One DGSS Regulator of Minimum 600 LPM capacity- manifold system comprise of bank of 2+2 cylinders (Bulk cylinder of D type ) capacity manifold high pressure copper pipe of size 1/2"IDx14 swg (approx. 2.0320 mm) & high pressure fitting made of high tensile strength brass be used to connect the cylinders to the header assemblies with 4 no's non return valves & 4 no's high pressure flexible tail pipe is made of copper pipe of 1/3"x16 swg (approx. 1.6256 mm) the manifold is hydraulically tested at 225 Kg/cm2 pressure it is also degreased and is to be offered duly wrapped in a polythene bag make CE approved /CE certified. Note: Providing of cylinders is in the scope of Hospital/End client. Appropriate Test Certificate/Report of product/accessories from OEM shall be submitted. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
M/S S.S. Engineering Enterprises (BID ID -3351227)
ATCORP MARKETING (BID ID -3350832)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 2.55 MB
Tendernotice_2.pdf
PDF • 7.44 MB
Tendernotice_3.pdf
PDF • 0.07 MB
Tendernotice_4.pdf
PDF • 2.69 MB
Tendernotice_5.pdf
PDF • 0.31 MB
CDSCO-COMPLIANCE-SHEET.pdf
Tender Documents • 0.11 MB
T-and-C-for-Electrical-work-DLP--Annexure-B---3-.pdf
Tender Documents • 0.24 MB
Terms-and-conditions-MGPS.pdf
Tender Documents • 0.35 MB
BOQ_905589.xls
BOQ • 0.39 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .