Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39.5 LAccepted-AOC | ₹39.5 L | L1 | Accepted-AOC ACCEPTED |
| 2 | L2₹41.2 L+₹1.7 L (4.33%)Rejected-Finance | ₹41.2 L+₹1.7 L (4.33%) | L2 | Rejected-Finance NOT THE LOWEST BIDDER |
| Sl No | Description | Qty | Unit | Athengsa Tamai L1 | ARRYA ENTERPRISES L2 |
|---|---|---|---|---|---|
| 1.00Total amount of Sch 'A' Part-I Building Works Note :- This schedule is not pre-priced by MES and the rate indicated as "Rs. 0.00" under column 6 signifies this fact only. | |||||
| 2.00 | Design, Fabrication and Construction of Provn of 01 x Single Officer Accn along with Servant Qtr at 619 Sata Bty at Shivi ji Nagar for the plinth area of 84.58 Sqm as shown in line plan / site plan and as per detailed DPR, such as RCC framed structure as per site plan and line plan and revised thereof. Specification given in Sch A Note and particular specifications including complete RCC foundation and plinth, flooring Joinery and Finishes complete all as specified.
(i) Size – As per Arch drawing (ii) Height – as per Drg
(iii) Fdn – To be design as per SBC report with RCC framed construction. (iv) Plinth – Burnt Brick wk in CM 1:6
(v) DPC – 40 mm thick PCC 1:2:4 with WPC
(vi) Super Structure – All RCC structure to be M25 design mix burnt brick wk wall upto ceiling.
(vii) Seismic Zone – Strengthening measures for Zone V
(viii) RCC Roof slab 150 mm thick shall be provided as per shown in structural design drawing with APP roof treatment.
(ix) Ceiling : False ceiling with powder coated snap grid frame work.
(ix) Internal Plaster – Internal 15 mm thick in CM (1:6)
(x) Mirror polished kota stone on, verandah & non skid ceramic tiles in toilet and bathroom over 15 mm thick screed bed in base of CM 1:6 over a layer of PCC 1:2:4 over sub base of 1:5:10.
(xi) Dado/Skirting – Glazed ceramic tiles over 10 mm thick cement screed in CM (1:3) up to lintel height.
(xii) Joinery – Frames – pressed steel, shutter – Factory made flush door shutter (TD Drg No CESZ/2015/TD/03 Sheet 1/2 & 2/2) & molded / WPC doors in toilet bathroom
(xiii) Joinery Window – aluminum powder coated window with Guard bars/grill
(xiv) Stainless steel routing on first floor of verandah & staircase.
(xv) Iron monger – Prefabricated aluminum anodized fittings. (TD Drg No CESZ/2015/TD/03 Sheet 1/2 & 2/2)
(xvi) Plinth Protection – 75 mm thick PCC 1:3:6 over stone hard core. (xvii) Painting – Synthetic enamel paint on steel/wooden surface.
(xviii) Finishes – Internal - 02 coats of oil emulsion distemper incl 1mm thick wall care putty over a coat of primer. External - 02 Coats of weather proof exterior emulsion over one coat of primer. (xix) Antitermite treatment - As per IS-6313 Part-II : 2001 (xx) Mosquito proofing - All external doors & Windows (xxi) 18mm thick granite over CM 1:3 for steps
(xxii) Sanitory Fitting – Vitreous China EWC, WHB ect of approved make including plumbing work (TD Drg No CESZ/TD-38 Sheet No 1/2 & 2/2 and TD Drg No CESZ/TD-31 Sheet No 1/2 & 2/2).
(xxiii) Mosquito Proofing – All external Door and window.
(xxiv) Green marbles on steps & raiser on staircase. | 1 | LUMP SUM | 27,50,000 ₹27,50,000 | 23,50,000 ₹23,50,000 Lowest |
| 3.00NOTE: Schedule ‘A’ Part II to VIII are Prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured. | |||||
| 4.00 | Total amount of Sch ‘A’ Part II (Lighting Protection) | 1 | LUMP SUM | 20,000 ₹20,000 Lowest | 20,846.7 ₹20,846.7 |
| 5.00 | Total amount of Sch ‘A’ Part III (Hot water supply Gyser) | 1 | LUMP SUM | 14,000 ₹14,000 Lowest | 14,427.34 ₹14,427.34 |
| 6.00 | Total amount of Sch ‘A’ Part IV (Road/Path/culverts) | 1 | LUMP SUM | 1,95,000 ₹1,95,000 Lowest | 2,08,296.8 ₹2,08,296.8 |
| 7.00 | Total amount of Sch ‘A’ Part V (External Water supply) | 1 | LUMP SUM | 24,800 ₹24,800 Lowest | 25,738.41 ₹25,738.41 |
| 8.00 | Total amount of Sch ‘A’ Part VI (External Electrification) | 1 | LUMP SUM | 3,20,000 ₹3,20,000 Lowest | 3,37,842.61 ₹3,37,842.61 |
| 9.00 | Total amount of Sch ‘A’ Part VII (Sewage Disposal) | 1 | LUMP SUM | 1,05,000 ₹1,05,000 Lowest | 1,15,371.51 ₹1,15,371.51 |
| 10.00SCH 'A PART XI (Miscellaneous B/R and E/M works) Note: This schedule is not pre-priced by MES and the rate indicated as "Rs 0.00" under Col 6 signifies this fact only | |||||
Tender Value
₹42 L
EMD Value
₹84,000
Closing Date
24 Mar 2026, 6:00 pmClosed
CWE DINJAN
COMMANDER WORKS ENGINEER DINJAN
PROVN OF SINGLE OFFRS ACCN ALONGWITH SERVANT QUARTERS OF 619 SATA BTY HM UNDER GE P LOHITPUR
2026_MES_754458_1
84526
Open Tender
Civil Works
Lump-sum
270 days
GE (P) Lohitpur
AS PER TENDER DETAILS
8 documents required · 8 mandatory
₹500
GE (P) Lohitpur
₹84,000
Yes
10 Jun 2026
26 Feb 2026
31 Mar 2026
26 Feb 2026
24 Mar 2026
19 Mar 2026
Total amount of Sch 'A' Part-I Building Works Note :- This schedule is not pre-priced by MES and the rate indicated as "Rs. 0.00" under column 6 signifies this fact only.
Design, Fabrication and Construction of SINGLE OFFRS ACCN ALONGWITH SERVANT QUARTERS OF 619 SATA BTY (H/M) in RCC Framed Structure as per Site plan and line plan and revised thereof. Specification given in Sch A Notes and Particular Specifications including complete RCC foundation and plinth, Flooring, Joinery and Finishes complete all as specified. (i) Size – As per Arch drawing (ii) Height – as per Drg (iii) Fdn – To be design as per SBC report with RCC framed construction. (iv) Plinth – Burnt Brick wk in CM 1:6 (v) DPC – 40 mm thick PCC 1:2:4 with WPC (vi) Super Structure – All RCC structure to be M25 design mix burnt brick wk wall upto ceiling. (vii) Seismic Zone – Strengthening measures for Zone V (viii) Roof – 0.50mm thick Pre-painted Galvalume sheet with MS steel frame structure on living area, roof slab with roof treatment - 150 mm thick on ground floor roof verandhah & Bathroom. (ix) Ceiling : False ceiling with powder coated snap grid frame work. (ix) Internal Plaster – Internal 15 mm thick in CM (1:6) (x) Mirror polished kota stone on, verandah & non skid ceramic tiles in toilet and bathroom over 15 mm thick screed bed in base of CM 1:6 over a layer of PCC 1:2:4 over sub base of 1:5:10. (xi) Dado/Skirting – Glazed ceramic tiles over 10 mm thick cement screed in CM (1:3) up to lintel height. (xii) Joinery – Frames – pressed steel, shutter – Factory made flush door shutter (TD Drg No CESZ/2015/TD/03 Sheet 1/2 & 2/2) & molded / WPC doors in toilet bathroom (xiii) Joinery Window – aluminum powder coated window with Guard bars/grill (xiv) Stainless steel routing on first floor of verandah & staircase. (xv) Iron monger – Prefabricated aluminum anodized fittings. (TD Drg No CESZ/2015/TD/03 Sheet 1/2 & 2/2) (xvi) Plinth Protection – 75 mm thick PCC 1:3:6 over stone hard core. (xvii) Painting – Synthetic enamel paint on steel/wooden surface. (xviii) Finishes – Internal - 02 coats of oil emulsion distemper incl 1mm thick wall care putty over a coat of primer. External - 02 Coats of weather proof exterior emulsion over one coat of primer. (xix) Antitermite treatment - As per IS-6313 Part-II : 2001 (xx) Mosquito proofing - All external doors & Windows (xxi) 18mm thick granite over CM 1:3 for steps (xxii) Sanitory Fitting – Vitreous China EWC, WHB ect of approved make including plumbing work (TD Drg No CESZ/TD-38 Sheet No 1/2 & 2/2 and TD Drg No CESZ/TD-31 Sheet No 1/2 & 2/2). (xxiii) Mosquito Proofing – All external Door and window. (xxiv) Green marbles on steps & raiser on staircase.
NOTE: Schedule ‘A’ Part II to VIII are Prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured.
Total amount of Sch ‘A’ Part II (Lighting Protection)
Total amount of Sch ‘A’ Part III (Hot water supply Gyser)
Total amount of Sch ‘A’ Part IV (Road/Path/culverts)
Total amount of Sch ‘A’ Part V (External Water supply)
Total amount of Sch ‘A’ Part VI (External Electrification)
Total amount of Sch ‘A’ Part VII (Sewage Disposal)
SCH 'A PART XI (Miscellaneous B/R and E/M works) Note: This schedule is not pre-priced by MES and the rate indicated as "Rs 0.00" under Col 6 signifies this fact only
M & L for boring 100 mm dia hole in all kind of soil upto maximum depth 6 meter or up to refuse (N=100) whichever meet earlier including collection of undisturbed sample from cohesive soil only conducting standard penitration test at 6 meter and 1.5 meter interval alternatively as per relevant IS code complete all as directed.
Completion of field work & lab test result and submission of report in Per Job quadruplicate suggesting depth of foundation type of fundation and safe bearing capacity with CD-1 (one) copy complete all as specified and directed.
Supply and laying DWC 50mm pipe SN8 laid in trenches for protection of cable all as specified anddirected by the Engr-in-Charge.
Supply install testing and commissioning outdoor type LT feeder pillar box of suitable size, pedastal mounted, IP54 CPRI type tested factory made totally enclosed dust and vermin proof double leaf shutter in front and single leaf shutter in rear side made of 3.00mm thick CRCA sheet, framing with 50x50x6 mm thick MS angle iron and legs of size 0.5m long duly fabricated and having proper locking arrangement in both front and rear door with 4 slanting roof duly projected and painted to both internal and external surfaces with powder coating paint in heat process of sheet and suitable for 500V, 50Hz, 3 phase 4 wire system and comprising with and including following accessories andmented on PCC platform made out of PCC 1:2:4, 100mm tick 1m all round the panel board complete with following items housed in: Note:- (i) Danger notice plate should be fixed on both sides of the LT panel. (ii) After installation of panel each MCB should be indicated by paint that connection goes to which building. (iii) Rate of earthwork, excavation and PCC platform shall be deemed included in the quoted rate. (A)BUSBAR: 200 Amps rated Al busbar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite /DMC insulator busbar support (square/round) insulators of suitable size and good insulation resistance. (B)Incomer: (i) MCCB 4P of capacity 125 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 25 KA with thermal magnetic release -01No, () On load changelever 4P, capacity125A, 415V, 50Hz breaking capacity 25KA - 01 Nos (iii) 3 Ph digital Amphere meter Class 1 accuracy, 0.5 VA burden with LED display - 01 No (iv) 3 Ph digital Ammeter class 1 accuracy, 0.5 VA burden with LED display-01 no, (v) MModular indicator lamp with integral circuit (230V) and cluster LED (RED, YELLOW, BLUE) -01 set, (vi) Current Transformer (100/5A)-03 Nos. (C)Outgoings: (i) MCCB 4 Pole of capacity 63 Amp, breaking capacity 16 KA with thermal release -2 Nos, (ii) MCCB 4 Pole of capacity 40 Amp, breaking capacity 16 KA with thermal release - 3 Nos, (iii) MCB 4 Pole of capacity 32 Amp, breaking capacity 10 KA with thermal release -2 Nos, (iv) MCB 2 Pole of capacity 32 Amp, breaking capacity 10 KA with thermal release -1Nos, (v) Spare pocket fo MCCB - 1, (vi) Time Switches astro type (having longitude and latitude of Indian cities in memory) 250 V single phase of 20 Amp Rating With 3 phase 63A Contactor fitted inside steel enclosure - 01 Nos, (vii) MCCB 80 Amp, 16KA,4P-1 Nos
S & F 100 Amps 415V Step type busbar chamber box IP 54 all as specified and directed.
S & F cable jointing kit for 1.1 KV grade cable for straight through/end joint complete with ininting material heat shring type and accessories suitable for 3.5/4 core XLPE, armoured, Al conductor cable of size 25 to 50 sqmm, Indoor/Outdoor type
Supply install testing and commissioning outdoor type LT feeder pillar box of suitable size, pedastal mounted, IP 54 CPRI type tested factory made totally enclosed, dust and vermin proof, double leaf shutter in front and single leaf shutter in rear side made of 3.00mm thick CRCA sheet, framing with 50x50x6 mm thick MS angle iron and legs of size 0.5m long duly fabricated and having proper locking arrangement in both front and rear door with 4 slanting roof duly projected and painted to both internal and external surfaces with powder coating paint in heat process of sheet and suitable for 550V, 50Hz, 3 phase 4 wire system and comprising with and including following accessories and mounted on PCC platform made out of PCC 1:2:4, 100mm thick, 1m all round the panel board complete with following items housed in: Note:- (i) Danger notice plate should be fixed on both sides of the LT panel. (ii) After installation of panel each MCB should be indicated by paint that connection goes to which building. (iii) Rate of earthwork, excavation and PCC platform shall be deemed included in the quoted rate. (A)BUSBAR :100 Amps rated Al busbar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite /DMC insulator busbar support (square/round) insulators of suitable size and good insulation resistance. (B)Incomer: (i)63A 4P changeover switch-01 no, (ii)40A 4P MCCB 18kA-01 no (iii) 3 Ph digital voltmeter class 1 accuracy, 0-500 V, 3 Ph, 4 digit with LED display -01 no(iv) 3 Ph digital Ammeter class 1 accuracy, 0.5 VA burden with LED display-01 no, (v) Modular indicator lamp with integral circuit (230V) and cluster LED (RYB)-01 set, (vi) CT (100/5A)-01. (C)Outgoings:- 32A TPN MCB 10KA-01nos. 32A DP MCB 10kA-02nos
Materials and labour for Cutting roads / hard standing to a depth not less than 45 cm and not less than 45 cm wide for laying of Gl pipe to draw the UG cable and making good the disturbed surfaces by filling of PCC (1:3:6) type C-2 using 40 mm graded stone aggregate and finished the surface even and smooth with out using extra cement and disposed off the surplus debris and soil to a distance not exc 50 m complete all as specified and as directed by the Engr-in-Charge.
Supply and fix octagonal poles of height 7.0 metres having top diameter 70mm and bottom diameter 139mm and sheet thicknes of 3mm having base plate of size 200x200x12 with appropiate size of foundation bolt as and specified by enginer-in-charge
Supply and fix PVC cable terminal boxes, outdoor type of size 1550mmx10mmx92mm polycarbonate, IP65 with MCB SP 6 to 32Amps including all necessary fittings and connection all as directed by Enginner-in-Charge
S&F Gl single arm bracket 1.5m long 40mm dia
S&F GI double arm bracket 1.5m long 40mm dia
Supply and Fix DOL Starter FOR 1 HP Motor
Supply and fixing pumpset,cetrifugal,electric driven 1 HP AC single phase 230V inclusive of electrical connections and PCC foundation with MS frame and GI sheet cover.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.22 MB
TenderDocuments84526.pdf
Tender Documents • 1.33 MB
BOQ_845028.xls
BOQ • 0.24 MB
drawing.pdf
Additional Documents • 11.09 MB
Amendment1.pdf
PDF • 0.07 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .