Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.8 CrAccepted-AOC 583 URBAN ESTATE II HISAR 125005 | HISAR | HISAR | HARYANA | 125005 | ₹7.8 Cr | L1 | Accepted-AOC Being reasonable and lowest. |
| 2 | L2₹8.9 Cr+₹1.1 Cr (14.8%)Rejected-Finance OFFICE NO 304 305 3RD FLOOR PLOT NO 1 USHA CHAMBERS L S C NEW RAJDHANI ENCLAVE DELHI 110092 | DELHI | EAST DELHI | DELHI | 110092 | ₹8.9 Cr+₹1.1 Cr (14.8%) | L2 | Rejected-Finance Not being lowest. |
| 3 | L3₹10.9 Cr+₹3.1 Cr (40.1%)Rejected-Finance 123 B CENTRAL AVENUE SAINIK FARMS SOUTH DELHI DELHI 110062 | SOUTH DELHI | DELHI | 110062 | ₹10.9 Cr+₹3.1 Cr (40.1%) | L3 | Rejected-Finance Not being lowest. |
| Sl No | Description | Qty | Unit | Siya constructions L1 | G and G Infratech Private Limited L2 | Third Wave Services Pvt Ltd L3 |
|---|---|---|---|---|---|---|
| 1.00Schedule ‘A’ Section-I | ||||||
| 1.01 | Design & Construction of Md Accn for 9 JCOs S+3 (4 Stories ) & 12 OR S+3 (4 Stories) of Entity 'B' 61 WEU Hirankudna as mentioned in Architectural drawings complete all as specified and shown on drawing and scope of work and other documents of the Tender and as mentioned in Annexure I to VII of scope of the work | 1 | Lump Sum | 7,08,73,000 ₹7,08,73,000 Lowest | 8,25,64,064 ₹8,25,64,064 | 10,25,00,000 ₹10,25,00,000 |
| 2.00Schedule ‘A’ Section-II | ||||||
| 2.01 | Lump sum price worked out by the contractor for Schedule 'A' Section-II (DG SET) (Ref pre priced Schedule attached seperately) | 1 | Lump Sum | 33,030 ₹33,030 | 35,000 ₹35,000 | 32,000 ₹32,000 Lowest |
| 2.02 | Lump sum price worked out by the contractor for Schedule 'A' Section-III (ROAD/PATH /HARD STANDING) (Ref pre priced Schedule attached seperately) | 1 | Lump Sum | 7,00,000 ₹7,00,000 Lowest | 8,85,000 ₹8,85,000 | 7,30,000 ₹7,30,000 |
| 2.03 | Lump sum price worked out by the contractor for Schedule 'A' Section-IV (AREA DRAINAGE) (Ref pre priced Schedule attached seperately) | 1 | Lump Sum | 4,20,000 ₹4,20,000 Lowest | 5,43,000 ₹5,43,000 | 4,47,995.7 ₹4,47,995.7 |
| 2.04 | Lump sum price worked out by the contractor for Schedule 'A' Section-V (EXTERNAL WATER SUPPLY) (Ref pre priced Schedule attached seperately) | 1 | Lump Sum | 2,91,000 ₹2,91,000 Lowest | 3,50,000 ₹3,50,000 | 3,15,000 ₹3,15,000 |
| 2.05 | Lump sum price worked out by the contractor for Schedule 'A' Section-VI (EXTERNAL ELECTRIC SUPPLY) (Ref pre priced Schedule attached seperately) | 1 | Lump Sum | 14,00,000 ₹14,00,000 | 14,50,000 ₹14,50,000 | 12,30,000 ₹12,30,000 Lowest |
| 2.06 | Lump sum price worked out by the contractor for Schedule 'A' Section-VII (SEWAGE DISPOSAL) (Ref pre priced Schedule attached seperately) | 1 | Lump Sum | 3,21,000 ₹3,21,000 | 3,48,000 ₹3,48,000 | 3,00,000 ₹3,00,000 Lowest |
| 3.00Schedule ‘A’ Section-III(Miscllaneous Items) | ||||||
Tender Value
₹9.0 Cr
EMD Value
₹7.8 L
Closing Date
8 Nov 2025, 6:00 pmClosed
HQ Chief Engineer Delhi Zone
HQ Chief Engineer Delhi Zone Delhi Cantt-10
PROVN OF MD ACCN FOR 09 JCOS 12 ORS OF ENTITY B 61 WEU HIRANKUDNA UNDER GE NORTH DELHI CANTT 10
2025_MES_722944_1
CEDZ/TOKEN-08 OF 2025
Open Tender
Civil Works
Lump-sum
360 days
Delhi Cantt-10
As per NIT
10 documents required · 10 mandatory
₹3,000
GE North
₹7.8 L
Yes
6 Apr 2026
28 Jul 2025
10 Nov 2025
17 Oct 2025
8 Nov 2025
1 Nov 2025
24 Oct 2025 - 31 Oct 2025
Item Rate
Item Description
Item Rate
Item Description
DG SET
ENGINE (PRIME MOVER). CPCB-IV + compliant Diesel Engine 1500 RPM of suitbale HP as recommended by manufacturer water cooled, Turbocharged aircooled, electronic governor, 12 Volts (of AH rating as per manufacturer specification) battery start, complete with fly wheel and all standard fittings/fixtures as per manufacturing practice including suitable engine control panel with tachometer, lub oil temp & pressure gauge, water temp guage and frequency meter (digital type) including safety shutdown contents) and also including self starter, dynamo, fuel tank etc and conforming to IS 10002, ISO 3046, BS-5514. The engine shall give electrical out put of 40 KVA at 0.8 PF (lag).
ALTERNATOR. AC alternator, self excited, self regulated, self ventilated, brushless design, conforming to IS/IEC: 60034-1, 3 Phase, 415 volts, 50 Hz, 4 wire system output 40 KVA PF 0.8 1500 RPM insulation class `H' enclosure IP 23/SPDP complete with AVR with ± 1.5% voltage regulation directly coupled to and match the above engine and capable for over load of 10% for one hr in 12 hr operation.
CONTROL PANEL (AMF PANEL) : Inbuilt control panel to match with the requirment of DG set and shall be manufactred with 14/16 gauge CRCA sheet and is powder coated for a weather proof and long lasting finish . The control panel consist of following parts as per manufactured norms: (i) PCC- key switch/ Autostart Generator set controller. (ii) Multifunction meter displaying the parameter as voltage current, frequency water oil pressure KVA,KW (iii) Contractors with HRC fuse of suitable rating,current transformers, AMF logic Battery Charger Aluminium Bus bar of suitable capacity indicating lamps. (iv) Standard foundation as per manufactrers specification anti vibration foundation pad of approved make & suitable capacity.
BASE FRAME. Made out of structural steel as per manufactur's recommended design/specications.
ACOUSTIC ENCLOSURE. Accoustic enclosure designed to meet stringent MoEF/CPCB norms of 75 dBA @ 1mtr at 75% load under free field conditions made of CRCA sheets and structural /sheet metal base frame with high quality noise absorbant anf fire retardant grade accoustic insulation material (foam) complying to IS: 8183 . Provision of LED light with door NO/NC contact, engine emergency stop push button, hinged door (with toughened glass on door shutter facing monitoring panel) locking and rain guard arrangement, thermostate to for automatic engine stop on increse of temp above set temp range. CATALOGUES. Operation and Maintenance manual, spare parts list, overhauling manual - 01 sets
Note :- Rates are inclusive of the below provns:- (i) PCC foundation as per manufacturer specifications. Foundation shall be at least 450mm above GL and extended 600mm on eachh side from base of DG set. (ii) Water/heater load test at site for 12 Hrs duration (1/2 Hr at No load, 1/2 Hr at 25% load, 2 Hrs at 50%,3 Hrs at 75% load, 4Hrs at 100% load, 1 Hr at load in excess of 10% of rated load) in presence of IEM / Rep of accepting officer with necessary artificial load , T&P and FOL etc. (iii) Periodical maintenance like A-Check, B-Check, C-Check, D-Check as per OEM maintenance manual including Lub oil change, filter replacement etc during Defect Liability Period .
AREA DRAINAGE
EXTERNAL WATER SUPPLY
Supply and fixing PP-R gate valve brass insert complete all as directed of following sizes :-
EXTERNAL ELECTRIC SUPPLY
Incomer:- (i) MCCB 4 Pole -200 Amps, 25 KA, 415V -01No (ii) Digital type Multifunction meter 100mm square dial suitable to measure Amp,Volt,KHW & PF -01 Nos (iii) LED type phase indicator lamp (RYB) - 01 Set Outgoing:- (i) MCCB 4 Pole - 160 Amps, 25 kA -01 Nos ( Bldg Non Essential Load Panel) (ii) MCCB 4 Pole -63 Amps, 16 kA, 415V -02Nos (DG set AMF Panel + 1No Spare)
Incomer:- (i) MCCB 4 Pole -160 Amps, 415V, 25 KA -01No (ii) LED type phase indicator lamp (RYB) - 01 Set Outgoing:- (i) MCCB 4 Pole - 100 Amps, 415 V,16 kA -03 Nos ( JCO Block Meter Panel-1No + OR Block Meter Panel -1No + Spare-1No)
Incomer:- (i) MCCB 4 Pole -63 Amps, 16 kA, 415V -01No (From DG AMF Panel) (iii) LED type phase indicator lamp (RYB) - 01 Set Outgoing:- (i) MCCB 4 Pole - 32 Amps, 10kA -05 Nos ( Lifts-2 Nos + Terrace-2 Nos + Spare-1No ) (ii) MCB SPN - 16Amps, 10kA -01 Nos ( Security Light Timer switch). (iii) MCB SPN 6Amp 10KA -04 Nos (Aviation obstruction light + Common area light) . (iv) Timer switch comprising of Analog type Timer,contactor,relay of suitable rating with bypass arrengement for auto/mannual operation-01No
Supply and laying HDPE DWC pipe ISI: 16205 marked for electric cable protection across road crossing/hard standing/along wall of following sizes :-
SEWAGE DISPOSAL
RCC Septic tank designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, RCC M-30 Design Mix in Walls , Base Slab , Baffle walls and Roof Slab including beams etc with Vent shaft , manhole openings with cover connection etc., complete with effective depth of 1.5 meter and overall depth of 3 meter for 150 Users.
Preparing compost pits of size 0.90x0.90x0.90 by excavation in ordinary soil carrying out antitermite, planting trees & refilling of the pit with compost (manure, sand and sweet earth mixed in ratio 1:1:4 BREAKING MOULDS, RAMMING AND FLOODING WITH WATER filling with more compost if necessary and fine dressing including removal of rubbish unserviceble materials and surpus soil to a distance n exc 100m. ATT shall be in form of 200 gms neem cake mixed with every cum of compost followed by dursban or equivalent applied at 2 ml per litre in the first watering of 20 litres per pit, colmplete as specified. Note (i) The rate for excacation and getting out soil shall be deemed to be included in the rate of this item. (ii) The rate for mixing only earth, manure and sand is deemed to be included in the unit rate of this item supply of sweet earth manure and sand hall be paid under respective item of this schedule.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.29 MB
BOQ_809262.xls
BOQ • 1.00 MB
dRGS.rar
Additional Documents • 0.84 MB
UPLOADTENDER83159.rar
Tender Documents • 3.57 MB
Tenderdocument.rar
Tender Documents • 0.84 MB
Tenderdocument_2.rar
Tender Documents • 3.57 MB
BOQ.xls
BOQ • 1.00 MB
06Amdt83159.pdf
PDF • 0.36 MB
05Amdt83159.pdf
PDF • 0.23 MB
04Amdt83159.pdf
PDF • 0.36 MB
03amdt83159.pdf
PDF • 0.36 MB
02Amdt83159.pdf
PDF • 0.36 MB
01amdt83159.pdf
PDF • 0.36 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .