GE AF THANE
Office of Military Engineer Services ,Garrison Engineer (AF) Thane, Kolshet Road, Sandoz Baugh Post, Thane 400607
REPAIRS / MAINTANANCE OF SERVICE CONNECTION, DISTRIBUTION BOARD, BUILDING SUB MAIN WIRING, EARTHING AND ALLIED WORKS AT AF STN YEOUR UNDER GE AF THANE (2nd call)
2025_MES_734826_2
GE (AF) T-43 OF 2025-26 (8536)
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
THANE
AS PER TENDER DOCUMENTS AND NIT
8 documents required · 8 mandatory
₹500
GE AF THANE
₹20,000
Yes
21 Nov 2025
21 Nov 2025
18 Dec 2025
21 Nov 2025
11 Dec 2025
28 Nov 2025
Material and labour in repair for sub main wiring complete with 2 run of 6 sqmm, single core, copper conductor cable 1100 volts grade, FRLS type, PVC insulated, unsheathed, flexible, multi stranded duly colour coded cable drawn through and including PVC existing/new casing and caping of size 25mm width or above as required at site and accessories such as tee, corners,overlaping connector etc of suitable size fixed on surface of walls/roofs/ceiling and including 01 run of 6 sqmm single core, copper conductor cable 1100 volts grade, FRLS type, PVC insulated, unsheathed, flexible, multi stranded of green colour as earth continuity conductor connected to common earth dolly including removing old unserviceable item complete and making good the disturbed surfaces to match with existing all as specified and directed. Note : - 02 run of 6 sqmm single core copper conductor cable and 01 run of 6 sqmm single core copper conductor and 01 run of PVC casing and caping shall be measured as one unit.
All as per item no 1 herein before but of size 2X4 sq mm and 1X4 sqmm all as specified and directed.
All as per item no 1 herein before but of size 2X2.5 sq mm and 1X2.5 sqmm all as specified and directed.
All as per item no1 herein before but of size 4X16 sq mm and 2X16 sqmm all as specified and directed.
Material and labour in repair for sub main wiring complete with 2 run of 6 sqmm, single core, copper conductor cable 1100 volts grade, FRLS type, PVC insulated, unsheathed, flexible, multi stranded duly colour coded cable drawn through and including PVC existing/new conduit of size 25mm width or above as required at site and accessories such as tee, corners,overlaping connector etc of suitable size fixed on surface of walls/roofs/ceiling and including 01 run of 6 sqmm single core, copper conductor cable 1100 volts grade, FRLS type, PVC insulated, unsheathed, flexible, multi stranded of green colour as earth continuity conductor connected to common earth dolly including removing old unserviceable item complete and making good the disturbed surfaces to match with existing all as specified and directed. Note : - 02 run of 6 sqmm single core copper conductor cable and 01 run of 6 sqmm single core copper conductor and 01 run of PVC conduit shall be measured as one unit.
All as per item no 2 herein before but of size 2X4 sq mm and 1X4 sqmm all as specified and directed.
All as per item no 2 herein before but of size 2X10 sq mm and 1X10 sqmm all as specified and directed.
S&F PVC Conduit 25mm dia, medium grade with necessary Conduit Accessories such as Tee, Bend, Elbow, Junction Box, etc. ISI marked including taking down/out unserviceable PVC Conduit with Fittings, complete all as specified and as directed.
S&F PVC Casing & Cappings, ISI marked, heavy duty of size 25mm with all Fittings including taking down old unserviceable one, complete all as per specified and as directed.
S & F in repair MCB SP 6 to 32 Amps 240 volts 50 HZ having 10 KA ,complete all as specified and as directed by Engr-in-charge.
Supply,lay and testing in replacement of over head line or cable XLPE insulated,galvanised steel strip armoured,1100 volts grade with multistranded aluminium conductor of cross-sectional area 50 sqmm; 3.5 core laid in trenches/pipes/ducts/walls and connection with necessary cable lugs and glands, nuts, bolts and washers etc and testing including removing old unserviceable item complete all as specified and directed. Note for item No 27 to 29- (i) Excavation & Earth work,sand cushioning, cable cover and protection pipe shall be measured and paid separately. (ii) The cable shall be in one length unless otherwise directed by the GE.
All as per item No.22 above but of size 70 sqmm, 3.5 core
All as per item No.22 above but of size 35 sqmm, 3.5 core
Supply and filling in and speading unwashed river sand for cushioning and covering the under ground cables in trenches and punning to provide required cover complete all as specified in SSR Part-I and as directed. Note: Punned thickess i.e 18 cm shall be measured for paymeny purpose.
Supply and laying unreinforced precast factory made concrete cable cover, class LV, Type -I, flat, size 250mm x 150mm x 40mm, complete all as specified and directed.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.31 MB
TD8536.pdf
Tender Documents • 2.04 MB
BOQ_829774.xls
BOQ • 0.25 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .