Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.6 LAccepted-AOC 205 IIND PHASE INDUSTRIAL AREA BARMER 344001 | BARMER | BARMER | RAJASTHAN | 344001 | L1 | Accepted-AOC AOC | |
| 2 | L2₹23.9 L+₹2.0 L (9.22%)Rejected-Finance 894 NEAR 132 KV POWER HOUSE SINDHARI ROAD BALDEV NAGAR BARMER RAJ 344001 | BARMER | RAJASTHAN | 344001 | L2 | Rejected-Finance Other than lowest | |
| 3 | L3₹24.4 L+₹2.5 L (11.5%)Rejected-Finance | L3 | Rejected-Finance Other than lowest |
| Sl No | Description | Qty | Unit | Devi Engineeing L3 | National Rewinding Works L1 | GITANSH ENGINEERS AND COMPANY L2 |
|---|---|---|---|---|---|---|
| 1.00M&L for monthly 'A' Check Inspection of DG sets of capacities as described in Ser Item No. 1.01 to 1.13 including alternator, electric panel board connection to DG set etc for smooth functioning and carrying out maintanance as required at site and directed by Engr-in Charge. Note: Items/ Spares required shall be measured and paid separately under respective item of BoQ i) Checking engine oil level and topping up as and when required. ii) Checking and adjusting the belt for tension and replacement of belt if required. iii Checking of oil bath air cleaner level. iv) Checking of exhaust system for leakage v) Draining of sediment from fuel filter and fuel tank vi) Cleaning of air cleaner elements vii) Checking engine alternator coupling, mounting bolts and alignment viii) Tighting all nuts, bolts, in altenator terminal block ix) Checking of alternator carbon brushes and connections in alternator. x) Checking and tightening of all connection in DC control wiring. xi) Checking of all radiator rubber hoses for leakage and replacement if required. xii) Checking and recording oil pressure, water and oil temperarute for smooth functioning. xii) Checking anti vibration mounting pads for any deformation. xiii) Checking throttle linkage for smooth operation. xiv) Checking battery for cell test, electrolyte level, gravity and topping up to required level xv) Routine check / repair work of panel, switches, MCCBs, main switch, all contactors, engine control unit etc. xvi) Checking of AMF panel, all electrical connections etc. xvii) Checking of earthing resistance xviii) Cleaning of vegitation around the DG set up to 1.5 mtr area. 'A' Check Service shall be carried out as described in ser items No. 1.01 to 1.27 | ||||||
| 1.01 | 125 KVA Capacity, Make : Ashok Layland, Model LP 125, Location : SMC | 6 | Per Month | 350 ₹2,100 Lowest | 550 ₹3,300 | 1,000 ₹6,000 |
| 1.02 | 100 KVA Capacity, Make : Cummins, Model SGL 100, Location : Gupta Pump House | 6 | Per Month | 400 ₹2,400 Lowest | 550 ₹3,300 | 1,000 ₹6,000 |
| 1.03 | 250 KVA Capacity, Make : Kirloskar, Model 6SL8800TA, Location : Auditorium | 6 | Per Month | 500 ₹3,000 Lowest | 740 ₹4,440 | 1,000 ₹6,000 |
| 1.04 | 100 KVA Capacity, Make : Kirloskar, Model 6KSWATC 105, Location : 175 SU | 6 | Per Month | 500 ₹3,000 | 400 ₹2,400 Lowest | 1,000 ₹6,000 |
| 1.05 | 40 KVA Capacity, Make : Ashok Layland Model ALGDW4DMKIEE, Location : 307 TRU | 6 | Per Month | 400 ₹2,400 Lowest | 400 ₹2,400 Lowest | 1,000 ₹6,000 |
| 1.06 | 100 KVA Capacity, Make : Kirloskar, Model 6R1080 T, Location :STP | 6 | Per Month | 250 ₹1,500 Lowest | 560 ₹3,360 | 1,000 ₹6,000 |
| 1.07 | 63 KVA Capacity, Make : Kisloskar Location : 175 Su pump house | 6 | Per Month | 400 ₹2,400 Lowest | 500 ₹3,000 | 1,000 ₹6,000 |
| 1.08 | 500 KVA Capacity, Make : Greaves Location :CPH | 6 | Per Month | 500 ₹3,000 | 110 ₹660 Lowest | 1,000 ₹6,000 |
| 1.09 | 125 KVA Capacity, Make : Ashok Layland Location : CPH | 6 | Per Month | 300 ₹1,800 Lowest | 550 ₹3,300 | 1,000 ₹6,000 |
Tender Value
₹27 L
EMD Value
₹54,000
Closing Date
19 Sept 2025, 6:00 pmClosed
GE (AF) Utarlai
GE (AF) Utarlai PB No. 11 Barmer
REPAIR AND REPLACEMENT OF OLD UNSV PARTS OF DG SETS, EARTHING, POLE PAINTING, LED STREET LIGHT AND CONNECTED WORKS AT AF STN UTARLAI
2025_MES_727212_1
8636/E8
Open Tender
Civil Works
Item Rate
240 days
Utarlai
As per NIT
8 documents required · 8 mandatory
₹500
GE (AF) Utarlai
₹54,000
Yes
16 Oct 2025
22 Aug 2025
20 Sept 2025
23 Aug 2025
19 Sept 2025
5 Sept 2025
Amount
M&L for monthly 'A' Check Inspection of DG sets of capacities as described in Ser Item No. 1.01 to 1.13 including alternator, electric panel board connection to DG set etc for smooth functioning and carrying out maintanance as required at site and directed by Engr-in Charge. Note: Items/ Spares required shall be measured and paid separately under respective item of BoQ i) Checking engine oil level and topping up as and when required. ii) Checking and adjusting the belt for tension and replacement of belt if required. iii Checking of oil bath air cleaner level. iv) Checking of exhaust system for leakage v) Draining of sediment from fuel filter and fuel tank vi) Cleaning of air cleaner elements vii) Checking engine alternator coupling, mounting bolts and alignment viii) Tighting all nuts, bolts, in altenator terminal block ix) Checking of alternator carbon brushes and connections in alternator. x) Checking and tightening of all connection in DC control wiring. xi) Checking of all radiator rubber hoses for leakage and replacement if required. xii) Checking and recording oil pressure, water and oil temperarute for smooth functioning. xii) Checking anti vibration mounting pads for any deformation. xiii) Checking throttle linkage for smooth operation. xiv) Checking battery for cell test, electrolyte level, gravity and topping up to required level xv) Routine check / repair work of panel, switches, MCCBs, main switch, all contactors, engine control unit etc. xvi) Checking of AMF panel, all electrical connections etc. xvii) Checking of earthing resistance xviii) Cleaning of vegitation around the DG set up to 1.5 mtr area. 'A' Check Service shall be carried out as described in ser items No. 1.01 to 1.27
125 KVA Capacity, Make : Ashok Layland, Model LP 125, Location : SMC
100 KVA Capacity, Make : Cummins, Model SGL 100, Location : Gupta Pump House
250 KVA Capacity, Make : Kirloskar, Model 6SL8800TA, Location : Auditorium
100 KVA Capacity, Make : Kirloskar, Model 6KSWATC 105, Location : 175 SU
40 KVA Capacity, Make : Ashok Layland Model ALGDW4DMKIEE, Location : 307 TRU
100 KVA Capacity, Make : Kirloskar, Model 6R1080 T, Location :STP
63 KVA Capacity, Make : Kisloskar Location : 175 Su pump house
500 KVA Capacity, Make : Greaves Location :CPH
125 KVA Capacity, Make : Ashok Layland Location : CPH
200 KVA Capacity, Make : Greaves Location : 269 SU
200 KVA Capacity, Make : Kirloskar Location : Z8 p/H
200 KVA Capacity, Make : Kirloskar Location : WSA P/H
160 KVA Capacity, Make : Kirloskar Location : S/S 7 (Trolly)
M&L for 'B' Check once in Six month OR 250 Hrs running whichever is earlier DG sets of capacities as described in Ser Item No. 2.01 to 2.13. Inspection, maintenance and serviceing including alternator, electric panel board connection to DG set etc for smooth functioning and carrying out maintenance as per OEM instructions and as directed by Engr-in-Charge. Note:Items/ Spares including 'B' Check kit, coolent, lubricating oil required shall be measured and paid separately under respective item of BoQ i) Repeat the activities of 'Á' Check services ii) Replacment of lubricant oil. iii) Replacing lubricant oil filters element with O rings vi) Replacing fuel filters element with O rings v) Replacing air filter elements with O rings vi) Replacing coolant. 'B' Chech Service shall be carried out as described in Ser Item No. 2.01 to 2.13
125 KVA Capacity, Make : Ashok Layland, Model LP 125, Location : SMC
100 KVA Capacity, Make : Cummins, Model SGL 100, Location : Gupta Pump House
250 KVA Capacity, Make : Kirloskar, Model 6SL8800TA, Location : Auditorium
100 KVA Capacity, Make : Kirloskar, Model 6KSWATC 105, Location : 175 SU
40 KVA Capacity, Make : Ashok Layland Model ALGDW4DMKIEE, Location : 307 TRU
100 KVA Capacity, Make : Kirloskar, Model 6R1080 T, Location :STP
63 KVA Capacity, Make : Kisloskar Location : 175 Su pump house
500 KVA Capacity, Make : Greaves Location :CPH
125 KVA Capacity, Make : Ashok Layland Location : CPH
200 KVA Capacity, Make : Greaves Location : 269 SU
200 KVA Capacity, Make : Kirloskar Location : Z8 p/H
200 KVA Capacity, Make : Kirloskar Location : WSA P/H
160 KVA Capacity, Make : Kirloskar Location : S/S 7 (Trolly)
Supply only 'B' check kit for DG set of following capacities as mentioned in respective Ser Item No. 3.01 to 3.13 Note : It includes oil filters (1.00 Ltr/0.5 ltr), Diesel filters and air filters inner and outer as recommended by OEM
125 KVA Capacity, Make : Ashok Layland, Model LP 125, Location : SMC
100 KVA Capacity, Make : Cummins, Model SGL 100, Location : Gupta Pump House
250 KVA Capacity, Make : Kirloskar, Model 6SL8800TA, Location : Auditorium
100 KVA Capacity, Make : Kirloskar, Model 6KSWATC 105, Location : 175 SU
40 KVA Capacity, Make : Ashok Layland Model ALGDW4DMKIEE, Location : 307 TRU
100 KVA Capacity, Make : Kirloskar, Model 6R1080 T, Location :STP
63 KVA Capacity, Make : Kisloskar Location : 175 Su pump house
500 KVA Capacity, Make : Greaves Location :CPH
125 KVA Capacity, Make : Ashok Layland Location : CPH
200 KVA Capacity, Make : Greaves Location : 269 SU
200 KVA Capacity, Make : Kirloskar Location : Z8 p/H
200 KVA Capacity, Make : Kirloskar Location : WSA P/H
160 KVA Capacity, Make : Kirloskar Location : S/S 7 (Trolly) Note For S.No. 1 to 3 above - Work mentioned in S. No. 1 to 3 for 'A' and 'B ' check incl servicing and supply only items mentioned in S. No. 4 to 14 below will be performed as decided by Engr-in-charge
Supply only premix coolant for diesel engine generator
Supply only Battery distilled water with electrolyte mix
Supply only Engine oil 15 W 40 complete all as directed by Engr-in-charge
Supply only radiator hose pipe set with clamps suitable for DG set of capacity 40 /63 KVA
Supply only radiator hose pipe set with clamps suitable for DG set of capacity 100 /125 KVA
Supply only radiator hose pipe set with clamps suitable for DG set of capacity 160/200/250 KVA
Supply only radiator hose pipe set with clamps suitable for DG set of capacity 500 KVA
Supply only fan belt set suitable for 40/63 KVA
Supply only fan belt set suitable for 100/125 KVA
Supply only fan belt set suitable for 160/200/250 KVA
Supply only fan belt set suitable for 500 KVA
Supply and fixing in replacement of battery lead with Negative & Positive brass terminals of suitable size and length of each lead all as directed
Servicing & repair to self starter of DG set of 16 KVA to 150 KVA 12 volt system incl replacement of parts such as washer, nut, bolts, bush, solonoid, rotor,winding etc. assembling and testing complete all as directed by Engr-in-Charge.
Servicing & repair to self starter of DG set of 160 KVA to 500 KVA 24 volt system incl replacement of parts such as washer, nut, bolts, bush, solonoid, rotor, winding etc. assembling and testing complete all as directed by Engr-in-Charge.
Supply & Fix in replacement of battery 12 V, 100 AH, maintenance free battery, 12 Volt initially charged with suitable size of copper leads and brass terminals complete as directed by Engr-in-Charge. Make: Exide/ Amron/ Luminous
Supply & Fix in replacement of battery 12 V, 150 AH, maintenance free battery, 12 Volt initially charged with suitable size of copper leads and brass terminals complete as directed by Engr-in-Charge. Make: Exide/ Amron/ Luminous
Supply & Fix in replacement of battery 12 V, 180 AH, maintenance free battery, 12 Volt initially charged with suitable size of copper leads and brass terminals complete as directed by Engr-in-Charge. Make: Exide/ Amron/ Luminous
M & L for complete checking of AMF panel, finding the fault, servicing complete including replacement of unserviceable spares with necessary wiring and testing complete for manual & Auto operations all as directed. (Note:- Items required for replacement will be measured & paid seperately under respective item of BoQ)
Supply only in replacement of AMF panel under and over voltage timing relay as per existing type, make and capacity
Supply only in replacement of AMF panel timer relay for circuit 230 V AC supply as per existing type, make and capacity
Supply only in replacement of AMF panel relay card 12 V DC supply for change over as per existing type, make and capacity
Supply only in replacement of AMF panel relay single with batch 8 pin 230 V AC supply as per existing type, make and capacity
Supply only in replacement of AMF panel reverse power relay for circuit 230 V AC supply as per existing type, make and capacity
Supply only in replacement of AMF panel earth fault relay for circuit 230 V AC supply as per existing type, make and capacity
M&L for replacement of unserviceable contactor 415 V AC supply, 4 pole suitable for the following capacity of DG set AMF panel:-
DG set 500 KVA
DG set 250 KVA
DG set 200 KVA
DG set 160 KVA
DG set 125 KVA
DG set 100 KVA
DG set 63 KVA
DG set 40 KVA
M&L in replacement of Start/ Stop switch with elements of AMF panel of any make and capacity.
M&L in replacement of solenoid switch for use of engine stop of AMF panel of any make and capacity.
M&L in replacement of Volt meter digital type of range 0-500 volts of AMF panel
M&L in replacement of Amp meter digital type of existing make,model and capacity of AMF panel
M&L in replacement of Indicator lamp 230 V AC Supply of AMF panel
M&L in replacement of battery charger 12 V DC SMPS 10 Amp for AMF panel
M&L in replacement of battery charger 24 V DC SMPS 10 Amp for AMF panel
Supply only in replacement of AMF panel control unit as per existing type, make and capacity
M & L for repair and replacement of broken conopy door hinges of DG set of any capacity and make. Setting of conopy door, properly locking arrengement complete all as directed by Engr-in Charge
S & F in replacement of fuel feed pump of DG Set engine as per existing make, model and capacity complete all as directed by Engineer-in-Charge.
Repair/overhauling of fuel pump of DG Set engine as per existing make, model and capacity complete all as directed by Engineer-in-Charge.
S & F in replacement of NRV of DG set engine as per existing make, model complete all as directed by Engineer-in-Charge.
S & F in replacement of fuel level gauge of DG set as per existing make, model complete all as directed by Engineer-in-Charge.
S & F in replacement of AVR of DG set engine 15 to 160 KVA as per existing make, model complete all as directed by Engineer-in-Charge.
S & F in replacement of AVR of DG set engine 200 to 500 KVA as per existing make, model complete all as directed by Engineer-in-Charge.
S & F in replacement of Alternator connection terminal block suitable for 15 to 500 KVA DG Set alternetor as per existing sample complete all as directed by Engr-in Charge.
S & F in replacement of Controller unit suitable for DG Set having capacity 15-500 KVA. Make of controller as per DG set complete all as specified and directed by Engr-in-Charge.
M & L in replacement of battery stand frame of size 4 feet x 1.5 feet with height of 1 feet made of 50x50x6mm angle iron and support with flat iron of size 40x6mm, duly painted, 20 mm wooden plank on top to place 02 Nos batteries complete all as directed by Engr-in-Charge.
M&L for taking the Diesel Generating set from site(domestic/Technical) to civil workshop where repair to be carried out safely, dismantling the engine completely for repair and top over hauling of Diesel Generating set 40 KVA to 160 KVA capacity any make, carry out required repair as per manufacture instuction including replacement of all defective parts as required for smooth functioning of the DG set complete.
Supply only the following U/S parts/components for fixing under ser item No 48 here-in-before
Cylinder Liners complete
Piston assly complete with gudgeon pin and ring set with 'O' rings.
Valve inlet and exhaust, valve sheet and valve guide
Push Roads
Connecting Rod
Connecting Rod bushes
Rocker arm bushes
Engine gasket set complete
Gasket set cylinder head complete
Set of Joints
RRA Assy
Valve Seal
Oil Seal
nozzle caliberation
Head Repair
turbo assembly
Following repairs also to be carried out under Ser item No 48 here-in-before
Repair to charging alternator assembly including replacement of carbon brushes and bushes complete and refixing all the components in position with necessary screws, nuts & bolts complete all as directed.
M&L for servicing / cleaning of air intake manifold assy with requsite tools and air pressure to remove dirt & foreign particle completetly including replacement / repair to fiexible coupling of silencer / exhaust manifold to ensure no leakage of exhaust inside the canopy complete all as directed.
M&L for cleaning / derusting for inner cushion foam (insulation) of all inside canopy to achieve neat & cleanliness of gererating cabin with requisite air blower / dust sucker suitable for the job complete all as directed.
M&L for replacment of dioade, DE and NDE bearing of AC generator and warnishing field coil and armature assy complete all as directed.
M & L for painting of outer surface only of canoply acquisite of generating set inculding cleaning and derusting and preperation of painting with requisite tools and painting with white bright super enamel / synthetic paint colour including rewriting of machine no complete all as directed.
M & L for leakage rectification of radiator, cleaning, pressure testing complete as required and directed.
Testing and tunning of DG set with load test complete all as directed by Engr-in-Charge.
Diesel tank cleaning complete all as directed by Engr-in-Charge.
M&L for taking the Diesel Generating set from site(domestic/technical) to civil workshop where repair to be carried out safely, dismantling the engine completely for repair and top over hauling of Diesel Generating set 200 to 500 KVA capacity any make, carry out required repair as per manufacture instuction including replacement of all defective parts as required for smooth functioning of the DG set complete.
Supply only the following U/S parts/components for fixing under ser item No 49 here-in-before
Cylinder Liners complete
Piston assly complete with gudgeon pin and ring set with 'O' rings.
Valve inlet and exhaust, valve sheet and valve guide
Push Roads
Connecting Rod
Connecting Rod Bushes
Rocker arm bushes
Engine gasket set complete
Gasket set cylinder head complete
Set of Joints
RRA Assy
Valve Seal
Oil Seal
nozzle caliberation
Head Repair
turbo assembly
M & L incl T&P for shifting of DG set capacity 40 KVA to 160 KVA within a distance of 6.0 KM range including disconnection and reconnect of electrical/mechanical connection in all respect. Testing og DG set after installation complete all as directed by Engr-in Charge
S & F in replacement of self starter 24V for DG set of 200 to 500 KVA as per existing make , model all as per existing and all as directed by Engr-in-charge
S&F in replacement of Copper cable ( Red/ black) of size single core 16/25 sqmm from batterry to self starter of DG set complete all as directed by Engr-in-charge
Material & Labour painting of all steel structures i.e channels angles complete 33 KV yard electrical system ,gantries channels , 2 pole structure bracket, 4 pole structures frame , steel plates angle of any size and length located inside 33 KV yard with and including with one under coat and one finishing coat with aluminum paint and also painting external surface of all power transformer, all outdoor VCB (33 and 11 KV), all outer OLTC and also writing of SM/MES No.after cleaning /preparation of surfaces including marking of pole No etc complete.
Material & Labour painting of steel tubular LT poles including cross arms, clamps etc in situ with one under coat and one finishing coat with aluminum paint after cleaning /preparation of surfaces including making yellow and black strips 30 cm wide 5 Nos with two coats of synthetic enamel paint etc complete.
Material & Labour painting of making yellow and black strips 30 cm wide 5 Nos with two coats of synthetic enamel paint on PCC LT poles including painting of cross arms, clamps etc in situ with one under coat and one finishing coat with aluminum paint after cleaning /preparation of surfaces.
Material & Labour painting of making yellow and black strips 30 cm wide 5 Nos with two coats of synthetic enamel paint on PCC HT poles including painting of cross arms, clamps, etc in situ with one under coat and one finishing coat with aluminum paint after cleaning /preparation of surfaces.
Material & Labour painting of steel tubular HT poles including cross arms, clamps etc in situ with one under coat and one finishing coat with aluminum paint after cleaning /preparation of surfaces including making white and black strips 30 cm wide 5 Nos with two coats of synthetic enamel paint and marking of pole No , Feeder No also.
Material and Labour for marking on pole number of any type (HT/LT) with font size of 3 x 2.5 inch and specifiucation shown on LT/HT pole will be (T/A) for technical area and (D/A ) for domestic area with pole No. Complete all as specified and directed by Engineer-in-charge.
M&L earthing complete as per electrical plate No. 3 of MES SSR Part-I with galvanised steel earth plate electrode 60cmx60cmx6.0mm thick, buried directly vertically in ground in a pit depth not less than 2.25 metres below ground level with top edge of earth plate at a depth not less then 1.5 metre below normal ground level connected to and including galvanised iron or steel earth wire 4mm by means of bolts, nuts check nuts and washers of galvanised iron or steel. Earthing strip shall be protected by galvanised iron or steel pipe 20 mm bore light grade and connected to continuous earth wire on pole / test point. Watering pipe shall be 20 mm bore GI medium grade. The earthing shall be of inclusive of excavation & earth work in any type of soil, charcoal, salt, funnel PCC pit and RCC cover complete all as specified & tested complete. Note 1. Following items deemed to be included in quoted rates (a) Earth electrode (b) Main earth lead from earth electrode to test point and further to equipment to be earthed upto 7.5 mtr. ( c) M&L for connecting earth electrode and earth lead as specified (d) adequate qty of charcoal ,dust and commom salt as per direction (e) All labour involved incl testing of earth network (f) Excavation and earth work or drilling hole for electrode (G) PCC pit and CI Cover (h) Funnel with watering pipe, wiremesh and copper lugsetc. as specified (j) GI protection pipe of size as specified for protection of earth lead from mechanical injury or tempring Note 2. On testing after completion if the desired earth resistence is not obtained the earthing will be redone at no extra cost
M&L earthing complete as per electrical plate No. 3 of MES SSR Part-I with galvanised steel earth plate electrode 60cmx60cmx6.0mm thick, buried directly vertically in ground in a pit depth not less than 2.25 metres below ground level with top edge of earth plate at a depth not less then 1.5 metre below normal ground level connected to and including galvanised iron or steel earth strip 32mmx6mm by means of bolts, nuts check nuts and washers of galvanised iron or steel. Earthing strip shall be protected by galvanised iron or steel pipe 40 mm bore light grade and connected to continuous earth wire on pole / test point. Watering pipe shall be 20 mm bore GI medium grade. The earthing shall be of inclusive of excavation & earth work in any type of soil, charcoal, salt, funnel PCC pit and RCC cover complete all as specified & tested complete. Note 1. Following items deemed to be included in quoted rates (a) Earth electrode (b) Main earth lead from earth electrode to test point and further to equipment to be earthed upto 7.5 mtr. ( c) M&L for connecting earth electrode and earth lead as specified (d) adequate qty of charcoal ,dust and commom salt as per direction (e) All labour involved incl testing of earth network (f) Excavation and earth work or drilling hole for electrode (G) PCC pit and CI Cover (h) Funnel with watering pipe, wiremesh and copper lugsetc. as specified (j) GI protection pipe of size as specified for protection of earth lead from mechanical injury or tempring Note 2. On testing after completion if the desired earth resistence is not obtained the earthing will be redone at no extra cost
M&L earthing complete as per electrical plate No. 3 of MES SSR Part-I with copper earth plate electrode 60cmx60cmx6.0mm thick, buried directly vertically in ground in a pit depth not less than 2.25 metres below ground level with top edge of earth plate at a depth not less then 1.5 metre below normal ground level connected to and including copper earth strip 20mmx3mm by means of bolts, nuts check nuts and washers of brass/brazing l. Earthing strip shall be protected by galvanised iron or steel pipe 40 mm bore light grade and connected to continuous earth wire on pole / test point. Watering pipe shall be 20 mm bore GI medium grade. The earthing shall be of inclusive of excavation & earth work in any type of soil, charcoal, salt, funnel PCC pit and RCC cover complete all as specified & tested complete. Note 1. Following items deemed to be included in quoted rates (a) Earth electrode (b) Main earth lead from earth electrode to test point and further to equipment to be earthed upto 7.5 mtr. ( c) M&L for connecting earth electrode and earth lead as specified (d) adequate qty of charcoal ,dust and commom salt as per direction (e) All labour involved incl testing of earth network (f) Excavation and earth work or drilling hole for electrode (G) PCC pit and CI Cover (h) Funnel with watering pipe, wiremesh and copper lugsetc. as specified (j) GI protection pipe of size as specified for protection of earth lead from mechanical injury or tempring Note 2. On testing after completion if the desired earth resistence is not obtained the earthing will be redone at no extra cost
M &L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc.as required to, GI wire 4mm
M &L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc.asrequired to, 32x6 mm galvanised iron strip
M &L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc.asrequired to, 20x3 mm copper strip
M& L for Painting of LT panel with one coat of synthetic enamel paint of approved colour, writing letters on LT panel (by using appropriate colour, size /font stencil) for all incoming and outgoing feeder complete all as specified and directed by Engr-in-Charge
M&L for disconnecting and taking down old U/S street light fittings of any type/rating from pole or wall, dismantling the same for necessary repair or replacment of U/S spares parts and refixing the same after necessary repair connecting and testing complete all as specified and directed by Engineer-in-Charge. Notes:- (a) Spares/accessories required for repair/replacement shall be measured and paid sepratley as supply only under respective items of BoQ. (b) T&P required for repair/ maintenance such as ladder, vehicle, manpower etc, shall be included in the quoted rate of this item.
Supply only Surge protection device compatible with industrial & outdoor LED fixtures 70 watt to 200 watt complete all as specified and directed by Engineer-in-Charge.
Supply only LED drivers compatible with industrial & outdoor LED fixtures 70 watt to 200 Watt of IS 15885 (Part 2/ Sec 13) as per existing make
(a) Suitable for 25 watt to 50 Watt LED fitting
(b) Suitable for 70 Watt LED fitting
(c) Suitable for 90-120 Watt LED fitting
(d) Suitable for 150 Watt LED fitting
Supply and fixing in replacement of GI pipe bracket light grade of 40mm dia ISI marked duly bent to shape with an angle including clamps, nuts, bolts, washers etc complete including two coat of synthetic enemal paint over a coat of primer and dismantling of existing old u/s brackets of all as specified and directed by Engineer-in-Charge. (Note: - The total length of the bracket shall be 1.5m)
M&L for disconnecting jumpers/electric connection of street light fittings from OH LT line or junction box removing the carbon and reconnecting the same complete all as per requirement of site.
Supply and fixing of 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections twin core cable conductor of following sizes including taking down old U/S cable :-(a) 2.5 sqmm 3 core
Supply and fixing PVC insulated and over all PVC sheathed, stranded copper conductor wire 1.5 sqmm x 3 core ISI marked.including Steel conduit pipe 20mm complete from fitting to pole junction box complete all as specified. Note: 1. PVC Copper wire 1.5 sqmm x 3 core and Steel conduit pipe 20mm will be mesured as Combine as one RM length
S & F in replacement of HDPE junction box of size 32 cm x 23 cm with cable glands, connector 3 P+1 N on insulators and necessary mounting arrangement ,MCB SP upto cap of 2 Amp and fixing on poles with MS Clamps and connecting with existing cable all as directed.
M&L for repair and replacment of U/S time switch accessories/ spares including reconnecting and testing complete Note : - Spares/accessories required for replacement shall be measured and paid sepratley under respective items of BoQ.
Supply only Nature Switch-02 (sensor) of illuminance level for switching ON is ≤ 30 Lux and for Switching OFF ≥ 10 Lux along with part night operation facility of 4-12 hrs.make- healer enterprises or equivalent as per site requirement
Supply only contactor 3 pole, 415 volts including suitable size of lugs make- siemens /L&T/BCH or equivalent of following ratings-
(a) 12-18 amps
(b) 25 amps
Supply only MCB TPN 415 Volts, 50 Hz AC supply system make- siemens /L&T/BCH or equivalent of following ratings-
(a) 40 Amps
(b) 63 Amps
Supply and fixing in replacement of 120 watt LED flood light, energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium IP65 flood light, suitable for highlighting architectural facade and general purpose lighting. Make: Havells/ Philips/Wipro/ Crompton
Supply and fixing in replacement of LED street light energy saving and environmental friendly long life made up of pressure die cast aluminium housing with high power LED as lighting source with IP65 protection as directed by Engineer-in-Charge. Make: Havells/ Philips/ Wipro/ Crompton . Rating and capacity are as below
(a) 150 watt
(b) 120 watt
(c) 70/72 watt
(d) 60 watt
(e) 45 watt
(f) 25 watt
Supply and fixing in replacement of LED halogen light 150 Watt energy saving and environmental friendly long life made up of pressure die cast aluminium housing with high power LED as lighting source with IP65 protection as directed by Engineer-in-Charge. Make: Havells/ Philips/ Wipro/ Crompton
Labour for removing and taking out existing underground LT Cable from trenches or pole or underground in pipe duct carefully cleaning of the same for relaying incase of serviceable cable complete all as specified.
(a) 25 Sqmm 3.5/ 4 core
(b) 10 Sqmm 3.5/ 4 core
(c) 16 Sqmm 2 core
(d) 10 Sqmm 2 core
Relaying, Jointing and testing only under ground armoured cable LT XLPE insulated cable 1100 Volts PVC bedded aluminium conductor cable received from Item No.16 here in above complete all as directed by Engineer-in-Charge.
(a) 25 Sqmm 3.5/ 4 core
(b) 10 Sqmm 3.5/ 4 core
(c) 16 Sqmm 2 core
(d) 10 Sqmm 2 core
Supply & Laying, Jointing and testing in replacement underground armoured cable LT XLPE insulated cable 1100 Volts PVC bedded galvanised steel strip or wire armoured electric LT UG cable heavy duty with multi stranded aluminium conductor laid in trenches / walls/ ducts passing through pipe cable of following size complete all as specified:- Note- Solid aluminium conductor upto 10 sqmm and balance stranded conductor, galvanised wire for cable upto 10 sqmm balance all galanized steel strip)
(a) 25 Sqmm 4 core
(b) 10 Sqmm 4 core
(c) 16 Sqmm 2 core
(d) 10 Sqmm 2 core
Excavation in trenches not exc 1.5 Mtr wide and not exc 1.5 mtr depth for laying of cable and getting out in any type of soil.
Removing of excavated surplus soil not exc 50 m and deposited where directed at a level not exc 1.5 m above the starting point.
Returning, filling in, including spreading, leveling, watering and well ramming in layer not exc 25 cm thick
M & L for sand cushioning to all around the cable protection of natural Tibba sand all as directed. (Note : Punning thickness will be measured and paid for payment purpose.)
M & L stone patti quarry faced Jodhpur type 4 to 5 cm thick and 25 to 30 cm wide putting on cable abutting to each other for cable protection all as directed.
Labour only for laying only serviceable stone patti obtained from item above in sch taken out old stone patti for protection of cable all as directed.
M & L PCC 1:3:6 type C1 using 20 mm graded stone aggregate for pedestal of pole. Complete all as directed by Engineer-in-Charge.
Material and Labour for trimming/cutting of tree branches touching HT/LT overhead lines wide growth around poles and making clear span of 2 mtr all around OH line with pole and plants all as directed by Engineer-in-Charge.
S & F in replacement MCB single pole, 230 Volt 10 KA,
(b) 0.5 to 2 Amp,
Supply and laying in replacement of light grade galvanised steel tube 40mm bore light grade for protection of cable complete all as directed by Engineer-in-Charge.
Supply and fixing in replacement of LT cable route indicator cast iron of suitable size mounted on 40 x 40 x 3 mm angle iron with height of 1.5 metre along with LT cable trench including planting in ground with PCC complete all as specified and directed.by Engr-in-Charge.
Labour for drilling hole under road for laying of U/G cable through and including HDPE pipe 80mm dia complete all as specified and directed at site.
(a) Single-Phase load of 5kW (Swadeep-02EC5kW1P) with Contactor, Incoming MCB & Outgoing MCB rating of 40-63 Amps & main load Circuit Wiring of min. 10 sq.mm. Make of Nature Switch: Kakatiya Energy Systems/ BAJAJ/ Healer, Contactors: BCH/ L&T/ Schneider, MCBs: HAGER/Schneider/L&T (Exora/AU series) /C&S, Enclosure & Circuit Sheet: Sintex or equivalent, Circuit Wiring: Polycab/Finolex or equivalent. Contactor should Conform to IEC-60947-4-1 / IS-13947-4-1 and MCBs should Conform to IEC-60898 / IS-8828
(b) Three-Phase load of 12kW (Swadeep-02EC12kW3P) with Contactor, Incoming MCB & Outgoing MCB rating of 40-63 Amps & main load Circuit Wiring of min. 10 sq.mm. Make of Nature Switch: Kakatiya Energy Systems/ BAJAJ/ Healer, Contactors: BCH/ L&T/ Schneider, MCBs: HAGER/Schneider/L&T (Exora/AU series) /C&S, Enclosure & Circuit Sheet: Sintex or equivalent, Circuit Wiring: Polycab/Finolex or equivalent. Contactor should Conform to IEC-60947-4-1 / IS-13947-4-1 and MCBs should Conform to IEC-60898 / IS-8828
Supply and Fixing in replacement of 9 watt pathway LED bollard light with opel arylic diffuser and IP 65 protection including cable connection to UG cable using 1.5 sqmm PVC insulated PVC sheathed 1100 V grade twin core copper conductor wire all as directed by Engr-in-Charge all as per Bajaj ordering product code No. 111284, Model;- Tulip, Cat No. BGBOM 650 9W LED or equivalent in Havells/Philips/wipro /crompton Greaves/Surya
Supply and fixing in replacement of LED aviation obstruction light with suitable wattage rating as per site comprising of aluminium housing with polycarbonate enclosure all as per Bajaj product code 110731 luminaire type BGAV302 LED or equivalent Philips/Wipro/Havells/surya including all necessary fitting accessories and LED lamps complete all as directed.
S&F in replacement of post top lantern light "MAPLE" decorative post top for 360 degree indirect light IP 65 protection resistant to impact and corrosion . Glare-free and better uniformity. 40 watt LED 230 V 50 Hz including necessry fitting accessories complete all as per Crompton cat No. LPTO-40-CDl or equivalent Philips/Wipro/Havells/surya
Supply and fixing in replacement of polycarbonated globe suitable for 15 W LED bulb/ CFL retrofit including holder including base plate suitable for mounting of globe complete with electric connection and required accessories all as directed by Engineer-in-Charge.
M & L for lowering of high mast lantern carriage for disconnecting and taking down U/S high mast light fittings of any type/rating dismantling the same for necessary repair or replacment of U/S spares and refixing, connecting, testing including raising high mast lantern carriage to its original position complete all as required at site and directed by Engineer-in-Charge. Notes:- (a) Spares/accessories required for replacement shall be measured and paid sepratley under respective items of BoQ. (b) T&P required for lowering/raising such as ladder, vehicle, menpower etc, shall be included in the quoted rate of this item.
M&L for repairing of highmast for electrical operation of raising and lowering mechanism of lantern carriage with its supporting stand complete as required at site and directed by Engr-in Charge including following:- (a) Fixing, connecting and testing of existing stainless steel wire rope of 6mm dia (7/19 construction) with double drum winch (b) Repair / servicing of integral power tool, three phase, high powered, reversible with mechanical tripping facility. (c) Checking serviceability of trailing cable, flexible Copper 5 core 2.5 Sqmm through shaft and reconnecting the same or new cable as per requirement ( Rate for new cable is not included in this item). (d) Repair of manual lowering hoisting chain link mechanism Notes:- (a) Spares/accessories required for replacement shall be measured and paid sepratley under respective items of BoQ. (b) T&P required for repair/ mantenance such as ladder, vehicle, manpower, welding cutting arrangement etc, shall be included in the quoted rate of this item.
Dismantling, opening, rewinding and refixing 3.0 HP motor, three phase, 415 V, 50 Hz motors with super enameled copper wire of existing gauge and existing class insulation including superior quality varnishing, heating / drying coils, making connections from coil to terminal box, spray painting with two coats of synthetic enamel paint, necessary mechinical works for shaft / bearing housing, renewal of DE and NDE bearings, transportation from installation to workshop & back, connecting, testing and commissioning at site for satisfactorily operation as required.
Supply only starter in replacement suitable for up to 3.0 HP motor, three phase, 415 V , AC supply with forward/ reverse switch for High mast raising and lowering of lantern carriage with its supporting stand.
GITANSH ENGINEERS AND COMPANY (BID ID -3429554)
Devi Engineeing (BID ID -3429997)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .