Improvement of Water Supply System at Seithur Town Panchayat
2024_DTP_508445_1
KNMT 2024-2025 Water supply 504/2024
Open Tender
Civil Works
Works
90 days
Seithur
Class I
3 documents required · 3 mandatory
₹0
₹7.1 L
Yes
Seithur
24 Dec 2024
7 Dec 2024
13 Dec 2024
7 Dec 2024
13 Dec 2024
7 Dec 2024
9 Dec 2024
Amount
Earth work open well excavation, complying with relevant clauses of T.N.D.S.S. Well sinking and with lead upto 10 metres in Hard stiff clay, stiff black cotton soil, hard red earth, shales,murrams gravel, stoney earth and earth mixed with small size boulders and hard gravelly soil - First depth of 2 metres Twad Pg No 312(0 to 1.30m)
Earthwork excavation in all soil and sub soils except hard rock requiring blasting with initial lead and lift including re filling the sides of foundation in layer of 15 cm thick watering, ramming, depositing the surplus earth in the premises as directed by the departmental officers, etc., complete complying with standard specification.
First depth of 2 m
Second Depth of 2 m
The rates for earth work excavation and refilling for pipe line works having bed width of 1.25m and below on linear measurement basis - Earth work rate for other than loose soil/m PVC/HDPE/GRP + Refilling the trenches with excavated earth (other than sand) in layers and watering, ramming and consolidation as per standard specification etc complete and as directed by Engineer in charge Twad Sor 24-25 Pg No 191
100mm Dia DI pipe
110mm Dia HDPE pipe
Earth work open well excavation, complying with relevant clauses of T.N.D.S.S. Well sinking and with lead upto 10 metres in Hard stiff clay, stiff black cotton soil, hard red earth, shales,murrams gravel, stoney earth and earth mixed with small size boulders and hard gravelly soil - First depth of 2 metres Twad Pg No 312(1.30m to 2.0m)
Earth work open well excavation, complying with relevant clauses of T.N.D.S.S. Well sinking and with lead up to 10 metres in soft disintegrated rock, laterite, soft rock or kankar, not requiring blasting - First depth of 2 metres 2m to 4m Twad Pg No 312(2.0m to 4m)
Earth work open well excavation, complying with relevant clauses of T.N.D.S.S. Well sinking and with lead up to 10 metres in soft disintegrated rock, laterite, soft rock or kankar, not requiring blasting - First depth of 2 metres 4m to 5m Twad Pg No 312(4.0m to 5m)
Earth work Open well excavation, complying with relevant clauses of T.N.D.S.S. Well sinking and with lead up to 10m in Medium rock and Dense medium rock not requiring blasting. First depth of 2 metres 4m to 6m Twad Pg No 312
Earth work Open well excavation, complying with relevant clauses of T.N.D.S.S. Well sinking and with lead up to 10m in Medium rock and Dense medium rock not requiring blasting. First depth of 2 metres 6m to 8m Twad Pg No 312
Earth work Open well excavation, complying with relevant clauses of T.N.D.S.S. Well sinking and with lead up to 10m in Medium rock and Dense medium rock not requiring blasting. First depth of 2 metres 7m to 9m Twad Pg No 312
Earth Work Open well excavation complying with relevant clauses of T.N.D.S.S. well sinking and with lead up to 10m in Medium rock and Dense medium rock requiring blasting. First depth of 2 metres 9m to 11m Twad Pg No 312
Earth Work Open well excavation complying with relevant clauses of T.N.D.S.S. well sinking and with lead up to 10m in Medium rock and Dense medium rock requiring blasting. First depth of 2 metres 8m to 10m Twad Pg No 312
Earth Work Open well excavation complying with relevant clauses of T.N.D.S.S. well sinking and with lead up to 10m in Medium rock and Dense medium rock requiring blasting. First depth of 2 metres 10m to 12m Twad Pg No 312
Earth Work Open well excavation complying with relevant clauses of T.N.D.S.S. well sinking and with lead up to 10m in Medium rock and Dense medium rock requiring blasting. First depth of 2 metres 12m to 14m Twad Pg No 312
Earthwork Open well excavation complying with relevant clauses of T.N.D.S.S. well sinking and with lead up to 10m in Medium rock and Dense medium rock requiring blasting. First depth of 2 metres 14m to 16m Twad Pg No 312
Earth Work Open well excavation complying with relevant clauses of T.N.D.S.S. well sinking and with lead up to 10m in Medium rock and Dense medium rock requiring blasting. First depth of 2 metres 16m to 18m Twad Pg No 312
Earth Work Open well excavation complying with relevant clauses of T.N.D.S.S. well sinking and with lead up to 10m in Medium rock and Dense medium rock requiring blasting. First depth of 2 metres 17m to 18m Twad Pg No 312
Earth Work Open well excavation complying with relevant clauses of T.N.D.S.S. well sinking and with lead up to 10m in Medium rock and Dense medium rock requiring blasting. First depth of 2 metres 18m to 20m Twad Pg No 312
Open well excavation complying with relevant clauses of T.N.D.S.S. Well sinking and with lead upto 10 metre in Hard granite measured in solid including blasting and stacking - First depth of 2 metre
Open well excavation complying with relevant clauses of T.N.D.S.S. Well sinking and with lead upto 10 metre in Hard granite measured in solid including blasting and stacking - First depth of 2 metre
Open well excavation complying with relevant clauses of T.N.D.S.S. Well sinking and with lead upto 10 metre in Hard granite measured in solid including blasting and stacking - First depth of 2 metre
Open well excavation complying with relevant clauses of T.N.D.S.S. Well sinking and with lead upto 10 metre in Hard granite measured in solid including blasting and stacking - First depth of 2 metre
Open well excavation complying with relevant clauses of T.N.D.S.S. Well sinking and with lead upto 10 metre in Hard granite measured in solid including blasting and stacking - First depth of 2 metre
Supplying and filling in foundation and basement with Crushed Stone Sand (M- Sand) in layers of not more than 15cm thick well rammed watered and compacted etc., complete complying with standard specification.
Plain Cement concrete in 1:4:8 (one cement, four M. sand and eight aggregate) mix using 40mm ISS hard broken granite metal for foundation and Flooring including dewatering where ever necessary including cost and conveyance of all materials to work site and labour charges etc., for mixing laying, leveling and curing etc., Complete
Plain Cement Concrete 1:2:4 (one cement, two Crushed Stone Sand (M- Sand) and four coarse aggregates) using 20mm size ISS HBG metal including cost and conveyance of all materials to site and including for the mixing, laying and labour charges etc., complete as per standard specification
Reinforced Cement Concrete M 30 Mix using 20mm and 10-12 mm size ISS HBG metal machine crushed from approved quarry including cost and conveyance of all materials to site, loading and unloading charges and labour charges for mixing, laying and curing but excluding cost of reinforcement etc. Complete with std. Specifications.
Above G.L
Below GL & upto 1.5 m
Below GL & beyond 1.5 m
Supply and erection of steel centering, shuttering for soffits and sides including necessary support strutting for all RCC works using MS sheets of suitable size of BG 10 stiffened with MS angle of size 25x25x3mm for boarding laid over Silver Oak joists of size 10cmx6.5cm space at 10cm c/cand supported by Casurino Prop 10cm-13cm spaced at 75cm c/c etc., complete and as directed by Departmental Officers.
Plain surface
Circular surface
Plain Surface
Providing and laying in position Standardised Concrete Mix M-20 Grade in accordance with IS 456 - 2000 using 20mm and down graded hard broken granite stone jelly for all RCC items of works with minimum cement contenet of 325Kg/ cum and maximum water cement ratio of 0.55 including admixture (Plasticiser / super plasticiser) in recommended proportions as per IS 9103 to accelerate, related setting of concrete, improve workability without imparing strength and durability with about (5.0cum), 7730Kg of 20mm machine crushed stone jelly and with about (3.3 cum), 5156kg of 10 - 12mm machine crushed stone jelly and with about (4.79cum) 7670 kg of Crushed Stone Sand (M- Sand), but excluding cost of reinforcement grill and fabricating charges centering and shuttering but including laying, vibrating with mechanical vibrators, finishing, curing, etc and providing fixtures like fan clamps in the RCC floor / roof slabs wherever necessary without claiming extra cost etc., complete complying with standard specification and as directed by the departmental officers -
Supply, delivery fabrication and placing in position of MS, RTS rods for reinforcement for binding ring, pilasters, roof slab and well curb including cost of binding wire etc. complete and as directed by TWAD Bd. Officers
Disposal of surplus earth including loading & unloading, conveyance within a distance of 5Km and spreading as directed by the Engineer-In-Charge.Twad Pg No 322
Supply an delivery of 600mm dia FRC manhole frame to have clear opening of 600mm dia to suit 600mm dia FRC Coverf approved quality including cost and conveyance of all materials and labour charges and other incidental charges to site etc., complete. as per standard specification
Suppliyng delivery of PVC Mould CI steps for sump including transportation.,
Supply, delivery and fixing of RCC Inner Ladder of approved quality including cost and conveyance of all materials and labour charges and other incidental charges to site etc., complete. as per standard specification
Supply, delivery and fixing of MS Outer Ladder of approved quality including cost and conveyance of all materials and labour charges and other incidental charges to site etc., complete. as per standard specification
Plastering in C.M. 1:3 mix (one part of cement and three part of M.Sand) 10 mm tk including mixing and finishing to a well smoothened surface, watering cost and conveyance all materials and all labour and other incidental charges and other incidental charges etc., complete. as per standard specification TNBPSS 56,57
Plastering in C.M. 1:5 mix (one part of cement and five part of Sand) 12mm tk including mixing and finishing to a well smoothened surface, watering cost and conveyance all materials and all labour and other incidental charges and other incidental charges etc., complete. as per standard specification TNBPSS 56,57
Supply and fixing of 100m dai GI pipe & Specials of approved quality as IS 1239/PART/1 / PART 2/2004. including cost and conveyance of all materials and labour charges and other incidental charges to site etc., complete. as per standard specification.
100mm Dia GI Pipe
100mm Dia GI coupling
100mm Dia GI Lbow
100mm Dia GI H Nipple
100mm Dia GI Union
100mm Dia GM Gate valve & GI NR Valve
Supplying and Painting the walls with two coats of weather sealed exterior Emulsion Paint of approved quality and colour including cost and conveyance of all materials and labour charges and other incidental charges to site etc., complete. as per standard specification (The Colour and shade of paint shall be got approved the departmental officers)
Painting two coats with Enamel paint of approved colour and quality including cost and conveyance of all materials and labour charges and other incidental charges to site etc., complete. as per standard specification
Brick work in CM 1:5 (one cement & Five Crushed Stone Sand (M- Sand)) using II class ground moulded bricks of size 9" X 43/8"X 2 3/4" including finishing, curing, etc., complete complying with standard specification - 100CFT
Supplying and fixing of Steel door and Window using ISA Sections and MS Sheet of approved quality including cost and conveyance of all materials and labour charges and other incidental charges to site etc., complete. as per standard specification
Paving the floor with colour and designed ceramic tiles 305mm x 305mm x 6mm of approved make, quality and colour in all floors over a base layer of cement mortar 1:3(one cement three sand) 20mm thick and laid straight alignment and pointed neatly with colour cement at the rate of 0.40kg/m2 laid without any air gap in the tiles neatly and fixing in position as per standard specifications and as directed by the departmental officer.
Weathering course in Brick jelly and lime concrete using broken brick jelly of size 20 mm uniform gauge in pure slacked lime ( no sand to be used ) the proportion of brick jelly to lime being 32:12.5 by volume laid over the RCC roof slab in a single layer of required design , slope and finished thickness by beating the concrete with wooden and beaters of approved pattern keeping the surface constantly wet by springing lime Jaggery water etc,. complete as per standard specification and as directed by the Engineer incharge.
Finishing the top of Roof with one course of machine pressed tiles of size ( 23x23x2 cm ) approved quality in C.M. 1:3 - 12 mm thick mixed with water proofing compoud confirming to IS @ 2 % by weight of cement used and the joints pointed neatly to full depth of tiles with the same cement mortar mixed with red oxide and water proofing compound including curing etc,. complete complying with Standard Specification
Wiring with 2x1.5 sqmm (22/0.3) PVC insulated SC.unsheathed Cu. Conductor of 1100 V grade in suitable PVC rigid pipe on wall and ceiling with PVC accessories and with TW switch box and 5A F.T. switch with painting of suitable Colourfor open PVC light point / fan point (For electronic regulator) (5 points per coil) SD 24
Wiring with 2x4 sqmm(56/0.3) PVC insulated SC unsheathed Cu.Conductor cable of 1100V grade in suitable pipe on wall and ceiling with PVC accessories with 150 mm x 100 mm x 63mm TW switch box for 15 A 3 pin non inter locking CS plug with painting of suitable colour, with continuous earth wire connection of 14 SWG TC wire for open PVC power plug point. SD 37
Supply and fixing of 32 Amps DP Switch of 500 V with metal clad with fuse and neutral (Side Handle) on suitable TW Board , with earth connection only SD 144
Earthing as per P.W.D standard with an earth electrode of 2 Mtr. Class 'B' GI pipe of dia not less than 32mm complete with necessary masonry work SD 234
Supply and fixing of TNEB meter Board suitable for 32A Single Phase service connection with 32A Fuse unit (500V) 32A neutral link and earth link (1" x 1/8" Copper flat) on TW plank of size 375mm x 300mm x 19mm with supporting TW reepers of 1" thick an either side with painting with suitable bolt and nuts for fixing the TW plank on wall with earth connection and inter connection with 7/20 PVC insulated copper wire from EB meter to fuse unit. SD 125
Supply and run of 4 of 4 sqmm (56/0.3) PVC insulated SC unsheathed Cu.Conductor of 1100V Grade in 25 mm GI Pipe (B Class) suitably bend at both ends with necessary angle iron upright and end supports for mains (SD 72)
Refilling as per IS specifications and as directed by the engineers for the following sizes in metres,as per drawing.
100mm Dia DI pipe
110mm Dia HDPE pipe
Supply & delivery of following sizes of HDPE PIPES confirming to IS 4984/2016 - PN10 Twad Sor 24-25 Pg No 14
110mm Dia HDPE pipe
Supply & delivery of following sizes DUCTILE IRON SOCKET/SPIGOT PIPES FOR CLASS K9 AS PER IS 8329/2000
100mm Dia DI pipe
Lowering pipes and specials to trench and laying to proper grade and alignment and as directed by the TWAD Officers Twad Sor 24-25 Pg No 171
100mm Dia DI pipe
110mm Dia HDPE pipe
Jointing Pipes and Specials by butt fusion welding / electro fusion welding joints using fusion equipment as per ISO 21307-2011 and as per IS 7634 (part-2) : 2012 including cost of hire charges for butt fusion equipment power supply arrangements etc., complete as per directed by TWAD Board Officers.Twad Sor 24-25 Pg No 184
100mm Dia DI pipe
110mm Dia HDPE pipe
Cutting P.V.C./HDPE rigid pipes and specials true to axis and finishing the ends complete.Twad Sor 24-25 Pg No 176
100mm Dia DI pipe
110mm Dia HDPE pipe
Barricading work (Where the lines are in narrow width of municipality area, busy streets like Market, Bus-stand and in the Highways etc.) for laying of pipe line using casurina poles at 1.50m center to center (8cm to 10cm dia. and 1.80m height) vertical with horizontal poles in two rows, painting the vertical poles in the road facing sides with ready mix paint, tying the vertical and horizontal poles with coir rope including supplying, delivery and fixing of GI sheet (0.90m x 0.8mm thick) in the horizontal poles and fixing 75mm dia. reflectors including earth work excavation for fixing vertical posts and finally removing and stacking the materials safely for further use etc., complete and as directed by TWAD Board officers.Twad Sor 24-25 Pg No 209
Testing of pipes for water supply with hydraulic testing equipment by filling with water (including cost of water @ Rs. 60/KL) and testing to recommended pressure in convenient stretches and attending the bursts if any occured during the test, excluding the cost of pipes but including other incidential and operational charges etc., complete for the following diametres of pipes.Twad Sor 24-25 Pg No 174
100mm Dia DI pipe
110mm Dia HDPE pipe
Supply , delivery and fixing of HDPE specials (lining and coated) at site etc., complete as directed by Engineer in charge.Twad Sor 24-25 Pg No 18
110mm Dia HDPE pipe-110mm deg bend
110mm Dia HDPE pipe-110mm deg Tee
Supply of DI Specials of approved quality including cost and conveyance of all materials and labour charges etc complete as per standard specification as per IS 9523 / 2000
100 mm - All socket
100 mm - aAll flange
100 mm MJCollar
End Cap
Labour charges for cutting of B.T road or WBM roads for laying of mains and as directed by Engineer in charge.Twad Sor 24-25 Pg No195
100 mm DI&110mm Dia HDPE PIPE
B.T. Roads (or) Maccadam road
Concrete Roads
Supply and delivery CI D/F SLUICE VALVE WITH CAP/ WHEEL AS PER IS 14846/2000 PN 1.0 WITH ISI MARKING AND WITH 5 YEARS WARRANTYIS specifications and as directed by the engineers.TWAD P.NO-57(2024-2025)
100mm Sluice Valve
10mm Di & 110mm Dia HDPE pipe
Construction of Valve Chamber in Brick work with CM 1:5 mix with RCC Slab 100 mm thick including cost and conveyance of all materials and labour charges to site etc., complete as per Standard specification
Size-1.00m x .90m chamber
Construction of Thrust blocks - with RCC M20 Grade concrete Earthwork - excavation and depositing on bank with an initial lead of 10 m and initial lift of 2 m in trenches (Hard stiff clay, stiff black cotton, hard red earth, shales, murram gravel, stoney earth and earth mixed with small boulders and hard gravelly soil) including all charges etc complete., complying with standard specification as directed by Corporation Engineers 'P.C.C 1:2:4 (one cement, two sand and four coarse aggregate) using Sulphate Resistant cement and 20 mm H.B.G stone, RCC M 20 grade using cement and 20 mm H.B.G stone including mixing concrete, laying, curing and compacting of concrete etc., complete and as directed by the Corporation Engineers. Refilling the trenches with suitable excavated earth available in layers of 150 mm thick, watering, ramming & consolidation complete as directed by the Corporation Engineer. Conveyance of excess earth to a distance not exceeding 5 km as directed by the Corporation Engineer including cost of loading, transportation and unloading charges etc
110mm HDPE pipe - 90 Deg Bend
110mm HDPE Pipe - 45 Deg Bend
110mm HDPE pipe - 22 Deg Bend
Supply and delivery of MS Kiosk of size 0.75m x 0.45m x 0.75m made up of MS angle of size 50mm x 50mmx 4mm alround covered with 16 gauge MS sheet and kiosk door made up of MS plates of size 25 mm x 3 mm including cutting, welding, grinding, locking arrangements and labour charges etc.,
SERVICE CONNECTION ACCESSORIES L.T. 1100V PVC ALUMINIUM ARMOURED UNDER GROUND CABLE WITH ISI MARK
31/2 core 25 sq.mm. PVC Armoured UG Cable
4 core 16 sq.mm. PVC Armoured UG Cable
Supply and delivery of Open well Submersible pump set conforming to IS 14220 /2002 and as amended thereafter and BEE 3 Star Rated capable of discharging the following duties due to all causes. The pump shall be with stainless steel shaft and dynamically balanced bronze mixed type impeller, CI FG 200 grade casing and brass screws and rotor shall be of copper rod as per IS 613/1984 with ISI mark. The pump suitable for installation in sump with 1.1KV grade 3 core suitable copper flat submersible cable to a length of 15m with necessary cable joints. The non-return valve located at the top of the pump in the discharge outlet connection is to be designed with minimum friction. The pump should be directly coupled to 2880 RPM, three phase, 50 Hz (±5), 415V+6% & 415V-15% squirrel cage induction motor suitable for DOL upto 5 HP, Fully Automatic Air break Star Delta up to 20 HP and Auto Transformer starter for above 20 HP starting and for continuous operation.
Proposed & Exisiting Open Well
Proposed & Exisiting Open Well
Proposed & Exisiting Sump
Labour charges for the erection of submersible pumpset in borewell/openwell including fixing and jointing submersible cable with proper clamps upto the starter to required depth and also fixing of riser pipes to the required depth valves erection clamps, pressure gauges upto the exterior wall of pump room and erection of panel board consisting of TPICN switches starter, Voltmeter, Ammeter, three pilot (indicating) lamps capacitor single phasing preventor, water level guard and laying and jointing the cables and twin earthing as per IE rules etc., complete and testing the pumpset and trail run for 10 days.
SUBBIAH ARUMUGAM (BID ID -1209671)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .