Providing internal and external Electrification to Construction of Hostel Block (Phase II) adjacent to Vasuki Ladies Hostel in Bharathiyar University Coimbatore.
2023_HE_351872_1
Vasukihostal_2023
Open Tender
Electrical Works
Lump-sum
180 days
Coimbatore
Please refer Tender documents.
7 documents required · 7 mandatory
₹0
₹56,000
Yes
7 Nov 2023
28 Jul 2023
18 Aug 2023
29 Jul 2023
17 Aug 2023
29 Jul 2023
Amount
Wiring with 2 x1.5 sq.mm. (22/0.3) PVC insulated single core unsheathed copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC ccessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate with continuous earth wire connection of 14 SWG TC wire and making good of the concealed portion with suitable colour for Concealed PVC Light point / fan point (for electronic regulator) (5 points / Coil) Higher End)
Wiring with 2 x1.5 sq.mm. (22/0.3) PVC insulated single core unsheathed copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate with continuous earth wire connection of 14 SWG TC wire and making good of the concealed portion with suitable colour for Concealed PVC Light point / fan point (for electronic regulator) (6 points / Coil) Higher End
Wiring with 3 x1.5 sq.mm. (22/0.3) PVC insulated single core unsheathed copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A two way module switch with module front plate with continuous earth wire connection of 14 SWG TC wire and making good of the concealed portion with suitable colour for Concealed PVC pipe Stair case Light point Higher End
Supply and fixing of single box type 4'20 W LED flu Fitting (Higher end) complete with electronic driver with TW round block on wall or ceiling with flu. LED Tube with PVC unsheathed leads from terminals to the fitting
Supply and fixing of single box type 4'20 W flu fitting complete with electronic driver (Philips /Crompton / Havells) with conduit pipe suspension from the ceiling with PVC unsheathed Copper leads from terminals to the fitting with LED tube.
Supply and fixing of 2x2 square type 36W LED 6500K Surface mounting type fitting (Higher end) Complete on wall or ceiling with PVC unloaded leads from terminal to the fitting
Supply and fixing of battorn holder with 9W LED lamp for BH point
Supply and fixing of WT bulk head fitting with guard (Higher end) suitable for 11W CFL lamp with CFL bulb
Supply and fixing of 1400 mm (56") sweep AC ceiling fan complete (Lower end) with 2 module 100W fan step regulator (Lower end) with 600mm down rod on the exisitng an clamp
Supply and fixing of 1200 mm (48") sweep AC ceiling fan complete (Higher end) with 2 module 100W fan step regulator (Higher end) with 600mm down rod on the existing an clamp
Supply and fixing of 375 mm (15") sweep (Heavy duty) AC exhaust fan complete without provision of hole in the wall
Supply and fixing of louver shutter arrangements for 375 mm (15") sweep (Heavy duty) AC exhaust fan
Supply and fixing of 3nos.6A two module 5 pin socket , 3 nos. 6A one module switch with module cover plate (plastic) on suitable module concealed Box (GI) in flush with wall with connections. Higher End
Supply and fixing of 1 no.6/16A two module socket, 1 no 16A one module switch with module cover plate (plastic) on suitable module concealed Box (GI ) in flush with wall with connections. Higher End
Supply and fixing of 16A flush type switch on suitable MS box covered with modular white cover plate for Room control switch
Supply and fixing of 32A DP MCB 10 KA in suitable sheet steel enclosure in flush with wall with earth connection (Legrand MDS)
Supply and fixing of 32A FP MCB 10 KA in suitable sheet steel enclosure in flush with wall with earth connection (Legrand MDS)
Supply and fixing of 8 way single pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 no.32A DP MCB switch as incoming and 6 Nos 6A to 32A SP MCB as outgoing in flush with wall with earth connection only. Higher End
Supply and fixing of 7 segment 4 way TPN MCB sheet steel distribution board (Higher end) with metal /acrylic door cover flush type /surface type fitted with busbars and neutral links with single / three phase MCB outgoings and seperate 4 way provision for accomodating one no. 4 pole incoming MCB / Isolator and another seperate 4 way provision for accomodating one no. 4 pole ELCB / RCD (totally 8 ways in one segment) (3x 4 ways in each segment) and seperate provision for MCB / Isolators (totally 12 nos.) for sub incomers in 3 segments with lable holder and provison for taking up cable for size not less than 35 sq.mm with the following in flush with wall with earth connection only. i. 63A 4P MCB - 1 No. i. 63A 4P 30 MA RCCB/ELCB - 1 No. i. 63A DP MCB isolator - 3 Nos. i. 6A to 32A SPMCB - 12 Nos.
Supply and fixing of 8 way Vertical Triple pole and neutral MCCB sheet steel enclosure distribution board (with MCCB incomer) with double door (metal door) with 1 no.160A 4P MCCB switch as incoming and 6 nos 63A 3P MCB, 2 nos. 32A TP MCB as outgoing with suitable cable end box in flush with wall with earth connection only. Higher End
Supply and fixing of 30W LED street light fitting with LED (Higher end) with 25 mm dia. GI pipe (class B) with 1 no. 25 mm GI bend complete on the existing post/ on wall with PVC unsheathed copper leads with MS clamps and with painting
Supply and Fixing of 3 Ph 4 way Vertical type MCB DB 10 KA with IP 43 protection Double door type DB (legrand) with 1No 63A 4P MCB 10 KA as incoming and 3 No's 32A TP MCB 10 KA and 3 No's 32A SP MCB 10 KA as outgoing in flush with wall and making good of the concealed portion with earth connection only. (Higher end) (Pump room)
Supply and Run of 2 of 2.5 sq.mm. (36/0.3) PVC insulated SC unsheathed copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with continuous earth wire connection of 14 SWG TC wire and making good of the concealed portion with suitable colour
Supply and run of 2 of 2.5 sq mm. (36/0.3) PVC insulated SC unsheathed Copper Conductor of 1100V Grade in suitable PVC rigid pipe concealed in wall and ceiling and making good of the concealed portion with painting of suitable colour
Supply and run of 2 of 4 sq mm (56/0.3) PVC insulated SC unsheathed Copper Conductor of 1100V Grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 14 SWG TC wire with and making good of the concealed portion with painting of suitable colour
Supply and run of 4 of 4 sq mm (56/0.3) PVC insulated SC unsheathed Copper Conductor of 1100V Grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 14 SWG TC wire with and making good of the concealed portion with painting of suitable colour
Supply and Run of 4 of 10 sq.mm. (140/0.3) PVC insulated SC unsheathed copper conductor of 1100 V grade in suitable PVC rigid pipe concealed in wall and ceiling with ontinuous earth wire connection by 4 sq.mm. PVC insulated SC unsheathed copper wire with painting of suitable olour
Supply and fixing of LT cable route indicator with suitable angle not less than 38mm x 38mm 6mm and 0.6mtr long excavation of earth to a depth of 0.6 mtr and concreting the ground level and making good of the ground as directed by the departmental officers
Supply and run of one of No.8 copper conductor for earth connection
Earthing as per the ISI specification with an earth electrode of 2.1 mt class 'B' GI pipe of dia not less than 40mm, with copper earth plate of size 125mmx50mmx6mm, with necessary funneling arrangements with necessary masonry work and with 38mm RCC cover slab for the brick masonry (
Supply and clamping of 3 1/2 X 95 sq mm PVC armoured LTUG cable on post or on wall with MS Clamps.
Supply and fixing of brass cable gland for 3 1/2 X 95 sqmm PVC LTUG armoured cable with earth connection
Supply and providing cable end termination of 3 1/2 X 95 sq mm PVC LTUG Aluminum armoured cable with necessary aluminium cable sockets by crimping etc. with electrical connection complete
supply and fixing of 65 mm dia. (2 -1/2") GI pipe (class B) of 6 metre length with 300mm x 300mm x 6mm MS base plate duly welded at the bottom with concreting with nstruction of masonary pedestal with suitable SMC box with door arrangement to house 6A SP MCB switch, 2/4 way connector on suitable hylem sheet and supply and fixing of 60W LED street light fitting with LED (Higher end) with 1 metre 32mm dia. GI pipe (class B) Complete with suitable MS clamps for LED steet light fitting and SMC box ith PVC unsheathed copper leads from SMC box to fitting and with painting of suitable colour
Supply and laying of 4 x 10 sq.mm PVC armoured LTUG cable in a trench to be excavated at a depth of 0.75 metre putting 0.15 mt. Layer of sand and covering the cable completely with bricks and sand and refilling the earth to make good
Supply and clamping of 4 x 10 sq mm PVC LTUGarmoured LTUG cable on post or on wall with MS Clamps
Supply and fixing of brass cable gland for 4 x 10 sq mm PVC armoured LTUG cable, with earthconnection
Supply and laying of 3 1/2 X 25 sq mm PVC armoured LTUG cable in a trench to be excavated at a depth of 0.75 metre putting 0.15 mt Layer of sand and covering the cable completely with bricks and sand and refilling the earth to make good
Supply and clamping of 3 1/2 X 25 sq mm PVC LTUGarmoured LTUG cable on post or on wall with MS Clamps
Supply and fixing of brass cable gland for 3 1/2 X 25 sq mm PVC armoured LTUG cable, with earth connection
Supply and providing cable end termination of 3 1/2 X 25 sq mm PVC LTUG Aluminum armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete
Sub switch Panel: Supply and Errection of 315A capacity dust and vermin proof cubical panel board made up of 16 SWG CRCA sheet steel with supply and fixing of the following interior mounting fuse switch with HRC fuses arrangement in two Horizontal rows with one switch over the other, with a central bus bar chamber and two ends one on each side next to the fuse switch chamber and cable alloy conforming to IE rules INCOMER: 315A FP switch disconnector fuse units interior only with HRC fuse Double Break Switch -1 Nos OUTGOING: 250A TPN switch disconnector fuse units interior only with HRC fuse Double Break Switch -3No 125A TPN switch disconnector fuse units interior only with HRC fuse Double Break Switch -6 Nos 63A TPN switch disconnector fuse units interior only with HRC fuse Double Break Switch -2 Nos L &T (All the TPN Switch should be Siemens with Front Handle) Suitable The bus bar chamber will consist of suitable size of tinned copper flat for phase and neutral buses on epoxy moulded bus insulated at proper and sufficient spacing between the buses as per IE Rules. This bus bar chamber should be segregated from the adjacent chamber by providing hylem sheet of suitable thickness as partisans. 2 Nos 25x3mm tinned copper flats should be provided all round the panel for earth bus. The fuse Switches should be connected with the phase and natural buses with suitable size of rigid copper flat/rod and each switch should be connected with the 2 Nos earth bus with 2 runs of No.8 SWG rigid Tinned copper rod with suitable lugs. Phase and neutral tinned buses should be tinned properly.
Supply and laying of 2 Run 3 1/2 X 120 sq mm PVC armoured LTUG cable in a trench excavated at a depth of 0.75 metre putting 0.15 mt Layer of sand and covering the cable completely with bricks and sand refilling the earth to make good
Supply and laying of 2 Run 3 1/2 X 120 sq mm PVC armoured LTUG cable in Suitable GI pipe to be excavated at a depth of 0.75 metre and refilling the earth to make good
Supply and clamping of 2 Run 3 1/2 X 120 sq mm PVC armoured LTUG cable on post or on wall with MS Clamps
Supply and fixing of brass cable gland for 3 1/2 X 120 sqmm PVC LTUG armoured cable with earth connection
Supply and providing cable end termination of 3 1/2 X 120 sq.mm PVC LTUG Aluminum armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete
Supply and fixing of 25x3mm copper flat with necessary clamp/ supports on wall / floor / ground for earth connection
Supply and fixing of Automatic Electrical water heater with copper container with glass wool/puf insulation with MS powder coated shell suitable for 35 liters capacity 230V/1000W (Racold / Venus)
Sub Total
T PAULKANNU & CO
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .