| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.0 CrAccepted-AOC | ₹37.0 Cr | L1 | Accepted-AOC L1 |
| 2 | L2₹40.7 CrRejected-Finance | ₹40.7 Cr | L2 | Rejected-Finance L2 |
| 3 | L3₹40.9 CrRejected-Finance | ₹40.9 Cr | L3 | Rejected-Finance L3 |
| 4 | L4₹41.5 CrRejected-Finance | ₹41.5 Cr | L4 | Rejected-Finance L4 |
| 5 | L5₹41.8 CrRejected-Finance | ₹41.8 Cr | L5 | Rejected-Finance L5 |
Tender Value
Refer Docs
EMD Value
₹57.6 L
Closing Date
30 Apr 2024, 3:00 pmClosed
G I WADHWA CHIEF EXECUTIVE
CCE R AND D WEST PUNE
Provision of Civil Works for MY 300 Mixer, Premix Storage, Hardware and Oxidizer Facilities at Acem Nasik
2024_DRDO_802786_1
CCEW/C8/80534/CIV/300MIX/ACEM
Open Tender
Civil Works
740 days
ACEM NASIK
Please refer Tender documents.
2 documents required · 2 mandatory
₹3,000
Yes
CCE R AND D WEST
₹57.6 L
Yes
2 Jul 2024
2 Apr 2024
1 May 2024
2 Apr 2024
30 Apr 2024
16 Apr 2024
3 Apr 2024 - 10 Apr 2024
Amount
SUBHEAD- I- SITE DEVELOPMENT
Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared.
SUBHEAD - II EARTH WORK AND EXCAVATION
Earth work in surface excavation not exceeding 30 cm in depth but exceeding 1.5 m in width as well as 10 sqm on plan including getting out and disposal of excavated earth upto 50 m and lift upto 1.5 m, as directed by Engineer-in- Charge:All kinds of soil.(No additional lift payment will be given for mechanical excavations)
Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. (No additional lift payment will be given for mechanical excavations) All kinds of soil
Excavation work by mechanical means (Hydraulic excavator)/ manual means in foundation trenches or drains (not exceeding 1.5m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soils as directed, within a lead of 50 m. (No additional lift payment will be given for mechanical excavations)
Ordinary rock
Hard rock (blasting prohibited)
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge.(No additional lift payment will be given for mechanical excavations) All kinds of soil .
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge. (No additional lift payment will be given for mechanical excavations)
Ordinary rock
Hard rock (blasting prohibited)
Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked materials.(Extra lift only for manual excavations as per IS:1200)
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.(5% voids to be deducted)
Banking excavated earth in layers not exceeding 20 cm in depth, breaking clods, watering, rolling each layer with ½ tonne roller, or wooden or steel rammers, and rolling every 3rd and top-most layer with power roller of minimum 8 tonnes and dressing up, in embankments for roads, flood banks, marginal banks, and guide banks etc., lead upto 50 m and lift upto 1.5 m :(5% voids to be deducted)
Extra for levelling & neatly dressing of disposed soil completely as directed by Engineer-in-charge.
Supply and filling of approved earth obtained from outside MD land for formation of sub base including spreading in layers not exceeding 200mm in thick,necessary watering,consolidation to the required level,gradient and camber with 8-10 Tonne road roller to achieve minimum of 95% proctor density including cost of excavation all as per specifications and drawings at all lead and lift and as directed by the Engineer.(Payment shall be made for consolidated quantity after deduction of 5% for voids.)
Supplying and filling in plinth with River sand / M-Sand under floors, including watering, ramming, consolidating and dressing complete
Credit For Hard Rock obtained from excavation
Supplying chemical emulsion in sealed containers including delivery as specified. Chlorpyriphos/Lindane emulsifiable concentrate of 20%
Diluting and injecting chemical emulsion for Pre & Post -CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) : Along external wall where the apron is not provided using chemical emulsion @ 7.5 litres / sqm of the vertical surface of the substructure to a depth of 300mm including excavation channel along the wall & rodding etc. complete: With Chlorpyriphos/Lindane E.C. 20% with 1% concentration
Treatment of soil under floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor. With Chlorpyriphos/Lindane E.C. 20% with 1% concentration.
PLAIN AND REINFORCED CEMENT CONCRETE WORK.
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources)
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level 1:3:6 (1 Cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources)
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources)
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement.
All works upto plinth level
Concrete of M25 grade with minimum cement content of 330 kg /cum
Concrete of M30grade with minimum cement content of 350 kg /cum
All works above plinth level upto floor V level
Concrete of M25 grade with minimum cement content of 330 kg /cum
Concrete of M30 grade with minimum cement content of 350 kg /cum
Add for using extra cement in the items of design mix over and above the specified cement content therein.
Extra for R.C.C./ B.M.C/ R.M.C. work above floor V(15 M) level for each four floors or part thereof.
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete (Below & above plinth & at all heights.Thermo-Mechanically Treated bars of grade Fe-500D or more.
Centering and shuttering including strutting, propping etc. and removal of form for
Foundations, footings, bases of columns, etc. for mass concrete
Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
Suspended floors, roofs, landings, balconies and access platform
Shelves (Cast in situ)
Lintels, beams, plinth beams, girders, bressumers and cantilevers
Columns, Pillars, Piers, Abutments, Posts and Struts
Stairs, (excluding landings) except spiral-staircases
Edges of slabs and breaks in floors and walls Under 20 cm wide
Weather shade, Chajjas, corbels etc., including edges
Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc., including cost of de-shuttering and decentering at all levels, over a height of 3.5 m, for every additional height of 1 metre or part thereof (Plan area to be measured). Suspended floors, roofs, landing, beams and balconies (Plan area to be measured)
Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand/ M-Sand, including necessary excavation, levelling & dressing & finishing the top smooth.
Brick edging 7cm wide 11.4 cm deep to plinth protection with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 including grouting with cement mortar 1:4 (1 cement : 4 fine sand / M-Sand ).
BRICK MASONRY WORK .
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand)
Providing and laying autoclaved aerated cement blocks masonry with 150mm/230mm/300 mm thick AAC blocks in super structure above plinth level up to floor 15mt heightl with RCC band at sill level and lintel level with approved block laying polymer modified adhesive mortar all complete as per direction of Engineer-in-Charge. (The payment of RCC band and reinforcement shall be made for seperately).
Extra for brick work / AAC block masonry / Tile brick masonry in superstructure above floor 15mt height, for each four floors or part thereof by mechanical means.
Half brick masonry with non modular fly ash bricks pf class designation 10,conforming to IS:12894,in super structure above plinth and upto floor V level. Cement Mortar 1:4 ( 1 cement : 4 coarse sand )
Extra for providing and placing in position 2 Nos 6mm dia. M.S. bars at every third course of half brick masonry.
PLASTERING AND SURFACE TREATMENT
Providing of 6mm cement plaster of mix in all surface with cement mortar 1:3 (1 cement : 3 fine sand / M-Sand ) at all levels
Providing of 12 mm cement plaster of mix in all surface with cement mortar 1:6 (1 cement : 6 fine sand / M-Sand ) at all levels.
15 mm cement plaster on the rough side of single or half brick wall.1:6(1 cement:6 coarse sand)
18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement : 5 coarse sand) and a top layer 6 mm thick cement plaster 1:3 (1 cement : 3 coarse sand) finished rough with sponge.
Extra for providing and mixing water proofing material in cement plaster work in proportion recommended by the manufacturers:
Extra for plastering exterior walls of height more than 10 m from ground level for every additional height of 3 m or part thereof.
Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections.
Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade :New work (two or more coats) over and including water thinnable priming coat with cement primer
White washing with lime to give an even shade :
Colour washing such as green, blue or buff to give an even shade : New work (two or more coats) with a base coat of white washing with lime
Finishing walls with Acrylic Smooth exterior paint of required shade : New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm)
Applying priming coat :
With ready mixed aluminium primer of approved brand and manufacture on resinous wood and plywood
With ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel galvanised iron/steel works
Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
Providing and applying two coats of fire retardant paint on cleaned wood / ply surface @ 3.5 sqm per litre per coat including preparation of base surface as per recommendations of manufacturer to make the surface fire retardant.
Providing and applying 12 mm thick (average) premixed formulated one coat gypsum lightweight plaster having additives and light weight aggregates as vermiculite/ perlite respectively conforming to IS: 2547 (Part - 1 & II) 1976, applied on hacked / uneven background such as bare brick/ block/ RCC work on walls & ceiling at all floors and locations, finished in smooth line and level etc. complete.
FLOORING
Providing and fixing 18mm thick gang saw cut mirror polished premoulded and polished machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size of approved shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 Cement : 4 coarse sand) with joints treated with white cement, mixed with matching pigment. epoxy touch ups, including rubbing, curing, moulding and polishing to edge to give high gloss finish etc. complete at all level Granite of any colour and shade Area of slab over 0.50sqm
Providing edge moulding to 18mm thick marble stone counters, Vanities etc. including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge. Granite work / Marble Work
Extra for fixing marble / granite stone over and above corresponding basic item, in facia and drops of width upto 150 mm with expoxy resin based adhesive including cleaning etc. complete.
Extra for providing opening of required size & shape for wash basin/kitchen sink in kitchen platform, vanity counter and similar location in marble/ Granite/ stone work, including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete.
Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete. 40 mm thick with 20 mm nominal size stone aggregate
62 mm thick cement concrete flooring with concrete hardener topping, under layer 50 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) and top layer 12mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate, 6mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacture’s specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete.
Cement plaster skirting up to 30 cm height, with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement. 18 mm thick
Providing and fixing aluminium strips in joints of terrazo/ cement concrete floors. 40 mm wide and 4 mm thick
Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) :25 mm thick
Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete
Extra for pre finished nosing in treads of steps of Kota stone/ sand stone slab.
Extra for Kota stone/ sand stone in treads of steps and risers using single length above normal size up to 2.00 metre.
Providing and laying rectified Glazed Ceramic floor tiles of size 300x300 mm or more (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in colours White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement: 4 Coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete
Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer?in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.Wall tile Size(300 x 450 mm)
Providing and laying Vitrified tiles in floor in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only . Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily. Double charge vitrified tile polished finish of size
Size of Tile 600X600 mm.
Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joint with white cement & matching pigments etc. complete. Double charge vitrified tile polished finish of any size
Providing & laying vaccum dewatered flooring 100-200mm thick with reinforced cement concrete using nominal mix of 1:1.5:3 (1cement :1.5 course sand :3 graded stone aggregate of 20mm nominal size) with reinforcement of 8mm dia at 150mm c/c both ways laid in alternate panel , channel formwork including levelling consolidation with vibrating table , withdrawel of excess water & finishing with compactor / power trowel sprinkling of cement , cutting grooves of size 4x15mm depth in early set concrete along the length of specified longitudinal and traverse joints (grooves spacing should not exceed 5m in either direction) using dimond point concrete saw , filling the grooves with approved with joint filler polysulphide sealent etc, complete all as per specification .(Reinft shall be measured separately.
Supply and fixing conductive flooring 615 x 615 x 2 mm thick tile bacteriostatic and fungistic in nature abrasion resistance homogeneously constructed product sliced from pressed vinyl block containing encapsulated conductive evenly distributed elements including surface levelling using uzine self levelling compounds,installing copper strips at every 2.0m grid and using uzine conductive adhesive with the following parameters and including 2 mm thick self levelling compound for sub floor-Make-Fosroc or equivalent.(As per manufacture specification)
DOOR WINDOW & WOOD WORK
Providing and fixing 2nd class teak wood plain lining tongued and grooved, including wooden plugs complete with necessary screws and priming coat on unexposed surface.40 mm thick
Providing & fixing mechanism for top hung sliding doors consist of roller with bracket,base plate,pins,washer spacer for bottom trolley and as per direction of engineer in charge. (cost for 2 roller & 2 bottom trolly in one set) (structural steel & wood work measured & paid separaterly)
Supplying, fitting & fixing fully glazed steel windows and ventilators & approved manufacture in single or composite units , both openable & fixing type as per IS:1038 & IS:1361 with all joints finished & butt welded including providing mullions , using 6mm thick wired glass fixed with aluminium & PVC gaskets etc complete with steel oxidised handels and peg stays as specified & approved .and shop coat primer.
a) Openable side hung shutters
b) Fixed glazed panels
Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters: 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws
Extra for cutting rebate in flush door shutters (Total area of the shutter to be measured).
Providing and fixing aluminium die cast body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 35 kg and door width upto 700 mm), with necessary accessories and screws etc. complete.
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) a) For fixed portion Powder coated aluminium (minimum thickness of powder coating 50 micron)
For shutters of doors, windows & ventilators including providing and fixing hinges / pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately.) Powder coated aluminium (minimum thickness of powder coating 50 micron)
Providing and fixing anodised aluminium grill (anodised transparent or dyed to required shade according to IS: 1868 with minimum anodic coating of grade AC 15) of approved design/pattern, with approved standard section and fixed to the existing window frame with C.P. brass/ stainless steel screws @ 200 mm centre to centre, including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodised aluminium standard section around the opening, all complete as per requirement and direction of Engineer?in-charge. (Only weight of grill to be measured for payment).
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):
With float glass panels of 5.0 mm thickness.
Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge. With stainless steel cover plate minimum 1.25 mm thickness
Providing and fixing aluminium sliding door bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc. complete :
Providing and fixing aluminium tower bolts ISI marked anodised ( anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade with necessary screws etc. complete:
Providing and fixing aluminium hanging floor door stopper ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade with necessary screws etc. complete. Twin rubber stopper
Providing and fixing of rubber nylon door buffer (dia of 40mm and 50mm long) on wall with rowl plug and screw.
Providing and fixing the following hardware fittings of approved make :a)Providing and fixing IS : 12817 marked stainless steel butt hinges with stainless steel screws etc. complete : i) Size 125 x 64 x 1.9 mm
Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete. Fixed to openings /wooden frames with rawl plugs screws etc.
Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of cross-section 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter of 30 mm thickness. The laminate shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat. Door frame laminate shall be 2mm thick and shall be filled with suitable wooden block in all the three legs. The frame shall be covered with fiber glass from all sides. M.S. stay shall be provided at the bottom to steady the frame.
30 mm thick Fiberglass Reinforced Plastic (F.R.P.) flush door shutter in different plain and wood finish made with fire retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate all around, with suitable wooden blocks inside at required places for fixing of fittings and polyurethane foam (PUF)/Polystyrene foam to be used as filler material throughout the hollow panel, casted monolithically with testing parameters of F.R.P. laminate conforming to table - 3 of IS: 14856, complete as per direction of Engineer-in charge.
STEEL WORK
Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete
Providing and fixing mild steel round holding down bolts with nuts and washer plates complete.
Steel work welded in built up sections/ framed work, including cutting, hoisting,fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required: In stringers, treads, landings etc. of stair cases, including use of chequered plate wherever required, all complete
Steel work welded in built up sections/ framed work, including cutting, hoisting,fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required: In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works
Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters. 80x1.25 mm M.S. laths with 1.25 mm thick top cover
Providing and fixing ball bearing for rolling shutters.
Extra for providing grilled rolling shutters manufactured out of 8 mm dia M.S. bar instead of laths as per design approved by Engineer-in- charge, (area of grill to be measured).
Extra for providing mechanical device chain and crank operation for operating rolling shutters. Exceeding 10.00 sqm and upto 16.80 sqm in the area
Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. Hot finished welded type tubes
ROOFING & WATER PROOFING
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes.
a) 110 mm diameter
b) 160 mm diameter
Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations:
a)Applying and grouting a slurry coat of neat cement using 2.75 kg/sqm. of cement admixed with water proofing compound conforming to IS:2645 and approved by Engineer - in- charge over the RCC slab including adjoining walls up to 300 mm height including cleaning the surface before treatment.
b)Laying cement concrete using broken bricks/brick bats 25 mm to 115 mm size(Brick to be used second class) with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS: 2645 and approved by Engineer - in- charge over 20mm thick layer of cement mortar of mix 1:5 (1 cement: 5 coarse sand) admixed with water proofing compound conforming to IS2645 and approved by Engineer - in- charge to required slope and treating similarly the adjoining walls up to 300 mm height including rounding of junctions of walls and slabs.
c)After two days of proper curing applying a second coat of cement slurry admixed with proprietary water proofing compound conforming to IS:2645 and approved by Engineer - in- charge .
d)Finishing the surface with 20 mm thick joint less cement mortar of mix 1:4 (1 cement : 4 coarse sand) admixed with water proofing compound conforming to IS:2645 and approved by Engineer - in- charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making of 300x300 mm square 3mm deep.
e)The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer-in-Charge.
With average thickness of 120 mm and minimum thickness at khurra as 65 mm.
Providing and fixing false ceiling with armstorng ceiling tiles'Fine fissured' with micro look size 600 x 600mm of approved colour . Suspension system shall be Armstrong exposed grid systems with 15mm wide T-section of approved said. Installation to comprise main runners spaced at 1200mm c/c securely fixed to the structural soffit by approved hanger at 1200mm maximum centres. The last hanger at the end of each main runner should not be greater than 450mm from adjacent wall. 600x600mm modules to be formed by fitting 600mm long flush fitting cross tees centrally between 1200mm cross tees , 4mm Galvanised annealeg iron wire with free straightened to be used for suspension & also including the cost of making opening for light fittings,grills,diffusesr,cut-out made with frame of primetre channels suitably fixed all complete as per drawings & specification & direction of the engineer incharge.
Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with :
12.5 mm thick tapered edge gypsum plain board conforming to IS: 2095- (Part I) :2011 (Board with BIS certification marks)
Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+ 0.05 %) total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required.
Providing and fixing precoated galvanised steel sheet roofing accessories 0.50 mm (+0.05 %) total coated thickness, Zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/ self tapping screws complete : Ridges plain (500 - 600mm)
Providing and fixing precoated galvanised steel sheet roofing accessories 0.50 mm (+0.05 %) total coated thickness, Zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/ self tapping screws complete : Gutter (600 mm over all girth)
SANITARY INSTALLATIONS
Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required:White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests.Euronics/Jaquar or equivalent
Supplying and fixing approved quality European water closet with FRP cistern set comprising of : ( a ) Star White glazed European water closet with wash down pattern of approved make with P or S trap fixed to floor with necessary teak wood plugs, CP brass screws, etc. ( b ) 10 ltrs. capacity PVC low level flushing cistern made of corrosive resistant materials fixed to wall with necessary brackets and screws, and plugs with matching chromium plated flush bend with float valve and flushing arrangements of slimline or equivalent. ( c ) 15 mm heavy quality flexible PVC inlet connection with brass hexagonal check nuts with washer at both ends. ( d ) Approved make plastic seat and cover to match the colour of water closet and CP hinges fixed to water closet. ( e ) 15 mm CP brass Angular stop cock fixed between GI outlet and PVC inlet.
Providing and fixing wash basin with C.I. brackets, 15mm C.P. brass pillar tap, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require with White vitreous china flat back wash basin size 550x400 mm with single 15 mm C.P. brass pillar tap, 15mm PVC connection pipe with angle valve , bottle trap, waste coupling & 2 CI brackets.Euronics/jaquar or equivalent
Providing and fixing white vitreous china flat back half stall urinal of size 580x380x350 mm with fittings, standard size C.P. brass flush pipe, CP Angle stop cock along with Urinal Spreader, 32mm dia waste fitting,waste pipe, including cutting and making good the walls and floors wherever required :
Providing and fixing 16mm thick stone slab with table rubbed, edges rounded and polished, fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as per direction of Engineer-in-charge and finished smooth. in Granite Stone of approved shade
Providing and fixing beveled edge mirror of superior glass of approved quality complete with 6mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.
Providing and fixing soap dish of approved quality including fixing with C.P. brass screws etc. complete.
Providing and fixing C.P. Brass towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fitting arrangement of approved quality colour and make. 600mm x 20mm size
Providing and fixing C.P. Brass towel ring 200 dia size complete with brackets fixed to wooden cleats with CP brass screws with concealed fitting arrangement of approved quality colour and make.
Providing and fixing C.P. brass toilet paper holder with concealed fitting arrangement of approved quality colour and make.
Providing and fixing 8 mm dia C.P. / S.S. Jet with flexible tube upto 1 metre long with S.S. triangular plate to Eureopean type W.C. of quality and make as approved by Engineer - in - charge.
Providing and fixing approved type SS Double coat hooks with concealed type screws.
Providing and fixing C.P.brass long body bib cock of approved quality conforming to IS standard and Weighing not less than 690 gms. 15 mm nominal bore.
Providing and fixing CP brass grating with frame of approved design including setting in floor with cement motor to match with floor finish as per architect requirement. a) Size 100 mm X 100 mm
Providing,fitting and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS:8931. 15 mm nominal bore
Supply, Installation, Testing & Commissioning of C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931, 15mm Nominal bore
INTERNAL WATER SUPPLY
Supply, Installation, Testing & Commissioning of Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge.
Concealed work, including cutting chases and making good the walls etc.
15 mm nominal outer dia Pipes
20 mm nominal outer dia Pipes
25 mm nominal outer dia Pipes
32 mm nominal outer dia Pipes
Providing and Fixing uPVC deep seal Nahani trap (Floor Trap) of deep seal of 50 mm P or S trap including provision for connecting pvc inlet fittings complete including cost of cutting and making good the walls and floors where ever required.
For 110mm inlet and 110mm outlet.
Supplying, fixing, testing & commissioning of PVC Floor Drain with frame complete in all respects.
110 x 63 mm Size
EXTERNAL SEWAGE DISPOSAL
Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m
All kinds of soil
Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia
Providing, laying and jointing glazed stoneware pipes class SP-1 with stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints etc. complete
110 mm diameter
150 mm diameter
Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round S.W. pipes including bed concrete as per standard design :
110 mm diameter S.W. pipe
150 mm diameter S.W. pipe
Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design:
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : (External)
150 mm dia. R.C.C. pipe
Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand (zone- III) : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand (zone- III) : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design
Inside size 60x60 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) with common burnt clay F.P.S. (non modular) bricks of class designation 50mm
Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) with common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Making soakpit 2.5m diameter 3.0meter deep with 45x45xcm dry brick honey comb shaft with brick of class desiganation 35 and SW drain pipe 100mm diameter,1.8m long complete as per standrd design with F.P.S bricks including filling back ballast of 50-80mm broken brick bats all around the honey comb shaft including finishing of 75mm thk precast concrete cover(1:2:4) and fixing of CI frame work with grating of size 455x610mm and wt of cover not less than 230KG.
Supply,lowering and installation of RC ready made hume pipe septic tank of 50 users capacity at suitable location as directed including providing CI 100 mm dia ventilating shaft of 1.8m length and cowl at top,sewer line connnections at inleet and outlet etc complete as per standard design and as directed.
Supplying, fixing, testing & commissioning of PVC Class- III (6 kg/cm2) pipe to IS:4985:2000 complete with fittings, cleanout plug,clamps and hinges including cutting and making good the walls and ceiling for waste pipes, bath wastes, overflow, kitchen equipment waste connections and condensate drainage including cutting of brick/RCC wall as required and making good the same as directed by the Engineer-in-charge.The quoated rate shall includes the supports like hanger supports, Grip bolts & Clamps in ceiling /wall for supporting etc.
TRAVERSE
Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.:All kinds of soil. (No additional lift payment will be given for mechanical excavations)
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge. (No additional lift payment will be given for mechanical excavations) All kinds of soil.
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge. (No additional lift payment will be given for mechanical excavations)
Ordinary rock
Hard rock (blasting prohibited)
Credit For Hard Rock obtained from excavation
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.(5% voids to be deducted)
Banking excavated earth in layers not exceeding 20 cm in depth, breaking clods, watering, rolling each layer with ½ tonne roller, or wooden or steel rammers, and rolling every 3rd and top-most layer with power roller of minimum 8 tonnes and dressing up, in embankments for roads, flood banks, marginal banks, and guide banks etc., lead upto 50 m and lift upto 1.5 m :(5% voids to be deducted)
Supply and filling of approved earth obtained from outside MD land for formation of sub base including spreading in layers not exceeding 200mm in thick,necessary watering,consolidation to the required level,gradient and camber with 8-10 Tonne road roller to achieve minimum of 95% proctor density including cost of excavation all as per specifications and drawings at all lead and lift and as directed by the Engineer.(Payment shall be made for consolidated quantity after deduction of 5% for voids.)
Extra for levelling & neatly dressing of disposed soil completely as directed by Engineer-in-charge.
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources)
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement.:
All works upto plinth level:
Concrete of M25 grade with minimum cement content of 330 kg /cum
All works above plinth level upto floor V level
Concrete of M25 grade with minimum cement content of 330 kg /cum
Add for using extra cement in the items of design mix over and above the specified cement content therein.
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete (Below & above plinth & at all heights.Thermo-Mechanically Treated bars of grade Fe-500D or more.
Centering and shuttering including strutting, propping etc. and removal of form for
Foundations, footings, bases of columns, etc. for mass concrete
Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
Lintels, beams, plinth beams, girders, bressumers and cantilevers
Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with :Cement mortar 1:6 (1 cement : 6 coarse sand)
Random rubble masonry with hard stone in superstructure and above plinth and upto floor five level, including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) at window sills, ceiling level and the like.Cement Mortar 1:6(1 Cement : 6 coarse sand)
Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.
In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works
Pointing on stone work with cement mortar 1:3 (1 cement : 3 fine sand) :Flush/ Ruled pointing
Providing and applying two or more coats of synthetic enamel paint of approved brand and shade including a coat of approved steel primer on steel surfaces.Two or more coats on new work
Supplying and fixing at site Angle iron post & strut of required size including bottom to be split and bent at right angle in opposite direction for 10 cm length and drilling holes upto 10 mm dia. etc. complete.
Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge.
Made of G.I. wire of dia 4 mm
Providing grass turfing over traverse earth filling including removal of weeds and other unwanted materials,providing antitermite treatment,adding cattle manure,mixing,placing,levelling,watering,removal of fresh growth if any after 15 days,fine dressing,levelling,supply and filling of good soil for arboriculture and maintenance for 03 month etc.complete
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. 110mm diameter
Providing & laying in position filler media consisting of pebbles (75mm & down), pea gravels,morrum etc .as per instruction of site engineer near weep holes.
ROAD/HARD STANDINGS ,AREA DEVELOPMENT & DRAINAGE
Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.:All kinds of soil. (No additional lift payment will be given for mechanical excavations)
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge. All kinds of soil.(No additional lift payment will be given for mechanical excavations)
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge. (No additional lift payment will be given for mechanical excavations)
Ordinary rock
Hard rock (blasting prohibited)
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.(5% voids to be deducted)
Banking excavated earth in layers not exceeding 20 cm in depth, breaking clods, watering, rolling each layer with ½ tonne roller, or wooden or steel rammers, and rolling every 3rd and top-most layer with power roller of minimum 8 tonnes and dressing up, in embankments for roads, flood banks, marginal banks, and guide banks etc., lead upto 50 m and lift upto 1.5 m :(5% voids to be deducted)
Supply and filling of approved earth obtained from outside MD land for formation of sub base including spreading in layers not exceeding 200mm in thick,necessary watering,consolidation to the required level,gradient and camber with 8-10 Tonne road roller to achieve minimum of 95% proctor density including cost of excavation all as per specifications and drawings at all lead and lift and as directed by the Engineer.(Payment shall be made for consolidated quantity after deduction of 5% for voids.)
Credit For Hard Rock obtained from excavation
Supplying and filling in plinth with River sand / M-Sand under floors, including watering, ramming, consolidating and dressing complete
Extra for levelling & neatly dressing of disposed soil completely as directed by Engineer-in-charge.
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources)
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:3:6 (1 Cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources)
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:2:4 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 20 mm nominal size derived from natural sources)
Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with :Cement mortar 1:6 (1 cement : 6 coarse sand)
Cement mortar 1:6 (1 cement : 6 coarse sand
Random rubble masonry with hard stone in superstructure and above plinth and upto floor five level, including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) at window sills, ceiling level and the like.Cement Mortar 1:6(1 Cement : 6 coarse sand)
15 mm cement plaster on the rough side of single or half brick wall.1:6(1 cement:6 coarse sand)
Pointing on stone work with cement mortar 1:3 (1 cement : 3 fine sand) :Flush/ Ruled pointing
Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 cm depth, dressing to camber and consolidating with road roller including making good the undulations etc. and re-rolling the sub grade and disposal of surplus earthwith lead upto 50 metres.
Providing, laying, spreading and compacting graded stone aggregate (size range 53 mm to 0.075 mm ) to wet mix macadam (WMM) specification including premixing the material with water at OMC in for all leads & lifts, laying in uniform layers with mechanical paverfinisher in sub- base / base course on well prepared surface and compacting with vibratory roller of 8 to 10 tonne capacity to achievethe desired density, complete as per specifications and directions of Engineer-in-Charge.
Providing and laying design mix cement concrete of M-30 grade, in roads/ taxi tracks/ runways, using cement content as per design mix, using coarse sand and graded stone aggregate of 40 mm nominal size in appropriate proportions as per approved & specified design criteria, providing dowel bars with sleeve/ tie bars wherever required, laying at site, spreading and compacting mechanically by using needle and surface vibrators, levelling to required slope/ camber, finishing with required texture, including steel form work with sturdy M.S. channel sections, curing, making provision for contraction/ expansion, construction & longitudinal joints (10 mm wide x 50 mm deep) by groove cutting machine, providing and filling joints with approved joint filler and sealants, complete all as per direction of Engineer-in-charge (Item of joint fillers, sealants, dowel bars with sleeve/ tie bars to be paid separately). Note:- Cement content considered in M-30 is @ 340 kg/cum. Excess/ less cement used as per design mix is payable/ recoverable separately.Cement concrete manufactured in automatic batching plant (RMC plant) i/c transportation to site in transit mixer
Providing and fixing pre-moulded joint filler in expansion joints of RCC roads / CC pavements after making the joints dust free with high pressure air jet cleaners, all complete as per direction of the Engineer-in-Charge. (Pre-moulded joint fillers shall be made of bitumen hot sealing compound impregnated fibre board having impregnation more than 35%, conforming to IS:1838 for fibre board and IS: 1834 for hot sealing bitumen compound grade A.)
Providing and filling in position rubberized bitumen hot sealing compound for sealing of expansion joints in roads / pavements all complete as per direction of the Engineer-in-Charge. Using grade 'A' sealing compound conforming to IS: 1834.
Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge. 80 mm thick C.C. paver block of M-30 grade with approved color design and pattern.
80 mm thick C.C. paver block of M-30 grade with approved color design and pattern
Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 40 mm nominal size) in pavements, laid to required slope and camber in panels as required including consolidation finishing and tamping complete.
Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :
300 mm dia RCC pipes.
450 mm dia RCC pipes.
600 mm dia RCC pipes.
900 mm dia RCC pipes.
ARBORICULTURE/LANDSCAPING WORK
SHRUBS. Digging of pits of size 0.60 x 0.60 x 0.60m in soft rock / murrum and refilling with good soil and well decomposed cattle manure in 2:1 ratio. Supply and planting of approved species of healthy, grown up saplings with good root system and minimum 2 ft height from ground.
HEGDES. Supply of Hedge plant (minimum 1 ft Ht) Transportation to site excavation of beds of size 0.45 x 0.45 x 0.5m deep . Filling pits with prepared manure soil ratio (1:3) by volume flooding with water and dressing including removal of surplus earth if any for all leads and lifts planting replacement of any dead sick plants in this period (07 plants per RM) as per requirement and instruction of Engineer - in - Charge, including one month maintenance period.
GROUND COVER. Digging upto 0.3m, refilling with agriculture soil and cattle manure in 4:1 ratio. Provision of ant termite treatment at plantation time. Supply and planting of healthy grown up plant material(Wedelia, Verbena, lantana etc.) Maintenance includes regular watering. deweeding, manuring with cattle manure and fertilizer, Pruning, trimming and spraying of insecticides and fungicides as and when required for a period of ONE Month.
Supply of indoor potted plants incl FRP Planters (Areca palms / Aerocaria / Dracaena/ Money Plant Croton / Aglonemia or equivalent (10 inch pots).
BRICK EDGING. Supply and fixing of good quality in bricks 1:6 cement and sand mortar along with the lawn and landscaping works in double.
INTERNAL ELECTRIFICATION ,POWER WIRING, FLP FIXTURE & CABLING
Point wiring for light points, fan points, exhaust fan points, 6A plug and socket with 2 runs of 1.5 Sq. mm FR PVC insulated, multistranded, copper wire of 1100V grade laid in and including 25 mm dia. heavy gauge FR PVC conduit in concealed in ceiling / walls conforming to IS 732 including one run of 1.5 sq.mm FR PVC insulated, multistranded, copper earth wire of 1100V grade including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, electronic fan regulator etc. (Including sub main wiring of 2 runs of 2.5 sq.mm & 1 x 1.5 sq.mm FR PVC insulated, multistranded, copper wire of 1100V grade in 25 mm dia heavy gauge PVC conduit with conduit accessories etc. complete).
One light point controlled by one 6A switch
Two light point controlled by one 6A switch
Three light points controlled by One 6A switch
Four light points controlled by One 6A switch
Five light points controlled by One 6A switch
Six light points controlled by One 6A switch
One exhaust fan point controlled by one 6A switch with 6A rated ceiling rose
One 3 pin 6A socket controlled by one 6A switch (Dependent)
One Ceiling Fan point controlled by one 6A switch with regulator
Wiring for 250 volts single phase and neutral 32 amps metal clad industrial 3 pin socket outlet (for split AC) with 32 amps double pole MCB in a metal enclosure of approved size and design with interlocked rotary switch with 4 sq.mm PVC insulated copper conductor 1100 volts grade stranded flexible FRLSH wires in concealed or surface mounted 25 mm dia 2mm FRLSH PVC conduit (Black colour), in 1.6 mm thick GI boxes with grid plates and earthing the third pin of socket outlet with 4 Sq. mm PVC insulated copper conductor stranded flexible FRLSH wire. Recess conduiting shall include the cost of chase cutting (By machine only no manual method),hooks to be support the conduit and back filling with cement mortar 1:3 mix. complete as per specifications and as required. All the circuit must be dressed with circuit identification tags.
Wiring for 250 volts single phase and neutral 32 amps metal clad industrial 3 pin socket outlet (for split AC) with 32 amps double pole MCB in a metal enclosure of approved size and design with interlocked rotary switch with 4 sq.mm PVC insulated copper conductor 1100 volts grade stranded flexible FRLSH wires in concealed or surface mounted 25 mm dia 2mm FRLSH PVC conduit (Black colour), in 1.6 mm thick GI boxes with grid plates and earthing the third pin of socket outlet with 4 Sq. mm PVC insulated copper conductor stranded flexible FRLSH wire. TE type encloser to be considered. Recess conduiting shall include the cost of chase cutting (By machine only no manual method),hooks to be support the conduit and back filling with cement mortar 1:3 mix. complete as per specifications and as required. All the circuit must be dressed with circuit identification tags.
METAL CLAD POWER SOCKETS
Normal Type
Supply and wiring for 6A Socket outlet with 2runs of 1.5sq.mm FR insulated multistranded copper conductor wire and 1run of 1.5 sq.mm earth wire laid in and including heavy gauge 25mm dia PVC conduit concealed in wall/ceiling along with required accessories, supply and fixing of 6A 3 pin modular type socket with switch in anodised GI box and front plate complete with fixing accessories including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, etc. as required. (Independent)
Supply, installation, testing and commissioning of 6 / 16A, 5 pin shuttered type socket controlled by one 16A modular switch of combination type with indication lamp including wiring with 2runs of 2.5sq.mm FR insulated multistranded copper conductor wire and 1run of 2.5 sq.mm earth wire laid in and including heavy gauge 25mm dia PVC conduit concealed in wall / ceiling along with required accessories from DB to socket, including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch, socket and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, etc. complete as required. (Independent)
Supply, installation, testing and commissioning of factory made 20A, metal clad socket outlet controlled by 20A, 10kA, SP MCB, in and including MS painted box in concealed manner of adequate sizes including plug top with necessary accessories including wiring with 2runs of 4.0sq.mm FR insulated multistranded copper conductor wire and 1run of 2.5 sq.mm earth wire laid in and including heavy gauge 25mm dia PVC conduit concealed in wall / ceiling along with required accessories from DB to socket, including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch, socket and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, etc. complete as required. etc. complete as required.
Supply, installation, testing and commissioning of factory made 32A, 3Phase+N+E, socket outlet controlled by 32A, 4P MCB in and including MS painted box in concealed/surface manner of adequate sizes including plug top with necessary accessories. from DB to socket, including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch, socket and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, etc. complete as required. etc. complete as required.
Supply, installation, testing and commissioning of factory made 63A, 3Phase+N+E, socket outlet controlled by 63A, 4P MCB in and including MS painted box in concealed/surface manner of adequate sizes including plug top with necessary accessories. from DB to socket, including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch, socket and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, etc. complete as required. etc. complete as required.
Totally Enclosed Type (TE)
Supply and wiring for 6A Socket outlet with 2runs of 1.5sq.mm FR insulated multistranded copper conductor wire and 1run of 1.5 sq.mm earth wire laid in and including heavy gauge 25mm dia PVC conduit concealed in wall/ceiling along with required accessories, supply and fixing of 6A 3 pin modular type socket with switch in anodised GI box and front plate complete with fixing accessories including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, etc. as required. (TE Type)
Supply, installation, testing and commissioning of 6 / 16A, 5 pin shuttered type socket controlled by one 16A modular switch of combination type with indication lamp including wiring with 2runs of 2.5sq.mm FR insulated multistranded copper conductor wire and 1run of 2.5 sq.mm earth wire laid in and including heavy gauge 25mm dia PVC conduit concealed in wall / ceiling along with required accessories from DB to socket, including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch, socket and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, etc. complete as required. (TE Type)
Supply, installation, testing and commissioning of factory made 20A, metal clad socket outlet controlled by 20A, 10kA, SP MCB, in and including MS painted box in concealed manner of adequate sizes including plug top with necessary accessories including wiring with 2runs of 4.0sq.mm FR insulated multistranded copper conductor wire and 1run of 2.5 sq.mm earth wire laid in and including heavy gauge 25mm dia PVC conduit concealed in wall / ceiling along with required accessories from DB to socket, including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch, socket and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, etc. complete as required. etc. complete as required.(TE Type)
Supply, installation, testing and commissioning of factory made 32A, 3Phase+N+E, socket outlet controlled by 32A, 4P MCB in and including MS painted box in concealed/surface manner of adequate sizes including plug top with necessary accessories from DB to socket, including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch, socket and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, etc. complete as required. etc. complete as required. (TE Type)
Supply, installation, testing and commissioning of factory made 63A, 3Phase+N+E, socket outlet controlled by 63A, 4P MCB in and including MS painted box in concealed/surface manner of adequate sizes including plug top with necessary accessories. The wiring with 4runs s from DB to socket, including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch, socket and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, etc. complete as required. etc. complete as required. (TE Type)
Electrical Fitting & Fixture
Normal Type
Supply, Installation & testing of 1200mm dia, High speed Ceiling fan suitable for suitable for single phase 230/240V, AC Supply complete with all accessories etc complete as required.
Supply, Installation & testing of 380mm 900 RPM Heavy Duty Exhaust fan ((Toilet) suitable for use on single phase, 230 volt, 50Hz AC supply complete with all accessories as required
Supply, installation, testing and commissioning of following light fittings complete with low loss electronic ballast, lamp holder, electrical connections by providing 3C x 1.5 sqmm Cu. multistranded flexible wires, suspended hanger, fixing & mounting accessories. All the fittings to be supplied with rated power lamps/CFL/LED etc., complete.
1x20W, LED surface and wall mounted LED batten with aluminum housing & integrated electronic driver having 100Lumen/watt output
1x40W, LED surface and wall mounted LED batten with aluminum housing & integrated electronic driver having 100Lumen/watt output
2x40W, LED surface and wall mounted LED batten with aluminum housing & integrated electronic driver having 100Lumen/watt output
9W, warm white, wall mounted LED batten with polycarbonate housing & integrated electronic driver,having 840 Lumen output
Bulk head LED for 10 watt, IP-66, surface mounted light
80W, LED Suspended mounted Highbay light with with PDC housing suitable for ceiling (Surface/Suspended) mounting with system efficacy upto 150 lm/W, indoor type, IP-65.
Total Enclosed Type (TE)
Supply, Installation & testing of 400mm dia, High Wall nounted fan suitable for suitable for single phase 230/240V, AC Supply complete with all accessories etc complete as required. The fixture shall be with totally enclosed.
Supply, Installation & testing of 750mm dia, High Bracket Industrial Type fan suitable for suitable for single phase 230/240V, AC Supply complete with all accessories etc complete as required. The fixture shall be with totally enclosed
Supply, installation, testing and commissioning of following light fittings complete with low loss electronic ballast, lamp holder, electrical connections by providing 3C x 1.5 sqmm Cu. multistranded flexible wires, suspended hanger, fixing & mounting accessories. All the fittings to be supplied with rated power lamps/CFL/LED etc., complete. The supplier has to be considered tight sealed encosure in all fixture.
1x36W, LED surface and wall mounted LED batten with aluminum housing & integrated electronic driver having 100Lumen/watt output similar / equivalent to Make : The fixture shall be with totally enclosed.
2x36W, LED surface and wall mounted LED batten with aluminum housing & integrated electronic driver having 100Lumen/watt output similar / equivalent to Make : The fixture shall be with totally enclosed.
80W, LED Suspended mounted Highbay light with with PDC housing suitable for ceiling (Surface/Suspended) mounting with system efficacy upto 150 lm/W, indoor type, IP-65. The fixture shall be with totally enclosed. similar / equivalent to Make :
POWER WIRING
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
2 runs of 2.5 Sq.mm wires with 1 run of 1.5 Sq.mm in 25mm dia Conduit
2 runs of 4 Sq.mm wires with 1 run of 2.5 Sq.mm in 25mm dia Conduit
Cable Trays
Supply and fixing of following size GI peroforated/Ladder cable tray made out of 2mm thick MS sheet and the tray covered with 2mm thick MS cover including MS supports, Tee, bend, reducer for fixing the tray, anchor fasteners and including 2runs of 25 x 6mm GI strip along with cable tray etc., complete as required.
100mm W x 40mm H (1.6 mm)
150mm W x 40mm H
300mm W x 50mm H
450mm W x 50mm H - Ladder Type
600mm W x 75mm H - Ladder Type
Providing, laying and fixing 50 mm dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep) and re-filling etc. as required
Providing, laying and fixing 80 mm dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep) and re-filling etc. as required
Wiring for FLP Fixtures
Supply and wiring for 6A Socket outlet with 3core of 1.5sq.mm FRLS insulated multistranded copper conductor cable laid in and including heavy gauge 25mm dia PVC conduit concealed in wall/ceiling along with required accessories, supply and fixing of 6A 3 pin modular type socket with switch in anodised GI box and front plate complete with fixing accessories including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, etc. as required. (FLP Type). All the following items shall be FLP type with all the protections and accessories as per the FLP requirements.
Supply, installation, testing and commissioning of 6/16A, 3 pin shuttered type socket controlled by one 16A modular switch of combination type with indication lamp including wiring with 3core of 2.5sq.mm FRLS insulated multistranded copper conductor cable laid in and including heavy gauge 25mm dia PVC conduit concealed in wall / ceiling along with required accessories from DB to socket, including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch, socket and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, etc. complete as required. (FLP Type). All the following items shall be FLP type with all the protections and accessories as per the FLP requirements.
Supply, installation, testing and commissioning of 20A, 3 pin shuttered type socket controlled by one 16A modular switch of combination type with indication lamp including wiring with 3core of 4sq.mm FRLS insulated multistranded copper conductor cable laid in and including heavy gauge 25mm dia PVC conduit concealed in wall / ceiling along with required accessories from DB to socket, including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch, socket and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, etc. complete as required. (FLP Type). All the following items shall be FLP type with all the protections and accessories as per the FLP requirements.
Supply, installation, testing and commissioning of 20A, 5 pin shuttered type socket controlled by one 16A modular switch of combination type with indication lamp including wiring with 3core of 4sq.mm + 2 core of 4sq. mm FRLS insulated multistranded copper conductor cable laid in and including heavy gauge 25mm dia PVC conduit concealed in wall / ceiling along with required accessories from DB to socket, including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch, socket and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, etc. complete as required. (FLP Type). All the following items shall be FLP type with all the protections and accessories as per the FLP requirements.
Supply, installation, testing and commissioning of 32A, 5 pin shuttered type socket controlled by one 32A modular switch of combination type with indication lamp including wiring with 3core of 6sq.mm + 2 core of 6sq. mm FRLS insulated multistranded copper conductor cable laid in and including heavy gauge 25mm dia PVC conduit concealed in wall / ceiling along with required accessories from DB to socket, including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch, socket and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, etc. complete as required. (FLP Type). All the following items shall be FLP type with all the protections and accessories as per the FLP requirements.
Supply, installation, testing and commissioning of 63A, 5 pin shuttered type socket controlled by one 63A modular switch of combination type with indication lamp including wiring with 3core of 10sq.mm + 2 core of 10sq. mm FRLS insulated multistranded copper conductor cable laid in and including heavy gauge 32mm dia PVC conduit concealed in wall / ceiling along with required accessories from DB to socket, including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch, socket and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, etc. complete as required. (FLP Type). All the following items shall be FLP type with all the protections and accessories as per the FLP requirements.
Supply and Wiring with the following size 1100V grade XLPE insulated Aluminium / Copper armoured conductor cables with FRLS outer sheath conforming to IS 7098 Part II on wall / ceiling / tray / pipe sleeves and excavated trenches including all accessories such as Flame proof junction boxes etc complete as required.
3C x 1.5sq.mm armoured (Copper)
3C x 2.5sq.mm armoured (Copper)
Provding end terminations for the cable specified below with Double compression type gland, Bi-Metalic lugs using crimping tool, Insulation tape, Identification tags etc. including end termination.
3C x 1.5sq.mm armoured (Copper)
3C x 2.5sq.mm armoured (Copper)
3C x 4.0sq.mm armoured (Copper)
5C x 4.0sq.mm armoured (Copper)
5C x 6.0sq.mm armoured (Copper)
5C x 10.0sq.mm armoured (Copper)
FLP FIXTURES & CABLING
FLP Fixtures
Supply, Installation, testing and commissioning of following FLP/Well Glass fixtures made out of Cast Aluminium alloy, toughened clear glass cemented into a bazel ring which is bolted to the body, and lamp holder with Insulator mounted on a bush plate and secured with screws. The body shall be finished with epoxy Grey stove enamelled outside and White inside. The fixture shall be inclusive of all accessories including lamp & control gear box containing Choke, condencer & igniter suitable for Lamp . All the following items shall be FLP type with all the protections and accessories as per the FLP requirements.
FLP LED Light Fixture (Box Type) for 36 watt with all fixing accessories,
FLP LED Light Fixture for 2x40 watt with all fixing accessories,
Supply, installation of 8 mm dia, MS hook in the slab for mounting FLP Well glass fixtures
Supply, installation, testing and commissioning of following rating FLP socket / switch Fuse units in FLP enclosure and plug top on angel iron frame work & other MS support structure complete with all fixing accessories, hardware etc. complete as required The FLP Sockets / SFUs shall be confirming to IP-65.
20A Single Phase 250V Grade FLP Socket with switch
20A Three Phase 500V Grade FLP Socket with switch
32A Three Phase 500V Grade FLP Socket with switch
63A Three Phase 500V Grade FLP Socket with switch
Supply & installation of FLP 4way Junction box of size 125 dia x 100mm depth suitable for 3/4" dia cable entries
Supply & installation of FLP 4way Junction box of size 200 dia x 150mm depth suitable for 1.25" dia cable entries
63A Three Phase 415V Grade FLP Switch Fuse Unit
32A Three Phase 415V Grade FLP Switch Fuse Unit
Supply, Installation, testing & commissioning of 305mm Sweep FLP Grade Exhaust fans with gravity louvers shutters including electrical connection, all fixing accessories/ installation materials as required, complete.
Supply, installation, testing and commissioning of 380mm sweep FLP Grade Wall Mounted fans including electrical connection, all fixing accessories/ installation materials as required, complete.
Supply, installation, testing and commissioning of 760mm sweep FLP Grade Wall Mounted fans including electrical connection, all fixing accessories/ installation materials as required, complete.
Supply, installation, testing and commissioning of SPN / TPN MCB Double Door Distribution Boards dust, water proof and vermin protected and rated for AC supply operation as per specifications and required capacity Neutral bar and Earth terminal complete as required and installed in flush with wall including cutting , chasing of wall make them good after fixing and other required civil works, all fixing materials required. MCBs shall conform to IS : 8828 and RCBO shall conform to IS : 12640. All MCBs shall be C Curve.
FLP Type DB
8 Way TPN MCB DB - FLP Type with 63A, 4P MCB, 3 nos 30mA DPole RCCB as incomer and 24 nos. 6 to 32A SP MCBs as outgoings as per SLD.
6 Way TPN MCB DB - FLP Type with 40A, 4P MCB, 3 nos 30mA DPole RCCB as incomer and 18 nos. 6 to 32A SP MCBs as outgoings as per SLD.
4 Way TPN MCB DB - FLP Type with 32A, 4P MCB, 3 nos 30mA DPole RCCB as incomer and 12 nos. 6 to 32A SP MCBs as outgoings as per SLD.
8 Way SPN MCB DB (Total 10way) - FLP Type with 40A, 30mA 2Pole RCBO as incomer and 8 nos. 6 to 32A SP MCBs as outgoings as per SLD.
6 Way SPN MCB DB (Total 8way) - FLP Type with 32A, 30mA 2Pole RCBO as incomer and 4 nos. 6 to 32A SP MCBs as outgoings as per SLD.
Normal Type DB
8 Way TPN MCB DB - Normal Type with 63A, 4P MCB, 3 nos 30mA DPole RCCB as incomer and 24 nos. 6 to 32A SP MCBs as outgoings as per SLD.
6 Way TPN MCB DB -Normal Type with 40A, 4P MCB, 3 nos 30mA DPole RCCB as incomer and 18 nos. 6 to 32A SP MCBs as outgoings as per SLD.
4 Way TPN MCB DB - Normal Type with 32A, 4P MCB, 3 nos 30mA DPole RCCB as incomer and 12 nos. 6 to 32A SP MCBs as outgoings as per SLD.
8 Way SPN MCB DB (Total 10way) - Normal Type with 40A, 30mA 2Pole RCBO as incomer and 8 nos. 6 to 32A SP MCBs as outgoings as per SLD.
6 Way SPN MCB DB (Total 8way) - Normal Type with 32A, 30mA 2Pole RCBO as incomer and 4 nos. 6 to 32A SP MCBs as outgoings as per SLD.
Totally Enclosed Type
6 Way TPN MCB DB - TE Type with 40A, 4P MCB, 3 nos 30mA DPole RCCB as incomer and 4 nos. 6 to 32A SP MCBs as outgoings as per SLD.
4 Way TPN MCB DB - TE Type with 32A, 4P MCB, 3 nos 30mA DPole RCCB as incomer and 12 nos. 6 to 32A SP MCBs as outgoings as per SLD.
8 Way SPN MCB DB (Total 10way) - TE Type with 40A, 30mA 2Pole RCBO as incomer and 8 nos. 6 to 32A SP MCBs as outgoings as per SLD.
6 Way SPN MCB DB (Total 8way) - TE Type with 32A, 30mA 2Pole RCBO as incomer and 6 nos. 6 to 32A SP MCBs as outgoings as per SLD.
MV Panels
Supply, installation, Testing and Commissioning of 3 phase and Neutral 415V 4 wire Free Standing Floor mounted MV panel made out of 14 SWG MS sheet with partition after seven tank process and painting with Epoxy powder coating. The panel shall consist of suitable rating TPN Aluminium busbar (at the rating of 0.8A/Sq.mm) supported with DMC/ SMC barriers and colour coded with Heat shrinkable sleeves. The Metering shall be provided as specified.
Tinned copper earth bus shall be provided through out the length of each board.
Enough space to be considered for cable alley for both incoming and outgoings.
LED lights, space heater and thermosate to be considered at each cable alley.
All the control wiring for HVAC panel & electrical required to operate the system shall be inclussive.
ll MCCB’s shall be with thermal magnetic releases up to and including 250 amps and miroprocessor based above 250 amps capacity, unless specified otherwise with inbuilt earth fault.
All hinged door shall be earthed through 4.0 sq mm tinned braided copper wire.
All the panels shall be as per BOQ and SLD. Kindly check before final offer.
Protection Releases Microprocessor based (PRMB) & Thermal magnetic (PRTM) shall be as describe below .
Fault current wherever mentioned shall be Ics value (Ics = 100% Icu) for all breaker.
Internal wiring of panel shall be with size 2.5sqmm Flexible FRLSH Copper Conductor for CT circuit and control wiring with 1.5 sqmm.
All the makes shall be as per approved make list only.
Note:The capacitor panel shall also stipulate the following
All the capacitors shall be suitable for 525 V
Necessary control and firing card with proper wiring and lugs of the required rating to be provided.
Heavy duty exhaust fans to be provided for cooling Contactor
LED indication for number of capacitor banks ‘ON & Power Factor lagging or leading as per SLD.
The APFC shall be protected from following
ON, OFF indication and Push button to be provided as per SLD.
* over-voltage & voltage unbalance
* Over temperature-system should be in standby mode and automatically restart after above condition restored.
* Total Harmonic Distortion
* The capacitor panel shall be as per specifications.
Emergency push button and breaker control switch as per SLD
Supply, installation, testing & commissioning of MDB-11C_New Hardware Block panel as described below :
INCOMER
1 No. 2000A 4 pole microprocessor based MDO, ACB, 40kA with integral protection, anti pumping protection microprocessor based O/C, S/C & E/F protection (LSIG) with ET6V releases and Class-C transient voltage surge suppression device suitable for 3 phases as per specifications.
1 set of 2000/5A, 15 VA, class-1 CTs for APFC relay
One (1) Set of SPD TYPE-2
Under voltage and over voltage protection to be considered in ACB.
METERING & INDICATION
1 set of R,Y,B phase indicating lamps
1 Set- of ON/OFF/TRIP indicating lamps.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (EM-6400 of Conzerv or equivalent).
BUS-BAR
1 Set of 2500A TPN Aluminium Bus Bar with colour coded heat shrimkable PVC Sleeves
OUTGOINGS
All MCCB & MCB outgoing feeder shall be provided with ON/OFF indication lamps. The Number of outgoing feeders shall be as follows and as per SLD:-
21 No. 63A TPN MCB
4 Nos. 40A TPN MCB
29 Nos. 32A TPN MCB
3 Nos. 400A TPN MCCB
6 Nos. 125A TPN MCCB
2 Nos. 630A TPN MCCB
CAPACITOR PANEL AS PER SLD. (300 kVAR)
INCOMER, METERING & INDICATION
1 Nos. 630A TPN MCCB (35 KA)
1 No. 8 step-Microprocessor APFC controller/Relay shall continuously monitoring all three phases and LCD displays for various Electrical Parameters like voltage, input current, capacitive current, KVA demand, KW, Power Factor, self diagnostic error code indication with printout facility of the above with RS 232/RS 485 port. Controller should mounted on the front side of the panel Capacitor bank having 3 phase MPP based mix dieelectric low loss ISI marked power capacitor.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (EM-6400 of Conzerv or equivalent).
One (1) set 3 Nos. CT's of ratio 630/5A,15VA, Class 1.0 as required.
Terminals to receive XLPE insulated Aluminium cables
BUS-BAR
1 Set of 800A TPN Aluminium Bus Bar with colour coded PVC heat shinkable Sleeves
METERING & INDICATION
1 set of R,Y,B indicating lamps as per SLD each with 3 nos. 2A SP MCBs.
1 Set- of ON/OFF indicating lamps.
OUTGOINGS
2 no 200 amp 35kA TP MCCB complete each with the following for 2x100 kVAR capacitor bank.
3 no 100 amp 35kA TP MCCB complete each with the following for 2x50 kVAR capacitor bank.
2 nos of 40 amp 35kA TP MCCB complete each with the following for 3x10 kVAR capacitor bank.
1 no 20 amp 35kA TP MCCB complete each with the following for 2x5 kVAR capacitor bank.
3 pole capacitor grade contactor suitable for automatic switching of 100,25,10 & 5 kVAR capacitor bank
Indicating lamp to give status of the circuit as per SLD
Manual/auto changeover switch
Hermetically sealed metallized polypropylene (MPP type) capacitor units complete with fuse protection, discharge resistors, interconnections etc complete as required.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels etc. complete as required
Supply, installation, testing & commissioning of MDB-12D-E-2_Oxidiser Grinding panel as described below:
INCOMER
1 No. 630A FP MCCB (35 KA) micro processor based with Class-C transient voltage surge suppression device suitable for 3 phases as per specifications.
1 set of 630/5A, 15 VA, class-1 CTs for APFC relay
One (1) Set of SPD TYPE-2
Earth Fault, under voltage and over voltage protection to be considered in MCCB.
METERING & INDICATION
1 set of R,Y,B phase indicating lamps
1 Set- of ON/OFF/TRIP indicating lamps.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (EM-6400 of Conzerv or equivalent).
BUS-BAR
1 Set of 800A TPN Aluminium Bus Bar with colour coded heat shrimkable PVC Sleeves
OUTGOINGS
All MCCB & MCB outgoing feeder shall be provided with ON/OFF indication lamps. The Number of outgoing feeders shall be as follows and as per SLD:-
3 No. 63A TPN MCB
4 No. 40A TPN MCB
5 Nos. 32A TPN MCB
3 Nos. 40A DP MCB
7 Nos. 250A TPN MCCB
CAPACITOR PANEL AS PER SLD. (100 kVAR)
INCOMER, METERING & INDICATION
1 Nos. 250A TPN MCCB (35 KA)
1 No. 4 step-Microprocessor APFC controller/Relay shall continuously monitoring all three phases and LCD displays for various Electrical Parameters like voltage, input current, capacitive current, KVA demand, KW, Power Factor, self diagnostic error code indication with printout facility of the above with RS 232/RS 485 port. Controller should mounted on the front side of the panel Capacitor bank having 3 phase MPP based mix dieelectric low loss ISI marked power capacitor.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (EM-6400 of Conzerv or equivalent).
One (1) set 3 Nos. CT's of ratio 100/5A,15VA, Class 1.0 as required.
Terminals to receive XLPE insulated Aluminium cables
BUS-BAR
1 Set of 125A TPN Aluminium Bus Bar with colour coded PVC heat shinkable Sleeves
METERING & INDICATION
1 set of R,Y,B indicating lamps as per SLD each with 3 nos. 2A SP MCBs.
1 Set- of ON/OFF indicating lamps.
OUTGOINGS
1 no 160 amp 35kA TP MCCB complete each with the following for 1x50 kVAR capacitor bank.
1 no of 100 amp 35kA TP MCCB complete each with the following for 1x25 kVAR capacitor bank.
2 no of 40 amp 35kA TP MCCB complete each with the following for 2x10 kVAR capacitor bank.
1 no 20 amp 35kA TP MCCB complete each with the following for 1x5 kVAR capacitor bank.
3 pole capacitor grade contactor suitable for automatic switching of 50, 25 10 & 5 kVAR capacitor bank
Indicating lamp to give status of the circuit as per SLD
Manual/auto changeover switch
Hermetically sealed metallized polypropylene (MPP type) capacitor units complete with fuse protection, discharge resistors, interconnections etc complete as required.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels etc. complete as required
Supply, installation, testing & commissioning of MDB-14-H-2-Premix Storage panel as described below:
1 No. 1000A 4 pole microprocessor based MDO, ACB, 40kA with integral protection, anti pumping protection microprocessor based O/C, S/C & E/F protection (LSIG) with ET6V releases and Class-C transient voltage surge suppression device suitable for 3 phases as per specifications.
1 set of 1000/5A, 15 VA, class-1 CTs for APFC relay
One (1) Set of SPD TYPE-2
Earth Fault, under voltage and over voltage protection to be considered in MCCB.
METERING & INDICATION
1 set of R,Y,B phase indicating lamps
1 Set- of ON/OFF/TRIP indicating lamps.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (EM-6400 of Conzerv or equivalent).
BUS-BAR
1 Set of 1200A TPN Aluminium Bus Bar with colour coded heat shrimkable PVC Sleeves
OUTGOINGS
All MCCB & MCB outgoing feeder shall be provided with ON/OFF indication lamps. The Number of outgoing feeders shall be as follows and as per SLD:-
3 No. 63A TPN MCB
14 Nos. 32A TPN MCB
3 Nos. 40A DP MCB
3 Nos. 125A TPN MCCB
5 Nos. 400A TPN MCCB
CAPACITOR PANEL AS PER SLD (55 kVAR).
INCOMER, METERING & INDICATION
1 Nos. 400A TPN MCCB (35 KA)
1 No. 6 step-Microprocessor APFC controller/Relay shall continuously monitoring all three phases and LCD displays for various Electrical Parameters like voltage, input current, capacitive current, KVA demand, KW, Power Factor, self diagnostic error code indication with printout facility of the above with RS 232/RS 485 port. Controller should mounted on the front side of the panel Capacitor bank having 3 phase MPP based mix dieelectric low loss ISI marked power capacitor.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (EM-6400 of Conzerv or equivalent).
One (1) set 3 Nos. CT's of ratio 400/5A,15VA, Class 1.0 as required.
Terminals to receive XLPE insulated Aluminium cables
BUS-BAR
1 Set of 500A TPN Aluminium Bus Bar with colour coded PVC heat shinkable Sleeves
METERING & INDICATION
1 set of R,Y,B indicating lamps as per SLD each with 3 nos. 2A SP MCBs.
1 Set- of ON/OFF indicating lamps.
OUTGOINGS
2 no 160 amp 35kA TP MCCB complete each with the following for 2x50 kVAR capacitor bank.
2 no of 100 amp 35kA TP MCCB complete each with the following for 2x25 kVAR capacitor bank.
1 no of 40 amp 35kA TP MCCB complete each with the following for 1x10 kVAR capacitor bank.
1 no 20 amp 35kA TP MCCB complete each with the following for 1x5 kVAR capacitor bank.
3 pole capacitor grade contactor suitable for automatic switching of 50, 25 10 & 5 kVAR capacitor bank
Indicating lamp to give status of the circuit as per SLD
Manual/auto changeover switch
Hermetically sealed metallized polypropylene (MPP type) capacitor units complete with fuse protection, discharge resistors, interconnections etc complete as required.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels etc. complete as required
Supply, installation, testing & commissioning of MDB - 14-I-2_My 300 Mixture Panel as described below:
1 No. 1000A 4 pole microprocessor based MDO, ACB, 40kA with integral protection, anti pumping protection microprocessor based O/C, S/C & E/F protection (LSIG) with ET6V releases and Class-C transient voltage surge suppression device suitable for 3 phases as per specifications.
1 set of 1000/5A, 15 VA, class-1 CTs for APFC relay
One (1) Set of SPD TYPE-2
Earth Fault, under voltage and over voltage protection to be considered in MCCB.
METERING & INDICATION
1 set of R,Y,B phase indicating lamps
1 Set- of ON/OFF/TRIP indicating lamps.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (EM-6400 of Conzerv or equivalent).
1 Set of 1200A TPN Aluminium Bus Bar with colour coded heat shrimkable PVC Sleeves
OUTGOINGS
All MCCB & MCB outgoing feeder shall be provided with ON/OFF indication lamps. The Number of outgoing feeders shall be as follows and as per SLD:-
4 No. 63A TPN MCB
2 No. 40A TPN MCB
12 Nos. 32A TPN MCB
4 Nos. 20A TPN MCB
3 Nos. 40A DP MCB
2 Nos. 125A TPN MCCB
5 Nos. 400A TPN MCCB
CAPACITOR PANEL AS PER SLD. (125kVAR)
INCOMER, METERING & INDICATION
1 Nos. 250A TPN MCCB (25 KA)
1 No. 4 step-Microprocessor APFC controller/Relay shall continuously monitoring all three phases and LCD displays for various Electrical Parameters like voltage, input current, capacitive current, KVA demand, KW, Power Factor, self diagnostic error code indication with printout facility of the above with RS 232/RS 485 port. Controller should mounted on the front side of the panel Capacitor bank having 3 phase MPP based mix dieelectric low loss ISI marked power capacitor.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (EM-6400 of Conzerv or equivalent).
One (1) set 3 Nos. CT's of ratio 250/5A,15VA, Class 1.0 as required.
Terminals to receive XLPE insulated Aluminium cables
BUS-BAR
1 Set of 300A TPN Aluminium Bus Bar with colour coded PVC heat shinkable Sleeves
METERING & INDICATION
1 set of R,Y,B indicating lamps as per SLD each with 3 nos. 2A SP MCBs.
1 Set- of ON/OFF indicating lamps.
OUTGOINGS
2 no 160 amp 25kA TP MCCB complete each with the following for 2x50 kVAR capacitor bank.
2 nos of 40 amp 25kA TP MCCB complete each with the following for 2x10 kVAR capacitor bank.
1 no 20 amp 25kA TP MCCB complete each with the following for 1x5 kVAR capacitor bank.
3 pole capacitor grade contactor suitable for automatic switching of 50, 10 & 5 kVAR capacitor bank
Indicating lamp to give status of the circuit as per SLD
Manual/auto changeover switch
Hermetically sealed metallized polypropylene (MPP type) capacitor units complete with fuse protection, discharge resistors, interconnections etc complete as required.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels etc. complete as required
MV Cables
Supply, laying, testing and commissioning of following size 1.1KV grade FRLS, XLPE insulated armoured aluminium/copper conductor cable, in built up cable trench/ already laid RCC hume pipe / cable tray /in ground with all installation materials. When the cable is to be laid in ground, the same shall be laid at a depth of 750mm below ground level including excavation in all kind of soil, SDR & HR, refilling of earth after cables are laid, providing protection with sand cushioning at bottom and bricks at sides & top, cable route markers at every 15mtr. interval also at the turnings & joints and identification tag at both the ends etc., complete. The cable shall conform to IS 7098/ Part II
a )3.5C X 300 Sq.mm aluminium armoured
b) 3.5C X 240 Sq.mm aluminium armoured
c)3.5C X 185 Sq.mm aluminium armoured
d)3.5C X 150 Sq.mm aluminium armoured
e) 3.5C X 120 Sq.mm aluminium armoured
f) 3.5C X 95 Sq.mm aluminium armoured
g) 3.5C X 70 Sq.mm aluminium armoured
h) 3.5C X 50 Sq.mm aluminium armoured
i) 3.5C X 35 Sq.mm aluminium armoured
j) 3.5C X 25 Sq.mm aluminium armoured
k) 4C X 16 Sq.mm Copper armoured
l) 4C X 10 Sq.mm Copper armoured
m) 4C X 6 Sq.mm Copper armoured
n) 4C X 4 Sq.mm Copper armoured
o) 4C X 2.5 Sq.mm Copper armoured
p) 3C X 16 Sq.mm Copper armoured
q) 3C X 10 Sq.mm Copper armoured
r) 3C X 6 Sq.mm Copper armoured
s) 3C X 4 Sq.mm Copper armoured
t) 3C X 2.5 Sq.mm Copper armoured
Control Cable (Includimng, Gland thimble and termination)
a) 4 C x 2.5 sq.mm control cable(LS)
b) 7 C x 2.5 sq.mm control cable(LS)
c) 12 C x 2.5 sq.mm control cable(LS)
Providing end terminations for the cable specified below with Double compression type gland, Bi-Metalic lugs using crimping tool, Insulation tape, Identification tags etc. including end termination.
a) 3.5C X 300 Sq.mm aluminium armoured
b) 3.5C X 240 Sq.mm aluminium armoured
c) 3.5C X 185 Sq.mm aluminium armoured
d) 3.5C X 150 Sq.mm aluminium armoured
e) 3.5C X 120 Sq.mm aluminium armoured
f) 3.5C X 95 Sq.mm aluminium armoured
g) 3.5C X 70 Sq.mm aluminium armoured
h) 3.5C X 50 Sq.mm aluminium armoured
i) 3.5C X 35 Sq.mm aluminium armoured
j) 3.5C X 25 Sq.mm aluminium armoured
k) 4C X 16 Sq.mm Copper armoured
l) 4C X 10 Sq.mm Copper armoured
m) 4C X 6 Sq.mm Copper armoured
n) 4C X 4 Sq.mm Copper armoured
o) 4C X 2.5 Sq.mm Copper armoured
p) 3C X 16 Sq.mm Copper armoured
q) 3C X 10 Sq.mm Copper armoured
r) 3C X 6 Sq.mm Copper armoured
s) 3C X 4 Sq.mm Copper armoured
t) 3C X 4 Sq.mm Copper armoured
Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :
a) 150mm dia
b) 300mm dia
TELEPHONE & LAN WIRING
Supply and installation of 50 Pair Krone connectors in MS box complete as required.
Supply and installation of 20 Pair Krone connectors in MS box complete as required.
Supply and fixing of Telephone outlet (RJ11) with anodised GI box with front plate etc. complete as required
Supply and laying of 50 pair 0.5mm dia Copper conductor, Jelly filled, armoured cable including excavation brick protection, backfilling, sand cushioning with all accessories complete etc., (Assumed Length - From Nearest Telephone Exchange)
Supply and laying of 20 pair 0.5mm dia Copper conductor, Jelly filled, armoured cable including excavation brick protection, backfilling, sand cushioning with all accessories complete etc.,
Supply and laying of 2 Pair 0.5mm dia PVC insulated unarmoured copper conductor Telephone wire conforming to DOT Specifications in existing /already laid PVC pipes.
Supply & fixing of UTP Cat-6 1 Module Socket (RJ-45) with shutter in a box with front plate and concealed in manner by cutting chasing in walls and making them good after fixing socket, etc., complete as required.
Supply and laying of CAT-6 UTP data cable (Yellow) conforming to DOT Specifications in existing /already laid PVC pipes.
Supplying and fixing of 20 MM Dia. of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (For 2 Pair Telephone Cables)
Supply & fixing of 1" Casing Caping / Flexible / PVC Pipe for LAN Cabling
Supply , Installation, Testing and Commissioning of Core Switch should have Min 24 x100/1000X SFP port , Min 8x10/100/1000T port , Min 4 X 10 G Based SFP+ port, 2x Stacking port comprising 128 Gbps of stacking bandwidth from day 1, Support less than 50 Millisecond convergence based of RFC 3619./REP/G.8032, Min Operating temp 0-500 C, Must have Common criteriacertification EAL3/NDcPP/NDPP, should support AVB, CE.2 and CB certified.
Supply, Installation, Testing & Commissioning of Access switch should have 16 x10/100/1000T port , Min 8 x1 G SFP port, should be upgradable to Min 4x 10 G based SFP+ port , 2x Stacking port comprising 40 Gbps of stacking bandwidth from day 1, Support less than 50 Millisecond convergence based of RFC 3619/REP/G.8032, Min Operating temp 0-50 Degree C, Must have Common criteriacertification EAL3/NDcPP/NDPP, should support AVB,CE.2 and CB certified.
Supply, Installation, Testing & Commissioning of fiber Modules 1000 Base.
Supply, Installtion, Testing and Comissioning of armoured 6 core Singlemode OFC cable for inter Building switches connectivity.
Supply , Installtion, Testing and Comissioning of 12 port loaded LIU with LC adaptor plates, pigtel cables etc complete as required.
Supply, Installtion, Testing and Comissioning of 24 port loaded LIU for with LC adaptor plates, pigtel cables for core switch to access switch connectivity over fiber.
Supply, Installtion, Testing and Comissioning of LC-LC singlemode fiber patch cord for LIU to switch connectivity.
Supply, installation, testing and commissioning of wall/floor mounted cabinet with drawer shelves and wiring channels to accommodate CCTV system equipment and accessories as mentioned in the BOQ above and including all connections and terminations as required fabricated from minimum 2 mm thick CRCA sheet including power coating after surface treatment complete as required. (Ref Make-Valrack & Dynamic)
9U rack for the Network Switch (W 500 x D 600)
LIGHTNING PROTECTION & SPECIAL EARTHING
Supply and installation of vertical air termination with 40mm dia copper hollow sphere with spikes, fixed on 1000mm length 25mm dia Copper rod including PCC block and all fixing accessories.
Supply and fixing of weather proof 14 SWG GI test link box of size 150 x 100 x 100 mm along with all fixing accessories etc., complete.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt complete as per manufactureres specifications & as directed by Engineer-in-charge. (For ESDS, PSDS Systems, PLC Room, Control Block, 2 Nos. Extra For Future Expansion)
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt complete as per manufactureres specifications & as directed by Engineer-in-charge. (For Electrical systems, Lightning Protection system, 2 Nos. Extra For Future Expansion)
Supply and laying of following size earth strips including excavation at a depth of 500mm and refilling of earth when laid in ground and with all fixing accessories including DMC insulators, 150 x 150 x 100mm PCC blocks wherever required when laid on the wall / Ceiling / Surface with necessary interconnections by providing GI bolt & nuts with earth station, joints and equipment's etc., complete.
For ESDS & PSDS
25 X 3 mm CU Strip laid in ground
25 X 3 mm CU Strip laid in ground through 75mm HDPE Pipe
25 X 3 mm CU Strip conductor with DMC Insulated Supports
For Main Panel
50 X 6 mm GI Strip laid in ground for main panel
50 X 6 mm GI Strip laid in ground through 75mm HDPE Pipe
Lightning Protection
32 X 6 mm GI Strip conductor without DMC Insulated Supports
32 X 6 mm GI Strip conductor with DMC Insulated Supports
0.5mm Thick flexible CU tape through flexible conduit including connection between antistatic floor with desired earth strip.
8 SWG GI wire
6 Sqmm. Cu. Multistrand Flexible wire
25 X 3 mm GI Strip laid in ground for equipment
Supply and fixing of Static Discharge Handles made out of 32mm dia Copper rod fixed on wall with brass spacers and conected to 25x3mm copper strip by brazing.
Supply, installation, testing and commissioning of Static Discharge Meter fixed on wall with 25x3mm copper strip by brazing etc., complete.
SUBHEAD - XVII:EOT CRANE
Design, Manufacturing, Supplying, Erection, Testing & commissioning of double girder, Crab type EOT crane (Flame proof) 40T Capacity, conforming to the standards given in IS: 3177, 807 & 2148 and other relevant IS standards of the latest revisions etc. all complete with all taxes, duties and other charges such as transportation to site, loading and unloading at stores / building, where to be installed etc., movement of material to work spot including the cost of paint as required. Duty: Indoor, Span: 18.0m, Bay length: 18.0m, Lift: 9.0m
Design, Manufacturing, Supplying, Erection, Testing & commissioning of double girder, Crab type EOT crane (Flame proof) 20T Capacity, conforming to the standards given in IS: 3177, 807 & 2148 and other relevant IS standards of the latest revisions etc. all complete with all taxes, duties and other charges such as transportation to site, loading and unloading at stores / building, where to be installed etc., movement of material to work spot including the cost of paint as required. Duty: Indoor, Span: 20.0m, Bay length: 30.0m, Lift: 8.0m
Design, Manufacturing, Supplying, Erection, Testing & commissioning of double girder, Crab type EOT crane (Flame proof) 15T Capacity, conforming to the standards given in IS: 3177, 807 & 2148 and other relevant IS standards of the latest revisions etc. all complete with all taxes, duties and other charges such as transportation to site, loading and unloading at stores / building, where to be installed etc., movement of material to work spot including the cost of paint as required. Duty: Indoor, Span: 22.0m, Bay length: 48.0m, Lift: 10m
Design, Manufacturing, Supplying, Erection, Testing & commissioning of single girder, Crab type EOT crane (Flame proof) 5T Capacity, conforming to the standards given in IS: 3177, 807 & 2148 and other relevant IS standards of the latest revisions etc. all complete with all taxes, duties and other charges such as transportation to site, loading and unloading at stores / building, where to be installed etc., movement of material to work spot including the cost of paint as required. Duty: Indoor, Span: 14.0m, Bay length: 15.0m, Lift: 18.0m
Design, Manufacturing, Supplying, Erection, Testing & commissioning of Double girder, Crab type EOT crane 2T Capacity, conforming to the standards given in IS: 3177, 807 & 2148 and other relevant IS standards of the latest revisions etc. all complete with all taxes, duties and other charges such as transportation to site, loading and unloading at stores / building, where to be installed etc., movement of material to work spot including the cost of paint as required. Duty: Indoor, Span: 6.0m, Bay length: 12.0m, Lift: 7.0m
Supplying, Erection, Testing & Commissioning of for drag chain type of current collection system complete with drag chain with vertical separators, mounting brackets with tie wrap plates, support plates, trough with glide bar including mounting kit, along with cable from switch and with all necessary fixtures.
Supplying, Erection, Testing & Commissioning of Gantry Rails section 60/90Lb of prime material in length of 10m and above complete with mounting arrangement and fixing hardware etc., complete over the bay length to match the span of the crane within the permissible accuracy levels for span in height variation as per the QA plan.
FIRE ALARM SYSTEM
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.
Supply, Erection, Testing and Commissioning of combined UV/IR detectors (UL-FM approved), 1200 cone of vision, Range min. 15Mtr to 300mts, explosion proof construction, including 24 V DC, Aluminium Housing complete with swivel mount, output module etc., complete.
Supply, installation, testing and commissioning of addressable type Double action manual call point pull station with back box having an integrally mounted addressable module that monitors & reports contact status.
Supply, Erection, Testing and Commissioning of Hooter
Supply, Erection, Testing and Commissioning of horizontal mounted Siren, 2.5 Km radius including Electrical connections etc., complete.
Supply, Erection, Testing and Commissioning of analogue addressable Fire Alarm control Panel (UL-FM approved) with integrated PA system. The fire alarm panel is designed to detect the fire through the fire detectors and process them into suitable audio – visual alarms, activate devices related to fire extinguishing systems, communicate to other Fire Alarm panels on peer to peer basis suitable for single mode optical fiber connectivity all necessary module/converter to be added for OFC connection.etc complete
Supply, installation, testing and commissioning of analogue addressable type monitor Modules along with all fixing accessories.
Supply and laying of armoured FRLS Cables for detectors to FA Panel, Panel to hooters, manual call points, deluge valves, siren etc and of size 2c x 1.5 sqmm twisted pair shielded Copper armoured cable including termination, electrical connection etc complete.
Supply, installation, testing and commissioning of analogue addressable type control Modules along with all fixing accessories.
Supply, installation, testing and commissioning of Fault isolator module for isolating shorted, dewired and loose circuits between two successive fault with automatic resetting arrangement.
Supplying, installation, testing & commissioning of central graphical fire alarm management system to centrally monitor and operate the fire alarm system complete as required.
Supplying, installation, testing & commissioning of intelligent interface unit BACnet/ Modbus protocol i.e. supplying communication links between building management system and fire alarm control panel complete as required
FIRE FIGHTING SYSTEM
Providing and laying S&S Centrifugally Cast (Spun) / 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239
including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :
External Firefighting services
80 mm dia
100 mm dia
150 mm dia
Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :
25 mm dia
32 mm dia
40 mm dia
50 mm dia
65 mm dia
80 mm dia
Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : 150 mm Dia
Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required :
a) 80 NB Class C
b) 100 NB Class C
c) 150 NB Class C
Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required
Single headed Stainless steel
Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required :
Single headed Stainless steel
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :
80 mm dia
100 mm dia
150 mm dia
Providing, installation, testing and commissioning of oriffice plate made out of 6 mm thick stainless steel (Grade 304) withoriffice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5kg/cm2 complate as required
Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required
Stainless Steel (Grade 304)
Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required.
20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585
20 mm internal dia gun metal globe valve & nozzle.
Drum and brackets for fixing the equipmets on wall.
Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket.
Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required
Stainless Steel (Grade 304)
Supply, installation, testing and commissioning of weather proof lockable cabinet of made out of M.S. sheet having central opening and 4 mm thick glazed glass doors (Two nos.) suitably marked on the outside with the letters "FIRE HOSE" including necessary locking arrangement and shall be painted as per approved shade. The cabinet shall be suitable to accommodate 2 nos. 30 mtr long Hose pipe & 1 Nos branch pipe nozzle. Including mounting on wall with anchor fastener or on Angle frame where wall is not available. The sign, \" YARD HYDRANT\" BRIGADE INLET\" etc. shall be painted in \"CAPITAL LETTERS in white synthetic paint. Size - 1150 x 800 x 250 (For Yard Hydrant)
Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required.
Supply, Erection, Testing and Commissioning of following size D-pack Deluge System (Skid mounted pre assembled Deluge System enclosed in a cabinet with front opening) consisting of deluge valve with all accessories, pressure gauge, solenoid valve, water motor gun, Two Isolation valve and one by pass butterfly valve internal piping and common drain etc complete UL/FM approved with all accessories etc,complete.,
Providing and laying S&S Centrifugally Cast(spun)/Ductile Iron pipes conforming to IS:8329
200 mm dia Ductile Iron Class K-9 pipes
250 mm dia Ductile Iron Class K-9 pipes
EXTERNAL ELECTRIC SUPPLY & AREA LIGHTING
Supply of Bajaj make 70 W LED Street light luminaire, LED Street light luminaire, electrical Class I, with a grey painted, Die casted GI body, an extra clear toughened glass protector, separate IP 66 optical & control gear compartments (for better thermal dissipation) with easy access to control gear, suitable for a horizontal mounting of 42-60mm diameter, each LED has a specific lens for uniform photometric distribution, 0% (at 00 inclination) Upward Light Output Ratio (ULOR) to avoid glare & light pollution, the luminaire shall have a CCT of 5700K and Colour Rendering Index (CRI) > 70, a driver (efficiency ≥ 85%) with internal surge protection of 4/4 kV up to 70W and external surge protection of 10 kV (in both Common & Differential Modes) above 70W, Power Factor ≥ 0.95, a residual flux of 70% (L70) @ 50,000 hours. The price shall be including all the necessary fittings and accessories to complete the system. Decorative GI - PU Painted GI pole. Classic pole- 3 Mt with 1mts single arm bracket, Junction Box and Base plate & J foundation Bolt.
Supply, Fixing, Testing & Commissioning of LED Aviation Light including necessary hardware fabrication on 2.5mtr long 50mm dia class B GI pipe wih two coats of primer redoxide and two coats zinc chromate aluminium paint, required PCC foundation above ground level coping upto 300mm, terminal box with MCB, 2C x 1.5Sqmm unarmoured cable and end termination of same at both side by providing necessary gland lugs etc. complete.
Providing Spiral coil earthing with 8 SWG GI wire including spreading of salt and charcoal as per IS 3043/87 with latest amendments.
Supply, laying, testing and commissioning of 3C X 2.5 Sq.mm size of 1100V grade XLPE insulated armoured Copper conductor cable, the cable is to be laid in ground, the same shall be laid at a depth of 300mm below ground level including excavation in all kind of soil, SDR & HR, refilling of earth after cables are laid, providing marker tape above 100 mm top of cable to avoid damage of cable during excavation for cable protection. The cable shall conform to IS 7098/ Part II
Providing cable end terminations for 3C X 2.5 Sq.mm Cu Arm. Cable with aluminium/ copper lugs, double compression type cable gland with neoprene gasket using Insulation tape, crimping tool etc., complete as required.
EXTERNAL WATER SUPPLY
Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc.
32 mm nominal outer dia Pipes
Making connection of G.I. distribution branch with G.I. main of following sizes by providing and fixing tee, including cutting and threading the pipe etc. complete :
25 to 40 mm nominal bore
50 to 80 mm nominal bore
Providing and fixing brass bib cock of approved quality :
20 mm nominal bore
Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :
32 mm nominal bore
40 mm nominal bore
Constructing masonry Chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C. I. surface box 100x100 x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat cement complete as per standard design :
With common burnt clay F.P.S.(non modular) bricks of class designation 7.5
Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank.
Providing and fixing Ball valve with C.I. wheel of approved quality (screwed end) :
20 mm nominal bore
Providing, fixing & testing G.I. Pipes (Medium class) complete with G.I. Fittings i.e. tees, elbows, sockets, clamps etc. including making good the walls etc. wherever required. (Pipe to be laid in shafts, terrace & Trenches, Structural supports to be paid separately).
80mm GI pipe
WATER COOLERS
Supply of self contained drinking water cooler with refrigerator R 22,cooling capacity 40Ltr/hr sorage capacity 40 ltr/hr,rate of maximum energy consumption in watt 575 along with water purifier etc,complete.
AIR CONDITIONING
Water Chilling Unit
Supply, installation, testing & commissioning of Modular Air cooled Chiller Cooling: LWT 7 Deg C, Water Flow 0.172 cu mtr/(h.kW) & 35 Deg C outdoor temperature DBT, with Minimum COP 3.2 Mutiple compressors in hermetic construction only as per OEM design, complete as per specifications. Suitable Nos & suitable capacity squirrel cage induction motor with class 'F' insulation suitable for operation on 415 volts +10% , 50 Hz, A.C. supply. Suitable Nos. & suitable capacity starter in IP 55 protection/As per OEM Std. First charge of R410 A refrigerant and oil duly charged at factory. 1 No. - Matching Air Cooled condenser with copper tubes and aluminium fins and 2 speed fans for noise control. 1 No. - Matching Cooler of Shell and Tube / BPHE type as per OEM standard 1 Lot - Refrigerant piping fittings, valves, accessories to inter connect compressor, condenser, chiller and expansion valve. 1 Set - Control panel with display comprising of Controls. It shall also be equipped with protection and monitoring devices such as H/L Pressure switch/ Thermal and Current Overload Protector
1 Lot - DP/ Flow switches at inlet and outlet of chiller, water drain & air purge valves, wherever required. Lot- suction line and chiller insulation Lot-frame work for mounting the above condenser, chiller, compressor and motor with base plate complete with antivibration pads/ springs. Lot- Initial/ first charge of refrigerant gas & compressor oil duly charged at factory. Lot- RCC/ cement concrete foundation for equipment Fins shall be 10-12/inch with hydrophobic coating to give 3-5 times higher corrosion resistance Package mounted Electical suitable Star Delta /DOL starters for compressor motors along with No volt coil, overload releases & single phase prevention devices other safeties & controls Electrical wiring and interconnecting control wiring for motors, starters & protective devices.
Scroll Chiller- 55 TR (Actual at Ambient Temperature ) (4W+2S)
Scroll Chiller- 45 TR (Actual at Ambient Temperature ) (3W+1S)
HOT WATER GENERATOR
Supply, installation, testing and commissioning of electrically operated Hot Water Generator of efficiency more than 90% in multiple bank complete with PLC based microprocessor controls, electrical panels, stainless steel braided pipe flexible connector etc. confirming to tender specifications section.
100 KW , 60 C Outlet Temperature
Chilled Water Pumps
Supply, Installation, Testing, Commissioning and handing over of End Suction Pump of capacity 40 Meters Head fitted with suitable Motor (TEFC and IP 55) chilled water including mechanical seal and coupling guard and necessary accessories etc complete. Suitable Nos & suitable capacity squirrel cage induction motor with IE3 class 'F' insulation suitable for operation on 415 volts +10% , 50 Hz, A.C. supply. max speed of pump shall be 3000 RPM. 4 working and 2 standby, Suction guide and Triple Duty valve shall be supplied along with the pumps (Head given is tentative,before procurement of pumps Actual head should be calculated as per site conditions and get it aprroved by the consultant)
132 GPM @ 40 Meter Head
108 GPM @ 40 Meter Head
Hot Water Pumps
Supply, Installation, Testing, Commissioning and handing over of End Suction Pump of mentioned capacity fitted with suitable Motor (TEFC and IP 55) chilled water including mechanical seal and coupling guard and necessary accessories etc complete. Suitable Nos & suitable capacity squirrel cage induction motor with IE3 class 'F' insulation suitable for operation on 415 volts +10% , 50 Hz, A.C. supply. max speed of pump shall be 3000 RPM. 5 working and 3 standby, Suction guide and Triple Duty valve shall be supplied along with the pumps (Head given is tentative,before procurement of pumps Actual head should be calculated as per site conditions and get it aprroved by the consultant)
110 GPM @ 25 Meter Head
Floor Mounted Type Air Handling Units
Supplying, installing, testing and commissioning of factory built Floor Mounted / Ceiling Suspended double skin type air handling units made of 43 mm thick panels consisting of pre plasticized G.I casing made of thickness 0.8 mm outside layer and G.I sheet of thickness 0.8 mm inside layer with polyurethane foam (PUF) insulation of density 40 kg/m3 factory injected between them by injection moulding machine, complete with Direct Driven Backward Curved Plug Type Fans with VFD's with aluminium finned copper tubes (tubes thickness not less than 0.5 mm),filter sections with 50 mm thick washable synthetic type pre filter having efficiency 90% down to 10 micron, chemical biological filter with dielectric media with an efficiency of MERV 16 and capacbility to gaseous contamination by 95% with a minimum IPD of 15mm having EN, CE, RoHS, ISO certification along with FDA compliance. The filtration shall be certified by Indian Government Organization such as ICMR/ Central Government Institute/ SAIS/ IACS, Unit Mounted ADC system ( Adavnced Oxidation plasma cell (AOP) ) based on nanoX technology certified by CCMB lab/ ICMR lab to kill covid-19 by greater than 99% within 45 mins. The product shall have CE & RoHS Certiffication, Green Pro with complete electrical accessories etc., ,backward curved plug fan with TEFC (IE-3) suitable for VFD operation at 415 ± 10% volts, 50 Hz, 3 phase, A.C supply, mixing box ,drain connections with drain valve, Flexible connection,stainless steel drain pan, necessary vibration isolation arrangement etc, suitable for VFD operation at 415 ± 10% volts, 50 Hz, 3 phase, A.C supply, mixing box . Humidifier Section with humidifier along with cellulose pad and recirulation pumps. TP isolator with MS enclosure box should be Provided. etc, complete as per specifications of following capacities
Humidifier Section with humidifier along with cellulose pad and recirulation pumps. TP isolator with MS enclosure box should be Provided. etc, complete as per specifications of following capacities
18000 CFM / 60 TR with 8 Rows Cooling Coil & 2 Row Heating Coil, 95 mm static pressure
18000 CFM / 55 TR with 8 Rows Cooling Coil & 2 Row Heating Coil, 95 mm static pressure
17000 CFM / 50 TR with 8 Rows Cooling Coil & 2 Row Heating Coil, 95 mm static pressure
10000 CFM / 75 TR with 8 Rows Cooling Coil & 2 Row Heating Coil, 95 mm static pressure
8500 CFM / 65 TR with 8 Rows Cooling Coil & 2 Row Heating Coil, 95 mm static pressure
AHU's Controls/Three Way Modulating Valve
Supply, Installation , Testing & Commissioning of Three way Modulating type Flow Control Valves of PN 16/25 etc. as per drawings and specifications.
Water flow rate 120-252 USGPM
Water flow rate 62.4-120 USGPM
Water flow rate 41-62.4 USGPM
Plumbing (Insulated Chilled / Hot Water)
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / cu m density,thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class ‘O’ insulation applied by suitable rubber based adhesive complete including repairing of damage to building etc. as per specifications and as required complete in all respect.Note:-The Pipes of sizes 150mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.
125 MM (32 mm Thick Insulation)
100 MM (32 mm Thick Insulation)
80 MM (32 mm Thick Insulation)
65 MM (32 mm Thick Insulation)
50 MM (32 mm Thick Insulation)
40 MM (32 mm Thick Insulation)
32 MM (32 mm Thick Insulation)
Supply, Installation, Testing, Commissioning of BUTTERFLY VALVE - (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & Oring PN 16 pressure rating for chilled water/hot eater circulation as specified
Supply, Installation, Testing, Commissioning of BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified.
Supply, Installation, Testing, Commissioning of MOTORISED BUTTERFLY VALVE with C I body SS Disc, Nitrile Rubber Seal & Oring PN 16 pressure rating for chilled water/hot eater circulation as specified
Supply, Installation, Testing, Commissioning of Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation
Supply, Installation, Testing, Commissioning of industrial type pressure gauges 0 to 10 Kg Sqcm with gun metal / brass valves complete as required
Supply, Installation, Testing, Commissioning of mercury in glass industrial type thermometerstemp range.2 Deg to 15 Deg
Flow Switches
Supply, Installation, Testing, Commissioning of water flow switch on chilled water outlet complete as per specifications and drawings.
Automatic Air Vents
Supply, Installation, Testing, Commissioning of auto airvent purging valve complete as per specification and drawings.
Expansion Tank
SITC of PVC Insulated EXPANSION Tank. The tank shall be with float valve, drain, overflow and make up connection with suitable valves. All hardware used should be hot dip galvanised. The tank should be suitable for chilled water application.The tank shall be located as shown in the tender drawing.
Drain Piping
Supply,installation,testing and commissioning of rigid PVC piping complete with fittings, supports as per specifications and duly insulated with 6 mm thick closed cell nitrile rubber class ‘O’ .
Ducting
Supply, fabrication, installation, balancing and commissioning of factory fabricated GI sheet metal rectangular ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. Ducts shall be coated with Fire Resistance Coating of minimum 600–700-micron (DFT) thickness applied over ducts to provide 2 hours Fire Rating. The Fire-Resistance Coating shall be tested as per requirements of BS 476: Part 6 ‘Class O’ and Part 7 ‘Class 1’ and BS 476 Part 24 (Type A and B) to analyze Stability, Integrity, and Insulation performance for 2 hours, the duct sheet shall also conform to performance criteria (stability, integrity, insulation) without insulation for 2 hours. The average and maximum temperature of unexposed faces with or without insulation shall not exceed 140 deg. Cel and 180 deg. Cel respectively to ensure the insulation performance criteria. The coating shall be free or has minimum toxic elements such as lead, mercury, arsenic and has low VOC less than 50 gm/liter. as per approved drawings of following gauges as mentioned-
Grilles/Diffusers
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications.
Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required.
Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core.
Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core
Aluminium exhaust/fresh air louvers
Jet Diffusers with butterfly leaf damper
Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications.
Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shalI be inbuilt mechanismn and not externally mounted.The damper shall also be closed in the event of fire signal complete as reguired and as per specifications.
Fire damper
Actuator
Insulation
Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class “O”) insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wideand 3 mm thick self adhesive nitrile rubber tape insulation complete as perspecifications and as required.
19 MM thick (Non Exposed)
25 MM thick (Exposed)
Duct Acoustic Lining
Supply and fixing of acoustic lining of supply air duct and plenum with 15 mm thick Engineered Nitrile Rubber open cell foam having a Noise Reduction Coefficient of 0.55 with Density 140 - 180 Kg/m3 passing Class 1 Fire Performance test as per BS 476 Part 7, Air Erosion test for 10,000 fpm air velocity as per ASTM C 1071-05 and with built-in antimicrobial protection. The material should pass Fungi Resistance Test as per DIN EN ISO 846 Method A and Bacterial Resistance Test as per DIN EN ISO 846 Method C; to be applied using manufacturer's recommended Rubber based Adhesive in a blend of solvents.
SPLIT Units
Supplying, fixing, testing and commissioning of Five Star Inverter Hi Wall type split air-conditioning unit suitable to operate from 230±10% volt, 50 Hz, 1 phase power supply, with air-cooled evaporator with coil, fan, and fan motor, air-cooled condenser with hermetically sealed rotery / reciprocating compressor condenser coil, propeller fans controls, control panel, Including control wiring, necessary power cable, M.S. frame duly painted to locate Outdoor Unit etc.
Refrigerant Piping
Supply,installation,testing and commissioning of Interconnecting non exposed refrigerant pipe work with (19mm/13 mm thick) , Class 'O', k value-0.035 w/mk minimum, Density not less than 55 Kg/cu.m closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per specifications, all piping inside the room shall be properly supported with MS hanger & clamps
15.9 mm O.D. (insulation : 13 mm)
12.7 mm O.D. (insulation : 13 mm)
9.5 mm O.D. (insulation : 13 mm)
6.5 mm O.D. (insulation : 13 mm)
Control & Transmission Wiring
Supply,installation,testing and commisioning of control cum transmission wiring of 2 core x 1.5 sqmm copper in suitable 25 MM PVC conduits between indoor and out door unit & outdoor units to central remotes controllers.
9 LPH Capacity
5 LPH Capacity
PAC-Supply of Single Circuit DIRECT EXPANSION MICROPROCESSOR BASED PRECISION A/C UNITS with Heater and Humidifier with All four sides doubled skin sandwich panels with A1 class insulation, air cooled condenser with independent casing and stepless variable speed fans for low ambient operation for each circuit, scroll compressor with crankcase heater, evaporator coil with hydrophilic coating, Electronically commutated brushless motor Backward curved Plug fan, Electronic Expansion Valve with pressure transducers to display real time display suction, discharge and superheat on microprocessor panel, Refrigerant shall be environment friendly refrigerant (R410A),stainless steel drain pan, Liquid Receiver, Pressure Relief Safety Valve, Liquid Line Solonoid Valve. Motor shall be suitable for 415 + 10% volts, 50 cycles, 3 phase AC supply and external static pressure shall be 20 Pa. Outdoor unit motor protection should be with IP-54 protection and should be weather proof, it should have Fan Speed Controller for all the all the fans to modulate the Fan Speed by sensing the Condensing Pressure for Low Ambient Operation. Auto sequencing of the unit for equal run time should be integral part of the micro-processor. The unit shall be capable of Display of:Environment temperature;Humidity, description of the alarms,state of controlled devices;Electric power supply, with suitable copper piping (approximate lenght of copper pipe 10 Mtrs)
The unit shall have electric heater , variable capacity auto-modulating humidifier (efficiency minimum 0.75kW/Kg/hr)
Each unit shall be complete with powder coated electrical panel and double earthing. The cables should be Cross linked polythene insulated, armoured Copper cabling and all termination between main panel and PAC.
Each unit shall have inbuilt sequential controller for operating unit in N+1 confguration. Microprocessor should have inbuilt features of Team Mode and cascade mode incase required.
5TR & 2500 CFM (Actual capacity at 22 Deg C /50% RH Return Air Condition & 40 Deg C Outside Ambient Conditions)
Electrical Control Panel
Electrical AC PANEL-for Premix Storage
Supplying, assembling, erecting, connecting, testing and commissioning Outdoor type of dust, damp and vermin proof free floor standing factory built sheet steel enclosed non-drawout modular type Panel fabricated out of suitable sized angle iron and flats, base channel and covered with 2.0mm thick PCRC sheet, duly painted complete with earth bus, aluminium bus bar, numbering & sign writing, interconnection & including the cost of connection through bus bar / copper conductor flexible connection with all accessories, rotary handles,phase barriers etc. complete as shown in drawing & as per specifications and mounted with the followings etc. complete as required. (All the starters should have NO/ NC contacts for remote/ fire control facility etc. complete)
Incomer
1 No. 800 Amps 4P ACB Electrical Draw out Type incoming
1 No. 1000. Amps aluminium conductor bus bar duly sleeved
1 No. electronic energy meter with CTs.
1 No. Ammeter with ASS & CTs.
1 No. voltmeter with VSS.
3 Nos. phase indicating lamps
3 Nos. On,Off,Trip indicating lamps
Outgoing
160 A TPN MCCB '35 ka' with TM release etc. with MFM showing V,A, KWH, KVA & ON/OFF/Trip indications, complete - 3 set (for Chiller) 250 A TPN MCCB '35 ka' with TM release etc. with MFM showing V,A, KWH, KVA & ON/OFF/Trip indications, complete - 3 set (for HWG) 40 A TPN MCCB '25 ka' with TM release etc. complete - 3 set (Chilled Water pumps), 40 A TPN MCCB '25 ka' with TM release etc. complete - 3 set (Hot Water pumps), 63 A TPN MCCB '25 ka' with TM release etc. complete - 2 set (AHU) with suitable By-Pass VFD starter Panel, 16 A TPN MCCB '25 ka' with TM release etc. complete - 2 set (Humidifier)
Electrical AC PANEL-for MY 300 Building
Supplying, assembling, erecting, connecting, testing and commissioning Outdoor type of dust, damp and vermin proof free floor standing factory built sheet steel enclosed non-drawout modular type Panel fabricated out of suitable sized angle iron and flats, base channel and covered with 2.0mm thick PCRC sheet, duly painted complete with earth bus, aluminium bus bar, numbering & sign writing, interconnection & including the cost of connection through bus bar / copper conductor flexible connection with all accessories, rotary handles,phase barriers etc. complete as shown in drawing & as per specifications and mounted with the followings etc. complete as required. (All the starters should have NO/ NC contacts for remote/ fire control facility etc. complete)
Incomer
1 No. 800 Amps 4P ACB Electrical Draw out Type incoming
1 No. 1000. Amps aluminium conductor bus bar duly sleeved
1 No. electronic energy meter with CTs.
1 No. Ammeter with ASS & CTs.
1 No. voltmeter with VSS.
3 Nos. phase indicating lamps
3 Nos. On,Off,Trip indicating lamps
Outgoing
160 A TPN MCCB '35 ka' with TM release etc. with MFM showing V,A, KWH, KVA & ON/OFF/Trip indications, complete - 3 set (for Chiller) 250 A TPN MCCB '35 ka' with TM release etc. with MFM showing V,A, KWH, KVA & ON/OFF/Trip indications, complete - 3 set (for HWG) 40 A TPN MCCB '25 ka' with TM release etc. complete - 3 set (Chilled Water pumps), 40 A TPN MCCB '25 ka' with TM release etc. complete - 3 set (Hot Water pumps), 63 A TPN MCCB '25 ka' with TM release etc. complete - 2 set (AHU) with suitable By-Pass VFD starter Panel, 16 A TPN MCCB '25 ka' with TM release etc. complete - 2 set (Humidifier)
Electrical AC PANEL-for Oydize Grinding
Supplying, assembling, erecting, connecting, testing and commissioning Outdoor type (IP55) of dust, damp and vermin proof free floor standing factory built sheet steel enclosed non-drawout modular type Panel fabricated out of suitable sized angle iron and flats, base channel and covered with 2.0mm thick PCRC sheet, duly painted complete with earth bus, aluminium bus bar, numbering & sign writing, interconnection & including the cost of connection through bus bar / copper conductor flexible connection with all accessories, rotary handles,phase barriers etc. complete as shown in drawing & as per specifications and mounted with the followings etc. complete as required. (All the starters should have NO/ NC contacts for remote/ fire control facility etc. complete)
Incomer
1 No. 800 Amps 4P ACB Electrical Draw out Type incoming
1 No. 1000. Amps aluminium conductor bus bar duly sleeved
1 No. electronic energy meter with CTs.
1 No. Ammeter with ASS & CTs.
1 No. voltmeter with VSS.
3 Nos. phase indicating lamps
3 Nos. On,Off,Trip indicating lamps
Outgoing:-
160 A TPN MCCB '35 ka' with TM release etc. with MFM showing V,A, KWH, KVA & ON/OFF/Trip indications, complete - 4 set (for Chiller) 250 A TPN MCCB '35 ka' with TM release etc. with MFM showing V,A, KWH, KVA & ON/OFF/Trip indications, complete - 2 set (for HWG) 40 A TPN MCCB '25 ka' with TM release etc. complete - 4 set (Chilled Water pumps), 40 A TPN MCCB '25 ka' with TM release etc. complete - 2 set (Hot Water pumps), 63 A TPN MCCB '25 ka' with TM release etc. complete - 2 set (AHU) with suitable By-Pass VFD starter Panel, 16 A TPN MCCB '25 ka' with TM release etc. complete - 2 set (Humidifier)
Electrical cable: Supply of PVC insulated armoured aluminium conductor cables of 1.1 Kv grade
3 1/2 Core - 120 mm2
Electrical cable: Supply of PVC insulated armoured Copper conductor cables of 1.1 Kv grade
4 core - 10 mm2
4 core - 10 mm2
4 core - 10 mm2
Termination: Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3 1/2 Core - 120 mm2
Termination: Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
4 core - 16 mm2
4 core - 10mm2
4 core - 6 mm2
TEMP and RH Control System
DDC Controller-Supply, Installation, Testing & Commissioning of Standalone Intelligent Microprocessor based Programmable DDC with inbuilt HMI, Onboard Modbus port, with Process bus for network functionalities with KNX protocol. It should have SD card interface for application and operating system upgrade & operating temperature range should be -20 to 60 degree.Celsius. It should include suitable Enclosures with all accessories including necessary switchgear, step down transformer, internal power and control cabling (excluding power & control cable to Fan), complete in all respect & as required to suit the site conditions etc.
Field devices-Supply, Installation, Testing & Commissioning of Air Differential Pressure Switch.
Field devices-Supply, Installation, Testing & Commissioning of Duct Temperature & RH Sensor.
SITC Temperature and RH setpoint adjustor Device
Immersion Temperature Sensor along with Thermowell
Supplying & laying of signal cables. (2 core x 1.5 Sq.mm), PVC insulated, Shielded tinned copper conductor cable.
Supply & Laying of MS Conduit 25 mm for Signal & Communication Cable
Supply & Laying of GI Flexible Pipe
Supply, Installation, & Fixing of Aluminium cladding
Supply, Installation, Testing & Fixing of Weather protective Coating for Insulation
Supply, Installation, Testing & Fixing of Fiber glass
Supply, Installation, Testing & Commissioning of Turbo roof Ventilators as per the drawings and specifications
VISHAL BUILDERS
Parth Infrastructure Pvt. Ltd.
Prad Infra
NIMMA NARAYAN ENGINEERS & CONTRACTORS
SHRI GURMUKHDAS CONTRACTORS PVT. LTD.
QUICK BUILDERS
RIC Projects Pvt. Ltd.
Rds Project ltd.
stage.html
html • 0.07 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid