Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.7 LAccepted-AOC FLAT NO 301 PEARL APARTMENT PLOT NO 121 SECTOR 8A AIROLI NAVI MUMBAI 400708 | NAVI MUMBAI | THANE | MAHARASHTRA | 400708 | L1 | Accepted-AOC Accepted. Being the L1 bidder. | |
| 2 | L2₹18.1 L+₹43,059.50 (2.44%)Rejected-AOC SHOP NO 10 BMC SHOPPING CENTRE MITHA NAGAR GOREGAON WEST MUMBAI 400 104 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400104 | L2 | Rejected-AOC Rejected as not being the lowest bidder. | |
| 3 | L3₹18.3 L+₹64,776.44 (3.66%)Rejected-AOC | L3 | Rejected-AOC Rejected as not being the lowest bidder. | |
| 4 | L4₹21.3 L+₹3.7 L (20.7%)Rejected-AOC | L4 | Rejected-AOC Rejected as not being the lowest bidder. |
| Sl No | Description | Qty | Unit | Radha Engineering Services L4 | R J ENTERPRISES L1 | Shree Ayyappa Engineering L2 | Chaudhary Enterprises L3 |
|---|---|---|---|---|---|---|---|
| 1.00 | Excavation in trenches n.exc 1.5 m wide and n. exc 1.5 m in depth and getting out in soft/loose soil for removing/laying of cables complete all as specified and as directed. | 245.16 | Cum | 250 ₹61,290 | 150 ₹36,774 Lowest | 200 ₹49,032 | 199 ₹48,786.84 |
| 2.00 | Returning, filling including spreading , leveling , watering and well ramming in layers n.exc 25 cm complete all as specified and as directed. | 162.53 | Cum | 40 ₹6,501.2 | 40 ₹6,501.2 | 20 ₹3,250.6 Lowest | 49 ₹7,963.97 |
| 3.00 | Removing excavated material to a distance n.exc 50 m and depositing where directed at a level n.exc 1.5 mtr above the starting point complete all as specified and as directed. | 74.37 | Cum | 40 ₹2,974.8 | 200 ₹14,874 | 30 ₹2,231.1 Lowest | 59 ₹4,387.83 |
| 4.00 | M&L for river washed river sand and screened dry for caushioning to ug cables in trenches below and around under ground cable for coushioning of cable in ducts including spreading and levelling complete all as specified and as directed. | 24.3 | Cum | 1,200 ₹29,160 | 650 ₹15,795 Lowest | 1,000 ₹24,300 | 900 ₹21,870 |
| 5.00 | Supply, Lay, Test & Commissioning cable LT XLPE insulated and screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade of Size 10 Sqmm, 4 core complete all as specified and as directed. | 250 | RM | 200 ₹50,000 | 145 ₹36,250 Lowest | 166 ₹41,500 | 159 ₹39,750 |
| 6.00 | Supply, Lay, Test & Commissioning cable LT XLPE insulated and screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade of Size 25 Sqmm, 3.5 core complete all as specified and as directed. | 260 | RM | 255 ₹66,300 | 190 ₹49,400 Lowest | 210 ₹54,600 | 197 ₹51,220 |
| 7.00 | Supply, Lay, Test & Commissioning cable LT XLPE insulated and screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade of Size 35 Sqmm, 3.5 core complete all as specified and as directed. | 250 | RM | 315 ₹78,750 | 260 ₹65,000 | 265 ₹66,250 | 249 ₹62,250 Lowest |
| 8.00 | Supply, Lay, Test & Commissioning cable LT XLPE insulated and screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade of Size 120 Sqmm, 3.5 core complete all as specified and as directed. | 110 | RM | 875 ₹96,250 | 620 ₹68,200 Lowest | 753 ₹82,830 | 699 ₹76,890 |
| 9.00 | Supply, Lay, Test & Commissioning cable LT XLPE insulated and screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade of Size 150 Sqmm, 3.5 core complete all as specified and as directed. | 100 | RM | 1,050 ₹1,05,000 | 690 ₹69,000 Lowest | 893 ₹89,300 | 879 ₹87,900 |
| 10.00 | Supply, Lay, Test & Commissioning cable LT XLPE insulated and screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade of Size 240 Sqmm, 3.5 core complete all as specified and as directed. | 90 | RM | 1,650 ₹1,48,500 | 1,350 ₹1,21,500 Lowest | 1,420 ₹1,27,800 | 1,419 ₹1,27,710 |
Tender Value
₹25.4 L
EMD Value
₹50,800
Closing Date
21 Sept 2024, 6:00 pmClosed
GE(NW) BHANDUP
GE(NW) BHANDUP, MUMBAI
REPAIR REPLACEMENT OF STREET LIGHT, LT PANELS, APFC PANELS, LT CABLES AND JOINTS AT INS HAMLA UNDER GE (NW) BHANDUP
2024_MES_658480_2
8336/B
Open Tender
Civil Works
Item Rate
270 days
GHATKOPAR
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE(NW) BHANDUP
₹50,800
Yes
12 Sept 2025
10 Jul 2024
23 Sept 2024
10 Jul 2024
21 Sept 2024
17 Jul 2024
10 Jul 2024 - 15 Jul 2024
Amount
Excavation in trenches n.exc 1.5 m wide and n. exc 1.5 m in depth and getting out in soft/loose soil for removing/laying of cables complete all as specified and as directed.
Returning, filling including spreading , leveling , watering and well ramming in layers n.exc 25 cm complete all as specified and as directed.
Removing excavated material to a distance n.exc 50 m and depositing where directed at a level n.exc 1.5 mtr above the starting point complete all as specified and as directed.
M&L for river washed river sand and screened dry for caushioning to ug cables in trenches below and around under ground cable for coushioning of cable in ducts including spreading and levelling complete all as specified and as directed.
Supply, Lay, Test & Commissioning cable LT XLPE insulated and screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade of Size 10 Sqmm, 4 core complete all as specified and as directed.
Supply, Lay, Test & Commissioning cable LT XLPE insulated and screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade of Size 25 Sqmm, 3.5 core complete all as specified and as directed.
Supply, Lay, Test & Commissioning cable LT XLPE insulated and screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade of Size 35 Sqmm, 3.5 core complete all as specified and as directed.
Supply, Lay, Test & Commissioning cable LT XLPE insulated and screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade of Size 120 Sqmm, 3.5 core complete all as specified and as directed.
Supply, Lay, Test & Commissioning cable LT XLPE insulated and screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade of Size 150 Sqmm, 3.5 core complete all as specified and as directed.
Supply, Lay, Test & Commissioning cable LT XLPE insulated and screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade of Size 240 Sqmm, 3.5 core complete all as specified and as directed.
Supplying and laying unreinforced precast concrete cable cover class LV type 1, flat, size 250 x 150 x 40 mm complete all as specified and as directed.
Supply and laying DWC HDPE pipe of pressure rating 6 kgf/cm2 (PE-63 grade) of size 32 mm bore laid in trenches for passing of cable complete all as specified and directed.
Supply and laying DWC HDPE pipe of pressure rating 6 kgf/cm2 (PE-63 grade) of size 40 mm bore laid in trenches for passing of cable complete all as specified and directed.
Material and labour for GI tubes "Medium Grade" 50 mm bore with and including all fittings laid in trenches/road crossing/floors etc for cable protection complete all as specified and directed.
Material and labour for GI tubes "Medium Grade" 80 mm bore with and including all fittings laid in trenches/road crossing/floors etc for cable protection complete all as specified and directed.
Supply and fixing in repairs LED bollards light fitting 10 to 15 watt mushroom shaped made in cast aluminium spigot housing with decorative clear acrylic diffuser for pleasant light output and weather proof and IP66 protection, PF>0.95, LED light luminous efficiency shall not be less than 90 Lumens/Watt and the colour rendering index shall not be less than 70 and Correlated Colour Temperature is 6500K and light should complying ISI and BIS marking complete all as specified and directed.
Supply and fixing in repairs LED post top lanterns fitting made in cast aluminium spigot housing with decorative clear acrylic diffuser and LED light luminous efficiency shall not be less than 90 Lumens/Watt and the colour rendering index shall not be less than 70 and Correlated Colour Temperature is 6500K and light should complying ISI and BIS marking 12/15 watt complete all as specified and directed.
Supply and fixing in repairs highly efficient high power multi LED flood fitting 150 watts with pressure die cast aluminium housing reflector and enclosed with toughened glass IP66 protection, PF>0.95, LED light luminous efficiency shall not be less than 90 Lumens/Watt and the colour rendering index shall not be less than 70 and Correlated Colour Temperature is 6500K and light should complying ISI and BIS marking complete prewired and connecting with 0.5 sqmm 3 core flexible wire including fixing arrangement on wall etc complete including dismantling of existing unserviceable flood light fittings complete all as specified and directed.
Supply and fix in repairs highly efficient high power LED street light fitting 100 W with pressure die cast aluminium housing reflector and enclosed with heat resistant toughened glass IP66 protection, PF>0.95, LED light luminous efficiency shall not be less than 90 Lumens/Watt and the colour rendering index shall not be less than 70 and Correlated Colour Temperature is 6500K and light should complying ISI and BIS marking protection AC 240 Volts 50 HZ refractive lens with suitable electronic drive PF > 0.9 complete including taking exiting unserviceable street light fitting complete all as specified and as directed.
Supply and fix in repairs highly efficient high power 45/50 W LED street light fitting with pressure die cast aluminium housing reflector and enclosed with heat resistant toughened glass IP66 protection AC 240 Volts 50 HZ refractive lens with suitable electronic drive PF > 0.9 complete including taking exiting unserviceable street light fitting complete all as specified and as directed.
Supply and fix in repairs pipe bracket made out of 40 mm dia GI pipe, medium grade, upto 1.5 mtr long, bent to shape and fixed on existing pole/ wall complete all as specified and directed. Note : Clamps nuts bolts etc will be measured and paid seprately under relevant items complete all as specified and as directed.
Supply and fixing in replacement pole mounting FRP looping box ISI marked type of size 250mm x 175mm x 100 mm, 3 phase with locking arrangements including necessary nut, bolt and clamps of the flat iron of size 25mm x 4 mm comprising of MCB SP 6 Amps, 240 Volts, 10 KA, 'C' series and 3 phase connector 100Amp for incoming/outgoing cables with proper fixing arrangements on pole / wall complete all as specified and directed.
Supply and fix in replacement of FRP looping box ISI marked of size 155x210x92 mm with connector, MCB 6 Amps, Din Rail, GI clamps made out of GI flat of size 25mm X 3 mm channel including making connections complete all as specified and directed.
M & L in repairs for for PVC copper cable 3 core, 2.5 sqmm copper conductor 1100 Volt grade multi core multi stranded PVC insulated unsheated drawn through and including PVC conduit and accessories fixing on poles/ wall with clamps, nuts bolts etc from FRP box to street light fiting complete all as specified and direcetd
M&L for Preparation of old exposed surface of LT steel tubular poles of any type / size with bracktes clamps etc and painting with one coat of aluminium paint upto 6 mtr long and exposed surface of pole yellow and black paint in strips alternative 30 cm wide upto 1.5 mtr from ground level including marking of pole no's with paint complete all as specified and as directed.
Dismantling exsting RCC & steel tubular poles with bracket & light and in lieu S&F 7 metre long hot dipped galvanised octagonal poles with top A/F 70mm bottom A/F 130 mm, made out of 3mm thick HT sheet alongwith base plate of size 220*220*12mm, including 1500mm long single arm bracket made out of 48mm dia, GI pipe, M20 in PCD 205mm, 700mm long and projected 100mm, "J" type EN8 grade set of 4 Nos foundation bolts alongwith templates, also including provision of the followings :- (a) MCB,SP,6A,230V, B series, 10KA mounted on and including 3mm thick plastic laminated sheet-01 No. (b) 4 way connector, bolt type having locking arrangement, weather proof and water proof control space : 01 No. Notes: (a) The rate quoted shall also be deemed to include the cost for provision of 50mm bore PVC pipe from cable trench to centre of the pole concrete of the pole concrete. (b) The earth work, RCC foundation reinforcement and form work will be measured and paid separately. (c) .quoted rate shall also be deemed to include for fixing of old light fitting retrived from dismantling. Make : BAJAJ Model BOP-7030 or its equivalent in Crompton/Philips / Wipro as approved by the GE.
M&L for mild steel TMT bars 6 mm to 8mm dia cut to length, bent to shape required, stirrups, spaces and binders and binding with mild steel wire (annealed) not less than 0.9 mm dia or securing with clips, complete all as specified and directed
M&L for RCC type B-1, 1:2:4 (nominal mix) using 20 mm graded stone aggregate as in footing, columns, post, pillars, piers, wall of culverts, suspended slabs, edges and struts etc complete all as specified and directed
M&L for form work to sides of concrete footings, columns, posts, pillars, piers, edges and struts of rectangular or triangular shape for rough finished flat concretesurface complete all as specified and directed
Supply and fixing in repairs high bay LED light fittings with highly efficient LED baylight capacity 100W made of pressure die cast aluminium housing extraded aluminium heat sink & enclosed with toughended glass IP66 protection, PF>0.95, LED light luminous efficiency shall not be less than 90 Lumens/Watt and the colour rendering index shall not be less than 70 and Correlated Colour Temperature is 6500K and light should complying ISI and BIS marking with all accessories prewired and making connection with 3 core copper flexible cable of size 23/.0076 from ceiling rose/PVC connector to light fitting, including fixing arrangement on truss with MS Clamps made out of 25x5mm flat iron with nuts, bolts etc complete painting with two coats synthetic enamel paint over a coat of red oxide complete dismantling existing unserviceable high bay fittings complete all as specified and as directed.
M & L prepration of old exposed surface of garden light pole 1.5/ 2.5/5 meter long applying two coats of aluminium paint over a coat of anticorrosive paint including painting to bottom of pole complete all as specified and directed.
Supply and fixing in repair maintenance lithium battery 11.1/33Ah (suitable for 32 watt solar lights) BMS circuit and other necessary wiresconnectors suitable for 32 watt integrated solar lights complete all as specified and directed.
Supply and fixing in repair maintenance lithium battery 11.1/19.8 Ah (suitable for 12 watt solar lights) BMS circuit and other necessary wiresconnectors suitable for 12 watt integrated solar lights complete all as specified and directed.
Materials and labour for servicing & spray painting factory made powder coated as approved colour and servicing of LT panel with burnts wiring, cleaning of panel , lugs, glands of any size, and others connected accessories complete all as specified and directed.
M&L for finding faults of LT UG cable XLPE, of any size and any length by using computerised / primary current injection method / any other method as directed by the GE and locating fault, cutting and removing the faulty portion of the cable and jointing with suitable cable joint and testing after jointing complete all as specified and as directed. Note: Joints shall be paid for separately.
Supply and fixing solar integrated system LED street light fitting 32 watt with Lithium ferrous phosphate battery dimming version(LFP),PIR inbuilt option of MPPT charge controller available solution with Li-Ion separately available power factor >0.9,having inbuilt surge protection device for overvoltage protection with all accessories prewired with IP 66 or better ingress protection with inbuilt Lithium Battery 11.1V/12.8Volt 33Ah, provided with 2 LED indicators : a green light to indicate charging in progress and a red LED to indicate deep discharge condition of the battery, green LED glow only when the battery is actually being charged, battery included in the luminary enclosure, with water proof (IP 66 or better) and corrosion resistant, material of construction of solar light fitting shall be FRP, LED lamp 32 watt (W-LED, 180-200 lm/watt, CRI>70) with 120Degree vide angle lens for better light distribution and colour temp-5700-6500K, Solar PV Module mono crystalline, > = 66 Wp. complete including warranty for light fitting 2 years after completion of the work complete all as specified and directed.
Supply installation, testing and commissioning of FAST ELECTRODE maintenance free Chemical Earthing of Dual Pipe Technology, each of 3 Meter long with Outer Pipe Diameter of 88mm (galvanised for 80-120 micron and wall thickness 1.80mm) and Inner Pipe diameter 48mm (galvanised for 80-120 micron and wall thickness 2.60mm). There shall be terminal of size 75 x 5.20mm for connection with two holes of 14mm diameter. FAST ELECTRODE shall be duly filled with the highly conductive, Non Magnetic, Non Corrosive material and duly sealed at both ends with lead terminal of 75x5.2mm at top. The ELECTRODE shall be of 'make' having approval of CPRI (Central Power Research Institute), Govt of India for a minimum short circuit current of 42 KArms for 1 Second with initial pick of 88.2 KA. The FAST ELECTRODE Earth Enhancing Compound (minimum 25Kg) shall be pored on alround the electrode. The chemical compound to be used shall be as per the manufacturer's instructions of 'Electrode' and as also certified by any BIS (Bureau of Indian Standards) accredited laboratory. Make : Fast Electrode or equivalent as approved by the GE. Notes:- (i) The contractor shall procure the above materials either directly from the manufacturer(s) or their authorised dealers only and shall produce the original purchase vouchers alongwith original manufacturer's test certificates and other authenticated documents in compliance of the provisions as mentioned in the above item. Also all the requisite testing as specified above, in relevant IS and as directed by the GE shall be got done by the contractor. Cost of all the above elements shall be deemed to be included in the contractor's quoted rates. (ii) Any additional quantity of Earth Enhancing Compound in case required to obtain the desired results, the same also be provided by the contractor without any additional cost to the Govt. and quoted rates of above item shall be deemed to include the above element also.
Comprehensive maintenance of electrically operated travelling (EOT) crane of 05 MT, Span -44900 mm, SWL-5000 Kgs capacity, floor operated comprising of hoist motor, micro motor, long travel motor, cross travel motor, gear box, control panel and other connected accessories installed at NAE Santacruz complete all as specified and as directed.
M & L for painting 5 ton crane completely with two coats of golden yellow paint including preparation of existing surface by scrapping detoritied paint etc. complete all as specified and as directed.
To carry out load Test of 5 MT Crane as per Manufacturer norms and provide a load test certificate by manufacturer complete all as specified and as directed.
Repair, Maintenance & Servicing of DG Set 500 KVA of approved make complete including with B Check through OEM complete all as specified and as directed.
Material only for carrying out 'B' check for 500KVA DG set all complete all as specified and as directed. Note : Rate quote shall be deemed to be inclusive of spares but excluding engine oil.
Supply and replacement of Greaves Max Therm Lub Oil
Supply and replacement of Oil filter
Supply and replacement of Fuel filter
Supply and replacement of K Kool additive oil
Comprehensive /Annual maintenance of CCTV System installed at NAE Santacruz and comprising of the following items as under :- Mini PTZ Dome cameras-4 Nos 16 Ch digital video recorder (DVR) - 01 No KBD digital keyboard/Joystick 24 Volt 2.1 Amp power supply -03 Nos Professiona CCTV Bosch monitor 21.5"-01 No Panasonic 22" LED TV -01 Nos 2 TB Survelliance harddisk Note:- a) The complaint to be attended within 24 working hours (b) The equipment will be maintained on SITE incase ofor a major repair the equipment will be taken to the company workshop through return gate pass. (c) spares will be charged on respective items.
Comprehensive Annual maintenance of fire alarm system installed at NAE Santacruz comprising of following items Main control panel -02 Nos Heat and smoke detector-150 Nos Mannual call point -12 Nos Hooter cum strobe- 20 Nos Note:- a) The complaint to be attended within 24 working hours (b) The equipment will be maintained on SITE incase ofor a major repair the equipment will be taken to the company workshop through return gate pass. (c) spares will be charged on respective items.
Supply and fix in repair Smoke and Heat Multisensor detector complete all as specified and directed. Make as approved by GE.
Repair and maintenance of 75 HP fire service main pump multi stage having 2280 LPM at 80 Mtr head multi stage pump of horizontal split casing running at 1450 RPM coupled with 100 HP diesel engine including servicing by replacing unserviceable items of gland packing , bearing and charging lubricants for smooth running including servicing of 75 HP diesel engine by replacing filters, lubricant oil including defective parts like coupling , oil air filters, servicing of radiator, replacement exhaust gasket, replacement of diesel supply and return pipes from tank to engine, battery leads and checking of charging circuit complete including base frame and pipe lines upto inside pump room of approved colour after preparation of existing surface complete all as specified and directed.
Takig down unserviceable Fire fighting motor pump set of capacity 3 phase 100 HP disconnecting the all necessary electrical connections and dismantlng the pump side and replacing the worn out winding and connected items like bearings, bush and coupling and rubber coupling etc; and rewinding with super enameled copper wire of suitable guage including varnishing, reassembling and re-coupling with pump set, testing and painting with synthetic enameled paint after preparing the existing surface complete all as specified.
Repair and maintenance of 7.5 hp fire service jockey / booster pump multi stage having 180 LPM at 56 mtrs head multi stage pump of horizontal split casing running at 2900 RPM coupled with 7.5 hp AC induction motor including servicing by replacing unserviceable items of gland packing, bearings, gaskets, nuts, bolts and charging lubricants for smooth running including painting of pumpset, base frame and pipe lines upto inside pumproom of approved colour after preparation of existing surface complete all as specified and directed.
Taking out split type air conditioner (both indoor and outdoor units) of capacity upto 02 ton of any make /type after disconnecting refrigerant pipes , drain pipe and electric connection and removing dust by using blower and cleaning the condenser coils and components by using water and caustic soda , checking and replacing the spares like relay, capacitors, thermostat, fan motor blades & blower and including servicing, overhauling and connecting of refrigerant pipe, drain pipe and charging of refrigerant and testing including fixing back in its original location complete all as specified and directed.
Repair/Replacement of fire fighting hose reel of 20mm dia & 30 mtrs long confirming to IS-5132 complete all as specified and directed
Repair/Replacement of fire fighting branch pipe & nozzle for 20 mm dia hose reel confirming to IS 8090 complete all as specified and directed
Repair/Replacement of fire fighting fire hydrant stand post with provn of single outlet confirming to IS 908 complete all as specified and directed
Repair /Replacement of fire fighting branch pipe & nozzle gun metal short branch pipes 63mm dia with male instantaneous inlet with Gun metal, hexagonal, detachable outlets nozzles bearing IS-903 complete all as specified and directed
Repair /Repalcement of Hydrant valves Female oblique type gun metal hydrant valve bearing IS 5290 type A 63 mm dia with flanged inlet and female instantaneous spring back outlet connection and complete with male blank cap & chain single hydrant valve complete all as specified and as directed.
Supply and fixing blower drum for split type air conditioner 2.0 ton capacity complete all as specified and as directed.
Supply and fixing outdoor fan blade for split type air conditioner 2.0 ton capacity complete all as specified and as directed.
Supply and fixing outdoor fan motor for split type air conditioner 2.0 ton capacity complete all as specified and as directed.
Supply and fixing running capacitor 45 mfd for split type air conditioner 2.0 ton capacity complete all as specified and as directed.
Supply and fixing starting capacitor 100 mfd for split type air conditioner 2.0 ton capacity complete all as specified and as directed.
Supply and fixing fan capacitor 4 mfd for outdoor unit for split type air conditioner 2.0 ton capacity complete all as specified.
Supply and fix new hermetically sealed compressor in existing split type air conditioner 2.0 ton capacity including initial filling of refrigerant gas to the required pressure , brazing making electric/piping connection etc complete all as specified and directed.
Material and labour for disconnecting & stopping of incoming/ washout and outgoing pipes by making suitable arrangements to avoid chocking of pipe line, removing total water from the tank manually & depositing the same in low laying areas all as directed cleaning the underground sump from in side by using high pressure cleaning method with rotary jet wilth approved detergent rubbing/ scrapping wall / floor /ceiling with wet vaccume cleaner sucking out all dirty water and disinfecting the tank chemical treatment (chemical approved by FOA/WHO) to make sump totally cleaned and bacteria free including painting pit cover marking date of cleaning and next due and pipes (raising delivery wash out and over flow with sluice valves) including painting of pipe with two coats of synthetic enemel paint as per MES colour approved by EIC at site for RCC underground sump 2000 gallons at fresh water sump and fire sump at NAE Santacruz.
Deduct Credit for Demolished/ Dismantled material Rs. (-) 71,585.00 (Minus) as listed in Schedule of Credit Note1: Tenderers will not quote against this item being a tentative amount to be considered to arrive at the 'Contract Sum' Note 2:- The tenderer must keep in mind when quoting rates against items out in multiple store house having height 4 mts to 7 mts. Necessary scaffolding and saftey measures required during execution of work are including in this items.
Shree Ayyappa Engineering (BID ID -3073207)
Chaudhary Enterprises (BID ID -3065775)
Radha Engineering Services (BID ID -3072129)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .