Loading…
Loading…
Updated dates
Tender Value
₹37.2 L
EMD Value
₹74,380
Closing Date
5 Jun 2026, 6:00 pmDue today
GE DANAPUR CANTT
GE DANAPUR CANTT
SPL REPAIR REPLACEMENT UPGRADATION OF ELECTRIC DISTRIBUTION SYSTEM APFC PANELS AND ALLIED WORKS AT HQ JANDB SUB AREA ADM OFFICE AND CONNECTED AREA UNDER GE DANAPUR CANTT
2026_MES_764214_1
CA NO GE/DNR/T-05 of 2026-27
Open Tender
Civil Works
180 days
DANAPUR CANTT
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE DANAPUR CANTT
₹74,380
Yes
8 May 2026
8 May 2026
12 Jun 2026
8 May 2026
5 Jun 2026
22 May 2026
Supply, laying, jointing & testing in replacement of cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 1100 volts grade, of following sizes complete all as specified and directed.
3.5 core x 185 Sqmm
3.5 core x 150 Sqmm
3.5 core x 95 Sqmm
3.5 core x 70 Sqmm
3.5 core x 50 Sqmm
2 core x 10 Sqmm
Supply ,fabrication, installation and testing in replacemnt of LT Panel out door type factory made , water and vermin proof protection of suitable size made out of 3.15 mm thick CRCA sheet dully supported with mild steel angle iron of suitable size vertical frame and legs with mild steel flat iron suitable size in horizontal sides of the frame with front and back side openable ,single hinged door / shutter with locking arrengement and powder coated finish both internal and external steel surfaces after necessary preparation of steel surfaces including providing PCC (1:3:6) type C2 foundation of suitable size and connections of all outgoing / incomming cable inclusive of necessary excavation and earthwork as required including the following fitment accessories and also including removing old exisisting one complete all as specified and directed. Note: Rate of earthwork and PCC work are deemed to be inclusive in this item.
INCOMMING
4 Pole MCCB 630 Amps , adjustable thermal magnetic release type, 4 poles, 415 Volts, Ics = 100% Icu, 50 KA breaking capacity including all fixing accessories with both ends spreader links -01 Nos
LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC -01 set (set of three) Make :- Legrand/L&T/Schneider.
Aluminium busbar of 800 amps rated capaacity wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including hydrograpic insulators with nuts & bolts at both ends = 06 Nos
OUTGOING
4 Pole MCCB 400 Amps , adjustable thermal magnetic release type, 4 poles, 415 Volts, Ics = 100% Icu, 36 KA breaking capacity including all fixing accessories with both ends spreader links -02 Nos
4 Pole MCCB 250 Amps, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 36 KA breaking capacity including all fixing accessories with both ends spreader links -01 Nos
4 Pole MCCB 160 Amps, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 36 KA breaking capacity including all fixing accessories with both ends spreader links -02 Nos
LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC -04 set (set of three) Make :- Legrand/L&T/Schneider.(For each O/G)
Enamelled iron danger notice plate of 1.60 mm thick mild steel sheet of size 200 mm X 150mm , white with letters , figures and conventional skull and bones in signal red and fixed with nuts and bolts on door / shutter of JB for LT -01 No.
Supply ,fabrication, installation and testing in replacemnt of LT Panel out door type factory made , water and vermin proof protection of suitable size made out of 3.15 mm thick CRCA sheet dully supported with mild steel angle iron of suitable size vertical frame and legs with mild steel flat iron suitable size in horizontal sides of the frame with front and back side openable ,single hinged door / shutter with locking arrengement and powder coated finish both internal and external steel surfaces after necessary preparation of steel surfaces including providing PCC (1:3:6) type C2 foundation of suitable size and connections of all outgoing / incomming cable inclusive of necessary excavation and earthwork as required including the following fitment accessories and also including removing old exisisting one complete all as specified and as directed. Note: Rate of earthwork and PCC work are deemed to be inclusive in this item.
INCOMMING
4 Pole MCCB 320 Amps , adjustable thermal magnetic release type, 4 poles, 415 Volts, Ics = 100% Icu, 36 KA breaking capacity including all fixing accessories with both ends spreader links -01 Nos
LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC -01 set (set of three) Make :- Legrand/L&T/Schneider.
Aluminium busbar of 500 amps rated capaacity wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including hydrograpic insulators with nuts & bolts at both ends = 06 Nos
OUTGOING
4 Pole MCCB 200 Amps , adjustable thermal magnetic release type, 4 poles, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links -02 Nos
4 Pole MCCB 160 Amps, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links -02 No
MCB TPN 40 Amps C series , adjustable thermal magnetic release type, 4 poles, 415 Volts, Ics = 100% Icu, 10 KA breaking capacity including all fixing accessories with both ends spreader links -02 Nos
LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC -04 set (set of three) Make :- Legrand/L&T/Schneider.(For each O/G)
Enamelled iron danger notice plate of 1.60 mm thick mild steel sheet of size 200 mm X 150mm , white with letters , figures and conventional skull and bones in signal red and fixed with nuts and bolts on door / shutter of JB for LT -01 No.
Supply, Installation, test and Commissioning factory fabricated, out door type,in replacement LT FEEDER PILLAR BOX Double Door , Both side openable made out of 3.15 mm thick CRCA Sheet of size 0.7mX0.6mX0.35m with projected Globe roof for rain water protection duly treated through 8 tank pre treatment process and painted with epoxy powder coated mat finish of SIEMENS GREY structural RAL 7032 shade colour Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embeded with 50X50X6mm Mild Steel Angle Iron Frame and 600 mm above the Normal Ground Level comp -lete with internal connection with suitable size of cable ,cable lugs,and cable glands PCC Foundation in Cement Concrete 1:3:6 (20mm Graded Stone Aggregate) and Test-ing after Installation complete all as specified and comprising of the following :–
(a) Aluminium bas bar 500amps - 04 Nos, supported with suitable size of heavy duty porcelain stand lock with suitable size of brass nut, bolts and washer with heat shrinkable PVC sleeving. The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral. b) MCCB 320 amps ,415 volt ,36 KA Breaking capacity 4 pole Electromagnetic release duly connected to Bus Bar As IN COMING - 01 Nos
Supply ,fabrication, installation and testing in replacemnt of LT Panel out door type factory made , water and vermin proof protection of suitable size made out of 3.15 mm thick CRCA sheet dully supported with mild steel angle iron of suitable size vertical frame and legs with mild steel flat iron suitable size in horizontal sides of the frame with front and back side openable ,single hinged door / shutter with locking arrengement and powder coated finish both internal and external steel surfaces after necessary preparation of steel surfaces including providing PCC (1:3:6) type C2 foundation of suitable size and connections of all outgoing / incomming cable inclusive of necessary excavation and earthwork as required including the following fitment accessories and also including removing old exisisting one complete all as specified and as directed. Note: Rate of earthwork and PCC work are deemed to be inclusive in this item.
INCOMMING
4 Pole MCCB 250 Amps , adjustable thermal magnetic release type, 4 poles, 415 Volts, Ics = 100% Icu, 36 KA breaking capacity including all fixing accessories with both ends spreader links -01 Nos
LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC -01 set (set of three) Make :- Legrand/L&T/Schneider.
Aluminium busbar of 500 amps rated capaacity wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including hydrograpic insulators with nuts & bolts at both ends = 06 Nos
OUTGOING
4 Pole MCCB 160 Amps , adjustable thermal magnetic release type, 4 poles, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links -02 Nos
4 Pole MCCB 100 Amps, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links -02 No
MCB TPN 40 Amps C series , adjustable thermal magnetic release type, 4 poles, 415 Volts, Ics = 100% Icu, 10 KA breaking capacity including all fixing accessories with both ends spreader links -02 Nos
LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC -04 set (set of three) Make :- Legrand/L&T/Schneider.(For each O/G)
Enamelled iron danger notice plate of 1.60 mm thick mild steel sheet of size 200 mm X 150mm , white with letters , figures and conventional skull and bones in signal red and fixed with nuts and bolts on door / shutter of JB for LT -01 No.
Supply and Fixing of HDPE Double Wall corrugated pipe IS 16205:Part 24 2017 for protection of cable including all couplers, rubber ring joint, cutting to required length, alignment, laying in position, making good, of size 90mm outer dia,testing complete all as specified and as directed.
Supply and Fixing of HDPE Double Wall corrugated pipe IS 16205:Part 24 2017 for protection of cable including all couplers, ribber ring joint, cutting to required length, alignment, laying in position, making good, of size 110mm outer dia,testing complete all as specified and as directed.
Excavation in trenches, in any type of soil not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation, etc or not exceeding 10 Sqm on plan for shafts, cesspits, manholes, pier holes, etc and getting out in any type of soil etc complete all as specified and directed.
Removing excavated soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
Returning, filling in excavated approved soil, including spreading, leveling, watering and well ramming in layers not exceeding 25cm each complete all as specified and directed.
M & L in repair for dry sand cushioning to underground cables with 8cm thick before laying of cables and 15cm thick after laying and stretching of cable complete all as specified and directed. Note: Punned down thickness of sand shall be measured for payment purposes.
M & L in repair for old size sub class ‘B’ bricks, laid in trenches as cable covers complete all as specified and directed.
Supply and fixing of GI tubing, light grade, 80 mm bore with all fitting lais in trenches / pole / wall for protection of cables in repairs complete all as specified and directed.
Supply and laying in replacement GI tubing light grade of size 40 mm for cable protection on road/drain/floor/pole including necessary clamps 40x4mm.
M & L for horizontal boring mechanically across the existing road without disturbing the road surface for inserting 80/40 mm bore GI pipe complete all as specified and directed. Note :- GI pipe will be measured and paid separately in respective item of sch'A'.
S & F in replacement of hot press moulded SMC junction / terminal box of size with internal diamensions of 200 x 140 x 95 mm with hinged door, incl provision of 4 way connector 415 Volts made out of polycarbonate or bakelite and 1 No MCB of 6 Amps with DIN bar, drilling holes for cable connections, connecting incoming and or out going cables by providing suitable size of cable lugs/glands, fixied on pole by means of clamps made out of MS flat iron of size 25 mm x 3 mm including dismantling of old unserviceable all as specified and as directed.Make: Hensel/Syntex/C&S
Supply and fixing in replacement power factor correction capacitor, 15 KVAR, heavy duty cylindrical type 440 volts 50 Hz complete including taking down old unserviceable capacitor complete all as specified and directed.
M&L for Advance Maintenance Free G.I. SAFE EARTHING Electrode with PIPE of not less than 50 mm outer dia( THICKNESS NOT LESS THAN -2.5MM) and two meter length, The electrode should be of galvinised (80 -100 micron) along with earth lead as Galvanised steel strip of size 32 X6 mm 7.5 m . The GI Electrode shall be pre-filled with Cristaline Conductive Material (CCM) . The GI electrode shall be surrounded with 25 kg BackFill compound to provide maximum contact between the electrode and Back Fill Compound. GI Electrode Shall be tested from CPRI.The earting pit should be cover with pcc(1:2:4 , B1) cover ,of 450 x 450 mm complete all as specified and directed. Note : After completion earth resistance shall be recorded with earth megger and the record should be submitted to to department duly signed by contractor and Engineer in Charge.
Removing existing PCC / cement concrete / tile flooring / interlocking paver blocks / stone slabs carefully, including stacking serviceable materials for reuse, and disposal of unserviceable debris.Reinstating the surface by providing Plain Cement Concrete 1:4:8 type D2 using 40 mm graded stone aggregate of required thickness for refixing original tiles/paver blocks to match with existing level, line and finish, complete in all respects as specified and directed.
Please Enable Macros to View BoQ information
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.40 MB
Tender9041.pdf
Tender Documents • 0.62 MB
ParticularSpecification9018doc.pdf
Additional Documents • 0.32 MB
Credit9041.pdf
Additional Documents • 0.06 MB
BOQ_855971.xls
BOQ • 8.52 MB
Download all tender documents and submit your bid