Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹42.0 LAccepted-AOC 205 PARSHAV VIHAR PLOT NO 50 1 P EXTN PATPARGANJ DELHI 110092 | DELHI | EAST DELHI | DELHI | 110092 | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹49.8 L+₹6.8 L (15.9%)Rejected-Finance 205 PARSHAV VIHAR PLOT NO 50 IP EXTN PARPARGANJ DELHI 110092 | EAST | DELHI | 110092 | L2 | Rejected-Finance Being other than lowest | |
| 3 | Rejected-Technical GROUND FLOOR F 11 PHASE II MAYAPURI WEST DELHI DELHI 110064 | DELHI | WEST DELHI | DELHI | 110064 | - | Rejected-Technical Documents not submitted as per requirement | |
| 4 | Rejected-Technical A 3 257 JANAKPURI NEW DELHI 110058 | WEST DELHI | DELHI | 110058 | - | Rejected-Technical Documents not submitted as per requirement |
| Sl No | Description | Qty | Unit | SANJEEV ENTERPRISES L1 | Saini Enterprises L2 |
|---|---|---|---|---|---|
| 1.00 | S & F in replacement of Handy and light weight remote control for patients with remote with jacket to fix mount on wall and having Battery type: 12volts DC / 23A & Range indoors: 20-30 meters complete all as specified and directed. Make:FORBIX SEMICON / Honeywell/ Hochiki. | 120 | Each | 2,300 ₹2,76,000 | 2,150 ₹2,58,000 Lowest |
| 2.00 | S & F in replacement of 4-digit receiver display Operates on 12VDC (comes along with 220-110VAC converter) having display size of extra large alphabets complete all as specified and directed.
Make : - FORBIX SEMICON / Honeywell/ Hochiki. | 3 | Each | 28,320 ₹84,960 | 25,000 ₹75,000 Lowest |
| 3.00 | S & F in replacement of Repeater booster enhances the range of signals furthermore high power repeater provides additional 50-60meters and additional repeater improves the signal to noise ratio (SNR), at some multiple repeaters in series are required complete all as specified and directed.
Make :FORBIX SEMICON / Honeywell/ Hochiki | 3 | Each | 10,000 ₹30,000 | 7,500 ₹22,500 Lowest |
| 4.00 | S & F in replacement Power supply adapter converter of input as 220V AC to 12V DC as out put complete all as specified and directed. | 3 | Each | 250 ₹750 Lowest | 250 ₹750 Lowest |
| 5.00 | S & F in replacement alkaline battery 23A 12V as out put complete all as specified and directed. | 300 | Each | 50 ₹15,000 Lowest | 50 ₹15,000 Lowest |
| 6.00 | Comprehensive maintemance of hermetically sealed sensor sliding/swing door of OT-11 Nos and ICU- 01 No, including all mechanical,electrical, electronic and structural component to ensure smooth silent and hygienic opeartion.The work includes preventive and corrective maintenance, cleaning, lubrication, calibration, testing and replacement of defective part (Major Defective part that need to be replaced shall be measuered and paid under respective item of this schedule).
The scope of work shall include but not be limited to the following:
1. Mechanical Components including :
(i) Door leaf alignment,track,rollers,hinges,guide rails,handles,seals and all moving parts.
(ii) Lubrication of bearing,roller and guides.
(iii)Adjustment of closing/opening speed and pressure.
2.Electrical and Automation System :
(i)Checking and servicing of sensors,control units,push buttons,touchless switches,magnetic lock and power supply.
(ii)Inspection and maintenance of motor,gear assembly and drive mechanism.
(iii)Replacement of damage cable, connectors and wiring where required.
3. Safety and sealing system :
(i) Checking of hermetically sealing,gaskets and air tightness.
(ii) Replacement of worn-out seals and adjustment for proper closure.
(iii) Testing of emergency manual operation and interlock system.
4.Periodic Preventive maintenance:
(i) Monthly Servicing and performance checks as per manufacturer's recommendations.
(ii) Record keeping of maintenance activities, inspection and repairs
Note:- The item need to be replaced shall be measured and paid under respective item. | 11 | Per Month | 3,000 ₹33,000 Lowest | 3,000 ₹33,000 Lowest |
| 7.00 | S & F in replacement motor for sliding door ICU complete all as specified and as directed. | 1 | Each | 20,000 ₹20,000 | 16,000 ₹16,000 Lowest |
| 8.00 | S & F in replacement controller for sliding door ICU complete all as specified and as directed. | 1 | Each | 20,000 ₹20,000 | 16,000 ₹16,000 Lowest |
| 9.00 | S & F in replacement wheel for sliding door ICU complete all as specified and as directed. | 1 | Set of Eight | 1,500 ₹1,500 Lowest | 1,500 ₹1,500 Lowest |
| 10.00 | S & F in replacement anti jump roller for sliding door ICU complete all as specified and as directed. | 1 | Set of four | 1,000 ₹1,000 Lowest | 1,000 ₹1,000 Lowest |
Tender Value
₹48.9 L
EMD Value
₹97,814
Closing Date
4 Feb 2026, 6:00 pmClosed
GE (EAST) DELHI CANTT-1
GE (EAST) DELHI CANTT-1
REPAIR/ MAINTENANCE OF UNSV NURSING CALL BELL SYSTEM ALONGWITH DISPLAY PANEL AND REMOTE PUSH SWITCHES, BED SIDE LAMPS, OT LIGHTS, OTLOW GLARE LIGHTS, OT SENSOR DOOR AND CONNECTED MISC E/M WORKS AT DIFFERENT WARDS AT BHDC UNDER GE (EAST) DELHI CANTT-1
2026_MES_748540_1
GE/DE-157/2025-26
Open Tender
Civil Works
Item Rate
335 days
GE (EAST) DELHI CANTT-1
Cat b(i)/ Class D
9 documents required · 9 mandatory
₹500
GE (EAST) DELHI CANTT-1
₹97,814
Yes
25 Mar 2026
14 Jan 2026
6 Feb 2026
14 Jan 2026
4 Feb 2026
28 Jan 2026
S & F in replacement of Handy and light weight remote control for patients with remote with jacket to fix mount on wall and having Battery type: 12volts DC / 23A & Range indoors: 20-30 meters complete all as specified and directed. Make:FORBIX SEMICON / Honeywell/ Hochiki.
S & F in replacement of 4-digit receiver display Operates on 12VDC (comes along with 220-110VAC converter) having display size of extra large alphabets complete all as specified and directed. Make : - FORBIX SEMICON / Honeywell/ Hochiki.
S & F in replacement of Repeater booster enhances the range of signals furthermore high power repeater provides additional 50-60meters and additional repeater improves the signal to noise ratio (SNR), at some multiple repeaters in series are required complete all as specified and directed. Make :FORBIX SEMICON / Honeywell/ Hochiki
S & F in replacement Power supply adapter converter of input as 220V AC to 12V DC as out put complete all as specified and directed.
S & F in replacement alkaline battery 23A 12V as out put complete all as specified and directed.
Comprehensive maintemance of hermetically sealed sensor sliding/swing door of OT-11 Nos and ICU- 01 No, including all mechanical,electrical, electronic and structural component to ensure smooth silent and hygienic opeartion.The work includes preventive and corrective maintenance, cleaning, lubrication, calibration, testing and replacement of defective part (Major Defective part that need to be replaced shall be measuered and paid under respective item of this schedule). The scope of work shall include but not be limited to the following: 1. Mechanical Components including : (i) Door leaf alignment,track,rollers,hinges,guide rails,handles,seals and all moving parts. (ii) Lubrication of bearing,roller and guides. (iii)Adjustment of closing/opening speed and pressure. 2.Electrical and Automation System : (i)Checking and servicing of sensors,control units,push buttons,touchless switches,magnetic lock and power supply. (ii)Inspection and maintenance of motor,gear assembly and drive mechanism. (iii)Replacement of damage cable, connectors and wiring where required. 3. Safety and sealing system : (i) Checking of hermetically sealing,gaskets and air tightness. (ii) Replacement of worn-out seals and adjustment for proper closure. (iii) Testing of emergency manual operation and interlock system. 4.Periodic Preventive maintenance: (i) Monthly Servicing and performance checks as per manufacturer's recommendations. (ii) Record keeping of maintenance activities, inspection and repairs Note:- The item need to be replaced shall be measured and paid under respective item.
S & F in replacement motor for sliding door ICU complete all as specified and as directed.
S & F in replacement controller for sliding door ICU complete all as specified and as directed.
S & F in replacement wheel for sliding door ICU complete all as specified and as directed.
S & F in replacement anti jump roller for sliding door ICU complete all as specified and as directed.
S & F in replacement motion sensor for sliding door ICU complete all as specified and as directed.
S & F in replacement safty sensor for sliding door ICU complete all as specified and as directed.
S & F in replacement encoder cable for sliding door ICU complete all as specified and as directed.
S & F in replacement glass clamp for sliding door ICU complete all as specified and as directed.
S & F in replacement belt for sliding door ICU complete all as specified and as directed.
S & F in replacement Return Pully for sliding door ICU complete all as specified and as directed.
S & F in replacement Belt Clamp set for sliding door ICU complete all as specified and as directed.
S & F in replacement floor guide for sliding door ICU complete all as specified and as directed.
S & F in replacement SMPS for sliding door ICU complete all as specified and as directed.
S & F in replacement Carrier head assembly for sliding door ICU complete all as specified and as directed.
S & F in replacement motor for OT door complete all as specified and as directed.
S & F in replacement controller for OT door complete all as specified and as directed.
S & F in replacement SMPS for OT door complete all as specified and as directed.
S & F in replacement Hand Sensor for OT door complete all as specified and as directed.
S & F in replacement safty beam sensor for OT door complete all as specified and as directed.
S & F in replacement foot switch for OT door complete all as specified and as directed.
S & F in replacement Roller set for OT door complete all as specified and as directed.
S & F in replacement belt for OT door complete all as specified and as directed.
S & F in replacement floor guide set for OT door complete all as specified and as directed.
S & F in replacement Belt Clamp Set for OT door complete all as specified and as directed.
S & F in replacement Carrier Assembly Set for OT door complete all as specified and as directed.
Comprehensive maintenance of Fire Alarm and Heat Detection System installed in OT and ICU complex through AMC (Make Argus Apolo) including all smoke detectors, heat detector , Smoke detector batteries and manual call points, sounders, control panels, and associated wiring and accessories. Detailed Scope of Work: General Maintenance: Contractor should responsible for Comprehensive preventive and corrective maintenance of the entire fire alarm and heat detection system installed in the premises of OT and ICU includes all parts like smoke detector, heat detector, wall sounder,Fire alarm panel, repeater panel , Manual Call point including Calibration of each loop with fire alarm panel complete with labour, and item required to replaced shall be covered under AMC including (Batteries of Smoke detector and heat detector / Smoke Detector / Heat Detector /Fire alarm Panel/ Repetaer Panel/ Wall sounder/ Manual Call point) to keep the system fully functional.The rate of the item need to be replaced deemed to be included in quoted rate.Nothing Extra in this respect shall be paid to the contrcator. System Components Covered under comprehensive maintennance: (i) Fire Alarm Control Panel (FACP) (ii) Repeater Panels (iii) Addressable / Conventional Smoke Detectors (iv) Heat Detectors (Rate-of-Rise / Fixed Temperature) (v) Manual Call Points (MCPs / Break Glass Units) (vi) Hooters / Sirens / Sounders / Flasher (vii) Interface Modules, Relay Modules, I/O Cards (viii) Power Supply Units and Batteries (ix) Cabling and Junction Boxes related to the fire alarm system NOTE FOR Sr. No. (i) to (ix) :- Any item need to be replaced for proper functioning of the Fire alarm system shall be replaced under the contract. Rate for the same deemed to be included in the quoted rate. Noting extra in that respect shall paid to the contractor.
Preventive Maintenance Activities: (i) Monthly inspection, testing, and servicing of all components. Cleaning of all detectors using manufacturer-approved methods. (ii) Testing of each detector and manual call point for proper operation. (iii) Verification of alarm annunciation at control panel and repeater panel. (iv) Testing of hooters/sounders and evacuation message (if applicable). (v) Checking of battery condition, charger output, and terminals. (vi) Software checks (for addressable systems) – loop communication, fault log review, and resetting. (vii) Calibration and replacement of faulty or aged sensors as needed. (viii) Ensuring all indicator lamps, buzzer, and mimic displays work correctly. Corrective Maintenance: (i)Attending breakdown calls on a priority basis (within 24 hours of fault reporting). (ii)Repair/replacement of defective modules, detectors, or accessories. (iii)Minor wiring repairs and termination corrections. (iv)Software updates or reprogramming if required. (v)Documentation and Reporting: (vi)Submission of monthly maintenance reports. (vii)Record of all tests, findings, and corrective actions taken. (viii)Maintenance logbook to be updated and countersigned by the client’s representative. (ix)Fault rectification certificates for each visit.
General Terms and Condition :- (i) All work shall be carried out only by authorised Rep of OEM and using all genuine spare parts supplied by OEM only, in this regard an MOU between OEM i.e M/S Argus (Apolo) and the Contractor must be perform ,A copy of the same MOU shall be uploaded with the tender document . (ii) Contractor should be responsible of proper functioning of all the system from current condition (either in malfunctioning or working) in the initial phase of contract and rate for for the same shall be included in the quoted. Nothing extra in that respect shall be paid to the contractor. (iii) Contractor through OEM shall be responsible for repair and replacement of all defective parts of the equipment as per OEM recommendation during entire comprehensive maintenance period. (iii) Preventive maintenance of all systems on monthly basis. (iv) Attending all complaints within 24 working hours intimated by Engr-in-Charge. (v) Field service report shall be maintained and submitted to the Engr-incharge after expiry of every month and before submission of RAR . (vi) The rates quoted by the contractor shall deemed to be inclusive of T&P etc (vii) A damage of Rs 500.00 per complaint per day shall be imposed on contractor, if the complaint shall not attended within 24 Hours of complaint intimated by Engr-in-Charge.
Comprehensive maintenance of Fire Alarm System installed in Medical Store through AMC (Make Seimen) including all smoke detectors, and manual call points, sounders, control panels, and associated wiring and accessories. Detailed Scope of Work: General Maintenance: Contractor should responsible for Comprehensive preventive and corrective maintenance of the entire fire alarm installed in the premises of Medical Store includes all parts like smoke detector, wall sounder,Fire alarm panel, Manual Call point including calibration of each loop with fire alarm panel complete with labour, and item required to replaced shall be covered under AMC including ( Smoke Detector /Fire alarm Panel/ Wall sounder/ Manual Call point) to keep the system fully functional.The rate of the item need to be replaced deemed to be included in quoted rate.Nothing Extra in this respect shall be paid to the contractor. System Components Covered under comprehensive maintennance: (i) Fire Alarm Control Panel (FACP) (ii) Addressable / Conventional Smoke Detectors (iii) Manual Call Points (MCPs / Break Glass Units) (iv) Hooters / Sirens / Sounders / Flasher (v) Interface Modules, Relay Modules, I/O Cards (vi) Power Supply Units and Batteries (vii) Cabling and Junction Boxes related to the fire alarm system NOTE For Sr. No. (i) to (vii) :- Any item need to be replaced for proper functioning of the Fire alarm system shall be replaced under the contract.Rate for the same deemed to be included in the quoted rate. Noting extra in that respect shall paid to the contractor.
Preventive Maintenance Activities: (i) Monthly inspection, testing, and servicing of all components. Cleaning of all detectors using manufacturer-approved methods. (ii) Testing of each detector and manual call point for proper operation. (iii) Verification of alarm annunciation at control panel and repeater panel. (iv) Testing of hooters/sounders and evacuation message (if applicable). (v) Checking of battery condition, charger output, and terminals. (vi) Software checks (for addressable systems) – loop communication, fault log review, and resetting. (vii) Calibration and replacement of faulty or aged sensors as needed. (viii) Ensuring all indicator lamps, buzzer, and mimic displays work correctly. Corrective Maintenance: (i)Attending breakdown calls on a priority basis (within 24 hours of fault reporting). (ii)Repair/replacement of defective modules, detectors, or accessories. (iii)Minor wiring repairs and termination corrections. (iv)Software updates or reprogramming if required. (v)Documentation and Reporting: (vi)Submission of monthly maintenance reports. (vii)Record of all tests, findings, and corrective actions taken. (viii)Maintenance logbook to be updated and countersigned by the client’s representative. (ix)Fault rectification certificates for each visit.
General Terms and Condition :- (i) All work shall be carried out only by authorised Rep of OEM and using all genuine spare parts supplied by OEM only, in this regard an MOU between OEM i.e M/S Seimens and the Contractor must be perform ,A copy of the same MOU shall be uploaded with the tender document . (ii) Contractor should be responsible of proper functioning of all the system from current condition (either in malfunctioning or working) in the initial phase of contract and rate for for the same shall be included in the quoted. Nothing extra in that respect shall be paid to the contractor. (iii) Contractor through OEM shall be responsible for repair and replacement of all defective parts of the equipment as per OEM recommendation during entire comprehensive maintenance period. (iii) Preventive maintenance of all systems on monthly basis. (iv) Attending all complaints within 24 working hours intimated by Engr-in-Charge. (v) Field service report shall be maintained and submitted to the Engr-in-Charge after expiry of every month and before submission of RAR . (vi) The rates quoted by the contractor shall deemed to be inclusive of T&P etc (vii) A damage of Rs 500.00 per complaint per day shall be imposed on contractor, if the complaint shall not attended within 24 Hours of complaint intimated by Engr-in-Charge.
S& F in replacement Bedside Light 3 Watt, 400 lumens - 3000k , separate on/off switches, shade material aluminium with powder coating, adjustable head for better beam and focus standard complete all as specified and as directed. Make :- Philips 48042 Black or equivalent in Bajaj/ Havells /Crompton
S&F in replacement Low glate OT light, modular recessed/Flush mount LED panel luminarie (2x2 or 595x595 mm nominal size) suitable for OT, high efficiency LED, SMD type in 40 to 50 watt having system lumens 4000 lumens, colour tempreture 5700K -6500K ,ultra -low glare complyiing with UGR<19 as per EN 12464-1 for visual comfort for 240 volt 50 Hz operation complete in all aspect all as specified and directed.
Supply, fixing and connecting in replacement recessed mounting back- LED 2'x2', 36 watt panel light with designer SKY diffuser tile in CRCA poder coated sheet steel housing with full opal diffuser suitable for Armstrong/ Grid Ceilings Type, size 595X595mm (Nominal),High lumen efficacy LED with viewing angle of 120 degree used to enhance the luman output Height suitable for White Housing & Isolated Electronic Driver, with Output Short-circuit protection, Surge Voltage protection minimum 2.5KV, safety & performance test as per IS:15885 Total system Lumen not less than 3600, in Cool day Light (6500K), Power factor>0.95, CRI (Ra) >80 with Average life of 50000 Burning hours complete with all accessories as required complete all as specified and as directed. Make: Halonix catpart no. HLFPR22-11-36-CW-SKY or equivalent
Comprehensive maintenance for shadowless LED 50 OT Light Double Dome of shaft, double arm, spring arm, dome arm, inside complete wiring of the unit including preventive and corrective maintennace of the entire system.The service shall cover all component such as LED, reflector, electronic control gear, arm suspension system ,balance spring mechanism,sterilizer handle,power supply unit,control panel,intensity control system and all electrical and mechanical part including scope of work for OT light at following location 1. OT -I -01 No 2. OT-II -01 No 3. OT-III -01 No 4. OT-IV -01 No 5. OT-V -01 No 6. OT-VI -01 No 7. OT-VII -01 No 8. OT-VIII -01 No 9. Minor OT -01 No 10. Labour Room OT-I -01 No 11. Labour Room OT-II -01 No 12. Labour Room OT-III -01 No 13. IOT (Square frame light) -01 No (i) Preventive maintenance :minimum one schedule visits per month and unlimited breakdown calls. (ii) Cleaning and replacing defective LEDs, control circuit or SMPS. (iii) Ensuring shadowless illumination and mechanical balance. (iv) Providing service reoprt for each visit.
(i) All work shall be carried out only by authorised Rep of OEM and using all genuine spare parts supplied by OEM only. (ii) Contractor should be responsible of proper functioning of all the OT light from current condition (either in malfunctioning or working) in the initial phase of contract and rate for for the same shall be included in the quoted. Nothing extra in that respect shall be paid to the contractor in any respect. (iii) Contractor through OEM shall be responsible for repair and replacement of all defective parts of the equipment as per OEM recommendation during entire comprehensive maintenance period. (iii) Preventive maintenance of all systems on monthly basis. (iv) Attending all complaints within 24 working hours intimated by Engr-in-Charge. (v) Field service report shall be maintained and submitted to the Engr-in-charge after expiry of every month and before submission of RAR . (vi) The rates quoted by the contractor shall deemed to be inclusive of T&P etc (vii) A damage of Rs 500.00 per complaint per day shall be imposed on contractor, if the complaint shall not attended within 24 Hours of complaint intimated by Engr-in-Charge.
S & F in replacement of LED 50 inner 8 port circuit complete all as specified and directed.
S & F in replacement of LED 50 outer controller circuit complete all as specified and directed.
S & F in replacement of LED 50 keypad complete all as specified and directed.
S & F in replacement of LED 50 LED's, 6 LED's with lens complete all as specified and directed.
S & F in replacement of LED 50 SMPS (switching mode power supply) with lens complete all as specified and directed.
S & F in replacement of extra sterilizable handle (yellow/white colour) complete all as specified and directed.
S & F in replacement of 650 VA UPS complete all as specified and directed.
S & F in replacement of 650 VA UPS Batteries complete all as specified and directed.
S & F in replacement of 650 VA UPS Circuit complete all as specified and directed.
S & F in replacement of 650 VA UPS Control box complete all as specified and directed.
Supply , Installation , Testing & Commissioning in replacement microprocessor based networkable analogue addressable Fire Alarm control panel The control panel shall have 1 loop upto 2 loop ,Mxpro 5 series control panel are fully expadable from 1-2 loops and supplied with 2 onboard sounder circuit,20 programmable zonal LEDs with slide lables, and 25 system LEDs for information purposes including 4 programmable function button with LED indication for confirmation of operation and comply BSEN54 part 2,4 and 13 complete in all aspect all as specified and as directed. Make:- Apolo Advance MX-5201V or equivalent
Supply , Installation , Testing & Commissioning in replacement loop card suitable for above panel complete in all aspect all as specified and as directed. Make:- Apolo Advance MXP-502V or equivalent
Supply , Installation , Testing & Commissioning in replacement TW-DO-01 taurus wireless dual optical smoke detector technology including advance drift compensation, Bi-directional wireless communication, dual channel redundancy, long communication, range(upto 1 km in open air),utilises standerd low cost dual lithium battery technology ,inbuilt magnet test allows easy activation to verify correct functionality and response to comply EN54-7 Class P and EN54-25 complete in all aspect all as specified and directed. Make:- Apolo Argus TW-DO-01 or equivalent
Supply , Installation , Testing & Commissioning in replacement TW-MTI-01 Taurus wireless translator module,the translator allows fully intelligent and seamless integration of the wireless devices alongside standard wired devices or can be used independently to form completely wireless system including features Bi-directional wireless communication, internal antennae design protects from enviromental conditions, vandalism, accidental damage or misuse low current consumption, compatible with up to 15 expander module , mesh expander technology progammable for redundent path to the translator, dual channel redundency, long communication range, full analogue data availability comply with EN54-17,18 &25 complete in all aspect all as specified and directed. Make:- Apolo Argus TW-MTI-01 or equivalent
Supply , Installation , Testing & Commissioning in replacement TW-ME-01 taurus expander module with convenient method to increse radio communication range beyond that possible from a single translator by relaying the radio communication to further expanders or directly to the wireless field devices .The expanders are programmable for redundant path to the translator,so that if any expander in the chain fails,the transmission path can find an alternate route,the redundant paths are identified and tested during system commissioning for maximum reliability. All the wireless communication relies on a channel pair for spurious RF noise rejection and maximum link reliability upto 32 wireless field devices per expander can be connected,Bi-directional wirelss communication range (1 km in open air) requires external power supply unit,low current consumption comply EN54-18 and EN 54-25 complete in all aspect all as specified and directed. Make:- Apolo Argus TW-ME-01 or equivalent
Supply , Installation , Testing & Commissioning in replacement TW-CP-R-01 taurus wireless manual call point latest in wirelss MCP technology, have a resettable plastic element which display a drop down warning indicator when operated bi directional wireless communication dual channel redundancy long communication range (upto 1km in open air) utilises standard low cost dual lithium battery technology complete in all aspect all as specified and directed. Make:- Apolo Argus TW-CP-R-01 or equivalent
Supply , Installation , Testing & Commissioning in replacement TW-MWSO-01 + CWS100-AV Taurus wall sounder VAD combines the wireless sounder interface module with the conventional wall sounder VAD.The taurus wall sounder VAD is a EN 54-3 (Type B), EN 54-25 and EN 54-23 complaint visual/alarm device,equipped with 3 level of volume adjustment,high output LED beacon and 32 recognised tones which can be set via the control equipment or locally at the sounder with bi-directional wireless communication,dual channel redundancy,long communication range(upto 1 Km) utilises standard low-cost dual lithium battery technology complete in all aspect all as specified and directed. Make:- Apolo Argus TW-MWSO-01 or equivalent
Supply and fix in replacement CR123A batteries for sensors devices complete in all aspect all as specified and directed.
Supply and fix in replacement 24 V DC Power supply for expander, commander box complete in all aspect all as specified and directed.
Supply and fix in replacement SMF batteries for panel 12 Volt complete in all aspect all as specified and directed.
Supply & laying in replacement of 2Core x 2.5 Sqmm of FRLS Copper Cable, complete all as specified and directed.
M&L for rewinding of ceiling fan including dismantling the fan from its existing location removing of the burnt or damaged winding cleaning of stator core rewinding with super-enamelled copper wire of suitable gauge as per original design Varnishing, drying, and reassembling the motor replacement of damaged bearings, bushes, capacitor, and other minor parts (if required) testing of the fan for smooth and vibration-free operation reinstallation at site including necessary connection and commissioning complete in all respects all as specified and as directed.
Taking down carefully copper/ aluminium point wiring (light, fan, socket or power, submain etc) complete (fitting such as switches, ceiling roses, pendent, regulator socket etc shall be measured and paid separately) and making good disturbed surfaces of wall floor etc complete all as specified and as directed.
Taking down old and unserviceable sub main wiring and removing from the site and making good the disturbed surface complete all as specified and directed.
M&L point wiring with casing capping duly fitted on wall for Normal piano type switches with 1.5 sqmm , single core , multi stranded copper conductor PVC insulated and unsheathed (FRLS) cable 1100 Volts grade, drawn through casing capping as requirement of site including cadmium plated screws as per ISI, including 1.5 Sqmm size including all PVC accessories and metal flush box, hylum sheet with desired slot as required at site, blanking plate etc complete and making good disturbed surfaces to match the existing for one light / bell / fan point controlled by one, one way switch 06 Amp, complete all as specified and as directed
Description all as per item no 62.00 above here in before but for one three pin, 5 Amp, socket out let on independent board complete all as specified and as directed.
Description all as per item no 62.00 above here in before but point wiring with 2.5 Sqmm, multistranded, copper conductor cable, for 15 Amps socket outlet on independent board with 2.5 Sqmm size earth conductor complete all as specified and as directed.
Description all as per item no 62.00 above here in before but point wiring with 4 Sqmm, multistranded, copper conductor cable, for AC point on independent board with 4 Sqmm size earth conductor complete all as specified and as directed.
S&F in replacement Ceiling rose, PVC/ polycarbonate, isolated body type, three terminal, 240 volt, fixed in position & connecting complete all as specified and as directed.
Supply and fix Switch Piano type, white polycarbonate body, single pole, one way 5 amp, 230 V, including connecting complete.
Supply and fix Switch Piano type, white polycarbonate body, single pole, one way 15 amp, 230 V, including connecting complete.
Supply and fix Socket outlet 2 in 1, 3 pin, 5 and 15A - 230 V, Multipurpose flush type, including connecting complete.
Supply and fix Socket outlet 2 in 1, 3 pin, 5A ,230 V including connecting complete.
Supply and fix stepped type electronic fan regulator, white polycarbonate body, flush type, 230 V, including connecting complete.
Supply, fixing and connecting in replacement of Slim LED Batten 20 watt with Surface/Wall Mounted integrated LED 4 feet Fitting Polycarbonate housing and diffuser with viewing angle of 120 degree used to enhance the luman output Height suitable for White Housing & Isolated Electronic Driver, with Output Short-circuit protection, Surge Voltage protection up to 2.5 KV . Total system Lumen of 20W Led should be 2000 or above in Cool day Light(6500K), Power factor>0.9, CRI (Ra) >80, System with Average life of 50000 Burning hours complete with all accessories as required complete all as specified and as directed.
S&F BLDC (Brushless Direct Current) 250 RPM Ceiling Fan (energy efficient), 1400 mm with IR Remote controlled also suitable for regulator, opertaing voltage 220V, minimum air delivery 265 cmm class of insulation 'F' having full copper motor winding & ribbed 3 Nos A/M blades making necessary electric connection of suitable PVC copper wire from ceiling rose to ceiling fan complete all as specified and directed.The fan shall have BEE 5 star rating and service value more than 7.1. the fan shall have CA no. and MES office details as provided by Engineer-in-charge i.e."Military Engineer service, AGE(E/M), GE (East) Delhi Cantt, CA no........" permanently embosed on the side of the fan facing the ceiling. Make-Havells/ Atomberg/ Crompton and Goldmedal.
S & F Heavy Duty Metallic Ventillation Fan 380 mm sweep 240 Volt, 1400 RPM , Air delivery 500 CMM connection with self closing louver frame flexible PVC copper wire from ceiling rose to exhaust fan including provn of opening of hole on brick wall and grouting nut and bolt of suitable size complete all as specified and directed.
Supply and Fixing of five star rated Geysers white blue in colour capacity 25 Ltr, Electric Driven, Single phase, 240 V, Storage vertical type and heating element 2 KW, inner shell made up of copper, automatic cutoff,manual tempreture setting , maintaining 8 bar pressue including electrical and water connection with hot and cold water connection pipe (PVC type) and fixed on the wall with mild steel fastner 150 mm long and 10 mm dia with pin and bolts complete all as specified and directed.
S & F in replacementwith proper connection through lugs/end ferrule for distribution board double door type, SPN, 6 way, complete including 200 Amps rated bus bar, 63 Amp SPN (25 KA breakng capacity) rating , 01 no of 25 Amp MCB SP (10 KA breaking capacity), 03 no of 16 Amp MCB SP (10 KA breaking capacity) , neutral link, blanking plates etc complete in all aspect all as specified and directed. Make ABB/ Schnider/ L&T
Supply and laying in replacement XLPE insulated,armoured heavy duty electric cable with aluminium conductor ,1100 Volt grade,cross section area of 10 sqmm 2 core complete in all aspect as specified and as directed.
Supply and Fix in replacement Hot-Swappable Inverter/Rectifier Power Module for 3-Phase True Online Double Conversion UPS System, incorporating IGBT-based Rectifier (PFC) and Inverter stages including faulty power component board of genuine make of OEM (Vertiv) including the main logic control PCB or display/monitoring card, aged DC Bus and AC Filter Capacitors, faulty fan module ,main I/O and battery node ensuring proper thermal management and insulation with inter-cell connectors, terminal caps, and necessary DC power cabling between the battery bank and the UPS and comprehensive functional testing of the repaired UPS system under simulated or actual load to verify stable operation, battery discharge/charge performance, and seamless transfer (Static Switch) complete in all aspect all as specified and as directed. MAKE:- Vertiv or equivalent.
Supply and fix in replacement Manual Maintenance Bypass (MMB) Switchgear/Board, designed to provide break-before-make switching for isolating the main UPS unit without interrupting power to the critical load, facilitating safe maintenance and specifically designed or certified for use with 30 KVA, Three-Phase (3:3) Vertiv make Uninterruptible Power Supply (UPS) systems to match the Input /Output of UPS system, typically 400/415V AC, 3 Phase, 4 Wire + Earth incorporated high-quality, rated switchgear for UPS Bypass, UPS Output, and Maintenance Bypass operation ensuring current rating to be suitable for 30 KVA load (approx. 43A per phase at 400V, with margin) complete in all aspect all as specified and as directed. Make:- Vertiv or equivalent.
S&F in replacement Bldg security light fitting LED 45 Watt, highly efficient IP66 LED, high power having aluminium pressure die cast housing and PC cover in the front and high power lens for batwing light distribution with electric connection with suitable size of PVC insulated copper wire including GI bracket 1.5 Mtr with clamps and bolts complete all as specified and directed.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.48 MB
Tender157.pdf
Tender Documents • 0.93 MB
BOQ_838284.xls
BOQ • 0.48 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .