| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹70.6 LAccepted-AOC 4TH FLOOR VOLTAS HOUSE A BLOCK DR BABASAHEB AMBEDKAR ROAD CHINCHPOKLI MUMBAI MAHARASHTRA 400033 | MUMBAI | MAHARASHTRA | 400033 | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹71.6 L+₹1.0 L (1.44%)Rejected-Finance 19 LAKE TEMPLE ROAD KOLKATA 700029 | KOLKATA | WEST BENGAL | 700029 | L2 | Rejected-Finance 2nd lowest bidder | |
| 3 | L3₹79.8 L+₹9.2 L (13.1%)Rejected-Finance | L3 | Rejected-Finance 3rd lowest bider |
| Sl No | Description | Qty | Unit | VOLTAS LIMITED L1 | VOLTAS LIMITED L1 | Shinryo Suvidha Engineers India Pvt. Ltd. L2 | TRANSTECH L3 |
|---|---|---|---|---|---|---|---|
| 1.00Supply, Installation, testing and commissioning of air cooled Condensing Unit of capacity mentioned below with high efficiency hermetic scroll compressor, air cooled condenser with axial type condenser fan and micro-processor based control panel. (Refrigerant – R410a) | |||||||
| 1.10 | Nominal Capacity : 8.5 TR (For ICU & HDU) [Make- Voltas/Bluestar/Zeco/Edgetech/Climcone] | 3 | Sets | 1,34,867 ₹4,04,601 Lowest | 1,34,867 ₹4,04,601 Lowest | 1,98,365 ₹5,95,095 | 2,08,217 ₹6,24,651 |
| 2.00 | Supply, Installation, testing and commissioning of Expansion Valve, Ball Valve & Filter Drier. | 3 | Sets | 15,815 ₹47,445 | 15,815 ₹47,445 | 11,853 ₹35,559 Lowest | 24,885 ₹74,655 |
| 3.00Supply, installation, testing and commissioning of copper piping with necessary joints and supports suitable for refrigerant-R410a of diameters mentioned below : | |||||||
| 3.01 | 15.9 mm dia. With Insulation | 45 | Mtrs | 1,101 ₹49,545 | 1,101 ₹49,545 | 499 ₹22,455 Lowest | 1,231 ₹55,395 |
| 3.02 | 15.9 mm dia. With Insulation | 45 | Mtrs | 1,888 ₹84,960 | 1,888 ₹84,960 | 458 ₹20,610 Lowest | 679 ₹30,555 |
| 4.00CHILLED WATER FLOOR MOUNTED AIR HANDLING UNITS : SITC of following Floor Mounted Modular Construction Double Skinned Air Handling Units with recommended Fresh Air arrangement each consisting of the following and having 23+2 mm thick PUF insulated extruded Aluminium section frame construction: a) Fan Section DIDW backward curved imported fan (MK.Krugar/Nikotra/Greenheck/ADS).The AHU shall consist of 1 no. Centrifugal Blower with 1 nos. TEFC Squirell cage induction motor. b) Coil section 6 Rows deep, 11-13 FPI Chilled Water Cooling Coil and cooling coil header must be made out of suitable Copper material OEM standards c) Filter section with washable Pre-filters efficiency 90% down to 10 microns and Microvee Fine Filters with efficiency of 95% down to 5 Microns d) Mixing Chamber with return air and fresh air dampers. e) TEFC sq,Cage Induction Motor 1 No. f) Sandwiched SS 304 Drain Pan. g) PUF section Inner skin - 0.63 mm thick plain GI sheet and outer skin - 0.63 mm thick precoated GI sheet h) AHU shall be complete with VFD.The VFD shall be of IP20 rating (MAKE:ABB/DANFOSS/SIEMENS) | |||||||
| 4.01 | Cooling capacity - 7000 CFM, 65 mm static pressure (For 3RD Floor ICU)[Make- Voltas/Bluestar/Zeco/Edgetech/Climcone] | 1 | Set. | 3,48,868 ₹3,48,868 | 3,48,868 ₹3,48,868 | 3,44,656 ₹3,44,656 Lowest | 6,89,423 ₹6,89,423 |
| 4.02 | Cooling capacity - 2500 CFM, 65 mm static pressure (For 3RD Floor HDU) [Make- Voltas/Bluestar/Zeco/Edgetech/Climcone] | 1 | Set. | 1,69,072 ₹1,69,072 Lowest | 1,69,072 ₹1,69,072 Lowest | 1,75,485 ₹1,75,485 | 3,14,240 ₹3,14,240 |
| 5.00DX-TYPE CEILING SUSPENDED AIR HANDLING UNITS : SITC of following Ceiling Suspended Modular Construction Double Skinned Air Handling Units with recommended Fresh Air arrangement each consisting of the following and having 23+2 mm thick PUF insulated extruded Aluminium section frame construction: a) Fan Section DIDW backward curved imported fan (MK.Krugar/Nikotra/Greenheck/ADS).The AHU shall consist of 1 no. Centrifugal Blower with 1 No. TEFC Squirell cage induction motor. b) Coil section 6 Rows deep, 11-13 FPI Dx-Type Cooling Coil and cooling coil header must be made out of suitable Copper material OEM standards c) Filter section with washable Pre-filters efficiency 90% down to 10 microns and Microvee Fine Filters with efficiency of 95% down to 5 Microns d) Mixing Chamber with return air and fresh air dampers. e) TEFC sq,Cage Induction Motor 1 No. f) Sandwiched SS 304 Drain Pan. g) PUF section Inner skin - 0.63 mm thick plain GI sheet and outer skin - 0.63 mm thick precoated GI sheet h) AHU shall be complete with VFD.The VFD shall be of IP20 rating (MAKE:ABB/DANFOSS/SIEMENS) | |||||||
Tender Value
₹80 L
EMD Value
₹1.6 L
Closing Date
18 Jul 2025, 12:00 pmClosed
Exe. Engr.-I, Kol. South Health El. Divn., PWDte
75 D H Road Kidderpore Kol_23
IPGMER-SSKM Hosp.-Gplus9 storied Private Cabin Bldg with the provision of Gplus9 storied foundation within the premises of IPGMER SSKM Hosp. EI Works and Other Utility Services.-Creation of 15 bedded CCU and 6 bedded HDU-SITC of AC system
2025_WBPWD_867913_1
WBPWD/EE-I/KSHED/Q27/25-26
Open Tender
A/C ORG
Item Rate
60 days
Kolkata
Please refer Tender documents.
4 documents required · 4 mandatory
₹1.6 L
O/o Exe. Engr., Kol. South Health El. Divn., PWDte
3 Sept 2026
20 Jun 2025
21 Jul 2025
20 Jun 2025
18 Jul 2025
26 Jun 2025
25 Jun 2025
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supply, Installation, testing and commissioning of air cooled Condensing Unit of capacity mentioned below with high efficiency hermetic scroll compressor, air cooled condenser with axial type condenser fan and micro-processor based control panel. (Refrigerant – R410a) | |||||
| 1.1 | Nominal Capacity : 8.5 TR (For ICU & HDU) [Make- Voltas/Bluestar/Zeco/Edgetech/Climcone] | 3 | Sets | - | - |
| 2 | Supply, Installation, testing and commissioning of Expansion Valve, Ball Valve & Filter Drier. | 3 | Sets | - | - |
| 3Supply, installation, testing and commissioning of copper piping with necessary joints and supports suitable for refrigerant-R410a of diameters mentioned below : | |||||
| 3.01 | 15.9 mm dia. With Insulation | 45 | Mtrs | - | - |
| 3.02 | 15.9 mm dia. With Insulation | 45 | Mtrs | - | - |
| 4CHILLED WATER FLOOR MOUNTED AIR HANDLING UNITS : SITC of following Floor Mounted Modular Construction Double Skinned Air Handling Units with recommended Fresh Air arrangement each consisting of the following and having 23+2 mm thick PUF insulated extruded Aluminium section frame construction: a) Fan Section DIDW backward curved imported fan (MK.Krugar/Nikotra/Greenheck/ADS).The AHU shall consist of 1 no. Centrifugal Blower with 1 nos. TEFC Squirell cage induction motor. b) Coil section 6 Rows deep, 11-13 FPI Chilled Water Cooling Coil and cooling coil header must be made out of suitable Copper material OEM standards c) Filter section with washable Pre-filters efficiency 90% down to 10 microns and Microvee Fine Filters with efficiency of 95% down to 5 Microns d) Mixing Chamber with return air and fresh air dampers. e) TEFC sq,Cage Induction Motor 1 No. f) Sandwiched SS 304 Drain Pan. g) PUF section Inner skin - 0.63 mm thick plain GI sheet and outer skin - 0.63 mm thick precoated GI sheet h) AHU shall be complete with VFD.The VFD shall be of IP20 rating (MAKE:ABB/DANFOSS/SIEMENS) | |||||
| 4.01 | Cooling capacity - 7000 CFM, 65 mm static pressure (For 3RD Floor ICU)[Make- Voltas/Bluestar/Zeco/Edgetech/Climcone] | 1 | Set. | - | - |
| 4.02 | Cooling capacity - 2500 CFM, 65 mm static pressure (For 3RD Floor HDU) [Make- Voltas/Bluestar/Zeco/Edgetech/Climcone] | 1 | Set. | - | - |
| 5DX-TYPE CEILING SUSPENDED AIR HANDLING UNITS : SITC of following Ceiling Suspended Modular Construction Double Skinned Air Handling Units with recommended Fresh Air arrangement each consisting of the following and having 23+2 mm thick PUF insulated extruded Aluminium section frame construction: a) Fan Section DIDW backward curved imported fan (MK.Krugar/Nikotra/Greenheck/ADS).The AHU shall consist of 1 no. Centrifugal Blower with 1 No. TEFC Squirell cage induction motor. b) Coil section 6 Rows deep, 11-13 FPI Dx-Type Cooling Coil and cooling coil header must be made out of suitable Copper material OEM standards c) Filter section with washable Pre-filters efficiency 90% down to 10 microns and Microvee Fine Filters with efficiency of 95% down to 5 Microns d) Mixing Chamber with return air and fresh air dampers. e) TEFC sq,Cage Induction Motor 1 No. f) Sandwiched SS 304 Drain Pan. g) PUF section Inner skin - 0.63 mm thick plain GI sheet and outer skin - 0.63 mm thick precoated GI sheet h) AHU shall be complete with VFD.The VFD shall be of IP20 rating (MAKE:ABB/DANFOSS/SIEMENS) | |||||
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
Tender Document • 1.26 MB
TenderForm.pdf
Tender Document • 0.69 MB
BOQ_1951140.xls
BOQ • 0.35 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .