Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.1 LAccepted-AOC BUNGLOW NO 75 CAVALRY ROAD JHANSI CANTT PIN 280001 | JHANSI | JHANSI | UTTAR PRADESH | 280001 | L1 | Accepted-AOC Being lowest bidder | |
| 2 | L2₹29.1 L+₹23,310 (0.81%)Rejected-Finance A 63 ELDECO COUNTY PHASE II RAJGARH JHANSI U P 284135 | JHANSI | JHANSI | UTTAR PRADESH | 284135 | L2 | Rejected-Finance Not become lowest bidder | |
| 3 | L3₹34.7 L+₹5.8 L (20.2%)Rejected-Finance D12 GROTH CENTRE COLONY BIJAULI JHANSI U P | JHANSI | UTTAR PRADESH | 284001 | L3 | Rejected-Finance Not become lowest bidder |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
27 Sept 2022, 6:00 pmClosed
Lt Col Deepak Kumar
Garrison Engineer Jhansi
REPAIR / MAINT TO VARIOUS DG SETS, EOT CRANES, INCINERATOR, CONTROL PANELS AND CONNECTED WORKS AT JHANSI CANTT, AAU AND CALEB VIHAR AREA UNDER AGE E/M AT GE JHANSI
2022_MES_549285_1
GE/JHA/TOK/34 OF 2022-2023
Open Tender
Civil Works
Item Rate
180 days
GE Jhansi
Please refer tender documents
7 documents required · 7 mandatory
₹500
Yes
GE Jhansi
₹80,000
Yes
11 Nov 2022
1 Sept 2022
29 Sept 2022
1 Sept 2022
27 Sept 2022
13 Sept 2022
Amount
Material and Labour for servicing of DG set by carrying out the following maintenance including testing on completion at connected load for entire satisfaction of Engineer-in-Charge and complete all as specified and directed for the DG set of capacity 320 KVA Make - Kirloskar, Greaves Power:-
Draining out engine oil from the sump by removing drain plug, cleaning the sump thoroughly and refilling the sump with new engine oil to required level (Note: Engine Oil will be measured and paid separately as 'Supply Only')
Draining out of diesel from tank and storing in cleaned containers, cleaning the tank thoroughly by removing sediments settled at the bottom and refilling the drained out diesel duly filtered.
Supply and replace complete set of fuel filters, engine oil filters and air cleaner element.
Draining out complete coolant water mixture from the radiator and re-filling the radiator with new coolant and water mixture with proportionate ratio (Note: Coolant will be measured and paid separately as 'Supply Only')
Check and top up the electrolyte/distilled water in starting batteries to maintain the required specific gravity. Cleaning of battery terminals & applying petroleum jelly to battery poles & brass connectors.
Tightening all the fasteners of complete DG set to the required torque.
All as per item No.1.00 to 1.06 here-in-before but for DG set of capacity 125 KVA Make – Ashok Leyland at Mil Stn Nowgong (BKD)
All as per item No.1.00 to 1.06 here-in-before but for DG set of capacity 100 KVA Make – Greaves Power -01 No, Kirloskar - 01 No. & Ashok Leyland - 01 No.
All as per item No.1.00 to 1.06 here-in-before but for DG set of capacity 82.5 KVA (Make – Ashok Leyland - 01 No & Kirloskar - 03 Nos.)
All as per item No.1.00 to 1.06 here-in-before but for DG set of capacity 75 KVA Make – Kirloskar
All as per item No.1.00 to 1.06 here-in-before but for DG set of capacity 62.5 / 63 KVA (Make – Kirloskar-04 Nos, Ashok Leyland-01 No, ) (01 No 62.5 KVA DG Set at Mil Stn Nowgong(BKD)
All as per item No.1.00 to 1.06 here-in-before but for DG set of capacity 50 KVA Make – Kirloskar
All as per item No.1.00 to 1.06 here-in-before but for DG set of capacity 40 KVA Make – Ashok Leyland - 01 No. and Kirloskar - 01 No.
All as per item No.1.00 to 1.06 here-in-before but for DG set of capacity 30 KVA Make - Kirloskar-01 No, Ashok Leyland-04 Nos
All as per item No.1.00 to 1.06 here-in-before but for DG set of capacity 25 KVA Make – Greaves Power
All as per item No.1.00 to 1.06 here-in-before but for DG set of capacity 15 KVA / 20 KVA Make – Kirloskar (01 No 15 KVA DG Set at Mil Stn Nowgong (BKD)
All as per item No.1.00 to 1.06 here-in-before but for DG set of capacity 7/5.5 KVA Make – Kirloskar
Supply only engine oil of grade 15W-40 for various DG Sets. Make : KOEL/Valvoline/Gulf/Castrol.
Supply only of coolant water mixture (50:50) suitable for DG sets. Make : KOEL/Valvoline/Gulf/Castrol.
Supply and replace complete set of fuel pipes & leak off pipe with clamps suitable for existing make & model of DG set up to 320 KVA capacity
Supply and replace 'V' belt suitable for existing make & model of DG set up to 320 KVA capacity
Supply and replace complete set of hoses with clamps suitable for existing make & model of DG set up to 320 KVA capacity
Attending of urgent complaints in any breakdown of standby DG sets upto 320 KVA and EOT Cranes at any location in Jhansi Cantt and AAU under GE Jhansi, whenever required round the clock, rectify the fault and restore the standby supply within one hour after receipt of the complaint, complete all as specified. Note : (i) The cost of all kind of replaced defective parts / spares / control cards / oil / lubricants etc, as and when required to making the DG Set and EOT Cranes fully functional, will be measured and paid seperately under respective items only. (ii) The cost of all kind of minor parts / spares, other than mentioned in BOQ, as and when required to making the DG Set/EOT Cranes fully functional, is deemed to be included in quoted rates and no extra cost shall be paid to the contractor in this effect. (iii) If complaint is not attended by the contractor within two hour the penality as applicable shall be impossed on him. (iv) Contractor to give the name of machanic, electrician and helpers those will attend the urgent breakdown. (v) All kind of transportation (to and fro) for all kind of necessary equipment/T&P shall be arranged/brought by contractor to complete the job at site or at workshop and no extra cost shall be paid to the contractor in this effect. (vi) Complaints shall be lodged by telephonically, so contractor has to give the telephone number of person who will receive the complaint round the clock.Normal defect rectification such as relay settings , loose wirings , oiling / greasing , sensor based settings include in this work . No separate cost will be charged against minor defect rectification.
De-scaling of radiator assembly by carefully removing from the engine, transporting to civil workshop and removing the sediments, scales and rust etc by means of chemical cleaning, high pressure water washing and air cleaning, arresting the leakages by gas welding / soldering with suitable material, re-assembling the same with new gaskets including replacement of radiator cap (wherever required) and transporting to the site, fixing to the engine for DG Set of capacity 320 KVA and testing for satisfactory performance complete all as specified and directed by Engineer-in-Charge.
All as per item No.19.00 here-in-before but for DG Set of capacity from 100 KVA / 125 KVA.
All as per item No.19.00 here-in-before but for DG Set of capacity from 62.5 KVA to 83 KVA.
All as per item No.19.00 here-in-before but for DG Set of capacity from 30 KVA to 50 KVA.
All as per item No.19.00 here-in-before but for DG Set of capacity from 15 KVA to 25 KVA.
Dismantling the defective water pump assembly and Supply and fix new water pump assembly suitable for existing DG set of capacity 320 KVA complete all as specified and directed by Engr-in-Charge.
All as per item No.24.00 here-in-before but for DG Set of capacity from 100 KVA / 125 KVA.
All as per item No.24.00 here-in-before but for DG Set of capacity from 62.5 KVA to 83 KVA.
All as per item No.24.00 here-in-before but for DG Set of capacity from 30 KVA to 50 KVA.
Dismantling the defective fuel injectors & FIP from the engine and Material & Labour for repair/calibration of fuel injectors & FIP including replacement of barrel plunger, cups & ‘O’ rings etc. for DG Set of capacity 320 KVA complete all as specified and directed by Engineer-in-Charge.
All as per item No.28.00 here-in-before but for DG Set of capacity from 100 KVA / 125 KVA.
All as per item No.28.00 here-in-before but for DG Set of capacity from 62.5 KVA to 83 KVA.
All as per item No.28.00 here-in-before but for DG Set of capacity from 30 KVA to 50 KVA.
All as per item No.28.00 here-in-before but for DG Set of capacity up to 25 KVA.
Dismantling/disconnecting the head of the engine carefully and opening the head for overhauling including the replacement following spare parts transporting the materials / parts to (Authorised workshop) for lathe works & calibration replacement the minor & major parts , like nuts, bolts,washers,gaskets, flexible pipes hose pipes, Piston rings, piston,Gasket set complete and value setting-assembling complete including installation at site and refixing the head with engine complete with proper alignment and testing the engine for 1 hrs on load to achive designed parameters ion presence of Engineer-in-Charge of capacity 62.5 KVA to 125 KVA. Note for item No 34.00 : - (a) Piston rings,Piston, flexible pipes, hose pipes, set of head etc material measured and paid separately. (b) Unit rate quoted shall also be included for testing the whole system and repair of any leakage. (c) Top up of Oil Premium blue 15 W 40 oil and coolant shall be measured and paid separately.
All as per item No. 33 Here-in-before but DG Set of Capacity from 7 KVA to 40 KVA.
M & L for opening the cylinder head of the engine and oil sump carefully for replacement of head gasket including sump gasket complete refixing the head and sump to arrest oil leakage with engine complete with proper alignment and testing the engine for 1 hrs on load to achive designed parameters all as directed by Engineer-in-Charge of capacity 82.5 KVA to 320 KVA.
All as per item No. 35 Here-in-before but DG Set of Capacity from 7 KVA to 62.5 KVA.
Taking down unserviceable lube oil pressure sender and Supply and fix Lube Oil Pressure Sender (Sensor + Switch) suitable for DG set of capacity 320 KVA complete all as specified and directed by Engineer-in-Charge.
All as per item No.37.00 here-in-before but for DG Set of capacity from 100 KVA / 125 KVA.
All as per item No.37.00 here-in-before but for DG Set of capacity from 62.5 KVA to 83 KVA.
All as per item No.37.00 here-in-before but for DG Set of capacity from 30 KVA to 50 KVA.
All as per item No.37.00 here-in-before but for DG Set of capacity up to 25 KVA.
Dismantling the fly wheel coupling between engine and alternator and Supply and replace complete set of bullet rubber bushes, coupling nuts & bolts including proper alignment of engine & alternator for smooth running for DG set of capacity 100 KVA / 125 KVA complete all as specified and directed by Engineer-in-Charge.
All as per item No. 42 here-in-before but for DG set of capacity 62.5 KVA to 83 KVA.
All as per item No.42.00 here-in-before but for DG Set of capacity from 30 KVA to 50 KVA.
Taking down unserviceable engine wiring and Material & Labour for rewiring of engine safety control system from control panel to engine control gadgets like HWT, LLOP, shut down valve, dynamo & self-starter etc with suitable gauge and grade of wires for DG set of capacity from 100KVA / 125 KVA complete all as specified and directed by Engineer-in-Charge.
All as per item No.45.00 here-in-before but for DG Set of capacity from 62.5 KVA to 83 KVA.
All as per item No.45.00 here-in-before but for DG Set of capacity from 30 KVA to 50 KVA.
All as per item No.45.00 here-in-before but for DG Set of capacity up to 25 KVA.
Dismantling the defective self starter assembly 12V/24V carefully from the DG set and carryout repair and servicing by cleaning all accessories with suitable cleaning agent and supply and replace commutator, carbon brush set, carbon brush holder, king pin holder, armature choke nut, body screens, clutch plate assembly and solenoid etc, re-assembling and re-fixing the same and testing on completion for DG set of capacity from 320 KVA complete all as specified and directed by Engineer-in-Charge.
All as per item No.49.00 here-in-before but for DG Set of capacity from 100 KVA / 125 KVA.
All as per item No.49.00 here-in-before but for DG Set of capacity from 62.5 KVA to 83 KVA.
All as per item No.49.00 here-in-before but for DG Set of capacity from 30 KVA to 50 KVA.
All as per item No.49.00 here-in-before but for DG Set of capacity up to 25 KVA.
Dismantling the defective 24 V battery charging alternator carefully from any capacity of DG set and carryout repair and servicing by cleaning all accessories with suitable cleaning agent and supply and replace carbon brush, brush holders, bushes/bearings, varnishing etc, re-assembling and re-fixing the same and testing on completion complete all as specified and directed by Engineer-in-Charge.
All as per item No.54.00 here-in-before but 12 V battery charging alternator for any capacity of DG set.
Supply and fix RPM Meter with cable suitable for DG Set including taking down of existing unserviceable meter complete all as specified and directed by Engineer-in-Charge.
Supply and fix Oil Pressure Gauge suitable for DG Sets including taking down existing unserviceable gauge complete all as specified and directed by Engineer-in-Charge.
Supply and fix Water Temperature Gauge suitable for DG Sets including taking down existing unserviceable gauge complete all as specified and directed by Engineer-in-Charge.
Supply and connect battery lead (1.50m long each set of 2 Red & Black) made out of PVC Insulated Plain/Striped Automobile Cables with high conductivity bright annealed copper conductor bunched together, insulated with dielectric grade PVC compound (impervious to oils, greases, acids, petrol and water) conforming to IS 2465 of size 25 sqmm soldered one end with brass connector with nuts and bolts for battery pole and the other with copper lug for self starter terminal including taking down of existing u/s battery lead with connector and lug of any description complete all as specified and directed by Engineer-in-Charge.
Supply and replace brass connector with bolt and nut suitable for positive/negative pole of battery of any size.
Taking down unserviceable AVR of any description from alternator including supply and fixing of new AVR of suitable model for existing alternator of capacity 320 KVA complete all as specified and directed by Engineer-in-Charge.
All as per item No. 61 here-in-before but for DG set of capacity from 100 KVA / 125 KVA.
All as per item No. 61 here-in-before but for DG set of capacity up to 83 KVA.
Supply and fix battery 12V, 100 AH for DG set including initial filling & Charging complete all as specified and directed by Engineer-in-Charge. Make : Exide / Amaron / Okaya.
All as per item No. 64 here-in-before but of rating 12V, 180 AH Make : Exide / Amaron / Okaya.
Material and labour for reconditioning 12 V 180 AH, 24 plates Batteries including replacement with new parts such as –ve & +ve plates, PVC separators, terminal post, Acid and distilled water etc making in serviceable conditions, all as specified and directed.
All as per Item No. 66.00 here in before but 12 Volts 100/150 AH, 24 Plate battery.
Dismantling the defective alternator from DG set, transporting to civil work shop, separating the stator and rotor from alternator housing, cutting and removing burnt winding of stator completely, cleaning the slots and rewinding the stator with existing gauge of super enameled copper wire with suitable grade of insulation, applying varnish and heating in heating chamber till completely dried and reassembling the alternator, transporting back to site and re-fixing to the DG set including proper alignment for smooth running and testing on completion for DG set of capacity 100 KVA / 125 KVA complete all as specified and directed by Engineer-in-Charge.
All as per item No. 68 here-in-before but for DG set of capacity 62.5 KVA to 83 KVA.
All as per item No. 68 here-in-before but for DG set of capacity 30 KVA to 50 KVA.
All as per item No. 68 here-in-before but for DG set of capacity 20 KVA to 25 KVA.
All as per item No. 68 here-in-before but for DG set of capacity up to 15 KVA.
Supply and fix in replacement of left hand/ right hand hinge suitable for acoustic enclosure doors for DG set of capacity up to 320 KVA including removing of existing broken hinge complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of left hand/ right hand lock with catcher suitable for locking doors of acoustic enclosure for DG set of capacity up to 320 KVA including removing of existing unserviceable lock complete all as specified and directed by Engineer-in-Charge.
Material & Labour for 2.0mm thick Mild steel, plain, black sheet in mobile DG set housing, wall cladding, steel gates and similar work, cut to size, holes punched; including round headed screws, clout nails or rivets and fixed steel framing with plain 40 mm lap joints with riveted or welded seams, including bending or turning up, mitred angles, etc. as required and applying two coats of synthetic enamel paint of approved colour over a coat of red oxide primer including cutting and removing corroded sheet complete all as specified and directed by Engineer-in-Charge.
Material & labour for Earthing complete using galvanised iron earth plate electrode of size 60cm X 60cm X 6mm thick burried directly in ground vertically at a depth not less than 2.25 m below normal ground level with top edge of earth plate at a depth not less than 1.5 m below normal ground level, earth plate surrounded from all sides by 15 cm thick and packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using galvanised iron strip of size 32X6 mm by means of bolts, nuts, check nuts and washers made of GI and protected by light grade 40 mm dia galvanised iron pipe and GI pipe light grade 20mm bore for watering, including funnel, wire mesh, CI pit cover and PCC chamber pit with PCC 1:2:4 type B-2 (including necessary excavation and earth work disposal of surplus soil to a distance not exceeding 50 m all as specified and shown on electrical plate No 3 of SSR Part-I 2009 and testing on completion all as specified and directed.
Material & Labour for Framed work as in doors or gates of angle or other section with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering. Doors, etc. to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails and guides) and hanging; also fastening and fixing complete in Fe 410 -W (Gde- E- 250) quality- A and applying two coats of synthetic enamel paint of approved colour over a coat of red oxide primer including cutting and removing corroded frames complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of MCCB, 500 A, 3 Pole, 50 KA (Ics=100%Icu), 415 V, 50 Hz, with adjustable thermal magnetic release along with busbar spreader terminal plates including taking down existing unserviceable MCCB of any description complete all as specified and directed by Engineer-in-Charge. Make : L&T / Havells / C&S / Indo Asian
Supply and fix in replacement of MCCB, 250 A, 3 Pole, 36 KA (Ics=100%Icu), 415 V, 50 Hz, with adjustable thermal magnetic release along with busbar spreader terminal plates including taking down existing unserviceable MCCB of any description complete all as specified and directed by Engineer-in-Charge. Make : L&T / Havells / C&S / Indo Asian
Supply and fix in replacement of MCCB, 200 A, 3 Pole, 25 KA (Ics=100%Icu), 415 V, 50 Hz, with adjustable thermal magnetic release along with busbar spreader terminal plates including taking down existing unserviceable MCCB of any description complete all as specified and directed by Engineer-in-Charge. Make : L&T / Havells / C&S / Indo Asian
Supply and fix in replacement of MCCB, 160 A, 3 Pole, 25 KA (Ics=100%Icu), 415 V, 50 Hz, with fixed thermal magnetic release along with busbar spreader terminal plates including taking down existing unserviceable MCCB of any description complete all as specified and directed by Engineer-in-Charge. Make : L&T / Havells / C&S / Indo Asian
Supply and fix in replacement of MCCB, 25 to 100 A, 3 Pole, 16 KA (Ics=100%Icu), 415 V, 50 Hz, with fixed thermal magnetic release along with busbar spreader terminal plates including taking down existing unserviceable MCCB of any description complete all as specified and directed by Engineer-in-Charge. Make : L&T / Havells / C&S / Indo Asian
Supply & fix in repair of Turbo kit for 125/320 KVA DG Set for Kirloskar/Greaves DG Set alongwith its connected items such as nuts & Bolts , Seals ,impeller as per existing etc complete all as specified and directed by Engineer-in-Charge.
Supply and fix in repair of Turbo kit for 25 /100 KVA DG Set for Ashok Leyland/Kirloskar/Greaves DG Set alongwith its connected items such as nuts & Bolts , Seals ,impeller as per existing etc complete all as specified and directed by Engineer-in-Charge.
Shifting / refixing of DG set, of capacity 20 KVA/100 KVA desmentaling all electric connection and costruction of suitable size plith (hight upto 2 feet form ground level) for DG set made by brick messonary and well plasterd. Refixing of DG set and panel with proper connection and earthing as per requirement all as directed secified by Engr- in Charge. Note:- Earthing will be measured and paid separately.
Supply, laying, jointing, testing and commissioning LT underground cables, 1100 volts grade, XLPE , heavy duty armoured, with multistranded aluminium conductors, IS-1554 marked, laid in trenches / ducts / fixed on poles / walls / laid under roads / paths / drain / culverts or encased in GI pipe complete all as specified and directed. (MAKE : polycab, Havells, universal cable, Finolex) Cables for the following sizes:-
(a) 150 Sqmm 3.5 Core
(b) 95 Sqmm 3.5 Core
(c) 70 Sqmm 3.5 Core
(d) 50 Sqmm 3.5 Core
(d) 35 Sqmm 3.5 Core
(e) 25 Sqmm 4 Core
(f) 16 Sqmm 4 Core
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of LT UG cables in soft/ loose soil and getting out it, including trimming sides and bottom of trenches complete all as specifiedand directed by Engr-in Charge
Returning, filling-in, including spreading, watering and well ramming in layers not exceeding 25 cm thick each, in soft / loose soil complete all as specified and directed by Engr-in-charge.
Removing excavated surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specifieddirected by Engr-in-charge.
supply and filling of sand in and around LT/HT cables 80mm thick below the cable and 150mm thick after laying the cable and gently punning down complete all as directed.
Supplying and laying precast concrete cable cover, class LV, type 1, flat size 250mmx 150mm x 40mm.
Material and labour for Double wall corrugated HDPE pipe, ISI marked of outer dia 50mm, inner dia 38mm with smooth internal and profiled external surface, non-pressure type, laid in trenches/floors/duct or fixed on walls /pole including all connections, accessories like socket, couplers, bends etc for protection of LT cable XLPE grade 1100 Volts complete all as specified and directed.
Servicing of AMF panel of DG set 320 KVA of capacity installed at Jhansi Cantt Area by cleaning the complete panel with suitable cleaning agent and checking the controller relays, timer, contactors for proper functioning, replacing defective spare parts, replacement of defective small wires of existing size, tightening of all connections and applying jelly on contactors complete all as specified and directed by Engineer-in-Charge:- Note : Spare parts required will be measured and paid separately as 'Supply Only' but cost of small wires shall be included in the quoted rate.
Supply only of following spare parts suitable for existing DG set AMF Panels, 3 Phase, 415 Volts, 50 Hz :-
AMF Logic controller relay complete assembly
Control relay
Timer
Battery Charging Unit 12 / 24 Volts
Auto / Manual switch complete assembly
Start/stop push button
Supply and fix in replacement of engine control panel consisting of ignition switch, water temperature gauge, oil pressure gauge, VAF meter, push button, indication lamp and provision for mounting MCCB etc suitable for DG set of capacity 30 KVA to 100 KVA complete all as specified and directed by Engineer-in-Charge. Make: Kirloskar / Ashok Leyland / Greaves Power
Material and Labour for overhauling of EOT Cranes of 15 Ton / 20 Ton capacity i.e. servicing and checking the serviceability of all mechanical parts such as Gear boxes, gears, rope drums, wire ropes, rope sheaves, track wheels, brakes, bearings etc including greasing and lubricating all moving parts and checking the serviceability of all electrical parts such as Motors, Control panels, switchgears, power & control cables, DSL, Limit switches, Control pendants, indicating lamps, push buttons, MCBs, earth wire etc, identifying the fault for replacement of defective spare parts and testing on completion for smooth functioning complete all as specified and directed by Engineer-in-Charge. Note : (i) The cost of grease shall deemed to be included in the quoted rate. (ii) Supply and replacement of Gear Oil and all other mechanical and electrical spare parts required for replacement shall be measured and paid separately.
Supply and fill in replacement of gear oil of suitable grade for EOT cranes
Supply and fix in replacement of limit switch for LT/CT motion suitable for 15 Ton / 20 Ton EOT crane.
Supply and fix in replacement of limit switch for vertical motion suitable for 15 Ton / 20 Ton EOT crane.
Supply and fix in replacement of brake liner of LT and CT motion suitable for 15 Ton / 20 Ton EOT crane.
Supply and fix in replacement of DE / NDE bearings suitable for existing make and model of electric motor of EOT cranes.
Supply and fix in replacement replacement of TPN current collectors suitable for copper bus bar of 15 Ton / 20 Ton EOT crane including necessary fabrication work.
Supply and fix in replacement of push button switch spring type in red or green colour suitable for control panel of 15 Ton / 20 Ton EOT crane
Supply and fix in replacement of transformer of capacity 250 VA having primary side 0-415 volts and secondary side 0-110 V AC.
Supply and fix in replacement of AC 3 pole, 415V, ML2 power contactor 32A (make: L&T or equivalent ) suitable for electric panel of EOT crane.
Supply and fix in replacement of AC 3 pole ML4 power contactor 70A (make: L&T or equivalent) suitable for electric panel of EOT crane.
Supply and fix in replacement of 3 Pole AC Control CE15 A Series 2.2 KW , 6A (make: BCH or equivalent) suitable for electric panel of EOT crane.
Supply and fix in replacement of AC 3 phase ‘NHD’ Series 4 Pole Contactor 16 A (make : BCH Cat No. C00N or equivalent) suitable for electric panel of EOT crane
Supply and fix in replacement of AC 3 phase ‘NHD’ Series 4 Pole Contactor 40 A (make : BCH Cat No. N1N or equivalent) suitable for electric panel of EOT crane
Supply and fix in replacement of R/Y/B indication lamp
Supply and fix in replacement of single phasing preventer
Supply and fix in replacement of Voltmeter / Ammeter of existing model suitable for 3 phase AC supply
Supply and fix in replacement of timer suitable for control panel of 15 ton / 20 ton EOT crane
Supply and fix in replacement of Overload Relay (OLR) suitable for control panel of 15 ton / 20 ton EOT crane
Supply and fix in replacement of wire rope 16mm dia , 6 x 36 construction of required strength suitable for 15 Ton / 20 Ton EOT crane.
Rewinding of electric motor of capacity up to 3 HP, 3 Phase, 415 Volts, 50 Hz by cutting and removing burnt out winding and rewinding with super enameled copper winding wire of existing gauge and number of turns including varnishing, heating etc including carefully taking down the motor from EOT crane from height up to 12 meters by disconnecting all electrical cables, earth strips and dismounting from base channel, Shifting of motor to civil workshop for repair / rewinding and bringing back and reinstalling in its original position, checking alignment and testing on completion for satisfactory performance complete all as directed by Engineer-in-Charge.
All as per item No. 117.00 here-in-before but for motor of capacity 5 HP / 7.5 HP, 3 Ph, 415 Volts, 50 Hz
All as per item No. 117.00 here-in-before but for motor of capacity 15 HP / 20 HP, 3 Ph, 415 Volts, 50 Hz
servicing of elcetric motor of capacity upto 15 HP , 3 Phase , 415 Volts 50 Hz by means of oiling and greasing , replacement of fan blade , nuts and bolts , vibration dampers , mounting assembly etc including minor defect rectification as per directed by Engr-in - Charge
Supply and and connect in replacement of PVC insulated and PVC Round Sheathed, multistranded Copper Conductor (flexible) industrial cable of size 2.5 sqmm, 3 core 1100 Volts, conforming to IS: 694 complete all as specified and directed by Engineer-in-Charge. Make: Havells / KEI / Polycab / Finolex / Gloster / Plaza / Universal / Kalinga
All as per item No.121.00 here-in-before but of size 4 sqmm, 3 core.
All as per item No. 121.00 here-in-before but of size 6 sqmm, 3 core.
Supply and fix in replacement of On-Load Changeover switch 4 Pole, 125A, 415 V in sheet steel enclosure with front operated handle complete all as specified and directed. Make : Indo Asian / Standard / Havells / HPL / C&S / L&T
Supply and fix in replacement of On-Load Changeover switch 4 Pole, 250A, 415 V in sheet Metal enclosure with front operated handle complete all as specified and directed. Make : Indo Asian / Standard / Havells / HPL / C&S / L&T
Supply and fix in replacement of On-Load Changeover switch 4 Pole, 400A, 415 V in sheet Metal enclosure with front operated handle complete all as specified and directed. Make : Indo Asian / Standard / Havells / HPL / C&S / L&T
Supply and fix electrnoics based/ sensor based/ On-Load Changeover switch 4 Pole, 125 Amp to 250 Amp, 415 V in sheet metal enclosure as per size of change over switch complete all as specified and directed. Make : Indo Asian / Standard / Havells / HPL / C&S / L&T
Supply and fix in replacement of ignition transformer as per sample suitable for existing oil fired incinerator complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of thermostat as per sample suitable for existing oil fired incinerator complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of electrode as per sample suitable for existing oil fired incinerator complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of nozzle for primary / secondary chamber as per sample suitable for existing oil fired incinerator complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of solenoid valve for primary / secondary chamber as per sample suitable for existing oil fired incinerator complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of fuel pump as per sample suitable for existing oil fired incinerator complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of pressure gauge as per sample suitable for existing oil fired incinerator complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of fuel filter as per sample suitable for existing oil fired incinerator complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of photocell for primary / secondary chamber as per sample suitable for existing oil fired incinerator complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of power contactor in control panel as per sample suitable for existing oil fired incinerator complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of relay in control panel as per sample suitable for existing oil fired incinerator complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of timer in control panel as per sample suitable for existing oil fired incinerator complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of conveyer belt as per sample suitable for existing oil fired incinerator complete all as specified and directed by Engineer-in-Charge.
ROHIT ENTERPRISES
FTH Traders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .