Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹59.0 LAccepted-AOC | ₹59.0 L Quoted ₹60.7 L | L1 | Accepted-AOC Negotiated the Lowest rate Quoted tenderer accepted |
| 2 | L2₹62.0 LRejected-AOC | ₹62.0 L | L2 | Rejected-AOC Rate quoted Higher than L1 Bidder |
| 3 | L3₹63.1 LRejected-AOC | ₹63.1 L | L3 | Rejected-AOC Rate quoted Higher than L1 Bidder |
| Sl No | Description | Qty | Unit | BHARATHI ENGINEERING AND ELECTRICAL CONTRACTORS L2 | ANNAI ELECTRICALS L3 | KARTHIKEYAN ELECTRICALS L1 |
|---|---|---|---|---|---|---|
| 1.00 | Wiring with 2 x1.5 sq.mm. PVC insulated single core unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate and making good of the concealed portion with suitable colour for Concealed PVC Light point / fan point (for electronic regulator) (5 points / Coil) Higher End). | 87 | Pts | 2,801 ₹2.4 L | 2,839 ₹2.5 L | 2,737 ₹2.4 L |
| 2.00 | Wiring with 2 x1.5 sq.mm. PVC insulated single core unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate and making good of the concealed portion with suitable colour for Concealed PVC Light point / fan point (for electronic regulator) (6 points / Coil) Higher End | 19 | Pts | 2,229 ₹42,351 | 2,272 ₹43,168 | 2,186 ₹41,534 |
| 3.00 | Wiring with 3 x1.5 sq.mm. PVC insulated single core unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A two way module switch with module front plate and making good of the concealed portion with suitable colour for Concealed PVC pipe Stair case Light point Higher End. | 2 | Pts | 3,405 ₹6,810 | 3,471 ₹6,942 | 3,339 ₹6,678 |
| 4.00 | Wiring with 2 x1.5 sq.mm. PVC insulated single core unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate with continuous earth wire connection of 1.5 sq.mm copper wire and making good of the concealed portion with suitable colour for Concealed PVC Light point / fan point (for electronic regulator) (5 points / Coil) (Higher End) (For Street Light Point) | 8 | Pts | 3,014 ₹24,112 | 3,072 ₹24,576 | 2,955 ₹23,640 |
| 5.00 | Supply and fixing of 24W LED 2x2 square type Surface fitting with LED (Higher end) on ceiling with PVC unsheathed copper leads from terminals to the fitting. | 4 | Nos | 2,378 ₹9,512 | 2,424 ₹9,696 | 2,332 ₹9,328 |
| 6.00 | Supply and fixing of 24W LED 2x2 square type Recessed fitting with LED (Higher end) on false Ceiling with suitable hanging support from ceiling with PVC unsheathed copper leads from terminals to the fitting. | 12 | Nos | 3,863 ₹46,356 | 3,938 ₹47,256 | 3,788 ₹45,456 |
| 7.00 | Supply and fixing of 4 Feet LED 20W Fitting with LED 20W tube (Higher End) complete with TW round blocks on wall or ceiling with PVC unsheathed FRLS Copper leads from terminals to the fitting. | 51 | Nos | 1,110 ₹56,610 | 1,132 ₹57,732 | 1,089 ₹55,539 |
| 8.00 | Supply and fixing of Twin Box type 4'20W LED fitting (Higher End) complete with TW round block on wall or ceiling with PVC unsheathed Copper leads from the terminals to the fittings with 2 Nos 20W LED tubes. | 12 | Nos | 1,445 ₹17,340 | 1,473 ₹17,676 | 1,417 ₹17,004 |
| 9.00 | Supply and fixing of 1200mm (48") sweep AC ceiling fan High speed complete with 2 module 100W fan step regulator (Higher end) with 300 mm down rod on the existing fan clamp. | 4 | Nos | 2,889 ₹11,556 | 2,945 ₹11,780 | 2,833 ₹11,332 |
| 10.00 | Supply and fixing of 9 W LED lamp (Higher End) with Battern Holder. | 16 | Nos | 328 ₹5,248 | 334 ₹5,344 | 321 ₹5,136 |
Tender Value
₹59 L
EMD Value
₹39,500
Closing Date
4 Feb 2026, 3:00 pmClosed
Superintending Engineer
Office of Superintending Engineer PWD Buildings construction and maintenance circle Madurai
Providing internal and external electrification,15 persons capacity stretcher cum passenger lift, 40KVA Diesel Generator set and Laminar flow AC arrangements to the additional building in Government Hospital at Pannaikadu in Dindigul District
2026_PWD_644457_1
45SE/Bldgs C and M Circle Madurai 2025-26-1 dated 13.01.2026
Open Tender
Electrical Works
90 days
Pannaikadu, Dindigul District
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
₹39,500
29 May 2026
20 Jan 2026
4 Feb 2026
20 Jan 2026
4 Feb 2026
20 Jan 2026
Wiring with 2 x1.5 sq.mm. PVC insulated single core unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate and making good of the concealed portion with suitable colour for Concealed PVC Light point / fan point (for electronic regulator) (5 points / Coil) Higher End).
Wiring with 2 x1.5 sq.mm. PVC insulated single core unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate and making good of the concealed portion with suitable colour for Concealed PVC Light point / fan point (for electronic regulator) (6 points / Coil) Higher End
Wiring with 3 x1.5 sq.mm. PVC insulated single core unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A two way module switch with module front plate and making good of the concealed portion with suitable colour for Concealed PVC pipe Stair case Light point Higher End.
Wiring with 2 x1.5 sq.mm. PVC insulated single core unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate with continuous earth wire connection of 1.5 sq.mm copper wire and making good of the concealed portion with suitable colour for Concealed PVC Light point / fan point (for electronic regulator) (5 points / Coil) (Higher End) (For Street Light Point)
Supply and fixing of 24W LED 2x2 square type Surface fitting with LED (Higher end) on ceiling with PVC unsheathed copper leads from terminals to the fitting.
Supply and fixing of 24W LED 2x2 square type Recessed fitting with LED (Higher end) on false Ceiling with suitable hanging support from ceiling with PVC unsheathed copper leads from terminals to the fitting.
Supply and fixing of 4 Feet LED 20W Fitting with LED 20W tube (Higher End) complete with TW round blocks on wall or ceiling with PVC unsheathed FRLS Copper leads from terminals to the fitting.
Supply and fixing of Twin Box type 4'20W LED fitting (Higher End) complete with TW round block on wall or ceiling with PVC unsheathed Copper leads from the terminals to the fittings with 2 Nos 20W LED tubes.
Supply and fixing of 1200mm (48") sweep AC ceiling fan High speed complete with 2 module 100W fan step regulator (Higher end) with 300 mm down rod on the existing fan clamp.
Supply and fixing of 9 W LED lamp (Higher End) with Battern Holder.
Supply and fixing of WT bulk head fitting with guard suitable with 7W / 9W LED bulb.
Supply and run of 2 of 1.5 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100V grade in suitable gauge MS conduit pipe on wall and ceiling with continuous earth wire connection of 1.5 sq.mm copper wire with painting of suitable colour.
Supply and fixing of 48W LED street light fitting with LED (Higher end) with 32mm dia. GI pipe (class B) with 1 no.32 mm GI bend complete on the existing post/ on wall with PVC unsheathed FRLS copper leads with MS clamps and with painting .
Supply and fixing of 300mm (12inch) sweep (light duty) AC exhaust fan complete without provision of hole in the wall.
Supply and fixing of louvers shuters arrangements for 300mm (12inch) sweep (light duty) AC exhasut fan.
Supply and fixing of 375 mm (15") sweep (light duty) AC exhaust fan complete without provision of holes in the wall.
Supply and fixing of louvers shutters arrangements for 375 mm (15") sweep light duty AC Exhaust fan.
Supply and fixing of 1 no.6A two module 3 pin socket , 1 no. 6A one module switch with module cover plate (plastic) on suitable module concealed Box (GI ) in flush with wall with connections. Higher End.
Supply and fixing of 1 no.6/16A two module socket , 1 no. 16A one module switch with module cover plate (plastic) on suitable module concealed Box (GI ) in flush with wall with connections. Higher End.
Supply and fixing of 2 no. 6A two module socket, 1no.6/16 A two module socket , 2 nos. 6A one module switch, 2 nos. 16A one module switch with module cover plate (plastic) on suitable module concealed Box (GI ) in flush with wall with connections. Higher End.
Supply and fixing of 3nos.6A two module 3 pin socket , 3 nos. 6A one module switch with module cover plate (plastic) on suitable module concealed Box (GI ) in flush with wall with connections. Higher End.
Supply and fixing of 20A Flush type Wall Socket 32A DP MCB complete set for AC Plug inflush with wall with earth connection (For AC Plug).
Supply and fixing of 32A DP MCB in sheet steel enclosure in flush with wall and making good of the concealed portion with earth connection. [The MCB and metal enclosure should be of Higher End].
Supply and fixing of 63A FP MCB in sheet steel enclosure in flush with wall and making good of the concealed portion with earth connection. [The MCB and metal enclosure should be of Higher End].
Supply and erection of 5.0kVA sinewave Single phase in single phase out online UPS with suitable capacity SMF battery for 2 Hour Backup Time depending for full load condition with connections complete. a) Capacity 5000VA with pure sinewave. b) Input volt range AC Single phase. C) Out put Voltage 230V AC, Single phase. D) Back up time 2 Hours. E) Digital indication showing mains On, Inverter ON, Low Battery, Battery Voltage, Connected load in watts. f) Fuse protection, in built resettable circuit breaker protection. g) Battery should be Exide make with warranty not less than 24 Months. h) Steel stand to house inverter and batteries.
Supply and fixing of 7 segment 4 way TPN MCB sheet steel distribution board (Higher end) with metal / acrylic door cover flush type /surface type fitted with busbars and neutral links with single / three phase MCB outgoings and seperate 4 way provision for accomodating one No 4 pole incoming MCB / Isolator and another seperate 4 way provision for accomodating one No 4 pole ELCB / RCD (totally 8 ways in one segment) (3x 4 ways in Each segment) and seperate provision for MCB / Isolators ( totally 12 Nos) for sub incomers in 3 segments with lable holder and provison for taking up cable for size not less than 35 sq.mm. with the following in flush with wall with Earth connection only. (i) 63A 4P MCB -1 No (ii) 63A 4P 30mA RCCB- 1 No (iii) 63A DP isolator - 3 Nos (iv) 6A to 32A SPMCB - 12 Nos
Wiring with 2 x 1.5 sq.mm. PVC insulated single core unsheathed FRLS copper conductor cable of 1100V grade in suitable heavy gauge MS conduit pipe on wall and ceiling with MS accessories with 150mm x 100mm x 75mm MS switch box for 5A 3 pin non inter locking flush type CS plug with painting of suitable colour with continuous earth wire connection of 1.5 sq.mm copper wire for open plug point.
Supply and fixing of 7 segment 6 way TPN MCB sheet steel distribution board (Higher end) with metal / acrylic door cover flush type /surface type fitted with busbars and neutral links with single / three phase MCB outgoings and seperate 4 way provision for accomodating one No 4 pole incoming MCB / Isolator and another seperate 4 way provision for accomodating one No 4 pole ELCB / RCD (totally 8 ways in one segment) (3x 6 ways in Each segment) and seperate provision for MCB / Isolators ( totally 18 Nos) for sub incomers in 3 segments with lable holder and provison for taking up cable for size not less than 35 sq.mm. with the following in flush with wall with Earth connection only. (i) 63A 4P MCB -1 No (ii) 63A 4P 30mA RCCB- 1 No (iii) 63A DP isolator - 3 Nos (iv) 6A to 32A SP MCB - 18 Nos
Supply and fixing of 8 way single pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 no. 32A DP MCB switch as incoming and 6 nos. 6A to 32A SP MCB as outgoing in flush with wall with earth connection only. Higher End.
lamps with HRC fueses connections complete etc. The panel should be fabricated as per CEIG specification. The housing accommodate 9 Nos 3 phase switches and supply and fixing of the following switches. 1. 100 A FP switch disconnector fuse units interior only with HRC fuses double break-1No 2. 63A TPN switch disconnector fuse units interior only with HRC fuses double break- 8 Nos The panel board should be powder coated with superscriptions. (lettering and numbering) The above cubical panel board rest on suitable angle iron base.[The TPN switches shoul be approved by the departmental officers]
Supply and run of 2 of 1.5 sqmm PVC insulated SC unsheathed FRLS Copper Conductor of 1100V Grade in rigid pipe concealed in wall and ceiling and making good of the concealed portion with suitable colour. (For UPS wiring)
Supply and run of 2 of 1.5 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100V grade in rigid pipe concealed in wall and ceiling with continuous earth wire connection of 1.5 sq.mm copper wire and making good of the concealed portion with suitable colour.
Supply and Run of 2 of 2.5 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with continuous earth wire connection of 2.5 sq.mm copper wire and making good of the concealed portion.
Supply and run of 2 of 4 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100V grade insuitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 4 sq.mm copper wire and making good of the concealed portion with suitable colour.
Supply and run of 4 of 6 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100V grade insuitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 6 sq.mm copper wire and making good of the concealed portion with suitable colour.
Supply and Run of 4 of 10 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 10 sq.mm copper wire and making good of the concealed portion.
Supply and clamping of 3 1/2 x 25 sq.mm PVC LTUG armoured LTUG cable on post or on wall with MS Clamps. (For Hepa Filter AC & Lift)
Supply and fixing of brass cable gland for 3 1/2 x 25 sq.mm PVC armoured LTUG cable, with earth connection.
Supply and providing cable end termination of 3 ½ x 25 sqmm PVC LTUG Aluminium armoured cable with necessary aluminium cable sockets by crimping etc. with electrical connection complete.
Supply and laying of 3 1/2 x 35 sq.mm PVC armoured LTUG cable in a trench to be excavated at a depth of 0.75 metre putting 0.15 mt. Layer of sand and covering the cable completely with bricks and sand and refilling the earth to make good. (For Gensest)
Supply and clamping of 3 1/2 x 35 sq.mm PVC LTUG armoured LTUG cable on post or on wall with MS Clamps.
Supply and fixing of brass cable gland for 3 1/2 x 35 sq.mm PVC armoured LTUG cable, with earth connection.
Supply and providing cable end termination of 3 ½ x 35 sqmm PVC LTUG Aluminium armoured cable with necessary aluminium cable sockets by crimping etc. with electrical connection complete.
Supply and laying of 3 ½ x 70 sq.mm PVC armoured LTUG cable in a trench to be excavated at a depth of 0.75 metre putting 0.15 mt. Layer of sand and covering the cable completely with bricks and sand and refilling the earth to make good. (For New building)
Supply and clamping of 3 1/2 x 70 sq.mm PVC LTUG armoured LTUG cable on post or on wall with MS Clamps.
Supply and fixing of brass cable gland for 3 1/2 x 70 sq.mm PVC armoured LTUG cable, with earth connection.
Supply and providing cable end termination of 3 ½ x 70 sqmm PVC LTUG Aluminium armoured cable with necessary aluminium cable sockets by crimping etc. with electrical connection complete.
Earthing as per the ISI specification with an earth electrode of 2.1mt class 'B' GI pipe of dia not less than 40mm, with copper earth plate of size 125mm x 50mm x 6mm, with necessary funneling arrangements with necessary masonry work and with 38mm RCC cover slab for the brick masonry.
Earthing as per PWD standard with an earth electrode of 2Mtr Class 'B' GI pipe of dia not less than 32mm complete with necessary masonry work.
Supply and Run of 1 of No.8 SWG copper wire in suitable PVC rigid pipe on wall / floor / ground for earth connection.
Supply and run of 25mm x 3mm tinned copper flat with necessary clamps / supports on wall / floor / ground for earth connection.
Supply and fixing of 65 mm dia. (2 -1/2") GI pipe (class B) of 6 metre length with 300mm x 300mm x 6mm MS base plate duly welded at the bottom with concreting with construction of masonary pedestal with suitable SMC box with door arrangement to house 6A SP MCB switch, 2/4 way connector on suitable hylem sheet and supply and fixing of 48W LED street light fitting with LED (Higher end) with 1 metre 32mm dia. GI pipe (class B) Complete with suitable MS clamps for LED steet light fitting and SMC box with PVC unsheathed copper leads from SMC box to fitting and with painting of suitable colour.
Supply and laying of 4 x 10 sq.mm PVC armoured LTUG cable in a trench to be excavated at a depth of 0.75 metre putting 0.15 mt. Layer of sand and covering the cable completely with bricks and sand and refilling the earth to make good.
Supply and clamping of 4 x 10 sq.mm PVC LTUG armoured LTUG cable on post or on wall with MS Clamps.
Supply and clamping of 4 x 10 sq.mm PVC LTUG armoured LTUG cable in suitable GI (Class'B') pipe on wall with MS Clamps.
Supply and fixing of brass cable gland for 4 x 10 sq.mm PVC armoured LTUG cable, with earth connection.
Supply and fixing of TNEB meter board suitable for 3 phase 100A service connection made up of suitableangle iron frame work of size 2 feet x 1-1/2 feet using angle iron of size 1-1/2" x 1-1/2 "x 1/4" rigidly fixed on wall covered with hylem sheet of size 2 feet x1-1/2 feet of 12mm thickness with necessary bolts and nuts supports and supply and fixing of 3 Nos. 100A fuse units (500V), 1No. neutral link, copper earth flat of size 1"x1/4" with interconnection of EB meter to fuse units by 16 Sq.mm PVC insulated copper wire with 1 No 100A 30mA FP RCBO(Higher End) with suitable necessary connection with earth connection complete.
Supply and fixing of 3 Phase 100A aerial fuse unit for 3 Nos 100A fuse units (500V) on suitable MS sheet covered with 6mm thick hylem sheet on suitable angle iron work the tapping pole with necessary clamps.
Supply, Testing Commissioning and Handing over of 40KVA Diesel Generator set with acoustic enclosure conforming to CPCB IV+ Norms and BIS Specifications of 0.8 P.F. Three phase 415V/ 420 Volts, 50Hz, 1500 RPM CPCB approved capacity developing 56 BHP with acoustic enclosure water cooled clock wise rotating feed pump with 32KW / 40KVA operating capacity brushless alternator close coupled underneath fuel tank standard safeties LLOP with stop solenoid battery with lead Electric start and vibration fitting and accessories and AMF panel as detailed below including transporting & unloading charges. (A) Engine: Water cooled diesel engine suitable for Generator application conforming CPCBIV+ norms and IS standards with a shaft out put of 56 BHP at 1500 RPM under NTP conditions. The Engine shall comprise the following standard fitting flexible coupling fly wheel, air cleaner, fan blower, radiator, water pump, fuel filter, lubricating oil filter, etc.
(B) 12/24 Volt Electronic starting Equipment: Complete with starter motor, dynamo, standard batteries with cable, flexible exhaust piping of 50cms length (C) Engine Instrument Panel / Mounted: Starting push button / starting key, lubricating oil, temperature gauge, lubricating oil pressure gauge, water temperature gauge, safety control for low lubricating oil, pressure, safety control for high water temperature, safety control for over speed, hour meter (mechnical ) and RPM indicator, battery charging ammeter. The engine should be capable of providing 10% over load for one hour for every 11 hours continuous at full load. D)ALTERNATOR: 40KVA/32KW Capacity of brushless alternator, AC 3 phase, 50Hz, 415/420V, 0.8 PF, 1500 RPM under NTP conditions, conforming to CPCB IV+ Norms. (E) AMF CONTROL PANEL: The AMF control panel (cubical) should be fabricated with vermin proof and dust proof best quality sheet steel and floor mounted with removable rear panels and hinged front doors with enamel painted and incorporating the following with suitable provision for connection incoming and outgoing leads having been made on the control panel.
22.1No signal lamp for indicating battery 23. 1set Pilot lamps of 3 nos 24. MCCB of suitable capacity with magnetic thermal overload release, instant start circuit trip and under voltage release switch 25.Rectangular copper bus bars (1No for each phase, neutral and earthing terminals) of adequate capacity duly colour coded with head shrinkable PVC sleeves. 26.1No mains voltage monitor 27.Hooter/Audio alarm for indicating set fails to start and for DG O/L. 28.1set Timers 29.Audio and Visual indicator arrangements for: a) Low lubricating oil pressure b) High water temperature c) Over speed 29.Audio and Visual Indicator arrangements for: a)Low lubricating oil pressure b)High water temperature c) Over Speed
30.1No Earth fault relay 31.Isolator to isolate the neutral 1. The control panel should be complete with necessary fuses, cables, label, other accessories with neutral isolation arrangements. 2. The engine should trip for the following: a) Low lubricating oil pressure b) High water temperature c) Over speed 3.Supply and fitment of Auto Mains Failure Panel, 1 EB Service wih suitable Amps switch and contactors SUF Control relays, timers etc suitable for auto change over of DG & EB Service.
F.FUEL TANK 120 litres fuel tank shall be fabricated out of 14 SWG CRCA MS sheet and is part of base frame. It is duly painted and fitted with inlet and outlet connections and mechanical fuel gauge. Fuel tank can be easily removed for cleaning or any maintenance. G. Exhaust Gas Recirculation system arrangements as per CPCB IV+ norms as amended H.BASE FRAME: Base frame should be fabricated with MS channel frame of rigidly welded construction for mounting of generaor set. The engine and alternator should be coupled by suitably designed diaphragm type flexible coupling with guard and mounted on the base frame with proper alignment. I) ACOUSTIC ENCLOSURE: The Acoustic enclosure, Self standing weather proof Acoustic canopy conforming CPCB IV+ norms floor mounting type with modular construction with the provision to assemble
and dismantle easily and designed to suit all weather condtions and compliance to IS standards. Erection of acoustic enclosure suitable for 40KVA Diesel generator complete with all accessories as above and suitable supports etc. as approved by competent authority to suit updated CPCB norms. J) Erection of generator set with proper alignment over the existing foundation. K)Supply of manuals for operation & maintenance of DG set with warranty card etc. L) CEIG approval: Preparation of site plan physical layout, electrical line schematic Diagram 10 sets, getting drawing approval from CEIG preparation of complection report rectification report etc., arranging CEIG inspection and obtaining CEIG safety certificate, payment of CEIG inspection fees if necessary and preparation of one set of approval Drawing and copy of safety certificate in a neat frame work.
(M)TESTING AND COMMISSIONING After the installation of DG set on its foundation, the DG set should be tested and commissioned with first charging of lubrication oil to its level, first charging of battery and run the set for eight hours on full load test complete. The Genset engine and alternator make should be approved by department officials before used on work.
Providing suitable concrete foundation with cement concrete 1:2:4 using 20mm jelly for wearing coat including laying, compacting, finishing and curing etc., complete as per standard specifications as directed by the departmental officers suitable for 40kVA Genset and suitable for GH, Pannaikadu.
Supply and fixing of 100 A Three phase 500V 4 Pole Change over Switch on suitable angle iron frame work with MS cable entry boxes with earth connection only.
Supply and run of 1.5 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100V grade in existing concealed PVC rigid pipe with necessary connection complete.
Design, Engineering, supply, fabrication, erection, testing, commissioning and handing over of 1No 15 persons capacity Gearless Stretcher cum passenger lift with M/C Room, Speed 1m/s with stainless steel panels, Disable friendly, Microprocessor based controller, VVVF Drive, fire rated doors and ARD as per the following specifications. Technical specifications: 1. Location: Post operative ward 2. No of Lift : 1 No 3. Type of lift : passenger cum bed lift. (1020Kgs) 4. Capacity of lift : 15 persons capacity Gearless passenger cum bed lift
5. Speed : 1.0 M / Sec 6. Type of Drive: Specific variable voltage variable frequency V3F drive with enhanced ride comfort and near Zero leveling functions. 7. No. of floors: (Ground + 1 floor) 8. Total Travel : 3.6 mtrs Travel. 9. Leveling Accuracy: High level accuracy with smooth & jerk free stopping 10. Construction of Car: 18SWG High quality S.S 304 Grade car Neat hairline finish, S.S hand rail, SS floor line finish, Perspex false ceiling, stretcher impact protection. 11. Position of machine: Directly above the lift well. 12. No. of landing entrance: one in front 2 Nos 13. No. of car entrance: one in front only 14. Car entrance door: power operated V3F drive side opening sliding 18SWG stainless steel hair line finish. 15. Landing entrance door: power operated V3F sliding, opening 18SWG stainless steel hair line finish with provision for emergency key 16. Lift well existing: 2370mm x 2470mm
27. Emergency light: Battery operated light to be provided with Automatic charging device. 28. Fireman’s switch: To be provided at ground floor 29. Minor builders work: to be provided by lift contractor. 30. Scaffolding: to be provided by lift contractor 31. Sill angles and facia plates: to be provided by lift contractor 32. Steel for lift machinery: to be provided by lift contractor 33. Servicing and maintenance: Free comprehensive servicing and maintenance should be provided by the lift contractor during the guarantee period of one year. 34. Automatic Rescue Device: To facilitate the landing of the lift to the nearest floor at the time of power failure. This shall consists of suitable type battery system with charger, invertor, under voltage protection system etc., complete with all accessories.
35. Provision of intercom with phone: To be provided by lift contractor 3 points EPABX system at three places vide 1) inside the car 2) Head room 3) at ground floor attender room 36. Lift License: Preparation of Drawing, payment of charges to CEIG and insurance policies if any and obtaining CEIG safety certificate as per lift act should be done by lift contractor. 37. Floor annunciator with music, included 38. Special features: a. Infra red door sensor with full height screen. b. Tubular S.S hand rail in cars. c. Voltage stabilizer for circuit control. d. Stainless Steel signal fixtures. e. Vendal proof S.S. Button with S.S. cover f. SS hairline finish door frames for landing doors.g. VF door Register signal h. Call Register signal
i. Stainless steel facia plate for car operating panel and landing fixtures. j. Steel ladder for machine room and ladder for lift Shaft pit, k. On – Off switch for fan and light l. Over load warning indicator With audio announcement. m. Fall width half height rear panel mirror. 39. Provision of architraves covering all three sides up to a width of 300 decorum sheet of plywood with TW frame with aluminum beading architraves should also cover the thickness of still level door frame at the landing and indicator boxes at all landings. 40. Other standard features: Voltage stabilizer for control units, Over speed governor, phase failure and phase reversal relay alarm bell, T. Guide brackets for car and counter weight, rubber padding under winding unit, motor of adequate capacity, electromagnetic brake with compression springs car safety gears buffer, electro mechanical door locks emergency key side supporting angles, motor over load protection devices final limits switch, main suspension ropes counter weights lifting hoist for mounting the machineries.
41. Guarantee: Guarantee for the materials and workmanship of equipments complete should be offered by lift firm for a period not less than one year. 42. Site testing in accordance with IS 14665/ Standards upto date should be carried out at the time of handing over. Necessary spares and tools required for the maintenance for a period of one year 43. Supply of operation and maintenance manual with Necessary tools for Operation. The list of tools required should be detailed by the contractor in a separate sheet duly signed by contractor. (Johnson/KONE/ OTIS / Eq.)
DX AIR COOLED CONDENSING UNITS:Design ,supply , installation, testing and commissioning of 5.5TR Nominal capacity DX Air-cooled Condensing unit fixed with energy efficient R410A Refrigerant scroll compressor along with grooved copper tube/aluminium fins air cooled condensor coil with anticorrosion coatings,liquid ,accumulator, low noise alumimium propeller condenser fan with Fan motor etc all suitably assembled neatly in heavy duty GSS sheet metal cabinet and duly powdercoated as per specifications .the unit to include built in safety controls like HP/LP switch power quality protector, in built thermal / temperature protection
Supply ,installation , testing and commissioning of 2200 cfm 5.5 TR Nominal capacity factory assembled double skin ceiling mounted AHU with 50mm-45kg/cum PUF Insulated detachable panels ,extruded thermal break aluminium profiles filled with PUF,panel external skin with 0.6 mm preplasticized sheet, panel internal skin with 0.6mm galvanized sheet, AMCA tested DIDW backward/forward curved centrifugal fan with EFF1 rating motor ,drive arrangement with taper lock pulleys for fan and motor ,vibration isolators out of heavy duty rubberized mounts, prefilters with 3ply HDPE 50mm thick filters having an efficiency of 90% 10 mic, 6row /12FPI deep DX copper cooling coil with copper header and aluminium fins ,GI mist arrestor ,condensate coil trough with SS-304-20G insulated with 9mm closed cell elastomeric foam, guard for inspection door ,out let damper of aerofoil blades &PVC gears ,and flexible fire retardant canvass complete with galvanized hardware.
Supply and filling of R410A Refrigerant Gas.
Supply and fixing of Refrigirant piping out of hard drawn copper pipe set of 28.60 mm size.
Supply and fixing of Refrigirant piping out of hard drawn copper pipe set of 15.9 mm size.
Supply and fixing of flexible Canvas connection.
Supply, Fabrication and Erection of fabricated ducting made up of GI sheets of 22 Gauge thickness.
Supply, Fabrication and Erection of fabricated ducting made up of GI sheets of 24 Gauge thickness.
Supply and providing thermal insulation of 9 mm thick vidoflex with Aluminium Foil.
Supply and providing Acoustic for initial portion of Ducting with 12mm thick fiber glass rigid board covered with Tissue Paper and Aluminium Perforated Sheet.
Supply and fixing of extruded Aluminium powder Coated, supply and return Air Grilles / Diffusers with volume control dampers.
Supply, installation, testing and commissioning of Laminar Flow arrangements with HEPA Filters, Frames, etc. 8 ft X 6 ft for OT Ceiling Suspended provides ultra clean sterile CLASS 100 clean air and designed as per CLASS 5 OF ISO 14644-1 standards with air plenum at Aluminium powder coated 1mm thick casing with Aluminium pleat HEPA filters & 0.3 micron 99.97% efficiency and SS 304 perforated grill with 13 mm thickness XLP Insulation with Modular Housing, Frame: Aluminium, Flange type, Filter Media: Micro glass fibre, Sealant : Plolyurethane with Air flow as per standards suitable for 5.5 TR.
Supply and fixing of 1" PVC water drain pipe line.
Supply, fabrication and fixing of MS channel for mounting the Airconditioning Indoor Unit.
Supply, fabrication and fixing of MS channel for mounting the Airconditioning Outdoor Unit.
Supply and providing of pipeline nitrile rubber insulation for refrigerant and drain pipe lines.
Supply and providing of 0.5sqmm 4 core flexible signal cable.
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.05 MB
formpannaikaduelectrical.pdf
Tender Documents • 1.36 MB
BOQ_772329.xls
BOQ • 0.39 MB
Download all tender documents and submit your bid