Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹49.5 LAccepted-AOC GLYPTIC RAIPUR P O BHITA BURDWAN 713102 | BURDWAN | PURBA BARDHAMAN | WEST BENGAL | 713102 | L1 | Accepted-AOC L Bidder |
Tender Value
Refer Docs
EMD Value
₹1.1 L
Closing Date
30 Sept 2019, 12:00 pmClosed
SE, Kolkata Electrical Circle, PWD
P-16, India Exchange Place Extn. KIT Building, 2nd Floor, Kolkata-700073
Installation, Commissioning of FDS and Facia, Decorative lighting (Phase-2) at Presidency University-SITC of FD along with Very Early warning Detection, Exit Signage System at N.S. Building, Main Bldg, Central Library Bldg.
2019_PWDE_243298_1
PWD/SE/KEC/NIT-03(2nd call)/19-20
Open Tender
FIRE FIGHTING ORG
Item Rate
60 days
Kolkata
Please refer Tender documents.
8 documents required · 8 mandatory
₹1.1 L
Office of the SE, Kolkata Electrical Circle, PWD
27 Feb 2020
9 Sept 2019
16 Oct 2019
9 Sept 2019
30 Sept 2019
20 Sept 2019
19 Sept 2019
Amount
Supply, Installation,Testing & Commisioning of EN standard, VDS / LPCB Approved Microprocessor based 4 Loops expandable up to minimum 6 Loops, fire alarm control panel fully networkable with each loop capable of taking atleast 125 devices and each loop should be connected to a dedicated loop card (even if a loop card supports multiple loop the panel should be provided with 4 nos loop cards and should have provision for accomodating total 6 nos loop card), 1/4 VGA display character alpha-numeric liquid crystal display.The panel shall be soft addressable type. The panel shall be able to give pin point location of all fire/fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered. The panel shall have in built rectifier, provision for external & internal printer (if required),Loop cards, LCD unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, having minimum 1000 event memory, integral SMF lead acid batteries with sealed cells of 24 V / 12 V with integral battery charger complete as required and as per specification. (Approved Make: Honeywell / Bosch / Securiton / Siemens).
Supply, Installation,Testing & Commisioning of EN standard, VDS / LPCB Approved Microprocessor based 2 Loops, fire alarm control panel fully networkable with each loop capable of taking atleast 125 devices and each loop should be connected to a dedicated loop card (even if a loop card supports multiple loop the panel should be provided with 2 nos loop cards, 1/4 VGA display character alpha-numeric liquid crystal display.The panel shall be soft addressable type. The panel shall be able to give pin point location of all fire/fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered. The panel shall have in built rectifier, provision for external & internal printer (if required),Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, having minimum 1000 event memory, integral SMF lead acid batteries with sealed cells of 24 V / 12 V with integral battery charger complete as required and as per specification. (Approved Make: Honeywell / Bosch / Securiton / Siemens).
Supply,lnstallation,Testing & Comrnisioning of Networked Repeater Panel with 8 line x 40 character alpha-numeric liquid crystal display with all commands such as reset, mute, silence with suitable battery backup complete as required following VDS:EN5 [Approved Make: Honeywell / Securiton / Siemens / BOSCH)
Supply, installation, testing & commissioning of EN-54 Standard, VDS/LPCB approved Addressable Multi-Sensor Detector (optical smoke as well as heat) with inbuilt / additional Isolator and integral LED status indicator with 360 degree viewing angle. Detector shall communicate 3 danger levels for differentiated alarm activation and high tolerance to dust,dirt, temperature fluctuations and air currents. Detector should have unquie address for communication and assigned through panel with Mounting Base as required with the protection category of IP40. (Approved Make: Honeywell / Bosch / Securiton / Siemens).
Supply, installation, testing & commissioning of EN-54 Standard, VDS/LPCB approved Inteliigent addressable manual call point with inbuilt / additional Isolator suitable for flush or surface mounting, call point shall include test key feature without removing the glass. Also should have protection category of IP44 and extra acceesories as required. (Approved Make: Honeywell / Bosch / Securiton / Siemens)
Supply, installation, testing & commissioning of EN-54 Standard, VDS/LPCB approved Addressable One input & One output module with inbuilt / additional isolator and shall have the LED indication for Normal, Fault, test, and activation.The module shall have the option for configuration as fail safe operation. (Approved Make: Honeywell / Bosch / Securitron / Siemens).
Supply & Installation of 12 Volt 7amphour SMF batterty (MAKE : EXIDE / Panasonic)
Supplying, Installing, Testing & Commissioning of LED technology, High efficiency, Double Sided Exit Signage cum Emergency light with Function Use either as an emergency luminaire or exit sign, Testing system Stand Alone, Housing Polycarbonate, Glow wire test : 850°C, RAL9003, Type of mounting Surface: Recessed base for ceiling, double sided cone diffuser, plexi plate diffuser, set of 3 exit legends (L, R, D), Degree of protection IP65, Battery: Ni-Cd, Duration 3 hours, Viewing distance 30m, Insulation class II, Dimensions for 30 m viewing distance version: 371 x 170 x 62. (Make: Eaton/Teknoware/ADB)
Supply, Installation, Testing & Commissioning of VDS approved Aspiration Type Laser Based Very Early Warning Detection System with minimum Coverage Area 2000 Sq.Mtr and support Total Pipe Length 200 Mtr and Single Pipe Distance 100 MtrMake: Honeywell / Bosch / Securitron / Siemens): Vds; EN54.
Supply & Drawing of 2 Core 1.5 sq.mm FRLS shielded copper Cable. (Make. Finolex / Technoflex/MEM/KEI/Approved by EIC)
Supply & Laying of 20 mm NB PVC rigid conduit pipe on the surface of the wall Incl. all fittings as required. (Make: Precisson/Presto Plast/Polycab-Medium).
Mending good the damages caused during laying of conduit and other fire detection accessories etc with all necessary materials and labour arrangement to it's original finish. N.B: (a) Copy of VDS, EN, LPCB approval / certification document for major items serial no. 1,2,3,4,5,6,7,8 & 10 etc in BOQ of this tender must be uploded with in the Technical folder for "Make_Model No. and Detailed technical Specification, OEM certificates." in addition to the Declaration of the bidder for Confirmation of compliance of Technical Specifications. Otherwise the bid may be rejected. (b) The Agency must procure the materials from the Manufacturer / OEM or from their authorized. Sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. (c) Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution of work / submission of bill. (d) Certification in original from the manufacturer / OEM, as the case may be, regarding originality of the material must be submitted before any payment. (e) If any refurbished material is supplied and installed, penal action will be taken as per existing rules.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .