Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹1.9 LAccepted-Finance 23 B NEW MANDI NEW MANDI MUZAFFARNAGAR MUZAFFARNAGAR UTTAR PRADESH 251001 INDIA | MUZAFFARNAGAR | UTTAR PRADESH | 251001 | 1 | Accepted-Finance Ist lowest | |
| 2 | 2₹2.0 L+₹6,050 (3.12%)Accepted-Finance | 2 | Accepted-Finance IInd lowest | |
| 3 | 3₹2.0 L+₹6,900 (3.56%)Accepted-Finance 19 A DURGA BARI SADAR BAZAR MEERUT MEERUT MEERUT UTTAR PRADESH 250001 | MEERUT | UTTAR PRADESH | 250001 | 3 | Accepted-Finance IIIrd lowest |
Tender Value
₹2.0 L
EMD Value
₹2,000
Closing Date
15 Feb 2023, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
EE ETD DHAMPUR
OFFICE OF THE EXECUTIVE ENGINEER, 132 KV SUBSTATION PREMISES, NEAR NEW TEHSIL DHAMPUR
Work for arresting oil leakage of 40 MVA T/F-I (IMP make) at 132 KV Substation Nagina and repair and overhauling of 145 KV CGL make CB at 220 KV Substation Nehtaur
2023_UPTCL_771787_1
08/ETDD/2022-23
Open Tender
Electrical Works
Fixed-rate
60 days
Nagina and Nehtaur
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
EE ETD DHAMPUR
₹2,000
22 Feb 2023
4 Feb 2023
15 Feb 2023
4 Feb 2023
15 Feb 2023
4 Feb 2023
Amount
Following work to be carried out at 132 KV S/S Nagina at 132/33 KV, 40 MVA T/F-I (IMP make).
Stopping of oil lekage from top cover, turret and other flanges with the application of cold welding products of Hypoxy (USA make) consisting of steel fast, Titan bond, Great Cleaner & silicon silent at 40 MVA T/F-I.
Repair & overhauling of 145 KV CGL make Circuit Breaker CB no. 79 (132 KV Bijnor feeder) installed at 220 KV S/S Nehtaur by doing following work in each breaker.
Opening/Dismantling of control valve assembly, cleaning of cap seal cylinder, removal of defective roller, re-fixing of new roller, reassembly of control valve assembly in mechanism. Replacement of control valve seal & bent O-ring, opening of anti-pumping pin assembly cleaning, de-rusting & lubrication of anti-pumping pin assembly. Replacement of spring in anti pumping. Opening and cleaning of closing spring, shock absorber, pneumatic cylinder, cleaning of piston & cylinder including their assembling replacing of oil & O-ring, Opening and reassembling of trip coil assembly after cleaning of its various parts including measurement of resistance adjustment of trip coil gap. Checking of NRV & Drain valve for air leakage with help of soap solution. Replacement of NRV and Drain Valve. Checking of air switch i.e governor switches, low air pressure alarm switch including adjustment. Checking of gas density switch including all adjustment. De-rusting lubrication of horizontal rod assembly & its various linkages, cleaning of bar pins, replacement of cercilip. Show operation of circuit breaker with help of manual jack for checking over stroke, wipe, poles traveling etc. for satisfactory operation of 132 SF-6 CB.
OHM ENTERPRISES AND ENGINEERS
Technocrat Electrical
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .