OFFICE OF THE SUPERINTENDING ENGINEER (P.W.D) South-Western Electrical Circle PWD Compound, Midnapore, Paschim Medinipur
Construction of New S.D.O Office Building (G PLUS 1) With Foundation of (G PLUS 4) including single story Electrical Substation building at Debhog Haldia in the district Purba Medinipur (Phase I) SITC of FDA System.
2025_WBPWD_793687_1
WBPWD/SE/SWEC/NIQ67/2024-25
Open Tender
ELECTRICAL WORKS ORG
Item Rate
Haldia
Please refer Tender documents.
3 documents required · 3 mandatory
₹27,839
OFFICE OF THE SE,SWEC,PWD
8 Jul 2025
4 Jan 2025
23 Jan 2025
4 Jan 2025
21 Jan 2025
9 Jan 2025
8 Jan 2025
Amount
SITC of Microprocessor based Intelligent, addressable fire alarm control panel ( VDS I UL I FM / ULC approved ) fully networkable having requisite numbers of loop with 20 % spare capacity with each loop capable of taking requisite number of devices as per latest IS/NBC , l/4 VGA display character alpha-numeric liquid crystal display.The panel shall be soft addressable type.The panel shall be able to give pin point location of allfire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered.The Panel should be able to store sufficient numbers of 1og events in its Memory as per recommended standards. IS / NBC. Shiuld have the provision for incorporating with BMS.
The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 Y capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emargency condition, with integral battery charger complete as required.
The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 bus.The FACP shall have provision for interfacing with the public address system and BMS( RS 48S ). The panel should have modbus output & ready to communicate with remote computer. The system must be preloaded with licenced software. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward/Secutron/ Securiton/ Apollo / Morley / System Sensor/GST/Mircom).
SITC of Analog Addressable Intelligent multisensor detector ( VDS / UL approved ) with inbuilt optical smoke sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable Photothermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard.(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended IS / NBC ) without any additional cost). (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward/Secutron/ Securiton/ Apollo / Morley / System Sensor/GST/Mircom).
SITC of Addressable Manual Call Point ( VDS / UL / FM / ULC approved )soft addressable type with in built fault isolator as per NFPA style 7 wiring complete as required. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward/Secutron/ Securiton/ Apollo / Morley / System Sensor/GST/Mircom).
SITC of Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base / Latest IP grade as recommended by NFPA-72 for indoor use having medium fire hazard and ( VDS / UL / FM / ULC approved) approved. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward/Secutron/ Securiton/ Apollo / Morley / System Sensor/GST/Mircom).
SITC of LED type Response Indicator ( VDS / UL approved) having 2 Nos. red coloured LED lamps including connections etc. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward/Secutron/ Securiton/ Apollo / Morley / System Sensor/GST/Mircom).
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex/RR Kable/Polycab ) with 20 mm NB PVC rigid conduit pipe of medium grade (Make: Precision /AKG/ATUL /VIP/ Universal /BEC/Polycab) on the surface of the wall.
Cutting Channel of size (40 mm x 40 mm/ 43mm x 43mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge 3 mm thick Polythene pipe (without earth continuity wire) by means of anchoring chemical (Hilti/Sika) and GI 'U' hooks of 8 SWG incl. supplying and drawing 18 SWG GI wire as Fish wire and mending good damages to original finish by using own tools and tackles incl. S&F of following pipe.[ Make-Parrot gold/geolite]
19 mm dia
SITC of Intelligent signal processing unit (monitor /Control module) having Voltage free No contact which would be connected in series with magnetic coil of AHU power supply unit. In case of Fire the voltage free contact would close the circuit to isolate the power supply ao AHU .(Approved Make:- Siemense Cerberus Pro/Secutron/Bosch)
TERMS & CONDITIONS
I) The Fire Alarm system shall comply with latest requirements of 1. National Fire Protection Association (NFPA) Standards. 2. lS 2189 3. NFPA 70 National Electric Code 4. NFPA 72 National Fire Alarm Code 5. local Statutory Regulations 6. Manufacturer Recommendation.
II) TESTS:1.The system shall be tested and commissioned by a qualihed competent,trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments ald tests for the system. 2. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation and other tests as per above standards must be done.
III) Auto CAD Drawing of whole FDA system & submission of 5 set hard copy of drawing and soft copy (in Auto-CAD format) is to be submitted.
IV) The Agency must procure the materials from the Manufacturer f OEM or from their authorised sales channel so that the standard warrant5z / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
V) Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer I OEM I authorized sales channel to the e-mail of Engineer-in Charge and hard copy of it to be submitted during execution, of work/submission of bill.
VI) If any refurbished material is supplied and installed, penal action will be taken as per existing rules
TAPAN KUMAR SARKAR (BID ID -5978520)
UJJWAL MUKHERJEE (BID ID -5978513)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .