Supply, Installation, Testing and Commissioning for SITC of HVAC Systems at District Headquarter Hospital, Angul, Odisha.
NBCC/ODISHA/ZO/ANGUL/22-23/72
NBCC/ODISHA/ZO/ANGUL/22-23/72
Open Tender-Domestic
Electronics Equipment
Anugul, Odisha
₹11,800
₹6.7 L
11 Oct 2022
27 Sept 2022
11 Oct 2022
11 Oct 2022
14 Nov 2022
Sl. No. Item of Work Unit Qty Rate Amount
AIR CONDITIONING AND VENTILATION SYSTEM
VRF /VRV Based ODU
Supply of modular type Variable Refrigerant Flow/Variable
Refrigerant Volume air cooled Outdoor units suitable for cooling
only, having all hermetically sealed inverter type Scroll
Compressor(s), with motor having 6 pole, minimum two compressors
for above 14 HP modules, microprocessor based Controller, top
discharge type condensing unit(s), with R 410 A Refrigerant,
vibration isolators, with suitable foundation etc. with refrigerant-
cooled PCB for better performance complete as required. The unit
shall deliver the rated capacity at AHRI Conditions and work even at
50°C ambient temperature without tripping. The unit shall be suitable
to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit
shall be filled with first charge of the refrigerant and ready for use as
required. MS/GI powder coated stand with vibration isolation pads.
The ODU shall have low noise condenser fans with external static
pressure of the outdoor unit shall be more then 75 Pa to avoid hot
air recirculation, auto address setting, auto check function
for connection error and complete with indoor and outdoor units
with individual controller and with fittings etc. The compressor
and VRV/VRF Outdoor make should be same. The compressor motor
pole should be more than 4 for enhanced energy savings. The unit
shall also have feature to automatically modulate the
evaporative temperature between 6 deg C to 11 deg C with respect
to load for better comfort and energy efficiency.The Unit should
have free phase technology so that unit can work in case of phase
reversal also without tripping of units.
4 way VRF/VRV cassettes with panel / drain pump /PM 2.5
Filter/ sensor & wireless remote
Supply of following minimum capacity 4-way/ round flow VRV/VRF
Cassette Type Indoor ceiling mounted unit equipped with cordless
remote , synthetic washable media pre-filter, fan section with low
noise fan/dynamically balanced blower, multispeed motor, coil
section with DX copper coil, electronic expansion valve, outer
cabinet, drain pan, drain pump, cassette grill, insulation, necessary
supports, vibration isolation etc, suitable for operation on 230 V ±
10%, 50 Hz single phase AC supply, complete as required. The unit
shall have automatic force shut down provision in case of fire. All
indoor Units should have force shut option to connect with fire alarm
adaptor, so that the unit automatically stops in case or fire. The
cooling capacity of indoor unit will be at air inlet conditions of 27
degree C DBT and 19 degree C WBT. All 4 louvers of the unit shall
be independently adjustable for position as per user preference.
Digitally signed by
Rakesh Rakesh Narayan Sinha
Narayan Sinha Date: 2022.09.27
Sl. No. Item of Work Unit Qty Rate Amount
The cassettes units shall have dual sensor which detect the presence of
people and floor temperature to provide comfortable air-conditioning
and energy saving. The sensor should detects human presence and
adjust the airflow direction automatically to prevent drafts. Room
temperature should increase upto 4 deg C or the indoor to be
switched off when no people are detected or as per user preference.
The sensor should detects the floor temperature and automatically
adjusts the operation of the indoor unit to reduce the temperature
difference between the ceiling and the floor. The cassette unit should
be with PM2.5 filter housed in filter chamber for better Indoor Air
2.4 1 TR ( 3 x 3) Type with PM 2.5 filter,sensing flow panel Nos 22.00 69998.78 1539973.16
2.5 1.25 TR ( 3 x 3 type)with PM 2.5 filter,sensing flow panel Nos 23.00 73386.56 1687890.88
2.6 1.5 TR ( 3 x 3 Type )with PM 2.5 filter,sensing flow panel Nos 37.00 75036.20 2776339.40
2.7 2.0 TR ( 3 x 3 Type )with PM 2.5 filter,sensing flow panel Nos 88.00 76338.92 6717824.96
2.8 2.5 TR ( 3 x 3 type )with PM 2.5 filter,sensing flow panel Nos 32.00 82418.28 2637384.96
2.9 3.0 TR ( 3 x 3 type )with PM 2.5 filter,sensing flow panel Nos 39.00 83633.68 3261713.52
2.10 4.0 TR ( 3 x 3 type )with PM 2.5 filter,sensing flow panel Nos 3.00 84936.40 254809.20
Ducted unit with sensor and remote
2.11 4.5 TR ( 1 working +1 standby ) - for MRI Room Nos 2.00 84370.00 168740.00
Air Handling Unit (AHU)
Supply of Double skin AHU with Outer skin 1 mm Pre- coated G.I.
Inner Skin 0.8 mm Plain G.I. Frame work, Thermal break Al profile
with thermal barrier Thickness of insulated panels, 45 mm thick, CFC
Free PUF injected (Density: 40 kg / Cu. m.) Material of Drain pan, SS
304-20 G Tray duly insulated with 13 mm closed cell Nitrile
insulation. Unit Base G.S.S base channel.
Cooling Coil 6 RD, Material Of Tube - Copper 12.7 mm dia, 1/2 "
thickness, 10-13 FPI Aluminium, DIDW Backward curbed fan with
TEFC Squirrel Cage IP 55 Protected VFD Compatible induction
Media of Filters
Synthetic (non-woven type) / Fiber Glass for (EU-9 / EU-13)
Efficiency of Pre-filters (EU-4)
90 % down to 10 micron. Efficiency of Fine-filters (EU-5)
99 % down to 05 micron. Efficiency of HEPA filters (EU-13)
99.97 % down to 0.3 micron.
3.1 10 TR, 3000 CFM, Static Pressure as per design (OT ROOM) Nos 2.00 568807.20 1137614.40
8 TR, 2400 CFM, Static Pressure as per design (MINOR OT ROOM)
3.3 8 TR, 2400 CFM, Static Pressure as per design ( ICU ) Nos 2.00 507700.90 1015401.80
8 TR, 2400 CFM, Static Pressure as per design ( TRAUMA CARE )
3.5 16 TR, 4800 CFM, Static Pressure as per design (BURN UNIT) Nos 1.00 894558.00 894558.00
3.6 Catch all filter & drier Set 8.00 23364.00 186912.00
3.7 AHU connecting kit Set 8.00 45902.00 367216.00
3.8 AHU controller Set 8.00 43778.00 350224.00
Supply of Cordlesss remotes for VRF/VRV indoor units for cassettes
Supply, installation, testing & commissioning of Touch screen Central
4.2 Controller Systems for VRF/VRV indoor units with ModBus/ Nos 6.00 295000.00 1770000.00
BACnet compatibility to operate & monitor the systems.
5 Laminar Flow
Supply, Instalaltion, testing and commissioning of Laminar Flow
plenum (6' X 6') for operation theatres complete with fixing
arrangements etc. as per specifications and complete in all respect as
5.2 99.9% down to 0.3 Micron Hepa filters Nos 24.00 73750.00 1770000.00
Heater Unit 0.00 0.00 0.00
5.3 SITC of heater unit to control the RH inside the room (OT) Nos 3.00 37170.00 111510.00
Digitally signed by
Rakesh Rakesh Narayan Sinha
Narayan Sinha Date: 2022.09.27
Sl. No. Item of Work Unit Qty Rate Amount
VRF Y JOINTS FOR BRANCH DISTRIBUTION
REFRIGERENT PIPE JOINTS
6.1 Indoor branch joints Nos 256.00 5192.00 1329152.00
6.2 Outdoor branch joints Nos 18.00 18526.00 333468.00
Supply, installation, balancing and commintioning of fabricated at
site GSS sheet metal rectangle/round ducting complete with neoprene
7 gaskets, elbow, splitter damper, vanes, hangers, supports etc. As per
approved drawings and specifications of following sheet thickness
complete as required.
Thickness 1.00mm sheet (As per DSR 2022(E & M) SL NO
Thickness 0.80mm sheet (As per DSR 2022(E & M) SL NO
Thickness 0.63mm sheet (As per DSR 2022(E & M) SL NO
Supplying and fixing thermal insulation 19 mm thickness duly
laminated aluminum foil of mat finish closed cell Nitrile rubber
(Class "O") insulation on existing duct after applying suitable
8 adhesive for Nitrile rubber. The joints shall be sealed with 50 mm Sqm 740.00 575.09 425566.60
wide and 3 mm thick self adhesive nitrile rubber tape insulation
complete per specifications and as required.Valves should have
pressure rating of 25 Bar minimum. (As per DSR 2022(E &M) SL
Supply and fixing of accoustic lining of supply air duct and plenum
with 25mm thick resin bonded glass wool having density of 32 kg/m3 ,
with25mm x 25mm GI section of 1.25mm thick, at 600mm center to
center covered with reinforced plastic tissue paper and 0.5mm thick
perforated aluminium sheet fixed to inside surface of duct with
cadmium plated nuts, bolts, stick pins, CPRX compaound etc.
complete as required and as per specifications.(As per DSR 2022(E
Supplying, fixing, testing and commissioning of supply air diffusers
of powder coated aluminium with aluminium volume control dampers
with anti smudge ring & removable core. (As per DSR 2022(E &M)
Supplying, fixing, testing and commissioning of Return air diffusers
of powder coated aluminium without volume control dampers with
anti smudge ring & removable core. (As per DSR 2022(E &M) SL
12 Cabinet Type Fan With Pre , Fine & Hepa Filter
2500 CFM 25 mm SP (ISOLATION WARD – GROUND FL &
PATHO LAB – 3RD FL)
12.2 4000 CFM 25 mm SP (TRAUMA CARE WARD – 1ST FL) Nos 2.00 227032.00 454064.00
12.3 7000 CFM 25 mm SP (ISOLATION WARD – 1ST FL) Nos 1.00 361080.00 361080.00
12.5 1200 CFM 25 mm SP (MRI & CT SCAN – GROUND FL) Nos 1.00 128148.00 128148.00
Supplying, Fixing,testing and commissioning of fire dampers in
supply air duct/main branch and return air path as and where required
of required sizes i/c control wiring,the damper shall be motorized and
spring return so as to close the damper in the event of power failure
automatically and open the same in case of power being restored. The
spring return action shall be inbuilt mechanism and not externally
mounted. The damper shall also be closed in the event of fire signal
complete as required and as per specifications.
13.1 a) Fire Damper (As per DSR 2022(E &M) SL NO 16.20.1) Sqm 1.00 8126.67 8126.67
13.2 b) Actuater (As per DSR 2022(E &M) SL NO 16.20.2) Nos 1.00 7585.07 7585.07
14 Canvas Connection Nos 3.00 3009.00 9027.00
Supply, Installation, testing and commissioning including
vaccumiazation and Nitrogen testing of following nominal sizes
of soft/hard drawn copper refrigerant piping for VRV/VRF
system, complete with fittings, with suitable adjustable ring type
15 hanger supports, jointing/brazing including accessories, insulated
with XPLE Class-O tubular insulation/with Class-O closed cell
elastometric nitrile rubber tubular sleeves sections of specified
thickness as given below for Suction and Liquid lines, all
accessories as per specifications etc. as required.
Digitally signed by
Rakesh Rakesh Narayan Sinha
Narayan Sinha Date: 2022.09.27
Sl. No. Item of Work Unit Qty Rate Amount
15.1 6.4 mm dia (OD) (Soft drawn) 13 MM INSULATION Rmtr. 180.00 424.80 76464.00
15.2 9.5 mm dia (OD) (Soft drawn) 13 MM INSULATION Rmtr. 850.00 578.20 491470.00
15.3 12.7 mm dia (OD) (Soft drawn) 13 MM INSULATION Rmtr. 360.00 731.60 263376.00
15.4 15.86 mm dia (OD) (Soft drawn) 13 MM INSULATION Rmtr. 520.00 802.40 417248.00
15.5 19 mm dia (OD) (Hard drawn) 19 MM INSULATION Rmtr. 230.00 1073.80 246974.00
15.6 22.2 mm dia (OD) (Hard drawn) 19MM INSULATION Rmtr. 190.00 1628.40 309396.00
25.4 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19
mm thick insulation
28.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with
19 mm thick insulation
31.8 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with
19 mm thick insulation
34.9 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with
19 mm thick insulation
38.1 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with
19 mm thick insulation
41.27 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with
19 mm thick insulation
Supply and installing following size of perforated Hot Dipped
Galvanised Iron cable tray (Galvanisation thickness not less than 50
16 microns) with perforation not more than 17.5%, in convenient
sections, joined with connectiors, suspended from the ceiling with
G.I. suspenders including G.I. bolts & nuts, etc. as required.
300mm width x 50 mm depth x 10 mm thickness (As per DSR
225mm width x 50 mm depth x 10 mm thickness (As per DSR
150mm width x 50 mm depth x 10 mm thickness (As per DSR
Supply & fixing of control cum transmission wiring of Copper
17 conductor cable along with PVC conduit for looping between indoor
& outdoor VRF system.
18 Additional Refrigerant charging Kg 495.00 1298.00 642510.00
Thermocol Insulation under Exposed Roof
Supply & fixing of 50mm thick expanded polysterne (EP), minimum
16 kg/mcu density, fire retardant type insulation under exposed roof
(under deck) fixing to be done as per IS standard, ASHRAE and
engineer in-charge.
Supply and Installation of PVC drain piping with 9 / 6 mm thick
20 nitrile rubber insulation as per specifications with all accessories &
Electrical Panel
Supply, installation, testing and commissioning of cubicle type panels
as specified and shown on drawing.
i)Main Cu bus bars with bar type feeder connections & all internal
wiring and connections.
ii) Earthing all components, frame etc. to a common internal earth
iii) Powder coated Painting all sheet metal works.
iv) All accessories & supporting structure.
21 v) Removable Gland Plate for Brass glands on sending and receiving Set 3.00 251340.00 754020.00
ends. (Crimping lugs forming part of the termination)
vi) All ammeters with C.T's and voltmeter and energy meters.
vii) Panel components as specified.
viii) MS base frame.
ix) Separate adequate Cable alley at the sending and receiving
termination ends.
x) Separate adequate bus bar Alley at the interconnection end.
xi) All switch gear to have short circuit levels as specified.
Digitally signed by
Rakesh Rakesh Narayan Sinha
Narayan Sinha Date: 2022.09.27
Sl. No. Item of Work Unit Qty Rate Amount
i) 1 No. - 415V, 4P ,40A MCB breaking capacity 36KA as Incomer
ii) 1 set digital KWhr meter 3 Phase 40A.
iii) 1 set 0-50A digital ammeter,ASS.
iv) 1set 0-500V digital voltmeter,VSS.
v) Phase indicating lights in R,Y,B colour.
vii)1 set CT of 50/5A.
viii)415V, 100A,50KA,CU BUS BAR with heat shrinkable sleeves.
ix)IP 54 protection.
i)25A FP MCB 36KA-2
ii)25A FP MCB 10KA -2
iii)25A FP MCB 36KA-Spare
STARTER REQUIREMENT FOR HVAC:
Starter complete with Auto manual selector switch,start/stop push
button,O/L Relay with single phasing preventer feature,heavy duty
contactors auxiliary contacts for building Automation
system,interlocking etc suitable for the motor.
ODU Panel (For OUTDOOR Units)
Supply, installation, testing and commissioning of cubicle type panels
as specified and shown on drawing.
i)Main Cu bus bars with bar type feeder connections & all internal
wiring and connections.
ii) Earthing all components, frame etc. to a common internal earth
iii) Powder coated Painting all sheet metal works.
iv) All accessories & supporting structure.
22 v) Removable Gland Plate for Brass glands on sending and receiving Set 1.00 988840.00 988840.00
ends. (Crimping lugs forming part of the termination)
vi) All ammeters with C.T's and voltmeter and energy meters.
vii) Panel components as specified.
viii) MS base frame.
ix) Separate adequate Cable alley at the sending and receiving
termination ends
x) Separate adequate bus bar Alley at the interconnection end
xi) All switch gear to have short circuit levels as specified.
23.1 Isolator box for each & individual AHU Nos 8.00 21594.00 172752.00
24.1 Distribution box for all indoor units Set 6.00 139240.00 835440.00
Variable frequency drive for controlling the frequency of the motor to
control the air flow inside the critical areas
26.1 To control the Heating ability (Percentage wise) of the heaters Nos 6.00 56050.00 336300.00
27.1 Humidity cum temperature sensors Nos 6.00 7670.00 46020.00
27.2 Duct mounted air flow sensors Nos 6.00 6310.64 37863.84
28.1 RH controller Nos 6.00 9776.30 58657.80
28.2 Temp controller Nos 6.00 9343.24 56059.44
29 Power Cables
6 sq mm Copper ,armoured PVC insulated four core multistranded
29.1 1100v grade cable. From PANEL to Individual machine carrying Rmt 84.00 704.46 59174.64
through cable tray.
4 sq mm Copper ,armoured PVC insulated four core multistranded
29.2 1100v grade cable. From PANEL to Individual machine carrying Rmt 40.00 641.92 25676.80
through cable tray.
10 sq mm Copper ,armoured PVC insulated four core multistranded
29.3 1100v grade cable. From PANEL to Individual machine carrying Rmt 60.00 821.28 49276.80
through cable tray.
Digitally signed by
Rakesh Rakesh Narayan Sinha
Narayan Sinha Date: 2022.09.27
Sl. No. Item of Work Unit Qty Rate Amount
16 sq mm Copper ,armoured PVC insulated four core multistranded
29.4 1100v grade cable. From PANEL to Individual machine carrying Rmt 45.00 942.82 42426.90
through cable tray.
30 Control cables
30.3 2C X 1.5 sqmm Flexible copper cable Rmt 20.00 201.78 4035.60
30.4 3C X 2.5 sqmm Flexible copper cable Rmt 1400.00 323.32 452648.00
31.1 Supply and fixing of 25mm x 6mm GI strip as required. Rmt 50.00 516.84 25842.00
31.2 Supply and fixing of 8 SWG GI wire as required. Rmt 100.00 129.80 12980.00
Digitally signed by
Rakesh Rakesh Narayan Sinha
Narayan Sinha Date: 2022.09.27
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT72.pdf
Tender Document
BoQ.pdf
Tender Document
GCC CONTRACTING.pdf
Tender Document
Signed IP.pdf
Tender Document
SCC.pdf
Tender Document
Physical Milestone.pdf
Tender Document
PLAN.pdf
Tender Document
HVAC Approved makes.pdf
Tender Document
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .